Carel ROC025500N, ROC0605000, ROC040500N User Manual

Reverse osmosis system with pump
compact
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
ENG
IMPORTANT
WARNINGS
CAREL Industries reverse osmosis systems (WTS) are advanced products, whose operation is specifi ed in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com. Each CAREL Industries product, in relation to its advanced level of technology, requires setup/confi guration/ programming/commissioning to be able to operate in the best possible way for the specifi c application. Failure to complete such operations, which are required/specifi ed in the user manual, may cause the fi nal product to malfunction; CAREL Industries accepts no liability in such cases. The customer (manufacturer, developer or installer of the fi nal equipment) accepts all liability and risk relating to the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. CAREL Industries may, based on specifi c agreements, act as a consultant for the installation/ commissioning/use of the unit, however in no case does it accept liability for the correct operation of the system and the fi nal installation if the warnings or suggestions provided in this manual or in other product technical documents are not heeded. In addition to observing the above warnings and suggestions, the following warnings must be heeded for the correct use of the product:
DANGER OF ELECTRIC SHOCK: Lthe system contains live electrical
components. Disconnect the mains power supply before accessing inside parts or during maintenance and installation.
DANGER OF WATER LEAKS: the automatically and constantly fi lls/
drains certain quantities of water. Malfunctions in the connections or in the system may cause leaks.
IMPORTANT
Environmental conditions and supply voltage must comply with the
values specifi ed in the product "dataplate".
Installation, use and maintenance must be performed by qualifi ed staff ,
aware of the required precautions and able to make the operations involved in the proper way.
The supply is designed exclusively to humidify rooms in direct mode or
using distribution systems (ducts).
All the operations performed on the product must be made following
the instructions of this manual. Any uses or modifi cations that are not authorised by the manufacturer are considered improper. CAREL Industries declines all liability for any such unauthorised use.
Do not attempt to open the system in ways other than those specifi ed
in the manual.
Observe the standards in force in the place where the system is
installed.
Keep the system out of the reach of children and animals.
Do not install and use the product near objects that may be damaged
when in contact with water (or condensate). CAREL Industries declines all liability for direct or indirect damage following water leaks from the system.
Do not use corrosive chemicals, solvents or aggressive detergents to
clean the inside and outside parts of the system, unless specifi cally indicated in the user manual.
Do not drop, hit or shake the system, as the inside parts and the linings
may be irreparably damaged.
CAREL Industries adopts a policy of continual development. Consequently, CAREL Industries reserves the right to make changes and improvements to any product described in this document without prior warning. The technical specifi cations shown in the manual may be changed without prior warning. The liability of CAREL Industries in relation to its products is specifi ed in the CAREL Industries general contract conditions, available on the website www.carel.com and/or by specifi c agreements with customers; specifi cally, to the extent where allowed by applicable legislation, in no case will CAREL Industries, its employees or subsidiaries be liable for any lost earnings or sales, losses of data and information, costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL Industries or its subsidiaries are warned of the possibility of such damage.
DISPOSAL:
The system is made up of metal parts and plastic parts. In reference to European Union directive 2002/96/EC issued on 27 January 2003 and related national legislation, please note that:
1. WEEE cannot be disposed of as municipal waste and such waste
must be collected and disposed of separately;
2. the public or private waste collection systems defi ned by local
legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment;
3. the equipment may contain hazardous substances: the improper use
or incorrect disposal of such may have negative eff ects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or
on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the
penalties are specifi ed by local waste disposal legislation.
Warranty on materials: 2 years (from production date, excluding consumables).
Approval: the quality and safety of CAREL products are guaranteed by the ISO 9001 certifi ed design and production system.
3
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
4
Content
1. GENERAL FEATURES AND MODELS 7
1.1 Description of the unit .............................................................................................7
1.2 General principle of reverse osmosis ..............................................................7
1.3 ROC operating principle .........................................................................................7
1.4 End of production of desalinated water .......................................................7
1.5 Part description ............................................................................................................8
1.6 Technical specifi cations
(for ROC025500N - ROC040500N - ROC0605000) ..................................9
1.7 Electrical system conformity ................................................................................9
2. INSTALLATION 10
2.1 Installation of cartridges ......................................................................................10
2.2 Diaphragm assembly .............................................................................................10
2.3 Water connections ..................................................................................................10
3. STARTING THE SYSTEM 12
3.1 Checks to be performed whenever starting the system.................12
3.2 Switching on and password entering .........................................................12
3.3 Language selection ................................................................................................12
3.4 First start.........................................................................................................................12
3.5 Checks and adjustment after start ................................................................12
3.6 System stopping .......................................................................................................13
3.7 Summary of the start and adjustment step ............................................13
3.8 List of available menus .........................................................................................14
ENG
4. TROUBLESHOOTING 15
5. MAINTENANCE 17
5.1 Routine maintenance ............................................................................................17
5.2 Overtime maintenance ........................................................................................17
5.3 Disposal ..........................................................................................................................17
5.4 Instructions for emergency situations ........................................................17
6. REGULAR MAINTENANCE RECORDING FORM 18
7. SPARE PARTS 19
7.1 ROC025-ROC040 spare parts ............................................................................19
7.2 ROC060 spare parts ................................................................................................20
8. WATER CIRCUIT 21
8.1 ROC025/040 water circuit ...................................................................................21
8.2 ROC060 water circuit .............................................................................................22
5
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
6
1. GENERAL FEATURES AND MODELS
ENG
1.1 Description of the unit
The reverse osmosis systems described in this manual are purpose­built for treating water used in technological processes. These units can resolve the problem of excessive mineral salts in the feed water. Reverse osmosis systems are made up of the following main components:
micron fi lter;
high pressure pump;
desalination module
electrical control panel;
expansion vessel.
Carel code Description
ROC025500N
ROC040500N
ROC0605000
(osmotic membranes)
Reverse osmosis system, 25 l/h, with pump and 15 l expansion vessel Reverse osmosis system, 40 l/h, with pump and 15 l expansion vessel Reverse osmosis system, 60 l/h, with pump and 15 l expansion vessel
;
Tab. 1.a
1.2 General principle of reverse osmosis
Osmosis is a natural process whereby diluted or lighter solutions spontaneously pass through semipermeable membranes into more concentrated solutions. When a solution passes through a semipermeable membrane, the pressure on the side with the lower concentration decreases and at the same time the pressure of the more concentrated solution increases, until reaching a point of equilibrium, at which point the solution stops fl owing. The pressure diff erence between the two solutions, in conditions of equilibrium, is called the “osmotic pressure”. Reverse osmosis, on the other hand, is a scientifi c process that reverses this natural process. It involves applying a pressure exceeding osmotic pressure to the more concentrated solution, so as to reverse the fl ow through the semipermeable membrane and separate the salts dissolved in the water. This principle can be applied to water desalination, for both drinking and technological uses. Reverse osmosis has several advantages:
water desalination regardless of salt content;
no chemicals that need to be drained after use, so no pollution problems;
relatively low running costs compared to ion-exchange resin systems, above all with high salinity of the water being treated;
easy operation.
