Carlo Gavazzi DIC01, PIC01 Data Sheet

Monitoring Relays 1-Phase True RMS AC/DC Over and Under Current Types DIC01, PIC01
• TRMS AC/DC over + under, over+over, under+under current and voltage monitoring relays
• DC process signal plus/minus monitoring relay (DIC01) Selection of measuring range by DIP-switches
• Adjustable current and voltage on relative scale
• Adjustable hysteresis on relative scale
• Separately adjustable delay functions (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 1 or 2 x 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DIC01) or plug-in module (PIC01)
• 45 mm Euronorm housing (DIC01)
D
IC01
PIC01
or 36 mm plug-in module (PIC01)
• LED indication for relay(s), alarm and power supply ON Galvanically separated power supply
Product Description Ordering Key
DIC01 and PIC01 are precise TRMS AC/DC over+under, over+over or under+under current and voltage (select­able by DIP-switch) monitor­ing relays. DIC01 can per­form also DC plus/minus measurement by short cir­cuiting pins Z3 and Y1. The devices can be connected to the MI or MP and A82 or E82 current transformers. Both relays have two individ­ual set levels with their own
time delay. Only for DIC01 each set level can work with a single SPDT relay. Owing to the built-in latch function, the ON-position of the relay output can be maintained. Inhibit function can be used to avoid relay operation when not desired (maintenance, transitions). The LED's indicate the state of the alarm and the output relays.
Housing Function Type Item number Output Power supply Range
DIC 01 D B23 AV0
Type Selection
Mounting Output Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail 2xSPDT DIC 01 D 724 AV0 DIC 01 D 748 AV0 DIC 01 D B48 AV0 DIC 01 D B23 AV0 Plug-in SPDT PIC 01 C 724 AV0 PIC 01 C 748 AV0 PIC 01 C B48 AV0 PIC 01 C B23 AV0
Input Specifications
Input
Current level DIC01: Terminals Y1, Y2
Voltage level DIC01: Terminals Y1, Y3
DC levels (DIC01 only) Connecting terminals Z3, Y1
Measuring current ranges
Direct Internal resis. Max. curr. Selectable by DIP-switch
0.5 to 5 mA AC/DC 50 35 mA 2 to 20 mA AC/DC 50 55 mA
-5 to 5 mA DC
-20 to 20 mA DC Max. current for 1 s 100 mA
Measuring voltage ranges
ect
Dir Selectable by DIP-switch
0.1 to 1 V AC/DC > 10 k 7 V 1 to 10 V AC/DC > 10 k 20 V
0.4 to 4 V
-1 to 1 VDC (DIC01 > 10 k 7 V
-10 to 10 VDC Max. voltage for 1 s 100 V
AC > 10 k 100 V
p
(DIC01 50
}
only)
}
only) > 10 k 20 V
PIC01: Terminals 6, 7
PIC01: Terminals 5, 7
35 mA 55 mA
Max. volt.
50
Inter
Ω Ω
nal r
esis.
Note 1:
The input voltage cannot raise over 300 VAC/DC with respect to ground (PIC01 only)
CT ranges AAC rms Max. curr.
MI and MP ranges (0.4 to 4 Vpinput)
1-ph.: 3-ph.: MI 5 MP 3005 0.5 to 5 A 20 AAC
MI 20 MP 3020 2 to 20 A 50 AAC MI 100 MP 3100 10 to 100 A 250 AAC MI 500 MP 3500
Note 2:
MP 3... current transformers not suitable for under current
ements due to the
measur output signal of the device (see data sheet)
50 to 500 A 750 AAC
Specifications are subject to change without notice (25.09.06) 1
DIC01, PIC01
Input Specifications (cont.)
CT ranges (cont.) AAC rms Max. curr.
