2 Specifications are subject to change without notice (09.05.05)
DPB01, PPB01
Mode of Operation
Connected to the 3 phases
(and neutral) DPB01 and
PPB01 operate when all 3
phases are present at the
same time, the phase
sequence is correct (not
DPB01...N and PPB...N) and
the phase-phase (or phaseneutral) voltage levels are
within set limits.
If one or more phase-phase
or phase-neutral voltages
exceeds the upper set level
or drops below the lower set
level, the red LED starts
flashing 2 Hz and the output
relay releases after the set
time period. In any case if
phase-neutral measurement
is selected both phasephase and phase-neutral
voltages are monitored. If the
phase sequence is wrong or
one phase is lost, the output
relay releases immediately.
Only 200 ms delay occurs.
The failure is indicated by the
red LED flashing 5 Hz during
the alarm condition.
Example 1
(mains network monitoring)
The relay monitors over and
under voltage, phase loss
and correct phase sequence.
In case of DPB01...N or
PPB01...N, the relay monitors over and under voltage.
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases, when one or more
voltages drop below the lower set level or exceed the
upper set level.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
L1, L2, L3, N (DPB01)
5, 6, 7, 11 (PPB01)
M23 - Delta Voltage: 208 to 240 VAC ± 15%
45 to 65 Hz
M48 - Delta Voltage: 380 to 480 VAC ± 15%
45 to 65 Hz
M48 - Star Voltage: 220 to 277 VAC ± 15%
45 to 65 Hz
Rated operational power
DPB01CM23, PPB01CM23 13 VA @ 230 ∆VAC, 50 Hz
DPB01CM48, PPB01CM48 13 VA @ 400 ∆VAC, 50 Hz
Supplied by L1 and L2
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time
Incorrect phase sequence or
total phase loss < 200 ms
Voltage level (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 200 ms (delay < 0.1 s)
Alarm OFF delay < 200 ms (delay < 0.1 s)
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment
Degree of protection IP 20
Pollution degree 3 (DPB01), 2 (PPB01)
Operating temperature
@ Max. voltage, 50 Hz -20 to 60°C, R.H. < 95%
@ Max. voltage, 60 Hz -20 to 50°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm
Plug-in version 36 x 80 x 94 mm
Weight Approx. 120 g
Screw terminals
Tightening torque Max. 0.5 Nm
according to IEC 60947
Approvals UL, CSA
CE Marking Yes
EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2
Emissions According to EN 50081-1
General Specifications