Specifications are subject to change without notice (02.11.01) 1
Monitoring Relays
Product Description Ordering Key
Housing
Function
Type
Item number
Output
Power supply
Measuring range
• TRMS AC/DC over or under current
monitoring relay
• Current measuring through internal shunt
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 mA to 10 A AC/DC
• Adjustable current on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DIB01) or plug-in module (PIB01)
• 22.5 mm Euronorm housing (DIB01)
or 36 mm plug-in module (PIB01)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
Input
Current level DIB01: T erminals Y1, Y2
PIB01: T erminals 5, 7
Measuring ranges
Internal resist. Max. curr .
..5MA:
0.1 to 1 mA AC/DC 50 Ω 50 mA
0.2 to 2 mA AC/DC 50 Ω 50 mA
0.5 to 5 mA AC/DC 50 Ω 50 mA
Max. current for 1 s 100 mA
..50MA: 1 to 10 mA AC/DC 5 Ω 150 mA
2 to 20 mA AC/DC 5 Ω 150 mA
5 to 50 mA AC/DC 5 Ω 150 mA
Max. current for 1 s 500 mA
1-Phase T rue RMS AC/DC Over or Under Current
Types DIB01, PIB01
Input Specifications
DIB 01 C B23 5A
DIB01 and PIB01 are precise
TRMS AC/DC over or under
current (selectable by DIPswitch) monitoring relays.
Direct measuring or through
current transformer.
Owing to the built-in latch
function, the ON-position of
the relay output can be
maintained. Inhibit function
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay. Through the built-in
shunt it is possible to monitor loads up to 10 A AC/DC.
DIB01
PIB01
Measuring ranges (cont.)
Internal resist. Max. curr .
..500MA:
10 to 100 mA AC/DC 0.5 Ω 700 mA
20 to 200 mA AC/DC 0.5 Ω 700 mA
50 to 500 mA AC/DC 0.5 Ω 700 mA
Max. current for 1 s 1.4 A
..5A: 0.1 to 1 A AC/DC 0.05 Ω 6 A
0.2 to 2 A AC/DC 0.05 Ω 6 A
0.5 to 5 A AC/DC 0.05 Ω 6 A
Max. current for 1 s 15 A
..10A: 1 to 10 A AC/DC 3 mΩ 11 A
Max. current for 1 s 15 A
Type Selection
Mounting Output Measuring range Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT 0.1 to 5 mA AC/DC DIB 01 C 724 5mA DIB 01 C 748 5mA DIB 01 C B48 5mA DIB 01 C B23 5mA
1 to 50 mA AC/DC DIB 01 C 724 50mA DIB 01 C 748 50mA DIB 01 C B48 50mA DIB 01 C B23 50mA
10 to 500 mA AC/DC DIB 01 C 724 500mA DIB 01 C 748 500mA DIB 01 C B48 500mA DIB 01 C B23 500mA
0.1 to 5 A AC/DC DIB 01 C 724 5A DIB 01 C 748 5A DIB 01 C B48 5A DIB 01 C B23 5A
1 to 10 A AC/DC DIB 01 C 724 10A DIB 01 C 748 10A DIB 01 C B48 10A DIB 01 C B23 10A
Plug-in SPDT 0.1 to 5 mA AC/DC PIB 01 C 724 5mA PIB 01 C 748 5mA PIB 01 C B48 5mA PIB 01 C B23 5mA
1 to 50 mA AC/DC PIB 01 C 724 50mA PIB 01 C 748 50mA PIB 01 C B48 50mA PIB 01 C B23 50mA
10 to 500 mA AC/DC PIB 01 C 724 500mA PIB 01 C 748 500mA PIB 01 C B48 500mA PIB 01 C B23 500mA
0.1 to 5 A AC/DC PIB 01 C 724 5A PIB 01 C 748 5A PIB 01 C B48 5A PIB 01 C B23 5A
1 to 10 A AC/DC PIB 01 C 724 10A PIB 01 C 748 10A PIB 01 C B48 10A PIB 01 C B23 10A