Carel MCmultizone User Manual

Integrated Control Solutions & Energy Savings
MCmultizone
atomising humidi ers
User manual
3
ENG
WARNINGS
CAREL S.p.A. humidifi ers are advanced products, whose operation is specifi ed in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com. Each CAREL S.p.A. product, in relation to its advanced level of technology, requires setup/confi guration/programming/commissioning to be able to operate in the best possible way for the specifi c application. The failure to complete such operations, which are required/indicated in the user manual, may cause the fi nal product to malfunction; CAREL S.p.A. accepts no liability in such cases. The customer (manufacturer, developer or installer of the fi nal equipment) accepts all liability and risk relating to the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal installation and/or equipment. CAREL S.p.A. may, based on prior agreements, act as a consultant for the installation/commissioning/use of the unit, however in no case does it accept liability for the correct operation of the humidifi er and the fi nal installation if the warnings or suggestions provided in this manual or in other product technical documents are not heeded. In addition to observing the above warnings and suggestions, the following warnings must be heeded for the correct use of the product:
DANGER OF ELECTRIC SHOCK
The humidifi er contains live electrical components. Disconnect the mains power supply before accessing inside parts or during maintenance and installation.
DANGER OF WATER LEAKS
The humidifi er automatically and constantly fi lls/drains certain quantities of water. Malfunctions in the connections or in the humidifi er may cause leaks.
Important
Important:
The installation of the product must include an earth connection, using the
special yellow-green terminal available in the humidifi er.
The environmental and power supply conditions must conform to the
values specifi ed on the product rating labels.
The product is designed exclusively to humidify rooms either directly or
through distribution systems (ducts, atomising racks).
Only qualifi ed personnel who are aware of the necessary precautions and
able to perform the required operations correctly may install, operate or carry out technical service on the product.
For the production of atomised water, only use water with the characteristics
specifi ed in this manual. Important, demineralised drinking water must be used (as specifi ed in the manual). In addition, the particles of water that are not absorbed by the air must be removed using the droplet collection tank (in the humidifi cation section) and the droplet separator (at the end of the humidifi cation section).
All operations on the product must be carried out according to the
instructions provided in this manual and on the labels applied to the product. Any uses or modifi cations that are not authorised by the manufacturer are considered improper. CAREL S.p.A. declines all liability for any such unauthorised use.
Do not attempt to open the humidifi er in ways other than those specifi ed
in the manual.
Observe the standards in force in the place where the humidifi er is
installed.
Keep the humidifi er out of the reach of children and animals.
Do not install and use the product near objects that may be damaged when
in contact with water (or condensate). CAREL S.p.A. declines all liability for direct or indirect damage following water leaks from the humidifi er.
Do not use corrosive chemicals, solvents or aggressive detergents to clean
the inside and outside parts of the humidifi er, unless specifi cally indicated in the user manual.
Do not drop, hit or shake the humidifi er, as the inside parts and the linings
may be irreparably damaged.
CAREL S.p.A. adopts a policy of continual development. Consequently, CAREL reserves the right to make changes and improvements to any product described in this document without prior warning. The technical specifi cations shown in the manual may be changed without prior warning. The liability of CAREL S.p.A. in relation to its products is specifi ed in the CAREL S.p.A. general contract conditions, available on the website www. carel.com and/or by specifi c agreements with customers; specifi cally to the extent where allowed by applicable legislation, in no case will CAREL S.p.A., its employees or subsidiaries be liable for any lost earnings or sales, losses
of data and information, costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL S.p.A. or its subsidiaries are warned of the possibility of such damage.
DISPOSAL
The humidifi er is made up of metal parts and plastic parts. In reference to European Union directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that:
1. WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately;
2. the public or private waste collection systems defi ned by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment;
3. the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative eff ects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties are specifi ed by local waste disposal legislation.
Warranty on materials: 2 years (from the date of production, excluding consumables).
