Carlo Gavazzi CA12CLC, CA18CLC, CA30CLC Data sheet

Proximity Sensors Capacitive Thermoplastic Polyester Housing
Types CA, M12, DC, Teach-in
Capacitive proximity switch­es with a sensing distance of either 4 mm flush mount­ed in metal or 8 mm non­flush mounted. The switching points can be altered by means of the
teach-in function. 3-wire DC output with selectable make (NO) or break (NC) switching and NPN Alarm. Grey poly­ester housing with 2 m PVC cable or M12 plug.
TRIPLESHIELD
• Featuring TRIPLESHIELD™ Sensor Protection
• Sensing distance: 0.5 - 8 mm
• Teach-in of sensing distance via push-button or wire
• Automatic detection of NPN or PNP load
• Selectable make or break switching by means of the Teach-in function
• Protection: short-circuit, transients and reverse polarity
• Humidity compensation
• Alarm output
Ordering KeyProduct Description
Capacitive prox im ity switch Housing diameter (mm) Housing material Housing length Detection principle Rated operating dist. (mm) Output type Output configuration Connection type Remote teach
CA12CLC08BPM1RT
Type Selection
Housing diameter Rated operating distance Ordering no. Ordering no. (Sn) Cable Plug
Specifications
Sensing range (Sd) Non-flush mounted 0.5 - 8 mm, ref. target 24x24 mm ST37, 1 mm thick, grounded Flush mounted 0.5 - 4 mm, ref. target 12x12 mm ST37, 1 mm thick, grounded
Sensitivity Adjustable (Teach-in) Effective operating dist. (Sr) 0.9 x Sn ≤ Sr ≤ 1.1 x S Usable operating dist. (Su) 0.8 x Sr ≤ Su ≤ 1.2 x S Repeat accuracy (R) ≤ 5% Hysteresis (H) Rated operational volt. (UB) 10 to 40 VDC (ripple incl.) Ripple ≤ 10% Output function NPN/PNP (auto detect) Output switching function N.O. or N.C. (teachable) Rated operational current (Ie) ≤ 200 mA (continuous) No-load supply current (Io) ≤ 12 mA Voltage drop (Ud) ≤ 2.5 VDC @ max. load Minimum operational
current (Im) ≥ 1 mA OFF state current (Ir) ≤ 0.3 mA
3 - 20%
n
r
Protection Short-circuit, reverse polarity, transients
TRIPLESHIELDTM protection Electrostatic discharge 30 kV Burst 3 kV Airborne HF > 15 V/m Wire-conducted noise >10 V > 3 Vrm (flush mounted)
Response time OFF-ON (ton) ≤ 35 ms Response time ON-OFF (t
Power ON delay (tv) ≤ 200 ms Frequency of operating
cycles (f) 15 Hz Indication
For output ON LED, yellow
Power and signal stability LED, green
Environment Installation category III (IEC 60664, 60664A;
60947-1) Degree of pollution 3 (IEC 60664, 60664A; 60947-1) Degree of protection IP 68 (24 hours) (IEC 60529; 60943-1)
) ≤ 31 ms
off
(non-flush mounted)
rms
Specifications are subject to change without notice (15.06.2017) 1
CA, M12, DC, Teach-in
Specifications (cont.)
NEMA type 1, 2, 12 Operating temperature
-20 to +85°C ( -4 to +185°F) Max. temperature on sensing face 120°C (248°F) Storage temperature
-40 to +85°C (-40 to +185°F) Vibration 10 to 150 Hz, 1 mm/15 g
(IEC 60068-2) Shock 30 g/77 ms, 3 pos, 3 neg
per axis (IEC 60068-2-32)
Rated insulation voltage 500 VAC (rms) Housing material
Body Grey thermoplastic polyester
Adjustment Guide
The environments in which capacitive sensors are in stall ed can often be un
stable as regards to tem-
perature, humi dity ,
object dis­tance and industrial (noise) inter ference. Because of this, Carlo Ga vazzi offers
as standard features in all TRIP LESHIELD™ capaci­tive sensors a user-friendly sensitivity adjustment instead of a fixed sensing range. Likewise, these sensors provide an extend ed sen­sing range to accommodate
Wiring Diagram
Cable gland Polyester, softened Nuts Black, PA12
Connection Cable PVC, 2 m, 4 x 0.14 mm2
Oil proof, grey Plug (M1) M12 x 1 - 4 pin Cable for plug (M1) CONB14NF.. -series
Weight Cable version 110 g Plug version 30 g
Approvals cULus (UL508) CE-marking Yes
mechanically de mand ing are­as and tem perature stability to en sure high immunity to elec tro magnetic interference
Note:
Sensors are factory set (default) to nominal sensing
range Sn. (EMI) and a minimum need for adjusting sensitivity if the temperature varies.
Detection Diagram
Sensor
X
BK
WH
(4)
Target
BN+
(1)
I
< 20mA
I
LOAD
< 200mA
ALARM
(2)
Teach-in
BU-
(3)
Y
-0,080,000,080,160,240,310,39
8,0
6,0
4,0
2,0
0,0
[mm]
-2,0
-4,0
-6,0
-8,0
Sensor front
-2 0246810
Distance [Inches]
Distance [mm]
The PNP- or NPN-load will be automatically detected.
The functions described in the Teach-in guide can be set up by means of the teach-in wire.
It is possible to teach-in several sensors at the same time by connecting the WH-wires in parallel to the common ”BU -” supply.
(#): Plug connections
Important: If the alarm output (WH-wire) is unused, it has to be connected to +supply
0,3
0,2
0,2
0,1
0,0
[Inches]
-0,1
-0,2
-0,2
-0,3
2 Specifications are subject to change without notice (15.06.2017)
Loading...
+ 2 hidden pages