1.3 ROC operating principle
The feed water enters the cartridge fi lter that guarantees dechlorination and fi nal fi ltering at 5 m. In this way, the required degree of limpidity for the water entering the permeators is guaranteed. The supply pressure, during standard operation, must be at least 1.5 bar, to guarantee the correct pressure quantity at the pump inlet.
When the pressure exiting the cartridge fi lter is below 0.8 bar, the pressure switch PS1 sends a dedicated signal to the board, stopping the machine. Water is then returned from pump P1 so that the membranes can have the pressure required for the demineralization process. Pressure switch PS2 is adjusted so that it sends a signal should the permeator pressure exceed 10 bar.
Treated water fl ows out the system through the permeate pipe supplied as standard; the system starting and switching off are operated with the aid of pressure switches PS2 and PS3. Example: on a 25 l/h machine (ROC025500N) of standard production, the following approximate values should be found: osmotised water production 25 l/h, discharge 60 l/h, pressure at the permeators 7-8 bar (PI1). These values are theoretical ones, because they can change when the feed water temperature varies and depending on its chemical­physical specifi cations. These values were taken into account for a recovery of 30% (TDS 250 ppm and feed water temperature 16°C); for calculating it, the following operation is required:
RECOVERY (%) =
To adjust the supply pressure to the permeators, you can act on the by-pass screw on the pump. The feed water temperature remarkably infl uences both productivity and quality of the permeate. As temperature increases, even only a few degrees, a higher productivity will be achieved (with an improved recovery) with a worse conductivity value.
PERMEATE
(PERMEATE+DISCHARGE)
x 100
1.4 End of production of desalinated water
The end of production of desalinated water is automatically managed by the electronic control through the pressure switches installed on the permeate piping. The max. pressure switch stops its operation when the pressure on the downstream circuit exceeds a given value (default 4.0 bar). The pressure on the downstream circuit is kept through the expansion vessel (included in the ROC% code). The min. pressure switch restarts the system when the pressure on the downstream circuit drops below 2.0 bar (close to an emptying of the expansion vessel).
Note: WTS Compact systems cannot operate if not coupled with the expansion vessel.
7
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
1.5 Part description
5
Ø 6
Ø 10 Ø 6
Rif. Description Re. circuit, chapter 9 1 Inlet fi lter 2 Inlet water pressure gauge 3 Fill solenoid valve 4 Min. pressure switch for feed water 5 Control electronic board 6 Lane rotary pump, 150 l/h 7 Motor 8 Pump outlet water pressure gauge 9 Osmotic membrane 10 Start pressure switch 11 Stop pressure switch 12 Flow restrictor drain pipe for ROC025 13 Drain pipeline (dia. 8 mm) 14 Permeate pipeline (dia. 6 mm) 15 TEE for expansion vessel
14
4
12
11
10
9
Ø 8
1415171816
Rif. Description Re. circuit, chapter 9 16 Expansion vessel 15 l 17 Permeate user line (dia. 10 mm) 18 Check valve for user line (ball valve, dia. 10)
In the ROC060 models present:
Rif. Description Re. circuit, chapter 9 19 Pump max. pressure switch 20 Flushing solenoid valve 21 Conductivity meter on the permeate line
2
3
6
1
7
8
13
1.6 Overall dimensions and weight (LxHxW))
Model ROC025500N ROC040500N ROC0605000
With package (mm) 600x450x450 600x450x450 650x700x510 Without package (mm) 420x580x200 420x580x200 600x650x270 Total weight (with package) 21 kg 22 kg 23 kg
580 mm
420 mm
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
Fig. 1.a
650 mm
Tab. 1.b
700 mm
8
1.7 Speci cations of the feed water
Water to be treated must be clear and drinking type; it must comply with the parameters recommended by the 98/83/EC standard. The max. allowed concentration is the following:
Appearance 1000 µS Turbidity < 1 NTU Iron < 0,15 ppm SDI (Silt Density Index) < 3 Water temperature 5 ÷ 30 °C Free chlorine < 0,2 ppm TDS (Total Dissolved Solids) < 750 ppm Water hardness < 30 °Fr SO4 < 75 ppm SiO2 < 15 ppm TOC (Total Organic Carbon) < 3 mg/l COD (Chemical Oxygen Demand) < 10 mg/l
Tab. 1.c
Again depending on the characteristics of the water being treated, the membrane separates around 93 % of all dissolved salts and can also trap bacteria. Nonetheless, it is also worth checking the quality of the feed water, so the membrane will not be damaged over time by the action of microorganisms.
1.8 Technical speci cations (for ROC025500N - ROC040500N ­ROC0605000)
Feed water pressure 1,5...4 bar Operating pressure 5 - 10 bar Water temperature 5...30 °C Room temperature 5...40 °C Power supply 230V – 50/60Hz monofase Storage and delivery conditions -5...40 °C and sheltered from
sunlight and excessive humidity
Function conditions 5...40 °C and sheltered from
sunlight and excessive humidity
Tab.1.c
ENG
Minimum feed water fl ow-rate (l/h) 150 (referred to the pump) 150 (referred to the pump) 300 (referred to the pump)
ROC025500* ROC040500* ROC060500*
Production (± 10%) - (l/h) 25 40 80 Drain (for 30 % recovery) - (l/h) 60 90 190 Number of membranes 1 2 2 Membrane model 2" x 15" 2" x 15" 2.8” x 15” Installed power (W ) 245 245 245 Feed water connection Ø ½" F ½" F ½" F Permeate connection Ø Dia. 10 mm pipe Dia. 10 mm pipe Dia. 10 mm pipe Drain connection Ø Dia. 8 mm pipe Dia. 8 mm pipe Dia. 8 mm pipe
Note: the above data refer to clear water, without iron and free
chlorine, at a temperature of 16°C, and TDS of 250 ppm.
1.9 Electrical system conformity
The reverse osmosis desalting kits comply with the following directives:
Machinery Directive 2006/42/EC;
Low voltage directive 2014/35/EC
Electromagnetic compatibility directive (EMC) 2014/30/EC
Tab. 1.d
9
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
2. INSTALLATION
The installation must be performed complying the regulations in force, according to the manufacturer's instructions and by skilled staff . The manufacturer cannot be held responsible for a wrong installation. Electrical safety is obtained only when the equipment is connected to a plug having an effi cient earthing system, equipped with magneto­thermal diff erential protection, as prescribed by the safety standards in force.
THE MANUFACTURER CANNOT BE HELD RESPONSIBLE FOR POSSIBLE DAMAGE CAUSED BY THE ABSENCE OF THE EARTHING SYSTEM OR NON-COMPLIANCE WITH THE STANDARDS IN FORCE.
Secure the system to a wall that can support the total weight with water (min. 25 kg). Use the supplied screws fi tting them in the holes on the sides.
Caution: leave enough space at the front so that the operator can
have space enough for adjustment and/or maintenance operations.
2.1 Installation of cartridges
Before fi tting the cartridge in the vessel make sure that water supply is closed and there is no pressure, then disassembly the fi lter covers using the supplied wrench. Position the new cartridge as shown in the picture and reposition the cover in the proper way, tightening it by the wrench.