Approval: the quality and safety of CAREL S.P.A. products are guaranteed by
the ISO 9001 certifi ed design and production system, as well as by the mark..
5
ENG
Content
6.6 Scheduled set points ......................................................................................23
7. INSTALLER MENU 24
7.1 Type of control ....................................................................................................24
7.2 Probe confi guration.........................................................................................24
7.3 Operating options ...........................................................................................24
7.4 Special functions ...............................................................................................24
7.5 Supervisor ..............................................................................................................25
7.6 External alarms ....................................................................................................25
7.7 pLAN confi guration .........................................................................................25
8. MAINTENANCE MENU 26
8.1 Reset confi gurations .......................................................................................26
8.2 System information (read only) ................................................................26
8.3 Manual procedure ............................................................................................26
8.4 Hour counter ........................................................................................................26
8.5 Alarm log ................................................................................................................26
9. TABLE OF ALARMS 27
10. ADVANCED FUNCTIONS 28
10.1 Wiring diagrams ..............................................................................................28
10.2 Operating principle .......................................................................................32
10.3 Control principles ...........................................................................................32
10.4 Pressure control ...............................................................................................34
10.5 Drain/fi ll ...............................................................................................................34
10.6 Periodical washing of the water line .................................................34
10.7 Automatic cleaning of the atomising heads .................................34
10.8 Pressure overboots ........................................................................................34
11. GENERAL CHARACTERISTICS OF THE
DISTRIBUTION SYSTEM 36
11.1 Atomising head ...............................................................................................36
11.2 Assembly kit .......................................................................................................36
12. DESIGNING A SYSTEM 37
12.1 Sizing an MC system .....................................................................................37
12.2 Sizing the compressor .................................................................................37
12.3 Sizing air/water lines between cabinet & distribution
system ..............................................................................................................................37
13. INSTRUCTIONS FOR INSTALLATION IN ROOMS 39
13.1 Tips for correct installation .......................................................................39
13.2 Assembling the atomising head ...........................................................39
13.3 Positioning the humidity probes ..........................................................39
13.4 Important rules to be followed .............................................................39
14. INSTRUCTIONS FOR INSTALLATION IN DUCTS 41
14.1 Positioning the atomisation manifold ...............................................41
14.2 Important rules to be followed .............................................................42
14.3 Positioning the humidity probes ..........................................................42
14.4 Manifolds for installation in ducts ........................................................42
15. MAIN ADJUSTMENTS 43
1. INTRODUCTION AND ASSEMBLY 7
1.1 MCmultizone atomising humidifi er .........................................................7
1.2 Models ........................................................................................................................7
1.3 Dimensions and weights ...............................................................................7
1.4 Components ..........................................................................................................8
1.5 Electrical specifi cations.....................................................................................8
1.6 Opening the packaging ..................................................................................8
1.7 Positioning the cabinet ....................................................................................8
1.8 Wall mounting........................................................................................................8
1.9 Opening the cabinet door .............................................................................9
1.10 Components and accessories ..................................................................9
2. WATER AND AIR CONNECTIONS 10
2.1 Characteristics of the water line ...............................................................11
2.2 Type of supply water ......................................................................................11
2.3 Characteristics of the air line ......................................................................11
2.4 Type of compressed air ..................................................................................11
2.5 Type of water and air lines ...........................................................................11
2.6 Water and air line accessories ....................................................................11
3. ELECTRICAL CONNECTIONS 12
3.1 Power supply .......................................................................................................13
