Accessories
AC Current Transformer (max 23mm
Type CTD-1X
• Cable and bus-bar type current transformer
• 0.5 class, currents from 50 to 300 A
• Removable DIN-rail mounting holder
Removable panel fixing clips
•
• 2 cable/bus-bar isolated fixing screws
• Double screw terminals (up to 8-wire connections)
• Sealable terminal block covers
Product Description
Cable/Bus-bar type current
transformer with DIN-rail/busbar and panel mounting
facility.
Type Selection
Primary current
Rated primary currents from
50 A to 300 A.
Secondary current
Ordering Key
Model
Primary current
Secondary current
Option
Optional fixing kit:
Option
φ cable)
CTD-1X 100 5A XXX
CTD-kit
From 50 to 300A
(Refer to Range Table)
1A
5A
Input Specifications
Operating frequency 48 to 62 Hz
Max. system voltage 0.72 kV
Rated insulation level 3 kV/1 min. @ 50 Hz
Insulation class E (max 75°C)
Short-time current rating
I
th
I
dyn
Extended current rating 120%
Security factor (FS) ≤ 5 (Class: 0.5, 1 and 3)
Typical 100 In/1 s
2.5 I
th
The short-time thermal
current I
by the cable/bus-bar size
is anyway limited
th
General Specifications
Standards According to EN60044-1
Housing ABS, self-extinguishing:
UL 94 V
Mounting DIN-rail bus-bar
and panel mounting
Standard accessories Two terminal block screws.
Two sealable terminal block
covers.
Two panel mounting
fixing clips.
One DIN rail adapter.
Optional accessories Extended fixing kit CTD-kit:
Six cable/bus-bar
fixing screws.
Six plastic caps for
cable/bus-bar fixing
screws.
-0
XXX: none
XTX: tropicalization
Two panel mounting
fixing clips.
Special features 1 A secondary current,
Working temperature -25°C to +60°C (-13°F to
Storage temperature -30°C to +70°C (-22°F to
Approvals CE, cUrus and CSA
Connection Screw type
Cable cross section area From 1.5 to 6 mm
Protection degree IP00
Cable diameter Max. 23 mm
Bus-bar size Max. 20x5 mm
Weight From 150 to 200 g
Tropicalization
140°F) (R.H. < 90% non
condensing @ 40°C)
158°F) (R.H. < 90% non
condensing @ 40°C)
2
Min/Max screws tightening
torque relevant to terminal
block screws:
From 1 to 2 Nm
Max screws tightening
torque relevant to the
cable/bus-bar fixing
screws: 0,3 Nm
IP20 (with sealable terminal
block covers + wire termi
nals)
Output Specifications
Rated secondary current 5 A or 1 A
Specifications are subject to change without notice CTD-1X DS ENG 100311 1
CTD-1X
44
65,2
φ
23,3
83,6
69,2
44
30
46
27
22
Range Table
odel CTD-1X from 50A to 100A
M
Primary
urrent
C
Burden (VA)
A CL 0.5 CL 1 CL 3
0 (@60°C/140°F)
5
1 1
.25
60 (@60°C/140°F) 1 1.25
70 (@60°C/140°F) 1.5 1.75
75 (@60°C/140°F) 1 1.25 1.75
80 (@60°C/140°F) 1.25 1.5 2
100 (@60°C/140°F) 1.5 1.75 2.25
120 (@60°C/140°F) 1.75 2 2.5
125 (@60°C/140°F) 2 2.25 2.75
150 (@60°C/140°F) 2.25 2.5 3
160 (@60°C/140°F) 2.5 2.75 3.25
200 (@60°C/140°F) 3 3.25 3.75
250 (@50°C/122°F) 4.5 4.75 5.25
Model CTD-1X from 120A to 300A
rimary
P
Current
A CL 0.5 CL 1 CL 3
300 (@50°C/122°F) 5 5.5 6
Benefits
1 2 3 4 5
Burden (VA)
6 7 8 9
•
Easy and quick mounting either on a panel or
on a DIN-rail (see figure 1-2).
Dimensions (mm)
• Protection of screw terminals using specific
sealable covers to assur
e always the best
safety (see figure 3).
Bridging of curr
•
changing the connection of the secondary
to avoid any output overvoltage during either
the maintenance or the installation procedure
(see figure 4).
Easy output and earth connection (see fig. 5).
•
ew terminals compatible with any kind of
Scr
•
ent transformer output without
, so
wire terminals (see figure 6-7-8-9).
• Multiple screws provided with insulation caps to
grant a str
ent transformer to the bus-bar (see figur
curr
ong and r
eliable fixing of the
e 10).
10
L
S1 S2
P1 P2
Wiring Diagram
N
2 Specifications ar
e subject to change without notice CTD-1X DS ENG 100311