Carel supernode Operating Manual

Page 1
supernode
Electronic controller for humidication
Technical Leaet
Integrated Control Solutions & Energy Savings
Page 2
Symbol:
Warning: The symbol in the plastic cover of the control means to refer to this technical leaet during the electrical installation.
Page 3
ENG
1. INTRODUCTION
The gateway can connect up to a maximum of 20 devices (humiSteam X-plus, heaterSteam, gaSteam), allowing up to 150 variables (50 analogue, 50 integer, 50 digital) for each connected device to be managed by the external supervisor. Seven pre-set templates allow the variables exchanged between the humidier and the gateway to be addressed automatically, depending on the device selected during programming: simply specify the type of device and the number of devices connected. The built-in pGD on the Supernode or an external pGD1 terminal can be used for programming.
Supernode or Kit* part number:
Description CAREL Code
Supernode for humidication + FLSTDmUGWS (controller only) SNU0000EM0 Kit Supernode HUM BACNET MSTP SNS0000EM0 +SNSCON00M0 +PCO10B0BA0
+CVSTDUMOR0 +FLSTDMUGWS Kit Supernode HUM BACNET ETHERNET WEB SNS0000EM0 +SNSCON00M0 +PCO10B0WB0
+FLSTDMUGWS Kit Supernode HUM MODBUS SNS0000EM0 +SNSCON00M0 +PCOS004850 +FLSTDMUGWS A-KSNU0CL4811
A-KSNU0CLBA11
A-KSNU0CLWB11
* Note: The Supernode Communication kits contain the controller, the connectors, and the appropriate communications card. The kit also contains a USB-Flash drive with the product manuals, technical leaets, device guides, and the Supernode variable to unit address mapping list.
On the external supervisor side, the protocol can be selected by choosing the corresponding optional serial card. The possible options are:
Item P/N Description
1 Modbus®/CAREL RS485 PCOS0004850 Opto-isolated RS485 serial 3 BACnet™ Ethernet™ PCO10B0WB0 Ethernet™ 8 MB serial 4 BACnet™ RS485 PCO10B0BA0 BACnet™ MS/TP 485 serial
tab. 1a
The module is DIN rail mounted, with 24 Vac power supply (+10%, -15%).
Supernode for humidication allows the possibility to select UR, UEX, and UG humidiers, including a combination of dierent models.
For the address settings of the variables on the supervisor side, refer to the dynamic table (included on the USB drive) the “FLSTDmUGWS_Supervisory_List_dinamic_table_supernode_for_ humidication” Excel le.
The application on Supernode also features the following options:
• Edit the humidier model, if necessary add/re-address the pre-set variables.
• Manage a generic device using the “Universal” model, which can be freely edited according to customer requirements.
3
Page 4
ENG
2. INSTALLATION
Install and mount the controller in a location that is appropriate for an industrial PLC.
Mechanical fastening
The Supernode is installed on a DIN rail. To fasten the unit to the DIN rail, press it lightly against the rail. The rear tabs will click into place, locking the unit to the rail. Removing the unit is just as simple, using a screwdriver through the release slot to lever and lift the tabs. The tabs are kept in the locked position by springs.
Below is a description of the connectors used for connection and installation of Supernode:
3 4
2.1 Connectors
Y2
Y1
PWM 0/10V
GNX
Tx/Rx
ISOLATED
+5Vref
+VDC
ID1
J4
C622P028/R2
input voltage: max. power: 24 V (+10/-15%); 50/60 Hz
8 VA / 6 W
48 V (36Vmin…72 Vmax)
J1
SYNC
G
G0
TLAN
GNDTx/Rx
J7
J6
serial card 2
serial card 1
B1B2B3B4B5B6GND
GND
J2
1 5 2
Key
1 power connector (G+,G0) 24 Vac or 36 V min...72 V max 2 SPDT relay digital output 3 pLAN network connector 4 optically-isolated “Field-Bus” serial connector 5 connector for BMS serial cards
GND
GNDJ3C1
C2
NO2
J10J9J8J5
NC1
NO1
4
Page 5
ENG
2.2 Connection diagram
Note: See each specic product/component technical leaet for specic wiring connections.