3.2 Remote ON/OFF (ID & COM) ......................................................................13
3.3 Modulating control signal (J24 & J2) .....................................................13
3.4 Control signals from ext. voltage-free contact i.e. ON/OFF
humidistat (ID & COM) ...........................................................................................14
3.5 Control signals from air line pressure transducer (J2) ................15
3.6 Connection of NO drain solenoid valve at end of water line
(group of ID terminals) ...........................................................................................15
3.7 External utility control (J13) ........................................................................15
3.8 Cumulative alarm relay (J14) ......................................................................15
3.9 Alarm inputs from external devices.......................................................16
3.11 Enable wash water line on external signal .....................................16
3.12 Supervisor network .......................................................................................16
3.13 Proportional 0 to 10 Vdc output ...........................................................16
4. MASTER/SLAVE APPLICATIONS 17
4.1 Applications for one large space or AHU (single point) ............17
4.2 Applications for multiple spaces or AHUs (multizone) .............17
4.3 Setting the serial address for units with multiple slaves ...........17
4.4 pLAN network connection (J11) ..............................................................18
5. STARTING AND USER INTERFACE 19
5.1 Starting ....................................................................................................................19
5.2 Stopping .................................................................................................................19
5.3 First start-up (setting the language) ......................................................19
5.4 Keypad ...................................................................................................................19
5.5 “Main” screen......................................................................................................... 19
5.6 “INFO” screens (read-only) ............................................................................20
5.7 “SET” screen ........................................................................................................... 20
5.8 “pLAN” screen .......................................................................................................20
5.9 Main menu ...........................................................................................................21
6. USER MENU 22
6.1 Alarm thresholds ...............................................................................................22
6.2 Clock ........................................................................................................................22
6.3 Enable scheduler ...............................................................................................22
6.4 Set scheduler .......................................................................................................22
6.5 Weekly scheduler ..............................................................................................22
16. MAINTENANCE 44
16.1 Maintenance procedures ..........................................................................44
16.2 Kits & optional accessories for the air/water line (see chap. 2) ........44
16.3 Kits & optional accessories for the atomising heads
(see chap. 11) ...............................................................................................................44
16.4 Spare parts for air/water line (see paragraph 1.4) ......................45
16.5 Pre-programmed pCO
3
controllers .....................................................46
16.6 Electrical panel kit and spare parts (see paragraph 1.4) .........46
17. TROUBLESHOOTING 47
17.1 Troubleshooting table .................................................................................47
7
ENG
cabinetdistributionmaintenance
1. INTRODUCTION AND ASSEMBLY
1.1 MCmultizone atomising humidi er
Humidifi cation system designed for medium/large installations, where are a large humidifi cation capacity is required with low energy consumption (high water fl ow without excessive energy costs). Water and air, suitably regulated in terms of fl ow-rate and pressure, are delivered to the atomising nozzles in two separate lines. Due to the special shape of the nozzles, the jet of water is nebulised into a mist of very fi ne droplets (5 to 8 microns). The atomised water can then easily change state and vaporise. The energy required for this transformation is supplied by the ambient air. For each litre/hour of water that vaporises, in fact, the environment gives up around 590 kcal (149 SkJ) of energy. Consequently, there is a decrease in temperature in the environment being humidifi ed, and this process may be useful in many applications (adiabatic cooling). A timed automatic system ensures the atomising nozzles are cleaned periodically, preventing debris or scale from causing malfunctions. Each atomising head is fi tted with a small piston for cleaning any deposits, whenever the control cabinet stops operating. The system guarantees optimal atomisation at all times and prevents dripping when the installation is off . The electronic controller ensures the ambient humidity is kept at the required value, showing the relative humidity read in the room on the display. The MCmultizone system is essentially made up of: control cabinet and compressed air-water supply, atomising nozzles, nozzle assembly kit.
1.2 Models
The MCmultizone humidifi ers are available by:
size: with maximum fl ow-rate of 60 l/h (MC060*), or 230 l/h (MC
models230*);
type of capacity modulation: ON/OFF (MC models***C*), or
proportional (MC models***H*);
power supply: single-phase 230 Vac 50 Hz (MC models****D*), or 110
Vac 60 Hz (MC models****1*);
version: Master (MC models*****M*), or Slave (MC models*****S*);
type of water used: mains, drinking (MC models*********0), or
demineralised/aggressive (MC models*********1).
