Datasheet DUB01, PUB01 Datasheet (Carlo Gavazzi)

Monitoring Relays 1-Phase True RMS AC/DC Over or Under Voltage Types DUB01, PUB01
• TRMS AC/DC over or under voltage monitoring relays
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 to 500 V AC/DC
• Adjustable voltage on relative scale
• Adjustable hysteresis on relative scale Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DUB01) or plug-in module (PUB01)
• 22.5 mm Euronorm housing (DUB01)
UB01
D
PUB01
or 36 mm plug-in module (PUB01)
• LED indication for relay, alarm and power supply ON
Product Description Ordering Key
DUB01 and PUB01 are pre­cise TRMS AC/DC over or under voltage (selectable by DIP-switch) monitoring relays. Owing to the built-in latch function, the ON-position of the relay output can be
maintained. Inhibit function can be used to avoid relay operation when not desired (maintenance, transitions). The LED's indicate the state of the alarm and the output relay.
Housing Function Type Item number Output Power supply Range
DUB 01 C B23 10V
Type Selection
Mounting Output Measuring range Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 10 V AC/DC DUB 01 C 724 10V DUB 01 C 748 10V DUB 01 C B48 10V DUB 01 C B23 10V
Plug-in SPDT 0.1 to 10 V AC/DC PUB 01 C 724 10V PUB 01 C 748 10V PUB 01 C B48 10V PUB 01 C B23 10V
Input Specifications
Input
Voltage level DUB01: Terminals Y1, Y2
Measuring ranges
..10V:
..500V
Note:
The input voltage cannot raise over 300 VAC/DC with r (PUB01 only)
Contact input
DUB01 PUB01 Disabled > 10 k Enabled Latch disable
0.1 to 1 V AC/DC >200 k 100 V
0.2 to 2 V AC/DC
0.5 to 5 V AC/DC 1 to 10 V AC/DC >200 k 100 V
Max. voltage for 1 s 200 V
:
2 to 20 V AC/DC 5 to 50 V AC/DC >500 k 350 V
20 to 200 V AC/DC >500 k 600 V 50 to 500 V AC/DC >500 k 600 V
Max. voltage for 1 s 1000 V
espect to gr
2 to 500 V AC/DC DUB 01 C 724 500V DUB 01 C 748 500V DUB 01 C B48 500V DUB 01 C B23 500V
2 to 500 V AC/DC PUB 01 C 724 500V PUB 01 C 748 500V PUB 01 C B48 500V PUB 01 C B23 500V
Output Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO
Resistive loads AC 1 8 A @ 250 VAC
Small inductive loads AC 15 2.5 A @ 250 VAC
Mechanical life 30 x 106operations Electrical life 10
Operating frequency 7200 operations/h Dielectric str
Dielectric voltage Rated impulse withstand volt.
ength
2
DC 12 5 A @ 24 VDC
DC 13 2.5 A @ 24 VDC
5
operations
(at 8 A, 250 V, cos ϕ = 1)
2 kVAC (rms) 4 kV (1.2/50
s)
µ
ound
PUB01: Terminals 5, 7
Internal resist. Max. volt.
>200 k >200 k 100 V
>500 k
minals Z1, Y1
er
T
erminals 8, 9
T
< 500 > 500 ms
100 V
350 V
1
DUB01, PUB01
Supply Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
A1, A2 or A3, A2 (DUB01) 2, 10 or 11, 10 (PUB01)
ielectric voltage DC supply AC supply
D
upply to input 2 kV 4 kV
S Supply to output 4 kV 4 kV Input to output 4 kV 4 kV
Rated operational power
AC 4 VA DC 3 W
24: 24 VDC ± 20%, insulated
7
48: 48 VDC ± 20%, insulated
7
B48: 24/48 VAC ± 15%
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
45 to 65 Hz, insulated
General Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
eaction time
R
Alarm ON delay < 100 ms Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Delay ON alarm ± 10% on set value ± 50 ms Repeatability ± 0.5% on full-scale
Indication for
ower supply ON LED, green
P Alarm ON LED, red (flashing 2 Hz
Output relay ON LED, yellow
Environment
Degree of protection IP 20 Pollution degree 3 (DUB01), 2 (PUB01) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
Approvals UL, CSA (except 748) CE Marking Yes EMC
Immunity According to EN 61000-6-2 Emission According to EN 61000-6-3
input signal variation from
(
-20% to +20% or from +20% to -20% of set value)
during delay time)
acc. to IEC 60947
Electromagnetic Compatibillity
Mode of Operation
DUB01 and PUB01 monitor both AC and DC over or under voltage.