2.3 Water connections
The reverse osmosis system can operate properly when the water supply pressure ranges between min. 1.5 bar and max. 4 bar. If pressure is below 1.5 bar, a pressurizing kit must be installed upstream of the equipment. On the other hand, if pressure exceeds 4 bar, a dedicated pressure reducer must be installed upstream of the equipment.
2.3.1 Connection of the system supply
Connect the system supply with a pipe having at least the same diameter as the one of the equipment (1/2" female GAS coupling). Provide for a cut-off valve upstream of the system. Provide for a possible by-pass if water is to be supplied to the users even when the WTS Compact system is stopped.
by-pass
utenza users
Fig. 2.a
Model ROC060 has two inlet fi lters: fi rst position the green charcoal one (CBEC) and then the white micrometric one (CPP)
Fig. 2.b
2.3.2 Connection of the osmotised water line
Connect the pipe of generated water (dia. 6-mm white pipe) to the couplings of the pressure switches (dia. 6-mm quick coupling).
Fig. 2.c
2.3.3 Connection of the concentrate drain line
Connect the concentrate pipe (dia. 6-mm black pipe) coming from the fl ow reducer to a free drain (using the dia. 8 black pipe); the connector between the two pipes D.6 and D.8 is included in the standard supply (Fig. 2.d, 2.e).
The free drain must be earthed or lower than the same connection. The supplied connector (3/8" male thread) can be used with the coupling for a drain pipe, ø 40, from under the sink.
2.2 Membrane assembly
Before fi tting the membrane in the vessel make sure that water supply
is closed and that there is no pressure. Then move away the pipe from the connector and, if required, disconnect it from the quick couplings to create space enough for performing the operation. Undo the vessel cap and fi t the membrane, paying attention to the fi tting direction (black lip seal facing downwards). Then, make sure that the membrane is properly positioned and close the vessel cap.
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
Fig. 2.d
10
ENG
2.3.4 Expansion vessel connection
Connect the permeate pipe (white, 6-mm dia. pipe) to the T-shaped connector (both included in the standard supply). Then, connect them to booster BV1 valve of the expansion vessel (Fig. 2.g, 2.h).
Coupling for pipe
permeate Ø 6 mm
Precharge valve
Expansion vessel
Fig. 2.e
Caution: it is advisable to install the expansion vessel close to the WTS Compact, within a range of 3-5 metres. The distance of the user depends on the diametre of the pipe used for the permeate and on the pressure required to the feed water. With a permeate pipe having 10 mm diameter and with a feed pressure request ≈ 1 bar, the recommended distance should not exceed 20 metres.
2.3.5 Precharge of the expansion vessel
Precharge the expansion vessel using compressed air until reaching a pressure lower or equal to the min. pressure of the permeate pressure switch (~1.5 ÷ 1.8 bar). Charge the vessel through the valve located at the bottom (see arrow, fi g. 2.e).
2.3.6 Storage tank connection
WTS Compact can also be installed with a storage tank equipped with pump. In this case, the authorisation to operation does not depend on pressure anymore (as it happened with the expansion vessel), rather it is determined by the high/low level signal sent by the fl oat inside the tank. In case of installation of WTS compact with storage tank, comply with the following instructions:
open the case of the electronic controller.
disconnect the cables of the pressure switches from terminals 22-23
and 33-34 (factory fi t wiring).
connect the high level signal to terminals 22-23 and the low level
signal to terminals 33-34 (Fig. 2.g).
enable the high level signal from menu "5 HIGH LEVEL - LIVELLO ALTO"
(see paragraph 3.6).
enable the low level signal from menu "4 LOW LEVEL - LIVELLO BASSO"
(see paragraph 3.6).
In these menus you can set the logic of the contact (N.C. or N.O.) and
the delay of the signal (DEFAULT 00 sec.)
2.1 Electrical connections
Connect the system to the single phase line 230 V (50 / 60 Hz) single phase through the supplied socket. The user should not install any other wiring, unless for connecting an alarm output (to be connected to terminals 19 [N.O.]-20 [C]-21 [N.C.]) or an external remote consent (to be connected to terminals 37 [common] - 38 [input]). For completeness purposes, the diagram of all internal connections and available terminals follows:
Caution:
precharge the expansion vessel at 1.5...1.8 bar
Fig. 2.g
Fig. 2.f
Terminal Description ROC025 - ROC040 ROC060
1[L] - 2[ground] - 3[N] Supply input (230 V) 50/60 Hz x x 4[L] - 5[ground] - 6[N] 230 Vac output for pump supply x x 7[L] - 8[ground] - 9[N] 230 Vac output for metering pump -- -­10[L] - 11[ground] - 12[N] 230 Vac for charge solenoid valve x x 13[L] - 14[ground] - 15[N] 230 Vac for drain solenoid valve -- -­16[L] - 17[ground] - 18[N] 230 Vac for fl ushing solenoid valve -- x 19[NO] - 20[C] - 21[NC] Alarm output optional optional 22[C] - 23[IN] Max. pressure switch for permeate line / high level x x 24[C] - 25[IN] Input to high pressure switch for pump delivery -- x 26[C] - 27[IN] Pump cut-out switch input -- -­28[C] - 29[IN] Metering pump alarm input -- -­30[shield] - 31 - 32 Probe for output permeate conductivity -- -­33[C] - 34[IN] Min. pressure switch for permeate line / low level x x 35[C] - 36[IN] Low pressure switch input x x 37[C] - 38[IN] Remote on/off input optional optional 39[C] - 40[IN] Filter inlet from softener -- -­41[shield] - 42 - 43 Input water conductivity probe -- --
Tab. 2.a
11
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
3. STARTING THE SYSTEM
3.1 Checks to be performed whenever starting the system
Each unit is pre-calibrated and tested in the factory according to a suitable testing procedure. At the fi rst starting of the equipment, the user should check as follows:
tightness of the various connections;
operation of the feed water circuit;
electrical connections;
Now water can be supplied to the system by opening the ball valve suitably installed upstream. Wait until the complete fi lling and the wetting of the input fi lter. Check on the pressure gauge if the supply pressure is enough (1.5 bar).
3.2 Switching on and password entering
After electrical and hydraulic connections, switch the equipment on:
press the button at least for two seconds. The display will show
"WAIT ON" for a few seconds (the time used by the equipment to preset), then the current status is displayed.
pressing the arrows and you can display (in read-only mode)
information about the equipment operation (hour counter, conductivity, ...).
press to access the confi guration templates of the system.
enter the PASSWORD. The default value is "0077". To enter the password,
use the value. Press
In this way you enter the list of items that can be modifi ed.
commissioning, thus they do not need any change. Check that the parameter confi guration complies with the default settings (as per paragraph 3.8). Comply with the information of the manual and change only the items listed here below.
and arrows to move the cursor, and to change the
to confi rm.
Caution: the parameters that can be modifi ed were already set at
The procedure is the following:
1. Disconnect the permeate line and temporarily convey it to a free
drain. Slightly open (one third) the feed water tap (suitably installed upstream of the system), so that the water fl ow coming from the network decreases to minimum.
