2 Specifications are subject to change without notice (21.10.00)
DUC01, PUC01
Mode of Operation
DUC01 and PUC01 monitor
both AC and DC over+under,
over+over or under+under
voltage.
Example 1
(no contact input - under+over
voltage - 2 x SPDT relays
(1 x SPDT for PUC01))
DUC01: One relay operates
when the voltage drops
below the under voltage set
point for more than the
respective delay time. It
releases when the voltage
exceeds the set level plus
the set hysteresis. The other
relay operates when the voltage exceeds the over voltage set point for more than
the respective delay time. It
releases when the voltage
drops below the set level
minus hysteresis (the hysteresis is the same for both
set levels).
PUC01: The relay operates
when the voltage drops
below the under voltage set
level for more than the
respective set delay time or
when it exceeds the over
voltage set level for more
than the respective set delay
time. The relay releases when
the voltage exceeds the
under voltage set level plus
hysteresis and it drops
below the over voltage set
level minus hysteresis (the
hysteresis is the same for
both set levels).
Example 2
(latch enabled active - under+
under voltage - 2 x SPDT
relays (1 x SPDT for PUC01))
DUC01: Each relay operates
and latches when the voltage drops below the respective set level for more than
the respective delay time.
Provided that the voltage
has exceeded the respective
set level (see hysteresis), each
relay releases when the contact input’s connection is interrupted.
PUC01: The relay operates
when the voltage drops
below the higher set level for
more than the respective
delay time. Provided that the
voltage has exceeded the
respective set level plus hysteresis, the relay releases
when the contact input is
opened.
Example 3
(inhibit enable active - over+
over voltage - DPDT relay
(1 x SPDT for PUC01))
Provided that the contact
input is opened, the relay
operates when the voltage
exceeds the lower set level
for more than the respective
delay time. It releases when
the voltage drops below the
lower set level (see hysteresis) or when the contact
input’s pins are connected.
Note:
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay(s) activation.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1, A2 or A3, A2 (DUC01)
2, 10 or 11, 10 (PUC01)
724: 24 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV
Supply to output 4 kV 4 kV
Input to output 4 kV 4 kV
Rated operational power
AC 5 VA
DC 3 W
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON 1 or 2 x LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3 (DUC01), 2 (PUC01)
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 45 x 80 x 99.5 mm
Plug-in version 36 x 80 x 87 mm
Weight Approx. 250 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
CE-Marking Ye s
General Specifications