Models recommended for speci c applications:
for duct applications (or air handling units), proportional units with
high humidity limit probe are recommended.
for applications directly in the room, both ON/OFF and proportional
control units are recommended
1.3 Dimensions and weights
Front view
500 28
580
Air Inlet
Water Inlet
Air Outlet
Water Outlet
Water Drain
Electric Intlet Electric Intlet Electric Intlet
224
detail of the cabinet, side view,
water and air inlet
detail of the cabinet, side view,
outlet (to nozzles)
150 8
303030
40110
101
4182
50100
150
123
224
123 101
50
224
Packaging dimensions:
height (H): 770 mm (30.14 inch);
width (W ) 605 mm (23.82 inch);
depth (D) 255 mm (10.00 inch).
Packaged humidi er weight:
models MC**H(D,1)*0*: 21 kg (46.3 lb);
models MC**C(D,1)*0*: 20.5 kg (45.2 lb).
Installed humidi er weight:
models MC**H(D,1)*0*: 19.5 kg (43 lb);
models MC**C(D,1)*0*: 19 kg (42 lb).
Mechanical speci cations:
Installation: wall mounting;
IP40;
cabinet operating conditions: 1 to 40 °C (34 to 104 °F) <80 % rH non-
condensing;
storage conditions: 1 to 50 °C (34 to 122 °F) <80 % rH non-
condensing.
8
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
1.4 Components
16
1 3
5
42
11 12 13 14 15
10
86
7
9
Key:
1. Electronic controller
2. Terminal (Master version only)
3. Transformer (CAREL code MCKTR00000)
4. Modulating valve regulator (modulating version only, CAREL code
MCKARVA000)
5. Terminal block (fuse kit MCKFUSE000)
6. Air inlet pressure gauge
7. Air pressure regulator/regulator
8. NC air solenoid valve
9. Air line pressure switch (ON/OFF versions only)
10. Air outlet pressure gauge
11. Water inlet pressure gauge
12. Water pressure regulator
13. NC water solenoid valve
14. Water outlet pressure gauge
15. NO water drain solenoid valve
16. Power supply 110/230 Vac 12 Vdc 0.5 A (modulating version only,
CAREL code MCKAL00000)
1.5 Electrical speci cations
Models MC****D*** (230 V 50 Hz)
(1)
MC***CD*00 MC***CD*01 MC***HD*00 MC***HD*01
Vac phases Hz
230 V
1
50/60 Hz
230 V
1
50 Hz
230 V
1
50/60 Hz
230 V
1
50 Hz Power 37 W 44 W 41 W 48 W Current 0.26 A 0.29 A 0.30 A 0.33 A
(1)
Product in compliance with EN55014, EN61000, EN60335
Models MC****1*** (110 V 60 Hz)
(1)
MC***C1*00 MC***C1*01 MC***H1*00 MC***H1*01
Vac phases Hz
110 V
1
60 Hz Power 37 W 44 W 41 W 48 W Current 0.54 A 0.60 A 0.64 A 0.70 A
(1)
Product approved to UL998 & CSA C22.2 No104
1.6 Opening the packaging
make sure the humidifi er is intact upon delivery and immediately
notify the transporter, in writing, of any damage that may be due to careless or improper transport;
move the humidifi er to the site of installation before removing from
the packaging, grasping the neck from underneath;
open the cardboard box, remove the protective material and remove
the humidifi er, keeping it vertical at all times.
1.7 Positioning the cabinet
The humidifi er should be positioned so as to guarantee the following:
reading the values on the display; access to the keypad on the display; opening the front panel; access to the inside parts for checks and maintenance; connection of the air and water supply lines; connection of the air and water distribution lines; power and control connections;
Important
Important: the drain hose must be connected directly to a drain
located at least 50 mm below the level of the atomising nozzles
1.8 Wall mounting
Fasten the humidifi er to a solid support surface using the screws and bracket supplies. Make sure there is enough space to connect the air and water inlet and outlet lines.