2. Switch the system on keeping pressed the button at least for two
seconds. The display shows WAIT ON for a few seconds, then it shows the main screen. Press the system.
3. enter the password "0077" to enter the menu 01. Now the equipment
functioning is stopped.
4. Using and arrows, scroll to the menu 14 "SYSTEM TEST". Press
to enter.
5. In this menu, all components are deactivated. You can decide to
activate/deactivate the individual components manually, using the following buttons of the controller:
inlet solenoid valve
drain solenoid valve (NOT PRESENT)
fl ushing solenoid valve (ONLY ON ROC060)
pump
metering pump (NOT PRESENT)
6. Press to activate the fi ll solenoid valve: in this way, the N.C. valve is
powered and opens the circuit, letting water in.
FOR ROC060 ONLY: press the arrow to operate the fl ushing valve: in this way, the N.C. valve is powered and opens additional drain, getting an increased water fl ow and reducing the pressure diff erence between upstream and downstream of the membranes.
Note: please note that it is always advisable to let the membranes work at the lowest possible pressure (5...6 bar), above all during start, but also during the system standard operation. This ensures a longer life of the same membranes.
to access the confi guration templates of
Fig. 3.a
3.3 Language selection
With equipment on, press to access the confi guration templates of
the system.
enter the password "0077" to enter the menu 01
Using and arrows, scroll to the menu 16 "LINGUA". Press to
enter.
Scroll the available languages moving and and select among
the available ones (ITALIAN, ENGLISH, FRENCH, GERMAN, SPANISH).
to confi rm.
Press
3.4 First start
During the fi rst start, the purpose is wetting the membranes gradually, without submitting them to the work pressure (5-6 bar) before they are completely wet. Water must fl ow according to the main pressure for a few minutes through fi lters and membranes, before the pump can be operated. Water produced during this stage cannot be used. It is advisable to disconnect the permeate line and free drain all the water produced during the fi rst start.
7. Leave the system in these conditions for at least 10 minutes.
8. Open again a little bit (two thirds) the water tap upstream of the
system, so that the water fl ow reaching the membranes increases. Leave the system in these conditions for at least 10 minutes.
9. Fully open the water tap upstream of the system, leave the system in
these conditions for 10 more minutes.
10. Check that the charge valve (and the fl ushing one if present) are
still open. Now, activate the pump pressing the inside the menu 14).
11. Immediately check the working pressure of the membranes, on the
pressure gauge on the pump delivery side. Turn the adjustment screw opening the by-pass valve of the pump (anticlockwise direction), to reduce the pressure to about 2-3 bar. Leave the system in these conditions for 10 minutes.
12. Close the fl ushing valve if installed (pressing the again). Adjust
again the Bypass (clock wise direction). Make the working pressure correspond to 5-6 bar, that is the standard operating pressure for a WTS Compact with new membranes.
13. Quit the menu 14 pressing and go back to the main template of
WTS Compact. Now the equipment is ready to work properly.
button (still from
3.5 Checks and adjustment after start
After start, some checks for the correct operation of the WTS Compact system must be made.
1. Before connecting the permeate pipe to the expansion vessel, check
that the permeate fl ow rate is correct and the conductivity ranges between the required values.
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
12
ENG
If the permeate fl ow rate is not enough it is advisable to close slightly the by-pass valve of the pump, to increase pressure to the permeators and get a higher fl ow rate of demineralised water (obviously with higher conductivity). Should the permeate conductivity become too high and not satisfactory enough, it is advisable to open slightly the pump by-pass valve, to reduce pressure to the permeators and get water with a lower salt content (with a reduction of permeate fl ow rate produced). Please note that the percentage of salt rejection depends on inlet water quality and temperature and in no way can it be measured only on the conductivity value at the outlet. To adjust the pump by-pass, remember the following basic rules:
clockwise tightening: close the by-pass, then increase the pressure to
the membranes.
anticlockwise loosening: open the by-pass, then decrease the pressure
to the membranes.
2. Connect the permeate pipe to the expansion vessel, that now has
no water. Please note that the vessel must have been precharged with compressed air, till getting a pressure of 1.5-1.8 bar. Let the WTS Compact operate until the vessel is full and thus until the pump stops automatically (according to the value on the max. pressure switch). Check that the stop pressure corresponds to about 4 bar.
3. Manually drain the expansion vessel opening one of the downstream
water taps. Wait until the pump switches on again automatically, activated by the minimum pressure switch. Make sure that the WTS Compact starts again when the pressure on the permeate line is about 2 bar.
3.6 System and intervals of operation
The correct operation of the reverse osmosis system depends on the continuous production of demineralised water. For a stop shorter than 10 days, just leave the equipment powered both electrically and hydraulically, as it occasionally fl ushes the membranes (the default value is 30 seconds every 24 hours of inactivity). This parameter can be selected in menu 11H - WASH CYCLE.
For stops longer than 10 days, up to max. 1-2 months, it is advisable to change the set of periodic fl ushing operations (menu 11H) to 15 minutes every 48 hours. To change the set of fl ushing operations proceed as follows:
enter the list of items that can be modifi ed;
use the and arrows to select the item "11 CLEANING";
press
scroll through all the templates 11A, 11B, 11C pressing , until
template 11H is displayed. Pay attention in order not to change the default values of the scrolled templates.
Template 11H is used to set the fl ushing of membranes cyclically
for an x time every n hours. Set the max. duration of the fl ushing, expressed in minutes and seconds (max. value 99 minutes and 59 seconds) and the recurrence in hours (max. value 99 hours). Use the selected digit; use the Caution: setting "00 h" means that the periodic fl ushing is disabled.
pressing you return to the main menu confi rming the modifi cations
made.
pressing you scroll backwards the various templates, until reaching
the main menu without confi rming the modifi cations made.
For inactivity periods longer than 1-2 months, or when you decide to disconnect the osmosis system from the hydraulic/electric supply, the system maintenance procedure must be applied. This procedure implies draining the system completely and then fi lling it using a dedicated maintenance liquid. This activity must be exclusively performed by authorised technical staff , as agreed with Carel.
Caution: please note that during equipment the expansion and accumulation vessel (if present) must be drained. At the following start, perform a fl ushing procedure of the line and of the vessel, using demineralised water. It is recommended to drain and fl ush periodically the expansion vessel also after long periods of standard operation (about every two months).
and arrows to move the cursor to the
and arrows to enter the value.
3.7 Summary of the start and adjustment step
Close the water tap upstream of the system
CLOSED
Disconnect the permeate line
and temporarily convey it to a drain
Slightly open the water tap (one third)
by 33%
Switch on the system and access menu 14
Start the charge solenoid valve using the UP arrow
Start the fl ushing solenoid valve using the LEFT arrow
Wait 10 minutes
Open the upstream water tap (two thirds)
by 66%
Wait 10 minutes
Completely open the upstream water tap
OPEN
Wait 10 minutes
Activate the pump using the RIGHT arrow
Adjust the pump by-pass so that
pressure reaches 2-3 bar
Wait 10 minutes
Close the fl ushing valve (if present)
Adjust the pump by-pass
so that pressure reaches 5-6 bar
Quit the manual procedure
and restore the standard operation
Check the fl ow rate values of the permeate and its conductivity
Connect the permeate pipe to the expansion vessel
Wait until the vessel is full.