+
­GND
GND
RS485 CAREL master
serial card 2
RS485 CAREL slave
+
­GND
+
­GND
device 1
device 2
G0
serial card 1
+
­GND
device n (n<=20)
G
BACnet™ MS/TP
status RS485
P1 P2 P3
GNX RS485+ –
PCO1000BA0
PCOS004850 RS485 serial card
BACnet™ MSTP RS485 interface
PCO1000WB0
-Ethernet™/BACnet™ interface card
5
Page 6
ENG
Alarm
Escape
Down
Enter
3. PROGRAMMING AND CONFIGURING THE DEVICES
Navigation of the Display Masks
Use the “Alarm”, “Program”, “Esc”, “Down/Up”, and “Enter” keys. Note: depending on the model of Supernode, the buttons may dier as indicated here below. In typcial control mode, the button icons are displayed on the masks in the controller software.
PRG ESC
clear
Up
3.1 Programming the Supernode
Use Password: 1234 for entering the Service or Manufacturer menu.
1. Set the number of devices connected to the gateway:
Values available: from 1 to 20 devices. Menu path: Service Service Settings Device settings
2. Set the address and type of device :
Models available: heaterSteam, humiSteam X-plus, gaSteam, generic device Menu path: Service Service Settings Device settings
The address setting and type of model must be selected for each device connected to the gateway.
6
Page 7
3. Set the BMS1 and BMS2 serial port for reading by external supervisor:
Address, protocol and baud rate setting. Menu path: Service BMS Cong.
4. Set the Carel master protocol for communication between Supernode and devices:
ENG
Supernode communication protocol setting with devices: baud rate (Retry n. and ORT can be left as default) Note: the baud rate to be set always corresponds to the slowest device connected (for heaterSteam the baud rate is 9600). Menu path: Manufacturer Factory Settings
5. Edit the model:
The selected model can be edited Menu path: Manufacturer Devices cong 1-10
6. Alarm settings:
Enable alarms in the event of supervisor oine Menu path: Manufacturer Factory Settings
7
Page 8
ENG
3.2 Conguring the Communications Card
Each type of protocol card has dierent tools and procedures needed to setup the card.
In general, the pCOnet and pCOWeb cards need; device instance (BACnet ID), Baud Rate, The MS/TP station address (MAC Address), and Max Master and Max frames. These settings can be congured in 2 ways; Using BACset, or by directly in the Supernode controller screens/masks;
• Using BACset on a computer and USB/485 Converter (see guides on using MS-TP startup and pCOnet/web cards).
• Using the pGD display on the Supernode controller (see guide on BACnet BIOS menu). On the PGD; hold alarm & enter: other informationPCOWEB/NET CONFIGPCONET
DHCP:---
IP ADDRESS:
---.---.---.---
3.3 Conguring the humidier unit
Please reference each specic humidier product manual for supervisory control setup. For reading of the humidier, most units will not need any settings changed. For both reading/writing (control the humidier by BMS), each unit will need some settings changed. In general, each humidier will have a setting for the control type and supervisory system:
• Type of control; on/o, slave-proportional, stand-alone %RH control, etc.
• Enable the humidier to be controlled by supervisory system (on/o enable, and control regulation by BMS).
8
Page 9
ENG
4. COMMUNICATING TO THE HUMIDIFIER(S)
The Supernode for humidication allows the possibility to select UR, UEX, and UG humidiers, including a combination of dierent models. For the address settings of the variables on the supervisor side, refer to the dynamic table (included in the USB Drive) “FLSTDmUGWS_Supervisory_List_dinamic_table_supernode_for_humidication” Excel le. The table includes the variable list table for heaterSteam, humiSteamx-Plug, gaSteam, and a generic device on separate tabs.
Note: When more than (1) device is in the system, use the appropriate device tab, and device number at the top to generate the correct variable addresses.
This table can be used also for generating the variable for more than 1 device (device 2-20).
9
Page 10
ENG
Note:
10
Page 11
Note:
ENG
11
Page 12
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: [email protected] - www.carel.com
CAREL USA
385 South Oak Street Manheim, PA 17545 Tel. (717) 664-0500 - Fax (717) 664-0449 e-mail: [email protected] - www.carel.com
Agenzia / Agency:
+08U003325 Supernode for humidication - 1.0 - 14.05.2015
Loading...