Accessories
AC Solid-core Current Transformer
Type CTD-10V / CTD10-H
Product Description
Solid-core current transformer
with bus-bar mounting facility.
Type Selection
Model
Rated primary currents from
400 A to 3200 A.
Primary current
( max 50x125 mm)
• Bus-bar type solid-core current transformer
• Class 0.5 accuracy
• Currents from 400 A to 3200 A
Up to 10 Bus-bar isolated fixing screws
•
• Double screw terminals (up to 8-wire connections)
• Sealable terminal block covers
Ordering Key
Model
Primary current
Secondary current
Option
Secondary current
CTD-10V 2000 5A XXX
Option
CTD-10V: vertical mounting
CTD-10H: horizontal mounting
From 400A to 3200A
(Refer to the Range Table)
Input Specifications
Operating frequency 48 to 62 Hz
Max. system voltage 0.72 kV
Rated insulation level 3 kV/1 min. @ 50 Hz
Insulation class E (max 75°C)
Short-time curr
I
th
I
dyn
Extended current rating Refer to the Range Table
Security factor (FS) ≤ 5 (Class: 0.5, 1 and 3)
ent rating
ypical 100 I
T
2.5 I
th
The short-time thermal
ent I
curr
by the cable/bus-bar size
/1 s
n
is anyway limited
th
General Specifications
Standards According to EN60044-1
Housing ABS, self-extinguishing:
Mounting Bus-bar mounting
Standard accessories Two terminal block screws.
Special features 1 A secondary curr
UL 94 V-0
en bus-bar
T
fixing screws.
en plastic caps for
T
bus-bar fixing scr
Two sealable terminal block
covers.
opicalization
r
T
ews.
ent,
1A (on request)
5A
Working temperature -25°C to: refer to the Range
Storage temperature -30°C to +70°C (-22°F to
Approvals CE.
Connection Scr
Protection degree IP00 (without sealable terminal
Bus-bar size Max. 50x125 mm
Weight From 450 to 700 g
Cable cr
oss section ar
ea
XXX: none
XTX: tropicalization
Table (-13°F to: refer to the
Range Table) (R.H. < 90% non
condensing @ 40°C)
F) (R.H. < 90% non
°
158
condensing @ 40°C)
cURus and CSA (400A to 2000A)
ew type
From 1.5 to 6 mm
Min/Max screws tightening
torque relevant to terminal
block screws: From 1 to 2 Nm
Max screws tightening
torque relevant to the
cable/bus-bar fixing scr
0,3 Nm
covers)
IP20 (with sealable terminal
block covers + wire terminals)
2
ews:
Output Specifications
Rated secondary curr
ent
5 A or 1 A
Specifications are subject to change without notice CTD-10VH DS ENG 150311 1
CTD-10V / CTD-10H
Range Table
Model CTD-10V and CTD-10H from 400A to 1200A
rimary
P
Current
Temperature
xtended
E
current rating
Burden (VA)
A CL 0.5 CL 1 CL 3
400
500
600
700
750
800
1000
1200
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@60°C/140°F) 120%
(@50°C/122°F) 120%
1 7 10
3 10 14
5 12 17
8 15 20
10 15 20
10 15 20
12 20 25
15 25 30
Benefits
1 2 3
4
5 6
Model CTD-10V and CTD-10H from 1250A to 3200A
Primary
Current
emperature
T
Extended
current rating
B
A CL 0.5 CL 1 CL 3
1250
1500
1600
2000
2500
3000
3200
(*) A Max overload of 120% for 1 min. every 30 min. is allowed.
(+) A continuous overload of 120% of the range is allowed @ amb.
temp. 40°C max.
(@50°C/122°F) 120%
(@50°C/122°F) 120%
(@50°C/122°F) 120%
(@50°C/122°F)
(@50°C/122°F)
(@40°C/104°F)
(@40°C/104°F)
100% (+)
100% (*)
100% (*)
100% (*)
15 25 30
20 30 40
20 30 40
25 40 50
30 50 60
30 50 60
30 50 60
Dimensions Vertical mounting (mm)
urden (VA)
• Bridging of current transformer output without
changing the connection of the secondary
, so
to avoid any output overvoltage during either
the maintenance or the installation procedure
(see figure 1).
• Easy output and earth connection (see fig. 2).
• Screw terminals compatible with any kind of wire
terminals (see figure 3-4-5-6).
Wiring Diagram
S1 S2
L
P1 P2
N
Dimensions Horizontal mounting (mm)
2 Specifications ar
e subject to change without notice CTD-10VH DS ENG 150311