Specifications are subject to change without notice 1
Solid State Relays
PCB, 1-Phase ZS
Types RAP 40 A ., RAP 48 A .
•AC Solid State Relay for PCB mounting
•Zero switching
•Rated operational current: 3 or 5 AACrms
•Non-repetitive voltage: Up to 1200 Vp
•Rated operational voltage: Up to 480 VACrms
•Input range: 3.5 to 40 VDC
4.5 to 40 VDC
•Insulation: OPTO (input-output) 4000 VACrms
•LED status indication
•Low off-state leakage current
•High surge ratings
Product Description
The RAP-series from Carlo
Gavazzi is a Solid State Relay
family for socket- or PCBmounting. With built-in LED
status indication for control
input, the relay is an ideal interface between PLC’s or
other logic controls and load.
The new housing design and
packing allows automatic insertion and soldering.
The relay has been designed
to switch inductive or resistive
loads as long as enough
attention is paid to the specifications stated in this data
sheet, e.g. max. current, ambient temperature etc.
Optotriacs for galvanic separation together with alternistors as output devices give
the most advanced performance. Additional snubbers are
no longer necessary. The zero
switching relay also works
with inductive loads due to its
high surge capability. An internal heatsink optimizes the
thermal resistance between
chip and ambient, thereby increasing the lifetime of the
relay.
Ordering Key
General Specifications
RAP 40 A . RAP 48 A .
Operational voltage range 10 to 440 VACrms 20 to 530 VACrms
Non-rep. peak voltage ≥ 1000 V
p
≥ 1200 V
p
Zero voltage turn-on ≤ 20 V ≤ 40 V
Operational frequency range 45 to 65 Hz 45 to 65 Hz
Power factor ≤ 0.2 ≤ 0.2
Approvals UL, CSA, VDE UL, CSA, VDE
Solid State Relay (PCB)
Switching mode
Mounting type
Rated operational voltage
Housing type
Rated operational current
Type Selection
Selection Guide
Rated operational Control voltage Rated operational current
voltage 3 AACrms 5 AACrms
400 VACrms 3.5 to 40 VDC RAP 40 A 3 RAP 40 A 5
480 VACrms 4.5 to 40 VDC RAP 48 A 3 RAP 48 A 5
Switching mode Rated operational voltage Rated operational current Control voltage
A: Zero switching 40: 400 VACrms 3: 3 AACrms 3.5 to 40 VDC
48: 480 VACrms 5: 5 AACrms 4.5 to 40 VDC
RAP 48 A 5