Carlo Gavazzi DPA01, PPA01 Catalog Page

Specifications are subject to change without notice (17.03.05) 1
Monitoring Relays
Product Description Ordering Key
Housing Function Type Item number Output Power supply
• 3-phase monitoring relays for phase sequence and phase loss
• Detect when all 3 phases are present and have the correct sequence
• Measure on own power supply
• Power supply range: 208 to 690 VAC (+10 -15%)
• Output: 8 A SPDT relay or 8 A DPDT normally energized
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DPA01) or plug-in module (PPA01)
• 22.5 mm Euronorm housing (DPA01) or 36 mm plug-in module (PPA01)
• LED indication for relay and power supply ON
Type Selection
Mounting Output 208 to 480 VAC 208 to 240 VAC 380 to 480 VAC 380 to 600 VAC 600 to 690 VAC
DIN-rail SPDT DPA 01 C M44 DPA 01 C M60 DPA 01 C M69 DIN-rail DPDT DPA 01 D M23 DPA 01 D M48
Mounting Output 208 to 415 VAC 208 to 240 VAC 380 to 415 VAC
Plug-in SPDT PPA 01 C M44 Plug-in DPDT PPA 01 D M23 PPA 01 D M48
Input
L1, L2, L3 DPA01: Terminals L1, L2, L3
PPA01: Terminals 5, 6, 7 Measures on own supply
Measuring ranges
208 to 480 VAC (DPA01CM44) 177 to 550 VAC 380 to 600 VAC (DPA01CM60) 323 to 690 VAC 600 to 690 VAC (DPA01CM69) 510 to 760 VAC 208 to 415 VAC (PPA01CM44) 177 to 475 VAC 208 to 240 VAC (DPA01DM23) 177 to 275 VAC 208 to 480 VAC (DPA01DM48) 323 to 550 VAC 208 to 240 VAC (PPA01DM23) 177 to 275 VAC 380 to 415 VAC (PPA01DM48) 323 to 475 VAC
ON-level > 85% of the mains phase-
phase voltage
3-Phase Sequence and Phase Loss Types DP A01, PPA01
Input Specifications
Output SPDT or DPDT relay, N.E. Rated insulation voltage 250 VAC Contact ratings (AgSnO
2
)µ DPA01C, PPA01C (SPDT): Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC DPA01D, PPA01D (DPDT): Resistive loads AC 1 8 A @ 250 VAC Small inductive loads AC 15 3 A @ 250 VAC
DC 13 2 A @ 24 VDC
Mechanical life 30 x 106operations Electrical life 10
5
operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
DPA 01 C M44
3-phase relay for detection of incorrect phase sequence, total and partial phase loss. Supply range from 208 to 690 VAC covered by two multi­voltage relays.
For mounting on DIN-rail or plug-in module. The device detects regenerated voltages up to 85% of the nominal voltage (phase-phase).
DPA01 PPA01
2 Specifications are subject to change without notice (17.03.05)
DPA01, PPA01
Mode of Operation
DPA01 and PPA01 monitor their own 3-phase power supply. The relay operates when all the phases are pre­sent and the phase sequence is correct. The relay releases when one
phase-phase voltage drops below 85% of the other phase-phase voltages.
Example 1
The relay monitors that the power supply has the correct phase sequence and that all phase voltages are present.
Example 2
The relay releases in case of interruption of one or more phases, provided that the regenerated voltage does not exceed 85% of the phase-phase voltage.
Power supply
Overvoltage cat. III Rated operational voltage (IEC 60664, IEC 60038) through terminals:
(DPA01) L1, L2, L3 (PPA01) 5, 6, 7
DPA01CM44 208 to 480 VAC ± 15%,
45 to 65 Hz DPA01CM60 380 to 600 VAC±15%,
45 to 65 Hz PPA01CM44 208 to 415 VAC ± 15%,
45 to 65 Hz DPA01CM69 600 to 690 VAC +10 -15%,
45 to 65 Hz DPA01DM23 208 to 240 VAC ± 15%,
45 to 65 Hz DPA01DM48 380 to 480 VAC ± 15%,
45 to 65 Hz PPA01DM23 208 to 240 VAC ± 15%,
45 to 65 Hz PPA01DM48 380 to 415 VAC ± 15%,
45 to 65 Hz
Rated operational power
M23 6 VA @ 230 VAC, 50 Hz
M44, M48 10 VA @ 400 VAC, 50 Hz
M60 15VA @ 600 VAC, 50Hz M69 15VA @ 690 VAC, 50Hz
Supplied by L2 and L3
Supply Specifications
Reaction time
Alarm ON delay < 100 ms Alarm OFF delay < 350 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Repeatability ± 0.5% on full scale
Indication for
Power supply ON LED, green Relay ON LED, yellow
Environment (EN 60529)
Degree of protection IP 20 Pollution degree 3 (DPA01), 2 (PPA01) Operating temperature
@ Max. voltage, 50 Hz -20 to +60°C, R.H. < 95% @ Max. voltage, 60 Hz -20 to +50°C, R.H. < 95%
Storage temperature -30 to +80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
Weight Approx. 100 g Screw terminals (DPA01)
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approval UL - CSA (except PPA01D,
DPA01CM69)
CE Marking Yes EMC Electromagnetic Compatibility
Immunity According to EN 61000-6-2 Emissions According to EN 50081-1
General Specifications
Wiring Diagrams
Example 1 Example 1
DPA01
PPA01
Loading...
+ 1 hidden pages