Carlin 601GAS User Manual

Supplement 1
Massachusetts Code
Installer/servicer — Except where specifically
stated otherwise, this manual must be used only by a quali- fied service technician.
Replace manual pages with:
Manual page 4 — Use Supplement page: .................... 2
Manual page 5 — Use Supplement page: .................... 3
Manual page 12 — Use Supplement page: ................... 4
Manual page 15 — Use Supplement page: ................... 5
Manual page 17 — Use Supplement page: ................... 6
Manual page 19 — Use Supplement page: ................... 7
Manual page 26 — Use Supplement page: ................... 8
This Supplement must be used with the 601GAS Instruction
manual, part number MN601GAS. Information given in this supplement replaces Instruction manual content where indi­cated.
In the state of Massachusetts, this product must be installed
by a licensed Plumber or Gas Fitter.
Failure to comply with this or other requirements in this manual
could result in severe personal injury, death or substantial property damage.
Co p y r i g h t 2007 — Carli n C o m b u s tion Tec h n ology, I n c .
©
Carlin Combustion Technology, Inc.
70 Maple Street East Longmeadow, MA 01028 Ph 413-525-7700 Fx 413-525-8306
Tech support 800-989-2275
carlincombustion.com
Model 601GAS burner — Instruction manual — Supplement – Massachusetts Code
Rep lac e Instr uct i on man u al cont ent :
This page replaces Instruction manual page 4.
Where appliance instructions differ from this manual, follow the appliance instructions.
601GAS Massachusetts Code burner at-a-glance . . .
1 Manual gas valve (with two test tappings)
Gas supply entrance (gas train size): — 1” NPT or 1¼” NPT (gas train size depends on input and application)
Supply pressure: 5” w.c. min; 14” w.c. max; natural gas or propane
2 Gas pressure regulator
3 Gas pressure regulator vent port (fitted with fixed orifice; vent to outside where
required by applicable codes)
4 Low gas pressure switch — manual reset
5 Automatic gas valve
6 Junction box with terminal strip
7 Automatic gas valve (two-stage regulating diaphragm valve)
9 High gas pressure switch — manual reset
10 Manual gas valve
10a Burner gas manifold pressure test port, 1/4” NPT
11 Union
12 Orifice nipple (burner gas orifice plug located inside)
13 Burner gas connection, 1” or 1¼” NPT
14 Air tube (flange omitted for clarity), with powder coat paint finish
15 Flame rod/insulator assembly
16 Combustion head assembly
17 Gas saddle connection gasket
18 Gas manifold
19 Ignition electrode/insulator assemblies
20 Motor (with permanently-lubricated bearings and thermal overload protection)
21 Hinged burner flange door — for access and removal of combustion head/gas
manifold assembly
22 Ignitor (Carlin Model 41000 solid state electronic ignitor — 14,000 volts, continu-
ous duty rated)
23 Hinged cover plate (for access to blower wheel & electrodes)
– 2 –
24 Airflow proving switch — Prevents burner from firing if air is not moving
25 Air damper — Only a single adjustment required for setting combustion air; see
page 9 for starting setting based on input
26 Door interlock switch — prevents burner operation if flanged door is open
27 Primary control — Carlin Model 60200FR microprocessor-based interrupted
ignition flame supervisory control (flame rectification); Flame current test jack is located to right of control terminal strip
28 Burner junction box (installer electrical entrance)
29 Time delay relay (8-second)
Carlin part number MN601GASM Rev. 05/01/07
Model 601GAS burner — Instruction manual — Supplement – Massachusetts Code
Where appliance instructions differ from this manual, follow the appliance instructions.
Rep lac e Instr uct i on man u al cont ent :
This page replaces Instruction manual page 5.
601GAS Massachusetts Code burner at-a-glance . . .
ITEM 7 — Model 601GAS Massachussetts Code
burners use a two-stage regulating diaphragm valve in place of the standard diaphragm valve. The gas valve shown in this illustration is the standard diaphragm valve.
ITEM 29 — Massachusetts Code burners also
include an 8-second time delay relay, located under the gas train junction box.