Check that the max. pressure is = 4 bar
Drain the vessel. Check that the min. pressure is = 2 bar
13
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
3.8 List of available menus
1 PROBE CAL. IN Conductivity probe on feed water 1a Zero setting of the conductivity probe not used (due to the ab-
2 PROBE CAL. OUT Conductivity probe on permeate
3 OUT SET POINT Check the conductivity value at the
4 IN SET POINT Check on the conductivity value at
5 LOW LEVEL Min. pressure switch on permeate
6 HIGH LEVEL Max. pressure switch on permeate
7 MINIMUM
PRESSURE
8 MAXIMUM
PRESSURE
9 PUMP TEMP. Protection of the pump motor from
10 FILTER Forced system stop when the
11 CLEANING Flushing at the start or after switch-
WASH CYCLE Flushing of the membranes in a
12 ALARM Output of the alarm signal with
13 RESET Reset of the counter for the work
14 SYSTEM TEST Manual procedure to be activated
15 ALARM TEST Check if the alarm output is
16 LANGUAGE Select the display language Italian / English / French / German / Spanish Italian Italian 17 SET PASSWORD Entering a new password Key in the new password twice to confi rm the choice 0077 0077 18 MAINTENANCE Maintenance warning interval 18a Maintenance warning: enabled / disabled enabled enabled
19 DOSING PUMP Locking alarm signal from metering
20 STAND-BY
INPUT
21 PUMP DELAY Pump delay, recommended when
water
outlet. If conductivity exceeds the set threshold (3B) for a certain time (3D), it locks in DRIVER ALARM FOR SYSTEM STOPPING
the inlet.
line
line
Contact of the min. pressure switch for feed water
Check of the value of max. pressure downstream of the pump (from pressure switch calibrated at 12 bar)
high temperature
upstream softener makes salt regeneration
ing off the system, before or after each production cycle
cyclical way, every "n" hours and for a variable "x" duration
connection to an external device
hours accumulated by the system
individually for each single compo­nent: to be used during the FIRST START of the system
operating
pump
Input for stand-by (remote on-off ) 20a Remote input: enabled / disabled disabled disabled
a return pump is installed upstream of the system
1b Setting of the reading scale of the conductivity probe
2a Zero setting of the conductivity probe not used (due to the ab­2b Setting of the reading scale of the conductivity probe
3a Enabled / disabled not used (due to the ab­3b Conductivity set point at the outlet (from 0.0 to 99.9
µS)
3c Reading at fl ushing end alarm(locking): enabled /
disabled
3d Delay time for alarm signal (from 0 min 0 sec to 9 min
59 sec)
4a Enabled / disabled disabled (due to the ab-
5a Enabled / disabled enabled enabled 5b State of the high level contact (high pressure): N.C. /
N.O. 5c Signal acquisition delay (from 0 to 59 sec) 0 sec 0 sec 6a Enabled / disabled enabled enabled 6b State of the high level contact (high pressure): N.C. /
N.O. 6c Signal acquisition delay (from 0 to 59 sec) 0 sec 0 sec 7a Enabled / disabled Enabled Enabled 7b State of the contact with right pressure: N.C. / N.O. N.C. N.C. 7c Signal acquisition delay (from 0 to 59 sec) 05 sec 05 sec 7d Number of attempts before the alarm 4 4 7e Alarm during fl ushing as well: YES/NO YES YES 8a Enabled / disabled disabled (due to the
8b State of the contact with right pressure: N.O. / N.C. - - - N.C. 8c Signal acquisition delay (from 0 to 59 sec) 00 sec 00 sec
9a Enabled / disabled disabled (due to the 9b State of the contact with right temperature: N.C. / N.O. 9c Signal acquisition delay (from 0 to 59 sec)
10a Enabled / disabled disabled (due to the 10b State of the contact with active softener: N.C. / N.O. 10c Signal acquisition delay (from 0 to 59 sec)
11a Enabled / disabled disabled enabled 11b Flushing with pump: YES / NO no yes 11c Flushing with charge solenoid valve open: YES / NO yes yes 11d Flushing at the beginning of production cycle:
enabled / disabled
11e Duration of the fl ushing from production start
(from 0 to 99 min 59 sec)
11f Flushing at the end of production cycle:
enabled / disabled
11g Duration of the fl ushing from production end
(from 0 to 99 min 59 sec)
11h PERIODIC FLUSHING OF MembraneS: duration of the
fl ushing (from 00 min 00 sec to 99 min 59 sec) and
frequency of the fl ushing (from 00 h to 99 h)
12a Enabled / disabled disabled disabled 12b State of the contact with no alarm: N.C. / N.O. - - - - - -
13a Reset of the hour counter: YES / NO
13b Reset of the time interval before next maintenance:
YES / NO
UP Inlet solenoid valve: enabled / disabled
DOWN Discharge solenoid valve: enabled / disabled absent absent
RIGHT Flushing solenoid valve: enabled / disabled absent
LEFT Pump: enabled / disabled
ENT Metering pump: enabled / disabled absent absent
UP Press the arrow up to manually activate the alarm
18b Interval before maintenance warning (from 0 to 19999 h) 240 h 240 h 19a Input for metering pump alarm: enabled / disabled not used (there is no 19b State of the contact with no alarm: N.C. / N.O. 19c Signal acquisition delay (from 0 to 59 sec)
20b State of the contact with no external signal: N.C. / N.O. - - - - - ­20c Signal acquisition delay (from 0 to 59 sec) - - - - - ­21a Start delay of the pump for the reverse osmosis system
after opening the charge solenoid valve (from 0 to
999 sec)
ROC025 - ROC040 ROC060
sence of the conductivity
meter at the inlet)
sence of the conductivity
meter at the outlet)
sence of the conductivity
meter at the outlet)
sence of the conductivity
meter at the inlet)
N.C. N.C.
N.C. N.C.
absence of the max.
pressure switch)
absence of temperature sensor on pump motor)
absence of the upstream
softener)
disabled enabled
00 min 00 sec 00 min 20 sec
disabled enabled
00 min 00 sec 00 min 15 sec
00 min 30 sec every 24 h 01 min 00 sec every
metering pump)
000 sec 000 sec
absence of the conduc­tivity meter at the inlet) already calibrated in the
absence of the conduc­tivity meter at the inlet)
absence of temperature sensor on pump motor)
disabled (due to the ab-
sence of the upstream
not used (due to the
factory
enabled
80 µS
disabled
5 min 00 sec
disabled (due to the
enabled
disabled (due to the
softener)
08 h
not used (there is no
metering pump)
Tab. 3.a
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
14
4. TROUBLESHOOTING
Alarm Cause Remedy
STOPPED SYSTEM ­HIGH PRESSURE
STOPPED SYSTEM ­LOW PRESSURE
CHECK HI-LEVEL LOW-LEVEL CONTACTS
STOPPED SYSTEM ­CONDUCTIVITY ALARM
MAINTAIN THE SYSTEM The time set for the scheduled maintenance has
The maximum pressure switch downstream of the pump measures a pressure higher than the set value (12 bar) (ONLY FOR ROC060)
The inlet minimum pressure switch measures a feed water pressure lower than the set value (0.8 bar) for a certain number of consecutive attempts
The contact opening/closing sequence for oper­ation authorisation (in the case of vessel fi lling/ draining) is incorrect
During the production phase, the conductivity exceeds the set threshold for a certain period of time (ONLY FOR ROC060)
expired.
