Carlo Gavazzi DFB01, PFB01 Catalog Page

Specifications are subject to change without notice (20.12.01) 1
Monitoring Relays Frequency Monitoring Types DFB01, PFB01
• Over/under frequency monitoring relays
• Measuring if power supply frequency is within set limits
• Measure on own power supply
• Separately adjustable upper/lower level on relative
scale
• Adjustable delay on alarm or on recovery (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DFB01) or plug-in module (PFB01)
• 22.5 mm Euronorm housing (DFB01) or 36 mm
plug-in module (PFB01)
• LED indication for relay, alarm and power supply ON
Product Description Ordering key
DFB 01 C M24
Housing Function Type Item number Output Power Supply
DFB01 and PFB01 are pre­cise frequency monitoring relays. The relays monitor their own power supply from 24 to 240 VAC. The advantage of using the latch function is that the relay can be kept energized
even after the end of the alarm condition. Inhibit func­tion can be used to avoid relay operation when not desired (maintenance, tran­sitions). The LED's indicate the state of the alarm and the output relay.
Type Selection
Mounting Output Measuring range Supply: 24 to 240 VAC
DIN-rail SPDT 50-60 Hz DFB 01 C M24 Plug-in SPDT 50-60 Hz PFB 01 C M24
Input Specifications Output Specifications
Input
Own power supply DFB01: A1, A2 (24 to 240 VAC)
PFB01: 2, 10 (24 to 240 VAC)
Measuring ranges Upper level Lower level
Selectable by DIP-switches 2 Hz range -0.2 to +2 Hz -2 to +0.2 Hz
50 Hz 49.8 to 52 Hz 48 to 50.2 Hz 60 Hz 59.8 to 62 Hz 58 to 60.2 Hz
10 Hz range -1 to +10 Hz -10 to +1 Hz
50 Hz 49 to 60 Hz 40 to 51 Hz 60 Hz 59 to 70 Hz 50 to 61 Hz
Contact input
DFB02 Terminals Z1, Z2 PFB02 Terminals 8, 9 Disabled > 10 k Enabled < 500 Pulse width > 500 ms
Hysteresis
2 Hz range ~ 0.05 Hz
10 Hz range ~ 0.25 Hz
Output SPDT relay Rated insulation voltage 250 VAC Contact ratings (AgSnO
2
Resistive loads AC 1 8A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations Electrical life 10
5
operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage 2 kVAC (rms) Rated impulse withstand volt. 4 kV (1.2/50 µs)
DFB01 PFB01
2 Specifications are subject to change without notice (20.12.01)
DFB01, PFB01
General Specifications
Power ON delay 1 s ± 0.5 s Reaction time (input signal variation from
-10% to +10% or from
+10% to -10% of the range) Alarm ON delay < 200 ms Alarm OFF delay < 200 ms
Accuracy (15 min warm-up time)
Temperature drift ± 200 ppm/°C Delay ON alarm ± 10% on set value ±50 ms Repeatability ± 0.02 Hz
Indication for
Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz
during delay time) Output relay ON LED, yellow
Environment
Degree of protection IP 20 Pollution degree 3 (DFB01), 2 (PFB01) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 87 mm
Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA CE-Marking Ye s EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2 Emission According to EN 50081-1
Mode of Operation
DFB01 and PFB01 monitor the frequency value of their own power supply.
Example 1
(Non-latching mode - N.D. relay)
The relay operates and the yellow LED is ON as soon as the measured frequency exceeds the upper set level or drops below the lower set level for more than the set delay time. The relay releas­es when the measured fre­quency comes back within the upper and lower limits. The red LED flashes until the delay time has expired or the measured value falls off the limits.
Example 2
(Latching mode - N.E. relay)
The relay operates and the yellow LED is ON as long as the measured frequency is within the upper and lower limits. The relay releases and latches in alarm position as soon as the measured fre­quency exceeds the upper set level or drops below the lower set level for more than the set delay time. The red LED flashes until the delay time has expired or the measured value comes back within the limits. Provided that the frequency has dropped below the upper set level (minus hysteresis) or exceeded the lower set level (plus hysteresis), the relay operates when the interconnections between terminals Z1, Z2 or 8, 9 are interrupted.
Supply Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) Through terminals:
DFB01: A1, A2 24 to 240 VAC ± 15%
PFB01: 2,10 24 to 240 VAC ± 15% Dielectric voltage Supply to output 4 kV Rated operational power 4 W
Adjust the system frequency setting DIP switch 3 and select the desired function setting the DIP switches 1, 2 and 4 as shown on the right. To access the DIP switches open the grey plastic cover as shown on the right.
Selection of level and time delay:
Upper knob: Setting of upper level:
-10 to +100% of the range.
Centre knob: Setting of lower level:
-100 to +10% of the range.
Lower knob: Setting of delay on alarm time: 0.1 to 30 s.
Function/Range/Level and Time Delay Setting
Setpoint range
ON: 2 Hz OFF: 10 Hz
Relay working mode
ON: Normally De-Energized OFF: Normally Energized
Contact input
ON: Lacth function enable OFF: Inhibit function enable
System frequency
ON: 60 Hz OFF: 50 Hz