Monitoring Relays
True RMS 3-Phase, 3-Phase+N, Multifunction
Types DPC01, PPC01
TRMS 3-phase over and under voltage,
•
hase sequence, phase loss and asymmetry
p
monitoring relay
• Detect when all 3 phases are present and have the
correct sequence
• Detect if all the 3-phase-phase or phase-neutral
voltages are within the set limits
• Detect if asymmetry is below set value
• Separately adjustable setpoints
Separately adjustable delay functions (0.1 to 30 s)
•
Output: 2 x 8 A relay SPDT NE
•
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPC01) or plug-in module (PPC01)
PC01
D
PPC01
• 45 mm Euronorm housing (DPC01) or 36 mm plug-in
module (PPC01)
• LED indication for relays, alarm and power supply ON
Product Description Ordering key
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss, asymmetry, over and
under voltage (separately
adjustable set points) with
built-in time delay function.
Supply ranges from 100 to
690 VAC covered by three
multivoltage relays (ranges
over 415 VAC only on the
DIN-rail housing).
Housing
Function
Type
Item number
Output
Power Supply
DPC 01 D M48
Type Selection
Mounting Output Frequency 100 to 115 VAC 208 to 240 VAC 380 to 415 VAC
DIN-rail 2 x SPDT 50 - 60 Hz DPC 01 D M23
DIN-rail 2 x SPDT 50 - 400 Hz DPC 01 D M11 400HZ DPC 01 D M23 400HZ DPC 01 D M48 400HZ
Plug-in 2 x SPDT 50 - 60 Hz PPC 01 D M23 PPC 01 D M48
Mounting Output Frequency 440 to 480 VAC 380 to 480 VAC 600 to 690 VAC
DIN-rail 2 x SPDT 50 - 60 Hz DPC 01 D M48 DPC 01 D M69
DIN-rail 2 x SPDT 50 - 400 Hz DPC 01 D M49 400HZ DPC 01 D M69 400HZ
Input Specifications
Input
L1, L2, L3, N
Note: Connect the neutral only
if it is intrinsically at the star
centre
Measuring ranges
M11
M23 177 to 275 ∆VAC
M48 DPC01 323 to 550 ∆VAC
M49
M69 DPC01 510 to 793 ∆VAC
Ranges
Upper level +2 to +22%
Lower level -22 to -2%
Asymmetry 2 to 22%
Tolerance 2 to 22%
DPC01:
PPC01:
DPC01 400HZ 323 to 475 ∆VAC
PPC01 323 to 475 ∆VAC
DPC01
erminals L1, L2, L3, N
T
minals 5, 6, 7, 11
er
T
Measure on own supply
V
85 to 132
375 to 550
of the nominal voltage
of the nominal voltage
of the nominal voltage
of the nominal voltage
∆
∆VAC
AC
Note: The input voltage must
not exceed the maximum rated
voltage or drop below the
minimum rated voltage
eported above.
r
Hysteresis
Set points from 2 to 5% 1%
Set points from 5 to 22%
2%
Specifications are subject to change without notice (24.10.06) 1
DPC01, PPC01
Output Specifications
utput
O
ated insulation voltage 250 VAC
R
Contact ratings (AgSnO2)µ
Resistive loads AC 1 8 A @ 250 VAC
mall inductive loads AC 15 2.5 A @ 250 VAC
S
Mechanical life ≥ 30 x 106operations
lectrical life
E
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage ≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
C 12 5 A @ 24 VDC
D
DC 13 2.5 A @ 24 VDC
x SPDT relays N.E.
2
5
0
perations
≥ 1
o
(at 8 A, 250 V, cos ϕ = 1)
Supply Specifications
ower supply
P
ated operational voltage (IEC 60664, IEC 60038)
R
through terminals:
L1, L2, L3, N (DPC01)
5, 6, 7, 11 (PPC01)
M11 - Delta Voltage:
M23 - Delta Voltage:
DPC01 M48 - Delta Voltage:
DPC01 M48 - Star Voltage:
PC01 M48 - Delta Voltage:380 to 415VAC ±15%;45 to 65Hz
P
PC01 M48 - Star Voltage:220 to 240VAC ±15%;45 to 65Hz
P
M48 400HZ - Delta Voltage:
M48 400 HZ- Star Voltage:
M49 400HZ - Delta Voltage:
M49 400 HZ- Star Voltage:
M69 - Delta Voltage:
M69 - Star Voltage:
M69 400HZ- Delta Voltage:
M69 400HZ- Star Voltage:
Rated operational power
M11 8 VA @ ∆115 VAC, 50 Hz
M23
M48 13 VA @ ∆400 VAC, 50 Hz
M69 21 VA @ ∆600 VAC, 50 Hz
vervoltage cat. III
O
100 to 115VAC ±15%; 45 to 65Hz
208 to 240VAC ±15%; 45 to 65Hz
380 to 480VAC ±15%;45 to 65Hz
220 to 277VAC ±15%;45 to 65Hz
380 to 415VAC ±15%;45 to 440Hz
220 to 240VAC ±15%;45 to 440Hz
440 to 480VAC ±15%;45 to 440Hz
254 to 277VAC ±15%;45 to 440Hz
600 to 690VAC ±15%;45 to 65Hz
347 to 400VAC ±15%;45 to 65Hz
600 to 690VAC ±15%;45 to 440Hz
347 to 400VAC ±15%;45 to 440Hz
9 VA @ ∆230 VAC, 50 Hz
Supplied by L2 and L3 for
the DIN-rail versions and
by L1 and L2 for the Plug-in
versions
General Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Reaction time
Incorrect phase sequence
or total phase loss < 200 ms
Voltage level (input signal variation from
Asymmetry level
Indication for
Power supply ON
Alarm ON LED, red (flashing 2 Hz
Output relays ON 2 x LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degr
Operating temperature
@ Max. voltage, 50 Hz -20 to +60°C, R.H. < 95%
@ Max. voltage, 50 Hz
Storage temperatur
m ON delay:
Alar
m OFF delay:
Alar
ee
e
-20% to +20% or from
+20% to -20% of set value)
< 200 ms (delay < 0.1 s)
< 200 ms (delay < 0.1 s)
LED, green
during delay time)
3 (DPC01), 2 (PPC01)
C, R.H. < 95%
-20 to +60
-30 to +80
°
°C, R.H. < 95%
Housing
Dimensions DPC01 45 x 80 x 99.5 mm
PPC01 36 x 80 x 94 mm
Weight Approx. 220 g
Screw terminals (DPC01)
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA
GL (DPC01 only, except
400Hz, M11)
CE Marking Ye s
EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
2 Specifications are subject to change without notice (24.10.06)