Proximity Sensors Capacitive
Thermoplastic Polyester Housing
Type CA, M 30, 2-wire AC/DC
• Featuring TRIPLESHIELD™ Sensor Protection
• Temperature stability
• Humidity compensation circuit
•
• Rated operational voltage: 20-250 VAC/DC
• Output: Power MOSFET
• Make and break switching function, selectable
• LED indication
• High noise immunity
• Flush and non-flush types
• Cable and plug versions available
™
LD
E
HI
S
LE
P
RI
T
Adjustable sensing distance 2-16 mm or 2-25 mm
Capacitive proximity switches with either sensing distance 16 mm flush mounted
or 25 mm sensing distance
non-flush mounted. 2-wire
AC/DC output with a switch
for choosing NO and NC
switching. Grey M 30
polyester housing with 2 m
PVC cable or plug. Ideal for
use in level and plastic machinery applications.
Ordering KeyProduct Description
Type: Cap. proximity switch
Housing style
Housing size
Housing material
Housing length
Detection principle
Sensing distance
Output type
Output configuration
Connection
CA30CLF25CPM6
Type Selection
Housing Rated Mounting Ordering no. Ordering no.
diameter operating Power MOSFET, cable Power MOSFET, plug
2)
M30
M30 25 mm Non-flush CA30CLN25CP CA30CLN25CPM6
1)
Object: Grounded steel plate
dist. (S
16 mm Flush (built-in) CA30CLF16CP CA30CLF16CPM6
1
)
)
n
Make & break switching Make & break switching
2)
No humidity compensation
Specifications
Rated operating dist. (Sn)
CA30CL.16CP..: 2 to 16 mm (preset at 16 mm)
CA30CL.25CP..: 2 to 25 mm (preset at 25 mm)
Sensitivity Adj. multiturn pot.meter
Effective operating dist. (Sr) 0.9 x Sn≤ Sr≤ 1.1 x S
Usable operating dist. (Su) 0.8 x Sr≤ Sn> 1.2 x S
Repeat accuracy (R) ≤ 5%
Hysteresis (H)
Rated operational volt. (UB) 20 to 250 VAC/DC
Ripple ≤ 10%
Rated operational current (I
Continuous ≤ 250 mA DC @ T
Short-time < 2.5 A (max. 20 ms)
Min. load current 10 mA
OFF-state current (I
Voltage drop (U
) < 1.9 mA (@ 20-250 VAC)
r
)
d
4 to 20% of sensing distance
(ripple included)
)
e
≤ 200 mA DC @ T
≤ 350 mA AC @ T
≤ 250 mA AC @ T
< 1.7 mA (@ 20-250 VDC)
≤ 5.5 VAC/DC @
I
e max
A
A
A
A
r
≤ 50ºC
≤ 80ºC
≤ 50ºC
≤ 80ºC
Protection Transients, reverse polarity
Power ON delay ≤ 200 ms
Freq. of operating cycles (f) 10 Hz
Indication for output ON LED, yellow
Environment
Degree of protection IP 67 (Nema 1, 3, 4, 6, 13)
Temperature (T
Operating temperature
Storage temperature
Housing material
Body Grey, thermoplastic polyester
Cable end Polyester
Nuts Black reinforced nylon
Connection
Cable Grey, 2 m, 2 x 0.5 mm
Plug (-6) M12 x 1 double keyed
Cable for plug (-6) CON.-6A-series
Weight (incl. nuts) CA30CL.16CP..: 140 g
Approvals UL, CSA
CE-marking Yes
)
A
-25° to +80°C ( -13° to +176°F)
-40° to +85°C (-40° to +185°F)
Oil proof, PVC
CA30CL.25CP..: 150 g
2
Specifications are subject to change without notice (24.06.2010) 1

CA, M 30, AC/DC
B
C D
S
W
A
L E D
M 1 2 x
E
Dimensions
Cable
Plug
Type ABCDEFSW
Ø mm mm mm mm mm mm
CA30CLF16CP(-M6) M 30 x 1.5 x 50 28 50 13.6 15.4 5 36
CA30CLN25CP(-M6) M 30 x 1.5 x 50 28 62 13.6 15.4 5 36
Adjustment Guide
The environments in which
capacitive sensors are installed can often be un
stable regarding temperature, humidity,
object distance and industrial
(noise) interference. Because
of this, Carlo Gavazzi offers as
standard features in all TRIP-
LESHIELD™ capacitive sensors a user-friendly sensitivity
adjustment instead of having
a fixed sensing range, extended sensing range to accom-
modate mechanically demanding areas, temperature stability
to ensure minimum need for
adjusting sensitivity if temperature varies and high immunity to electromagnetic interference (EMI).
Note:
Sensors are factory set
(default) to maximum rated
sensing range.
A30CLF16CP(-M6)
C
CA30CLN25CP(-M6)
Installation Hints
Sensitivity
Adjustment AC models
Max.
Sensitivity
Min.
Tripleshield
Dist.
Programmable make or break
(by selector switch backview)
Output
Capacitive sensors have the
unique ability to detect almost all materials, either in liquid or solid form. Capacitive
sensors can detect metallic
as well as non-metallic objects, however, their traditional use is for non-metallic
materials such as:
• Plastic Industry
Resins, regrinds or moulded products.
current peaks, separate the prox. switch power cables from any other power cables, e.g.
motor, contactor or solenoid cables
• Chemical Industry
Cleansers, fertilisers, liquid
soaps, corrosives and petrochemicals.
• Wood Industry
Saw dust, paper products,
door and window
frames.
• Ceramic & Glass
Industry
Raw material, clay or
finished products, bottles.
Relief of cable strain
Not correct
Correct
The cable should not be pulled
• Packaging Industry
Package inspection for level
or contents, dry goods,
fruits and vegetables, dairy
products.
Materials are detected due to
their dielectric constant. The
bigger the size of an object,
the higher the density of material, the better or easier it is
to detect the object. Nominal
sensing distance for a capaci-
Protection of the sensing face Switch mounted on mobile carrierTo avoid interference from inductive voltage/
A proximity switch should not serve as
mechanical stop
tive sensor is referenced to a
grounded metal plate (ST37).
For additional information
regarding dielectric ratings
of materials please refer to
Technical Information.
Any repetitive flexing of the
cable should be avoided
2 Specifications are subject to change without notice (24.06.2010)