390
9
ENG
cabinetdistributionmaintenance
rear of the cabinet
200
440
drilling template
440
200
390
= =
= =
1.9 Opening the cabinet door
1. press and turn anticlockwise using a fl at-head screwdriver (max 8
mm) until releasing the door;
2. open the door on the cabinet by swinging to the left.
1
2
1.10 Components and accessories
Once having opened the front cover of the humidifi er, make sure the following are included:
kit of screws with
plugs for wall­mounting;
PG13 cable glands for the electrical
connections
10
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
2. WATER AND AIR CONNECTIONS
Important: before proceeding, disconnect the humidifi er from the power supply.
--RILSAN PA1
1 O 6 8 x 6 DIN 74324 AIM 29 --
--RILSAN PA1
1 O 6 8 x 6 DIN 74324 AIM 29 --
--RILSAN
PA1
1 O 6 8 x 6 DIN 74324 AIM
29 --
11
12
13
13
14
1
2
3
4
1
5
6
6
7
8
9
Air
Water
10
Connections:
1. Install two manual valves upstream of the installation to allow the
air and water lines to be isolated (not supplied by CAREL).
2. Install an oil fi lter (CAREL code MCFILOIL01) to remove particles of
oil from the compressed air
3. Install a 5 micron air fi lter (CAREL code MCFILAIR01) upstream of the
cabinet to solid particles from the compressed air.
4. Install a 5 micron water fi lter (CAREL code MCC05PP005 and the
fi lter casing code MCFILWAT05) to remove solid particles from the supply water.
5. Optional: install a UV lamp to sanitise the water (CAREL code
MCKSUV00000). The lamp has an external 230 V 50 Hz power supply. These UV lamps are used to eliminate any bacteria from the supply water.
6. Install the air and water lines
7. Prepare a hose at least 50 mm below the level of the atomising
nozzles to drain the water remaining in the lines when the installation is in standby or off .
8. Atomising nozzle assembly kit for rooms and ducts (CAREL code
MCK1AW0000)
9. Atomising nozzles (for the models see par. 11)
10. Optional, install one of the following components:
pressure gauge at the end of the air line (CAREL kit code
MCKMA04000) to display the pressure at the end of the line;
a pressure probe at the end of the line (for the codes of the probes
see Chap. 16.2 “Maintenance“) to measure and display the pressure at the end of the line on the humidifi er display
11. Install the humidity probes (for the codes of the CAREL probes see
Chap. 16.2 “Maintenance“)
12. Install a manual valve at the end of the air line.
13. Install one of the following two valves:
manual valve at the end of the line (not supplied by CAREL).
drain solenoid valve (CAREL code MCKDVWL000 or code
MCKDVWL001) to perform the “drain”, “fi ll”, and “washing” functions (see par. 10.5 “Operating principles”).
14. Optional, install a pressure gauge at the end of the water line
(CAREL code. kit MCKMW02501) to display the pressure at the end of the water line
Fittings provided for the water connections:
side view, water & air inlet side view, outlet (to nozzles)
1
2
1
2
3
Key:
1. air inlet and outlet
2. water inlet and outlet
3. drain water outlet
11
ENG
cabinetdistributionmaintenance
2.1 Characteristics of the water line
Models
MC060*D*0* MC060*1*0* MC230*D*0* MC230*1*0* max  ow­rate (l/h, lb/h, G/d)
60 l/h
130 lb/h
380G/d
60 l/h 130 lb/h 130 lb/h
230 l/h
500 lb/h
1450 G/d
230 l/h
500 lb/h
1450 G/d
inlet pressure (Mpa,Bar,PSI)
0.3 to 0,7 Mpa 3 to 7 Bar
40 to 100 PSI
temperature
1 to 50 ºC / 34 to 122 ºF
inlet
G1/2”F NPT1/4”F G1/2”F NPT1/4”F
outlet
G1/2”F NPT1/2”F G1/2”F NPT1/2”F
drain
TCF 8/10 NPT1/4”F TCF 8/10 NPT1/4”F
2.2 Type of supply water
demineralised water by osmosis;
drinking water ((however more dust in the room and more frequent maintenance and cleaning the nozzles);
softened water (the mineral content dissolved in the water is not reduced).