A82 ranges (2 to 20 mA input)
A82-10/20 25 2.5 to 25 A 30 AAC A82-10/20 50 5 to 50 A 60 AAC A82-10/20 100 10 to 100 A 120 AAC
82-10/20 250 25 to 250 A 300 AAC
A A82-10/20 500 50 to 500 A 600 AAC
E82-20 ranges (2 to 20 mA input)
E82-20 25 2.5 to 25 A 50 AAC E82-20 50 5 to 50 A 100 AAC
Contact input
DIC01 PIC01 Terminals 8, 9 Disabled > 10 k Enabled < 500 Latch disable > 500 ms
Terminals Z1, Y1
Supply Specifications
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
A1, A2 or A3, A2 (DIC01) 2, 10 or 11, 10 (PIC01)
724: 24 VDC ± 20%, insulated 748: 48 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Output Specifications
Output 1 or 2 x SPDT relays
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2)µ
Resistive loads AC 1 8 A @ 250 VAC
Small inductive loads AC 15 2.5 A @ 250 VAC
Mechanical life 30 x 106operations Electrical life 105operations
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage Rated impulse withstand volt. 4 kV (1.2/50 µs)
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV Supply to output 4 kV 4 kV Input to output 4 kV 4 kV
Rated operational power
AC 5 VA DC 3 W
DC 12 5 A @ 24 VDC
DC 13 2.5 A @ 24 VDC
(at 8 A, 250 V, cos ϕ = 1)
2 kVAC (rms)
General Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s Reaction time (input signal variation from
Alarm ON delay < 100 ms Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
emperature drift ± 1000 ppm/°C
T Delay ON alarm ± 10% on set value ± 50 ms Repeatability ±
Indication for
Power supply ON Alarm ON LED, red (flashing 2 Hz
Output relay ON 1 or 2 x LED(s), yellow
-20% to +20% or from +20% to -20% of set value)
0.5% on full-scale
LED, green
during delay time)
Mode of Operation
DIC01 and PIC01 monitor both AC and DC current and voltage. DIC01 can also monitor positive and nega­tive DC voltage connecting terminals Y1 and Z3.
Example 1
(no contact input - under+over voltage - 2 x SPDT N.D. r (1 x SPDT for PIC01) - TRMS) DIC01: One relay operates when the voltage drops below
elays
onment
Envir
Degree of protection IP 20 Pollution degree 3 (DIC01), 2 (PIC01) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions DIC01 45 x 80 x 99.5 mm
Weight Approx. 250 g Screw terminals
ightening tor
T
ovals
Appr CE Marking Ye s EMC
Immunity Emission According to EN 61000-6-3
the under voltage set point for more than the respective delay time. It r the voltage exceeds the set level plus the set hysteresis. The other relay operates
que Max. 0.5 Nm
eleases when
PIC01 36 x 80 x 94 mm
(EN 60529)
acc. to IEC 60947 UL, CSA (except 748)
Electromagnetic Compatibillity
ding to EN 61000-6-2
Accor
when the voltage exceeds the over voltage set point for
e than the r
mor delay time. It releases when the voltage drops below the set level minus hysteresis.
espective
2 Specifications are subject to change without notice (25.09.06)
DIC01, PIC01
Mode of Operation (cont.)
PIC01: The relay operates when the voltage drops below
he under voltage set level
t for more than the respective
et delay time or when it
s exceeds the over voltage set
evel for more than the rela-
l tive set delay time. The relay releases when the voltage exceeds the under voltage set level plus hysteresis and
t drops below the over volt-
i age set level minus hystere-
is (the hysteresis is the
s same for both set levels).
Example 2
(latch enable active - under+under current - 2 x SPDT relays (1 x SPDT for PIC01) - TRMS) DIC01: Each relay operates and latches when the cur drops below the respective set level for more than the re­spective delay time. Provided that the current has exceeded the respective set level plus hysteresis, each relay releas-
es when the contact input’s connection is interrupted.