- check that the pressure switch is calibrated correctly and that the alarm actually occurs when the set pressure is exceeded (12 bar, readable from the manometer downstream of the pump)
- act on the pump by-pass to reduce the pressure downstream of the pump (sug­gested value between 5 and 10 bar)
- use the menu 8C to set a specifi c delay in reading the maximum pressure switch (5 seconds)
- If the problem persists, check that the permeate pipe is not obstructed and that the produced fl ow is close to the nominal value.
- check that the water supply pipe upstream of the system has a suitable diameter (at least 1/2")
- while reading the inlet pressure on the manometer, check that the supply water pressure is guaranteed (both static pressure with WTS off and dynamic pressure with WTS pump on).
- if there is a pressurisation pump upstream of the WTS, check that it operates cor­rectly. If necessary, delay the WTS pump switching-on (menu 21A) of a few seconds to allow the upstream pressurisation pump to activate.
- check the conditions of the inlet fi lters and the pressure loss caused by them (by means of a pressure gauge upstream and one downstream of the fi lters). If neces­sary, replace the fi lter cartridges and clean the inside of the vessels.
- check that the pressure switch is calibrated correctly and that the alarm actually oc­curs below the set pressure (0.8 bar) Check whether the NC/NO logic of the contact is implemented correctly (menu 7B, with reference to terminals 35-36). If necessary, carry out a new calibration of the pressure switch.
- the authorisation to START is given by a minimum pressure switch (when the pressure drops below 2 bar) or by a fl oat (which indicates the low level). The signal is controlled by terminals 33-34 of the electronic board. Check that the authorisation to START activates the signal (check that the signal is enabled in menu 5A; use a tester to measure the terminal continuity at its ends) and that the signal logic (NC/NO) complies with the one set in the display (menu 5B)
- STOP is given by a maximum pressure switch (when the pressure reaches 4 bar) or by a fl oat (which indicates the high level). The signal is controlled by terminals 22-23 of the electronic board. Check that the authorisation to STOP activates the signal (check that the signal is enabled in menu 6A; use a tester to measure the terminal continuity at its ends) and that the signal logic (NC/NO) complies with the one set in the display (menu 6B)
- Carry out an independent measurement of the produced water conductivity (for example by means of an external conductivity meter)
- check that the conductivity meter on the machine operates correctly; if necessary, clean the head and/or recalibrate the measuring instrument
- check the conditions of the membranes and monitor their performance deteriora­tion over time
- check the supply water quality: the output conductivity always depends on the quality of the supply water.
- correct the threshold value set in menu 3B if it is too low
- basically, the fi rst water produced after a period of inactivity will always have a higher conductivity. It is advisable to increase the alarm delay by a time that can be set in menu 3D
- if you want to ignore the alarm and you do not want to stop the normal operation of the WTS, disable the Output Set Point in menu 3A
- reset the scheduled maintenance timer in screen 13B to the value set in menu 18B
- enable or disable the scheduled maintenance warning in screen 18A; use screen 18B to set the time before maintenance request
ENG
Tab. 4.a
15
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
The following problems can be found and solved with the following procedures:
Problem Solution
The fl ow rate of the permeate is not the rated one. The demineralised water quantity from the permeate line is not enough.
The conductivity of permeate is too high.
The conductivity meter of the WTS Compact is not calibrated (on ROC060 only).
The WTS Compact system never starts or never stops.
Password 0077 does not work. - Try to enter "0000".
- check that the feed fl ow rate is guaranteed and that there are not obstructions on the charge line. Check the conditions of the inlet fi lters.
- check that the pressure generated downstream of the pump and reaching the membranes corresponds at least to 5-7 bar. If necessary, close the by-pass tightening the screw (clockwise). Check that there are no leaks from junctions or pipelines.
- Check the drain line: the installed fl ow restrictor must generate a proper charge loss for generating pressure to the mem­branes and thus for producing permeate. Check that the relationship between drain water and permeate is about unit (0.8 ÷ 1.2). Replace the fl ow restrictor (if necessary).
- check that the membranes are not clogged and refer to the periodic maintenance sheets to check their conditions. In standard conditions, the membranes have a gradual performance loss over time. If necessary, replace the membranes.
- fi rst of all, measure the conductivity of the feed water, because conductivity value at the outlet can always be compared with the inlet one (90%-95% of salty rejection with new membranes).
- conductivity is the most signifi cant value but there are others to be taken into account: the reduction of TDS is extremely important for evaluating the good conditions of the membranes and the good operation of the system.
- when the operating pressure of the membranes is higher, a higher fl ow rate of permeate is generated, with a higher con­ductivity value. - check that the pressure generated downstream of the pump and reaching the membranes corresponds approx. to 5-7 bar. If necessary, open the by-pass loosening the screw (anticlockwise).
- check that the membranes are not clogged and refer to the periodic maintenance sheets to check their conditions. In standard conditions, the membranes have a gradual performance loss over time. If necessary, replace the membranes.
- remove the conductivity meter from its housing and clean the heads. Perform the measurement again.
- check the non-calibration of the conductivity meter on the equipment: to do so, you need to measure the conductivity of the permeate with a second independent device. Make sure that the calibration of the second conductivity meter is certifi ed.
- the conductivity meter on the equipment is calibrated following the standard factory procedure and this operation is not easy to repeat. For a new calibration, proceed as follows: - arrange a buff er solution with known salinity (ranging between 0 and 100 µS), measured through an external device - remove the conductivity meter from its housing and keep it hanging, still connected to the power line - enter the menu 2A ZERO CALIB - press ENTER to confi rm the value displayed in the "lettura" box: in this way, the zero is calibrated - If the "lettura" box displays an irregular value, the display shows "ZERO cal errata"; press ESC to quit without saving, then clean again the heads of the conductivity meter, or replace it. - enter the menu 2B SLOPE CALIB - dip the conductivity meter in the buff er solution with known conductivity - wait until the "lettura" value stabilises - press ENTER to save the measurement or press ESC to go back to the previous menu and quit. - if the conductivity meter measures a conductivity value of the buff er solution extremely diff erent from the actual one (known), replace the conductivity meter.
- the logic of the permeate pressure switches might have been entered in a wrong way: check on the display that status N.C. corresponds to menus 5b and 6b.
- the pressure switch could be not calibrated. Check the calibration pressure by monitoring the behaviour of the WTS and of the pressure switches during the vessel charging (check which is the pressure value that closes the contact) and during the manual draining of the vessel (check at what pressure value the pressure switch opens the contact).