recommended supply water characteristics unit of
measure
limits
min. max.
pH 6.5 8.5 Specifi c conductivity at 20 °C (
σ
R, 20 °C
)
µS/cm 0 50
Total hardness (TH) mg/l CaCO
3
025 Temporary hardness mg/l CaCO3015 Total dissolved solids (cR) mg/l (1)(1) Dry residue at 180° (R180°C) mg/l (1)(1) Iron + Manganese mg/l Fe+Mn 0 0 Chlorides ppm Cl 0 10 Silicon dioxide mg/l SiO
2
01 Chlorine ions mg/l Cl
-
00 Calcium sulphate mg/l CaSO
4
05
(
1
)= values depend on the specifi c conductivity; in general:
C
R
0,65 * σ
R, 20 °C
; R
180
0.93 * σ
R, 20 °C
Important: the supply water must comply with the requirements of UNI 8884 UNI 8884 standard, “Characteristics and treatment of the water in cooling and humidifi cation circuits”. According to this standard, the humidifi er must be supplied with water that, as well as being drinkable (EC directive 98/83), must remain within the following limits:
electrical conductivity <100 µS/cm;
total hardness <5 °fH (50 ppm CaCO3);
6.5 < pH < 8.5;
chloride content <20 mg/l;
silica content <5 mg/l;
conductivity less than 30 µS/cm (it is recommended to use the MC
cabinet in the version for aggressive water). Similar requirements are also specifi ed in the European reference standards VDI6022, VDI3803.
Upstream of the cabinet, connect the following to the water line:
a water fi lter with a fi lter size no greater than 5 microns (fi lters available
upon request).
an expansion vessel (not supplied by Carel SpA) with a capacity of several
litres, to avoid water hammer that may damage the installation. The water line is tested, and checked at a pressure of 0.35 bars downstream of the cabinet.
2.3 Characteristics of the air line
Models
MC060*D*0* MC060*1*0* MC230*D*0* MC230*1*0* inlet pressure (Mpa,Bar,PSI)
0.5 to 0.7 Mpa 5 to 7 Bar
80 to 100 PSI
temperature
1 to 50 ºC / 34 to 122 ºF
inlet
G1/2”F NPT1/2”F G1/2”F NPT1/2”F
outlet
G1/2”F NPT1/2”F G1/2”F NPT1/2”F
2.4 Type of compressed air
YES
dry and oil-free air
Upstream of the cabinet connect the following devices (available upon request):
a 5 micron fi lter upstream of the cabinet.
a fi lter to remove oil and particles upstream of the 5 micron air fi lter
The air line is tested, and checked at a pressure of 2.1 bars downstream of the cabinet.
2.5 Type of water and air lines
YES
copper pipes (mains drinking water only), plastic hoses, polypropylene hoses: ensure faster and simpler connections by welding.
NO
galvanised steel pipe: may lead to the detachment of impurities, and cause blocking or damage to the nozzles.
Important: Apply sealant to the joints of the pipes and hoses
running to the atomising nozzles (preferably Tefl on or liquid Tefl on).
