Carlo Gavazzi DUB71 Technical data

Monitoring Relays 1-Phase True RMS AC/DC Over or Under Voltage Type DUB71
• TRMS AC/DC over or under voltage monitoring relays
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 to 500 V AC/DC Adjustable voltage on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 5 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN 50 022
• 35.5 mm DIN-rail housing
• LED indication for relay, alarm and power supply ON
Product Description Ordering Key
DUB71 is a precise TRMS AC/DC over or under voltage (selectable by DIP-switch) monitoring relay. Owing to the built-in latch function, the ON-position of
elay output can be
the r maintained. Inhibit function can be used to avoid relay
operation when not desired (maintenance, transitions). The LED's indicate the state of the alarm and the output relay.
35.5 mm wide housing suit­able both for back and fr panel mounting.
Housing Function Type Item number Output Power supply
ont
Range
DUB 71 C B23 10V
Type Selection
Mounting Output Measuring range Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 10 V AC/DC DUB 71 C B48 10V DUB 71 C B23 10V DIN-rail SPDT 2 to 500 V AC/DC DUB 71 C B48 500V DUB 71 C B23 500V
Input Specifications
Input
oltage level Terminals Y1, Y2
V
Measuring ranges
..10V:
..500V
Contact input T
Disabled > 10 k Enabled < 500 Latch disable > 500 ms
0.1 to 1 V AC/DC >120 k 100 V
0.2 to 2 V AC/DC
0.5 to 5 V AC/DC 1 to 10 V AC/DC >120 k 100 V
Max. voltage for 1 s 200 V
:
2 to 20 V AC/DC 5 to 50 V AC/DC 500 k 350 V
20 to 200 V AC/DC 50 to 500 V AC/DC 500 k 600 V
Max. voltage for 1 s 1000 V
Internal resist. Max. volt.
>120 k
100 V
>120 k
500 k
500 k
600 V
erminals Z1, Y1
100 V
350 V
Output Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO
Resistive loads AC 1 5 A @ 250 VAC
Small inductive loads AC 15 2.5 A @ 250 VAC
Mechanical life 30 x 106operations Electrical life 10
Operating frequency Dielectric strength
Dielectric voltage Rated impulse withstand volt. 4 kV (1.2/50 µs)
2
DC 12 5 A @ 24 VDC
DC 13 2.5 A @ 24 VDC
5
operations
(at 5 A, 250 V, cos ϕ = 1)
7200 operations/h
AC (rms)
2 kV
Supply Specifications
Power supply Over
Rated operational voltage (IEC 60664, IEC 60038)
ough terminals:
thr
A1, A2 or A3, A2
B48: 24/48 VAC ± 15%
B23: 115/230 VAC ± 15%
voltage cat. III
45 to 65 Hz, insulated
45 to 65 Hz, insulated
Dielectric voltage AC supply
Supply to input 4 kV (1.2/50µs) Supply to output 4 kV (1.2/50µs)
Input to output 4 kV (1.2/50µs)
Rated operational power
AC
3 VA
1
DUB71
General Specifications
ower ON delay
P Reaction time (input signal variation from
Alarm ON delay < 100 ms
larm OFF delay < 100 ms
A
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
elay ON alarm ± 10% on set value ± 50 ms
D
epeatability ± 0.5% on full-scale
R
Indication for
Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz
Output relay ON LED, yellow
Environment
Degree of protection IP 20 Pollution degree 3 Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions 35.5 x 81 x 67.2 mm Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
Approvals UL, CSA CE Marking Yes EMC
Immunity According to EN 61000-6-2 Emission According to EN 61000-6-3
s ± 0.5 s or 6 s ± 0.5 s
1
-20% to +20% or from +20% to -20% of set value)
during delay time)
acc. to IEC 60947
Electromagnetic Compatibillity
Mode of Operation
DUB71 monitor both AC and DC over or under voltage.
Example 1
(no connection between ter­minals Z1, Y1 - latch func­tion disabled)
The relay operates when the measured value exceeds (or drops below) the set level for more than the set delay time. It releases when the voltage drops below (or exceeds) the set level (see hysteresis setting), or when power sup­ply is interrupted.
Example 2
(connection between termi­nals Z1, Y1 - latch function enabled)
The relay operates and latches in operating position when the measured value exceeds (or drops below) the set level for more than the set delay time. Provided that the voltage has dropped below (or has exceeded) the set point (see
hysteresis setting) the relay releases when the intercon­nection between terminals Z1, Y1 is interrupted, or power supply is interrupted as well. The yellow LED flashes until
he delay time has expired
t or the measured value has dropped below the set point (see hysteresis setting).
Note
When the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse before relay activation.
Function/Range/Level and Time Delay Setting
Adjust the input range set­ting the DIP switches 1 and 2 as shown below.
Select the desired function setting the DIP switches 3 to 6 as shown below.
To access the DIP switches open the gr as shown below.
Selection of level and time delay:
Upper knob:
Setting of hysteresis on rela­tive scale: 0 to 30% on set value.
Centr
oltage level setting on r
V tive scale: 10 to 110% on full scale.
ey plastic cover
e knob:
Lower knob:
Setting of delay on alarm time on absolute scale (0.1 to 30 s).
-
ela
Measuring range
Model 500 V 10 V ON OFF 20 V 1 V OFF OFF 50 V 2 V
ON 200 V
ON OFF ON
Relay working mode
ON: Normally De-Energized OFF: Normally Energized
Power ON delay
ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable OFF: Inhibit function enable
Monitoring function
ON: OFF: Under voltage
500 V
Over voltage
5 V
10 V
2