- check the operation of the pressure switches, possibly disconnecting the cables at the ends of the pressure switch, and try to enable/disable the WTS opening the contact. If either pressure switch features an irregular operation, replace the pressure switches. Please note that the max. pressure switch for the permeate is calibrated at 4 bar and is placed in the high position. The min. pressure switch for the permeate is calibrated at 2 bar and is placed in the low position.
- If this password as well does not work, make a "RESET PASSWORD" procedure, restoring the default value "0000". Proceed as follows: - disconnect power supply from the equipment - simultaneously press the buttons "UP" and "ESC" and recon­nect power supply.
- For a few seconds the display shows "RESET PASSWORD" before going back to standard operation. The stored password now is "0000".
- To confi gure a new password, access the menu 17 of the electronic controller.
Tab. 4.b
Please note that the logics of pressure switches on the equipment is the following:
Pressure
Logic Calibration Operating example
switch
Pump min. fl ow rate Permeate min. fl ow rate Permeate max. fl ow rate
N.O. 1 bar >1 bar = closes equipment ON
<1 bar = opens equipment OFF
N.C. 2 bar >2 bar = opens equipment OFF
<2 bar = closes equipment ON
N.C. 4 bar >4 bar = opens equipment OFF
<4 bar = closes equipment ON
Tab. 4.c
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
16
5. MAINTENANCE
ENG
For a good operation of the reverse osmosis system, the working conditions must be constantly monitored, in particular:
check that the concentrate of chlorine concentration in the feed water
is not too high (max. 0.2 ppm);
check that hardness and conductivity of the feed water range between
the limit values (indicated in par. 1.6);
check the inlet pressure and the charge loss due to the fi lter;
check the working pressure of the membranes: it should range
between the limit values (max. 10 bar);
check the conditions of pipes and connections, making sure that there
are no water leaks.
check the permeate water fl ow and the drain water fl ow; monitor the
recovery value;
check the conductivity of the feed water and that of the produced
water;
check the regular operation of the system overtime. It's important that
WTS works regularly. Too long stops aff ect durability and performances;
avoid any prolonged stagnation of water in the expansion vessel, drain,
rinse it and then refi ll it at regular intervals;
keep the equipment and the surrounding area properly clean
For all these operation, a monthly frequency is recommended. It is recommended to note down the operations performed on a copy of the model shown in chapter 7.
5.1 Routine maintenance
The routine maintenance is extremely important: otherwise, the WTS operation might be impaired. In particular, a regular use and a regular production of demineralized water should be ensured, with a suitable frequency of fl ushing steps.
5.1.1 Replacement of the inlet  lters
The inlet fi lter unit is formed by a single CBC charcoal fi lter in the ROC025500N and ROC040500N units. On the other hand, the ROC0605000 model is formed by two fi lters with serial connection; the fi rst one is the CBC charcoal fi lter, while the second one is a CPP micrometric fi lter. These fi lters need a continuous monitoring and replacement, when required.
Replacement of the CBC charcoal  lt
abate the content of chlorine in the feed water. The presence of chlorine in water might damage the membranes beyond repair. The charcoal fi lter has a chemical operation, combining and absorbing all chlorine molecules. Performance decay over time is normal. The CBC cartridge should be replaced:
every four months if the content of chlorine in feed water is lower that
0.1 ppm.
every two months if the content of chlorine in feed water ranges
between 0.1 and 0.2 ppm.
Replacement of the 5 μm CPP micrometric  lter: the CPP micrometric fi lter retains the foreign particles over 5 m. The fi lter has a mechanical operation, making feed water pass through a fi ltering mesh. It is normal for the fi lter to get clogged over time, making less water pass and decreasing its pressure. The replacement of the CPP cartridge is necessary when the system supply pressure (after passing through the inlet cartridge fi lters) is lower than 1 bar during standard operation (pressure shown in the pressure gauge PI01).
5.1.2 Reset of the hour counter for the maintenance interval
To display the production hours of the system, from the home screen showing the system status, press ARROW DOWN, sequentially scrolling through the templates, until reading the working hours of the system (where one working hour corresponds to one decimal) and the count­down of the hours before the next scheduled maintenance operation, displayed by default every 240 operating hours (maintenance interval that can be set through the menu "18B MAINTENANCE").
er: the CBC charcoal fi lter is used to
The reset of the system hour counter (menu "13A HOUR COUNTER RESET) is not recommended, unless exceptional circumstances occur (e.g. replacement of the membranes). The reset of the hour counter for maintenance (menu "13B MAINTENANCE RESET") must be performed after the equipment has signalled the maintenance alarm, meaning that an intervention on the system is required.
The reset of the hour counter can be managed through the user interface, in menu "13 RESET":
The display shows the fi rst template "13A HOUR COUNTER RESET".
The cursor default setting is NO (press OK to confi rm).
Press ARROW UP or DOWN, to change the setting to YES-NO.
Press "OK" to confi rm the selection.
Pressing again, the second template "13B MAINTENANCE RESET" is
displayed
The cursor default setting is NO (press OK to confi rm).
Press ARROW UP or DOWN, to change the setting to YES-NO.
Press "OK" to confi rm the selection.
5.2 Overtime maintenance
Overtime maintenance concerns repair or replacement of one or more components: usually this type of intervention is not required, unless exceptional circumstances occur.
5.2.1 Replacement of membranes
Membranes have a natural decay over time, in particular:
yearly decrease of produced permeate: 7%
yearly increase of conductivity of the produced permeate: 10%
Membranes, after a longer or shorter period, depending on the features and the volume of treated water, get clogged, thus reducing their effi ciency. The decay of membrane performance can depend on the following main factors:
clogging due to precipitation of iron or sulphate and calcium carbonate
biological clogging
long interval between CBC charcoal fi lter replacement (resulting in
corrosion due to the presence of chlorine in the feed water) The replacement is required when the following main parameters in the system change (recorded at the same temperature of the feed water):
decrease of the produced water fl ow rate until reaching an insuffi cient
value for the application connected downstream of the osmosis
system;
too high increase of the conductivity of produced water until reaching
a too high value for the application connected downstream of the
system.
5.3 Disposal
Should you decide not to use the WTS system anymore, it must be dismantled. This operation must be carried out according to the regulations in force and with separate collection of the diff erent materials inside (rubber, plastic, polyethylene, fi breglass, PVC, electronic circuits, etc.).
5.4 Instructions for emergency situations
In case of fi re, use powder fi re extinguishers in compliance with the regulations in force. Never use liquid fi re extinguishers. Pay attention to combustion gases, as they can be extremely toxic.
17
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
6. REGULAR MAINTENANCE RECORDING FORM
Model: WTS Compact Serial number Date of  rst start-up
Regular maintenance recording form (to be fi lled in with a monthly interval)
Values to be measured on the spot
Conductivity at the inlet Conductivity at the outlet
Decay quantity Drain quantity
Expansion vessel
Stop pressure (default 4 bar) Air precharge pressure (default 1.8 bar)
Start pressure (default 2 bar)
Spare parts
Micrometric  lter
Feed water pressure
Water pressure downstream of the  lter
If pressure drop > 1 bar IMMEDIATELY REPLACE THE FILTER or REPLACE EVERY YEAR
Date of last fi lter replacement:
Pump working pressure
(default from 5 to 10 bar)
Recovery value
permeate / (permeate+drain) = about 40-60%
To measure the precharge pressure, it is advisable to drain the vessel and use a pressure gauge to measure the air residual pressure in the same vessel. It is advisable to perform this operation every month, to guarantee the hygiene of the stored water.