Example 1
(no connection between ter minals Z1, Y1 or 8, 9 - latch function disabled)
The relay operates when the measured value exceeds (or drops below) the set level for more than the set delay time. It releases when the voltage
ops below (or exceeds) the
dr
2
-
set level (see hysteresis set­ting), or when power supply is interrupted.
Example 2
(connection between ter nals Z1, Y1 or 8, 9 - latch function enabled)
The relay operates and latch­es in operating position when the measured value exceeds (or drops below) the set level for more than the set delay time.
mi-
Provided that the voltage has dropped below (or has exceeded) the set point (see hysteresis setting) the relay releases when the intercon­nection between ter Z1, Y1 or 8, 9 is interr or power supply is interrupt­ed as well. The red LED flashes until the delay time has expired or the measured value has dropped below the set point (see hys­teresis setting).
minals upted,
Note
When the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse befor
elay activation.
e r
DUB01, PUB01
Example 1
Example 2
L
N(-)
PE
µ
5
7
10 1
43
U
89
L
N(-)
PE
µ
5
7
10 1
43
U
89
24 VDC (+)
48/230 VAC
24/115 VAC
112
24 VDC (+)
48/230 VAC
24/115 VAC
112
Latch/inhibit
enable
Example 1
Example 2
L
N(-)
PE
µ
Z1
Y1
Y2
A1 A3
A2 15
16 18
U
L
N(-)
PE
µ
Z1
Y1
Y2
A1 A3
A2 15
16 18
U
24 VDC (+)
48/230 VAC
24/115 VAC
24 VDC (+)
48/230 VAC
24/115 VAC
Latch/inhibit
enable
Function/Range/Level and Time Delay Setting
Adjust the input range set-
ing the DIP switches 1 and
t
as shown below.
2
Select the desired function setting the DIP switches 3 to 6 as shown below.
To access the DIP switches
pen the grey plastic cover
o
s shown below.
a
Selection of level and time
elay:
d
pper knob:
U
Setting of hysteresis on rela­tive scale: 0 to 30% on set value.
Centre knob:
oltage level setting on rela-
V
ive scale: 10 to 110% on
t
ull scale.
f
Lower knob:
Setting of delay on alarm time on absolute scale (0.1 to 30 s).
Measuring range
Model 500 V 10 V ON OFF 20 V 1 V OFF OFF 50 V 2 V ON ON 200 V 5 V OFF ON 500 V 10 V
Relay working mode
ON: Normally De-Energized OFF: Normally Energized
Wiring Diagrams
24/48 VDC (+)
Power ON delay
ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable OFF: Inhibit function enable
Monitoring function
ON: Over voltage OFF: Under voltage
24/48 VDC (+)
DUB01
24/48 VDC (+)
24/48 VDC (+)
PUB01
3
Power supply
O
ver voltage Under voltage - Latch function
Under voltage
Power supply
Latch ON
Set Level
Relay ON
Red LED ON
Set Level
Relay ON
Red LED ON
P
ower supply
Red LED ON
Set Level
Hysteresis
Hysteresis
Hysteresis
R
elay ON
1
or 6 s
1 or 6 s
1 or 6 s
Over voltage - Inhibit function
Power supply
Inhibit ON
Set Level
R
elay ON
Red LED ON
Hysteresis
1 or 6 s
DUB01, PUB01
22.5
80
83.5
99.5
63
28.5
36
80
94
28.5
63
90
Operation Diagrams
Over voltage - N.D. relay
Under voltage - N.D. r
elay
Under voltage - Latch function - N.D. relay
Over voltage - Inhibit function - N.D. relay
Dimensions
DIN-rail
Plug-in
4
Loading...