IC01:The relay operates
P
when the current drops
elow the higher set level for
b more than the respective
elay time. Provided that the
d current has exceeded the higher set level plus hystere­sis the relay releases when the contact input’s connec-
ions is interrupted.
t
ote
N
Different delay times can be used for appropriate reaction according to the set points.
Example 3
(inhibit enable active - over+over current with MI CT - DPDT
rent
elay (SPDT for PIC01) - TRMS)
r Provided that the contact input’s connection is inter­rupted, the relay operates when the current flowing in the MI CT exceeds the lower set level for more than the
respective delay time. It releases when the current
rops below the lower set
d level minus hysteresis or
hen the contact input’s
w pins are connected.
Example 4
(inhibit enable active - over+over current with A82-10 CT ­DPDT relay (1 x SPDT for
IC01) - TRMS
P Provided that the contact
nput’s connection is inter-
i rupted, the relay operates when the current flowing in the A82-10 CT exceeds the lower set level for more than its delay time. It releases when the current drops below the lower set level minus hyster contact input’s pins are con­nected.
Example 5 (DIC01 only)
(no contact input - under+over voltage - 2 x SPDT N.D. relays
esis or when the
- plus/minus DC One relay operates when the
oltage drops below the
v under voltage set point for
ore than the respective
m delay time. It releases when
he voltage exceeds the set
t level plus the set hysteresis. The other relay operates when the voltage exceeds the over voltage set point for
ore than the respective
m delay time. It releases when
he voltage drops below the
t set level minus hysteresis.
In this case the spare front label has to be placed on the device for proper level adjustment.
Note
When the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse before relay(s) activation.
Function/Range/Level and Time Delay Setting
Adjust the input range set­ting the DIP switches 1 and 2 of the main black selector as shown below. Select the desired function setting the DIP switches 3 to 6 of the black selector and 1, 2 of the small red selector as shown below.
o access the DIP switches
T open the gr as shown below The selection between cur­rent and voltage is automati­cally selected through the input connectors. TRMS or positive/negative DC monitoring selectable by
t-circuiting ter
shor Y1 and Z3 (DIC01 only).
Set Point 2 (SP2) monitoring function
ON: Over cur OFF: Under cur
Relay(s) coupling
ON: 2 x SPDT (DIC01 only) OFF: 1 x DPDT (DIC01, PIC01)
ey plastic cover
minals
ent or voltage
r
ent or voltage
r
Selection of level, time delay and hysteresis:
Upper knob:
Setting of hysteresis on rela­tive scale: 0 to 30% on set value.
Centre knobs:
Current level setting on rela­tive scale: 10 to 110% on full scale.
Measuring range (depending on connections)
Connect Input term. SW2 OFF ON ON None DIC01: Y1,Y2 0.5 to 5 mA 2 to 20 mA None
Y1 to Z3
None DIC01: Y1,Y3 0.1 to 1V 4 V
Y1 to Z3
Relay(s) working mode
ON: Normally De-energized (ND) OFF: Normally Energized (NE)
Power ON delay
ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s
Contact input
Latch function enable
ON: OFF: Inhibit function enable
Set Point 1 (SP1) monitoring function
ON: Over current or voltage
Under cur
OFF:
Lower knobs:
Setting of delay on alarm time on absolute scale (0.1 to 30 s).
SW1 ON ON OFF
PIC01: 5,7 DIC01: Y1,Y2 -5 to +5
PIC01: 6,7 DIC01: Y1,Y3
rent or voltage
AC/DC
mA DC
AC/DC
-1 to +1 None -10 to +10 V DC V DC
AC/DC
-20 to +20 None mA DC
1 to 10 V
p
AC/DC
Specifications are subject to change without notice (25.09.06) 3
DIC01, PIC01
Wiring Diagrams
DIC01
Specifications are subject to change without notice (25.09.06) 5
PIC01
DIC01, PIC01
45
80
83.5
99.5
63
28.5
36
80
9
4
28.5
63
90
Dimensions
DIN-rail
Plug-in
6 Specifications are subject to change without notice (25.09.06)