Accessories AC Current Transformer (max 64x20 mm bus-bar) Type CTD-4X
• Bus-bar type current transformer
• 0.5 class, currents from 150 to 1600 A
• Removable panel fixing clips Up to 6 Bus-bar isolated fixing screws
• Double screw terminals (up to 8-wire connections)
• Sealable terminal block covers
Cable/Bus-bar type current transformer with DIN-rail/bus­bar and panel mounting facility.
Rated primary currents from 150 A to 1600 A.
Type Selection
Primary current
From 150 to 1600A (Refer to Range Table)
Secondary current
1A 5A
Input Specifications
Operating frequency 45 to 65 Hz Max. system voltage 0.72 kV Rated insulation level 3 kV/1 min. @ 50 Hz Insulation class E (max 75°C) Short-time current rating
I
th
I
dyn
Extended curr Security factor (FS) 5 (Class: 0.5, 1 and 3)
ent rating
Typical 100 In/1 s
2.5 I
th
The short-time thermal current I by the cable/bus-bar size
Refer to Range T
is anyway limited
th
able
General Specifications
ds
Standar Housing ABS, self-extinguishing:
Mounting Panel mounting Standard accessories Two terminal block screws.
Optional accessories Extended fixing kit: CTD-kit
ding to EN60044-1
Accor
UL 94 V-0
Two cable/bus-bar fixing screws.
wo plastic caps for
T cable/bus-bar fixing screws.
wo panel mounting fixing
T clips. Two sealable terminal block covers.
wo panel mounting
T fixing clips. Six cable/bus-bar fixing
ews.
scr
Ordering Key
Model Primary current Secondary current Option
Optional fixing kit:
Option
XXX: none XTX: tropicalization 2XX: class 0.2S (depending
on the primary current)
Special features 1 A secondary current,
Working temperature -25°C to: refer to Range Table
Storage temperature -30°C to +70°C (-22°F to
Approvals CE, cURus and CSA Connection Screw type
Cable cross section area From 1.5 to 6 mm
Protection degree IP00
Cable diameter Max. 51 mm Bus-bar size
Horizontal
ertical
V
Weight From 450 to 700 g
CTD-4X 1250 5A XXX
CTD-kit
Six plastic caps for cable/bus-bar fixing screws
Class 0.2S Tropicalization
efer to Range
r
F to:
°
(-13 Table) (R.H. < 90% non condensing @ 40°C)
158°F) (R.H. < 90% non condensing @ 40°C)
2
Min/Max screws tightening torque relevant to terminal block screws: From 1 to 2 Nm
ews tightening tor
Max scr relevant to the cable/bus-bar fixing screws: 0,3 Nm
IP20 (with sealable terminal block covers + wir
Max. 64x20, 51x43 mm Max. 51x31 mm
que
e terminals)
Output Specifications
Rated secondary curr
ent
5 A or 1 A
Specifications are subject to change without notice CTD-4X DS ENG 150311 1
CTD-4X
131,5
113
81,2
42
63
30
31
51
64
90
49,9
45
φ 51
20,5
43,5
51
Range Table
Model CTD-4X from 150A to 700A
Primary Current
Temperature
Extended
current rating
Burden (VA)
A CL 0.5 CL 1
150 (@60°C/140°F) 120% 2.5 (5)
200 (@60°C/140°F) 120% 3.25 (6)
250 (@60°C/140°F) 120% 2.5 4.5 2
30 (@60°C/140°F) 120% 3 4 3
400 (@60°C/140°F) 120% 6 9 3
500 (@60°C/140°F) 120% 10 12.5 4
600 (@60°C/140°F) 120% 11 13.5 4
700 (@60°C/140°F) 120% 12.5 15 5
Benefits
1 2 3
(CL 3)
5P5
Model CTD-4X from 750A to 1600A
Primary Current
A
Temperature
Extended
current rating
Burden (VA)
CL
0.5CL1CL5P5
750 (@50°C/122°F) 120% 13 15.5 5
800 (@50°C/122°F) 120% 14 16.5 5
1000 (@50°C/122°F) 120% 17.5 20 6
1200 (@50°C/122°F)
1250 (@50°C/122°F)
1500 (@50°C/122°F)
1600 (@50°C/122°F)
100% (+)
100% (+)
100% (*)
100% (*)
20 22.5 6
20 22.5 6
27.5 30 8
27.5 30 8
(*) A max overload of 120% for 1 min. every 30 min. is allowed. (+) A continuous overload of 120% of the range is allowed @ amb.
temp. 40°C max.
4
5
6 7 8 9
• Easy and quick mounting on a panel (see e 1).
figur
Dimensions (mm)
• Protection of screw terminals using specific
sealable covers to assure always the best safety (see figure 3). Bridging of curr
ent transformer output without changing the connection of the secondary, so to avoid any output overvoltage during either the maintenance or the installation procedure (see figure 4).
• Easy output and earth connection (see fig. 5).
• Screw terminals compatible with any kind of wire terminals (see figure 6-7-8-9). Multiple scr
ews to grant a strong and reliable fixing of the
scr
ews provided with isolation cap
current transformer to the bus-bar (see figure 10).
Wiring Diagram
S1 S2
L
P1 P2
N
2 Specifications ar
e subject to change without notice CTD-4X DS ENG 150311
Loading...