Micrometric  lter
Quantity of free chlo­rine in the feed water
If < 0.1 replace 3 months0.1< If < 0.2 replace 2 months
Date of last fi lter replacement:
Osmotic membrane
Replacement recommended when the conductivity value of the permeate or the permeate  ow rate value is not satisfactory any more
Regular replacement recommended once every two years.
Date of last membrane replacement:
Various remarks
N. Date Person in charge Signature
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
18
UV light (optional)
The UV light should be replaced every 10000 hours of opera­tion (about once a year). Date of last UV light replacement:
The removal and cleaning of quartz is recommended ap­proximately every 6 months
Date of last UV/quartz light cleaning:
7. SPARE PARTS
7.1 ROC025-ROC040 spare parts
Where necessary, the parts of the WTS must only be replaced by qualifi ed personnel, when the appliance is off and depressurised. In all cases, contact the supplier or the manufacturer directly.
14 16
13
ENG
5
20
2
4
9b
1b
Rif. n° Code Description
1a ROKC00HOU1 Single BLUE container for water inlet fi lter, 10" - 1/2" connection 1b ROKC00FLT2 Cartridge CBEC 10'' – 5 micron 2 - - - Pressure gauge 0-6 bar – radial connection 1/8'' 3 ROKL00IV12 Water inlet solenoid valve with coil 230 V – 1/2" 4 ROKC00PSLP N.O. min. pressure switch, made of brass, calibrated at 1 bar - 1/4'' 5 ROKC00EP01 Preset electronic control board 6 ROKC00PUMP Pump 150 l/h 7 ROKC00MOT5 Single phase, 230 V, 50/60 Hz, 245 W motor 8 ROKC00MAK1 Kit of pressure gauges for permeate, dia. 25, installed on T-shaped quick coupling (for dia. 6 pipe) 9a ROKC00VESS Vessel for membrane 2" (there are two on ROC040 models) 9b ROKC00MEMB Osmotic membrane (there are two on ROC040 models) 10 ROKL00PSLL Permeate N.C. min. pressure switch, calibrated at 2 bar 11 ROKL00PSHL Permeate N.C. max. pressure switch, calibrated at 4 bar 10-11 ROKC00PSK0 Kit of min./max. pressure switches installed on PVC mount 12 ROKC00FR25 Drain adjuster 800 for ROC025
ROKC00FR40 Drain adjuster 2 x 600 for ROC040 (required quantity: 2)
13 ROKC00BR08 Black pipe, dia. 8 mm for water drain with bracket connector under the sink (L = 3 m) 14 ROKC00P064 PE white pipe, dia. 6 - whole coil L = 100 m 15 ROKC00TEE1 T-shaped connector with quick couplings for dia. 10 pipe
ROKC00RD10 Reduction connection, dia. 10-6 with quick coupling
16 ROKC00KTVE Kit of additional expansion vessel, capacity 15 l + pipe and connectors
ROKC00VE15 Expansion vessel (spare part without pipes and connectors) 17 ROKC00P107 PE white pipe, dia. 10, for permeate line - whole coil L = 150 m 18 ROKC00VALS Quick coupling ball valve for dia. 10 pipe 19 - - - Reduction connection, dia. 10-8 with quick coupling for drain pipe 20 ROKC00WREN Spanner for 10" fi lter tightening
12
11
10
9a
1519
1817
Fig. 7.a
3
6
1a
7
8
Tab. 7.a
19
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
7.2 ROC060% spare parts
14
1c
1b
13
9b
11
10
9a
114
5
3
12
20
8
19
1a
6
7
15
18
17
Fig. 7.b
Rif. n° Code Description
1a ROKL00HOU1 Double WHITE container for water inlet fi lter, 10" - 1/2" connection 1b ROKC00FLT1 Spare fi lter cartridge CBEC 10'' – 10 micron 1c ROKC00FLT3 Spare fi lter cartridge CPP 10'' – 5 micron 3 ROKL00IV12 Water inlet solenoid valve with coil 230 V – 1/2" 4 ROKC00PSLP N.O. min. pressure switch, made of brass, calibrated at 1 bar - 1/4'' 5 ROKC00EP01 Preset electronic control board 6 ROKC00PU00 Pump 300 l/h 7 ROKC00MOT5 Single phase, 220 V, 50/60 Hz, 245 W motor 8 ROKL00MA16 Stainless steel, dia. 63 pressure gauge, 0-16 bar, with brass connector - 1/4" rear connection 9a ROKC00VS28 Vessel for membrane 2.8" 9b ROKL00MEMB Membrane 2.8" 10 ROKL00PSLL Permeate N.C. min. pressure switch, calibrated at 2 bar 11 ROKL00PSHL Permeate N.C. max. pressure switch, calibrated at 4 bar 10-11 ROKC00PSK0 Kit of min./max. pressure switches installed on PVC mount 12 - - - Drain adjuster with check valve 13 ROKC00BR08 Black pipe, dia. 8 mm for water drain with bracket connector under the sink (L = 3 m) 14 ROKC00P064 PE white pipe, dia. 6 - whole coil L = 100 m 15 ROKC00TEE1 T-shaped connector with quick couplings for dia. 10 pipe 16 ROKC00KTVE Kit of additional expansion vessel, capacity 15 l + pipe and connectors
ROKC00VE15 Expansion vessel (spare part without pipes and connectors) 17 ROKC00P107 PE white pipe, dia. 10, for permeate line - whole coil L = 150 m 18 ROKC00VALS Quick coupling ball valve for dia. 10 pipe 19 ROKL00PSHP Pump max. pressure switch, in brass, calibrated at 12 bar - 1/4" - N.C. 20 ROKL00IV14 Flushing solenoid valve, 230 V - 1/4" 21 ROKL00EC01 Conductivity meter for permeate conductivity measurement 22 ROKC00WREN Spanner for 10" fi lter tightening
1620
Tab. 7.b
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
20
8.1 ROC025/040 water circuit
ENG
8. WATER CIRCUIT
PRODUCT
DRAIN
INLET WATER
EV
Fig. 8.a
21
Key
PI pressure gauge PS pressure switch P electric rotary pump CV check valve C.P. control panel FR fl ow restrictor BV ball valve SV solenoid valve EV expansion vassel
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
ENG
8.2 ROC060 water circuit
Key PI pressure gauge
PS pressure switch P electric rotary pump EC conductivity probe CV check valve C.P. control panel FR fl ow restrictor BV ball valve SV solenoid valve EV expansion vassel
EV
"osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
Fig. 8.b
22
CAREL INDUSTRIES - Headquarters
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: carel@carel.com - www.carel.com
Agency:
Klimatbyrån AB Travbanegatan 6, 213 77, Malmö 040-671 27 50 www.klimatbyran.se
"Osmosi inversa" +0300017IE rel. 1.3 - 12.10.2016
Loading...