Carlo Gavazzi DUB01, PUB01 Technical data

Monitoring Relays 1-Phase True RMS AC/DC Over or Under Voltage Types DUB01, PUB01
• TRMS AC/DC over or under voltage monitoring relays
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 to 500 V AC/DC
• Adjustable voltage on relative scale
• Adjustable hysteresis on relative scale Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DUB01) or plug-in module (PUB01)
• 22.5 mm Euronorm housing (DUB01)
UB01
D
PUB01
or 36 mm plug-in module (PUB01)
• LED indication for relay, alarm and power supply ON
Product Description Ordering Key
DUB01 and PUB01 are pre­cise TRMS AC/DC over or under voltage (selectable by DIP-switch) monitoring relays. Owing to the built-in latch function, the ON-position of the relay output can be
maintained. Inhibit function can be used to avoid relay operation when not desired (maintenance, transitions). The LED's indicate the state of the alarm and the output relay.
Housing Function Type Item number Output Power supply Range
DUB 01 C B23 10V
Type Selection
Mounting Output Measuring range Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 10 V AC/DC DUB 01 C 724 10V DUB 01 C 748 10V DUB 01 C B48 10V DUB 01 C B23 10V
Plug-in SPDT 0.1 to 10 V AC/DC PUB 01 C 724 10V PUB 01 C 748 10V PUB 01 C B48 10V PUB 01 C B23 10V
Input Specifications
Input
Voltage level DUB01: Terminals Y1, Y2
Measuring ranges
..10V:
..500V
Note:
The input voltage cannot raise over 300 VAC/DC with r (PUB01 only)
Contact input
DUB01 PUB01 Disabled > 10 k Enabled Latch disable
0.1 to 1 V AC/DC >200 k 100 V
0.2 to 2 V AC/DC
0.5 to 5 V AC/DC 1 to 10 V AC/DC >200 k 100 V
Max. voltage for 1 s 200 V
:
2 to 20 V AC/DC 5 to 50 V AC/DC >500 k 350 V
20 to 200 V AC/DC >500 k 600 V 50 to 500 V AC/DC >500 k 600 V
Max. voltage for 1 s 1000 V
espect to gr
2 to 500 V AC/DC DUB 01 C 724 500V DUB 01 C 748 500V DUB 01 C B48 500V DUB 01 C B23 500V
2 to 500 V AC/DC PUB 01 C 724 500V PUB 01 C 748 500V PUB 01 C B48 500V PUB 01 C B23 500V
Output Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO
Resistive loads AC 1 8 A @ 250 VAC
Small inductive loads AC 15 2.5 A @ 250 VAC
Mechanical life 30 x 106operations Electrical life 10
Operating frequency 7200 operations/h Dielectric str
Dielectric voltage Rated impulse withstand volt.
ength
2
DC 12 5 A @ 24 VDC
DC 13 2.5 A @ 24 VDC
5
operations
(at 8 A, 250 V, cos ϕ = 1)
2 kVAC (rms) 4 kV (1.2/50
s)
µ
ound
PUB01: Terminals 5, 7
Internal resist. Max. volt.
>200 k >200 k 100 V
>500 k
minals Z1, Y1
er
T
erminals 8, 9
T
< 500 > 500 ms
100 V
350 V
1
DUB01, PUB01
Supply Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
A1, A2 or A3, A2 (DUB01) 2, 10 or 11, 10 (PUB01)
ielectric voltage DC supply AC supply
D
upply to input 2 kV 4 kV
S Supply to output 4 kV 4 kV Input to output 4 kV 4 kV
Rated operational power
AC 4 VA DC 3 W
24: 24 VDC ± 20%, insulated
7
48: 48 VDC ± 20%, insulated
7
B48: 24/48 VAC ± 15%
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
45 to 65 Hz, insulated
General Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
eaction time
R
Alarm ON delay < 100 ms Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Delay ON alarm ± 10% on set value ± 50 ms Repeatability ± 0.5% on full-scale
Indication for
ower supply ON LED, green
P Alarm ON LED, red (flashing 2 Hz
Output relay ON LED, yellow
Environment
Degree of protection IP 20 Pollution degree 3 (DUB01), 2 (PUB01) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
Approvals UL, CSA (except 748) CE Marking Yes EMC
Immunity According to EN 61000-6-2 Emission According to EN 61000-6-3
input signal variation from
(
-20% to +20% or from +20% to -20% of set value)
during delay time)
acc. to IEC 60947
Electromagnetic Compatibillity
Mode of Operation
DUB01 and PUB01 monitor both AC and DC over or under voltage.
Example 1
(no connection between ter minals Z1, Y1 or 8, 9 - latch function disabled)
The relay operates when the measured value exceeds (or drops below) the set level for more than the set delay time. It releases when the voltage
ops below (or exceeds) the
dr
2
-
set level (see hysteresis set­ting), or when power supply is interrupted.
Example 2
(connection between ter nals Z1, Y1 or 8, 9 - latch function enabled)
The relay operates and latch­es in operating position when the measured value exceeds (or drops below) the set level for more than the set delay time.
mi-
Provided that the voltage has dropped below (or has exceeded) the set point (see hysteresis setting) the relay releases when the intercon­nection between ter Z1, Y1 or 8, 9 is interr or power supply is interrupt­ed as well. The red LED flashes until the delay time has expired or the measured value has dropped below the set point (see hys­teresis setting).
minals upted,
Note
When the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse befor
elay activation.