PGD1 Remote Interface Unit (RIU) Installation
PoolPak Part #: 24-0145 Manufacturer: Carel PPK Models: PoolComPak (ECCPCP), RoofPak (ECCPCP), PoolPak MPK (ICC)
INTRODUCTION
The Remote Interface Unit (RIU) is the main user interface for the ECCPCP and ICC control systems. It can be installed at the PoolPak unit or in another convenient location up to 1000 feet away. Each PoolPak supports connection to as many as three RIUs. All status, set points and configuration points are available through the RIU.
MOUNTING The RIU should be mounted in a convenient location, outside the natatorium, that is protected
from splashing pool water and corrosive air. The ambient temperature of the mounting location must always be greater than 32°F. The maximum distance from the PoolPak control panel is 1,000 feet. For distances greater than 1,000 feet, contact the factory.
Warning!
Failures due to mounting the keypad inside the pool room will not be covered under warranty.
The wall mounting of the terminal first requires the back piece (A) of the RIU assembly. The RIU is designed to fit a single gang, extra-deep electrical box mounted horizontally in the wall. The RJ25 jack and most of the black cable should be placed inside the box before installing the mounting bracket. A ¾” hole must be drilled for the 6-conductor cable which connects the remote interface unit to the PoolPak unit. See figure below and detailed instructions.
1. Fasten the back piece (A) to the gang box using the rounded-head screws supplied in the packaging. Use the screws that come with the box to secure the bracket.
2. Thread the 6-conductor cable through the back piece (A) and connect to the back of front panel (B).
3. Rest the front panel (B) on the back piece A and fasten the parts together using the flush-head screws supplied in the packaging.
4. Finally, fit the click-on frame (C).
ECCIII RIU Install Instructions
SUPERSEDES:
none
FORM NO: RPW02-PGD1RIU-20140711
WIRING
Proper polarity and connection is essential for correct operation of the RIU. Improper wiring can cause permanent damage. See below for the correct cable to connect the RIU (plug in back) with each model controller. At minimum, cable must be 6-conductor (three twisted pairs), 16-20 AWG.
Controller Type of Cable Control Connection
ECCPCP RJ-12 Black Crossover Plug J10 at ECCPCP Ctrl
ICC RJ-12 Black Crossover Plug J10 CMI
For hard-wiring the RIU to the controller, refer to the field wiring diagram in the Installation and Operation Manual specific to your unit.
CONFIGURATION
The RIU network address is set by pressing the UP, DOWN, and ENTER buttons simultaneously and holding them down for approximately 5 seconds. The display will show “Display address setting”. Press ENTER to move the cursor to the current address field. Use the UP and DOWN buttons to change the address to either 10, 11, or 12 and press ENTER.
To configure the PGD1 RIU addresses, press the UP, DOWN, and ENTER buttons simultaneously and hold them down for approximately 5 seconds. The display will show “Display address setting”. Press the ENTER four times to move the cursor past the screens showing “Display address setting”, “I/O Board address” and “Terminal config” Press ENTER to continue. Use the keypad to enter the RIU configuration as follows:
Adr Priv/Shared (x = CM1 I/O address)
P: 0x Trm1 10 Sh Trm2 11 Sh Trm3 12 Sh Ok? Y
When prompted “OK?”, select “Y” to save the configuration and to exit. The RIU will go blank and then beep several times before bringing up the normal status display.
If you have any questions, please call the PoolPak Service department. (800) 959-7725