Accessories
AC Solid-core Current Transformer
Type CTD-9V / CTD-9H
Product Description
Solid-core current transformer
with bus-bar mountng facility.
Type Selection
Model
Rated primary currents from
400 A to 3200 A.
Primary current
( max 35x125 mm)
• Bus-bar type solid-core current transformer
• Class 0.5 accuracy
• Currents from 400 A to 3200 A
Up to 10 Bus-bar isolated fixing screws
•
• Double screw terminals (up to 8-wire connections)
• Sealable terminal block covers
Ordering Key
Model
Primary current
Secondary current
Option
Secondary current
CTD-9V 2000 5A XXX
Option
CTD-9V: vertical mounting
CTD-9H: horizontal mounting
From 400A to 3200A
(Refer to the Range Table)
Input Specifications
Operating frequency 48 to 62 Hz
Max. system voltage 0.72 kV
Rated insulation level 3 kV/1 min. @ 50 Hz
Insulation class E (max 75°C)
Short-time current rating
I
th
I
dyn
Extended curr
Security factor (FS) ≤ 5 (Class: 0.5, 1 and 3)
ent rating
Typical 100 In/1 s
2.5 I
th
The short-time thermal
current I
by the cable/bus-bar size
efer to the Range T
r
is anyway limited
th
able
General Specifications
ds
Standar
Housing ABS, self-extinguishing:
Mounting Bus-bar mounting
d accessories
Standar
Special features 1 A secondary current,
ding to EN60044-1
Accor
UL 94 V-0
wo terminal block screws.
T
Ten bus-bar fixing screws.
Ten plastic caps for bus-bar
fixing screws.
wo sealable terminal block
T
covers.
Tropicalization
1A (on request)
5A
Working temperature -25°C to: refer to the Range
Storage temperatur
Approvals CE.
Connection Screw type
Protection degree IP00 (without sealable terminal
Bus-bar size Max. 35x125 mm
W
Cable cr
eight
oss section ar
e
ea From 1.5 to 6 mm
XXX: none
XTX: tropicalization
Table (-13°F to: refer to the
Range Table) (R.H. < 90% non
condensing @ 40°C)
C to +70°C (-22°F to
°
-30
158°F) (R.H. < 90% non
condensing @ 40
cURus and CSA (400A to 2000A)
Min/Max screws tightening
torque relevant to terminal block
screws: From 1 to 2 Nm
Max screws tightening torque
elevant to the cable/bus-bar
r
fixing screws: 0,3 Nm
covers)
IP20 (with sealable terminal
block covers + wire terminals)
om 450 to 700 g
Fr
°C)
2
Output Specifications
Rated secondary curr
ent
5 A or 1 A
Specifications are subject to change without notice CTD-9VH DS ENG 150311 1
CTD-9V / CTD-9H
Range Table
odel CTD-9V and CTD-9H from 400A to 1200A
M
Primary
Current
Temperature
A CL 0.5 CL 1 CL 3
400 (@60°C/140°F) 120% 3 6
500 (@60°C/140°F) 120% 2 4 8
600 (@60°C/140°F) 120% 4 6 10
700 (@60°C/140°F) 120% 4 8 10
50(@60°C/140°F)
7
800 (@60°C/140°F) 120% 4 8 10
1000 (@60°C/140°F) 120% 6 10 13
1200 (@50
°C/122°F)
Extend.
current rating
20%
1
120% 8 12 15
Burden (VA)
4 8 1
Model CTD-9V and CTD-9H from 1250A to 3200A
Primary
urrent
C
Temperature
Extend.
urrent rating
c
Burden (VA)
A CL 0.5 CL 1 CL 3
1250 (@50°C/122°F) 120% 8 12 15
1500 (@50°C/122°F) 120% 10 15 18
1600 (@50°C/122°F) 120% 10 15 18
2000 (@50°C/122°F)
0
2500 (@50°C/122°F)
3000 (@40°C/104°F)
3200 (@40°C/104°F)
(*) A max overload of 120% for 1 min. every 30 min. is allowed.
(+) A continuous overload of 120% of the range is allowed @ amb.
temp. 40°C max.
100% (+)
100% (*)
100% (*)
100% (*)
15 20 24
20 25 30
25 30 35
25 30 35
Benefits
1 2 3
4
• Bridging of current transformer output without
changing the connection of the secondary, so
to avoid any output overvoltage during either
the maintenance or the installation procedure
(see figur
• Easy output and earth connection (see fig. 2).
• Screw terminals compatible with any kind of wire
terminals (see figur
5 6
e 1).
e 3-4-5-6).
Dimensions Vertical mounting (mm)
Dimensions Horizontal mounting (mm)
Wiring Diagram
S1 S2
L
P1 P2
N
2 Specifications ar
e subject to change without notice CTD-9VH DS ENG 150311