2.6 Water and air line accessories
code description  ttings reference
dwg. page 10
MCFILOIL01 3/8” oil fi lter for air G3/8”F in /out 2 MCFILAIR01 1/2” air fi lter G1/2”F in /out 3 MCFILWAT05 5” water fi lter container G1/2”F in /out 4 MCKSUV0000 UV sanitising kit G1/4”F in /out 5 MCKPT**000 pressure transducer G1/4”M 10 a MCKMA04000 air outlet pressure gauge 0
to 4 bars
G1/4”M 10 b
MCKDVWL00* NO solenoid valve at end
of line
G1/4”F in /out 13
MCKMW02501 water outlet pressure gauge
0 to 2.5 bars
G1/4”M 14
12
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
3. ELECTRICAL CONNECTIONS
Wiring
Important:
make sure that the cable glands are applied;
to avoid interference, separate the power cables from the probe/external
signal cables.
J2
Control signals from humidity/ temperature probes, external controller & air line pressure transducer
Power supply
Important: install a power switch outside the humidifi er to completely
isolate the mains power supply.
J13
External utility control
Digital Input
Control signals from external voltage-free contact i.e. ON/OFF humidistat alarm input from external devices enable wash water line from external signal
J14
Cumulative alarm relay
J11
Connection for master/slave communication networks (pLAN) External supervisor systems
J24
Power supply for humidity/temperature probes and references for external controllers
Proportional 0 to 10 Vdc output
pCO3 terminal block
service card
NO8
C7
C4
C1
C8
NO7
NO4
NO1
NC8
C7
NO5
NO2
NO6
NO3
C4
C1
Rx-/Tx-
Rx+/Tx+
GND
J9 J10
J11
J12 J13 J14 J15
J5
J4
J3J2
J1
serial card
field card
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V term
GND
+5V
ref
GND
+VDC
G
G0
max. power: 40 VA / 15 W
1
0
ON
J5
J4
J3J2J1
serial card
field card
service card
J24
J9 J10
J11
J12 J13 J14 J15
J2 J4J24
J10 J13 J14J9 J11
13
ENG
cabinetdistributionmaintenance
3.1 Power supply
Depending on the model: MC****D*** voltage 230V 1~ 50Hz MC****1*** voltage 110V 1~ 60Hz
Important: The cables must be shielded and conform to local standards. Install a power switch outside the humidifi er to completely isolate the mains power supply.
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
L N/W GR/PE
Connections:
MC cabinet Power cable
L L/F (phase)
N N/W (neutral)
GR GR/PE (earth)
3.2 Remote ON/OFF (ID & COM)
Use two-wire shielded cable, AWG20/22
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
1
1
Remote ON/OFF
Connections:
MC cabinet Remote ON/OFF
ID1 NC/NO
COM (1 or 2 or 3) CON
GR shield
3.3 Modulating control signal (J24 & J2)
The input control signal connections depend on the control algorithm activated.
cables
up to 30 m: shielded cables, size 0.5 mm2 (AWG20) over 30 m: shielded cables, size 1.5 mm
2
(AWG15) connect the shield (cabinet side) to specifi c earth terminal GR (see connection diagrams)
the signal can come from
a. modulating control with external controller b. modulating control with ambient humidity probe c. external controller & limit humidity probe d. ambient humidity probe & limit humidity probe e. modulating control with temperature control f. mod. control with temperature control & limit probe
To set the type of operation, control and signal: installer menu > type of control (see chap. 7).
a. Modulating control with external controller
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
1
GR
1
External controller
Connections:
MC cabinet external controller
J24 GND REF
J2 B1 OUT
b. Modulating control with ambient humidity probe
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V term
GND
+5V ref
GND
+VDC
1
GR
1
Ambient humidity probe
Connections:
MC cabinet ambient humidity probe
J24
+V term +(G)
GND M
J2 B1 out H
c. Modulating control with external controller and limit probe
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
1
GR
2
GR
1
Limit humidity probe 2 External controller
14
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
Connections:
MC cabinet limit humidity probe external controller
J24
+V term +(G) -
GND M REF
J2
B1 - OUT B2 out H -
d. Mod. control with ambient probe & limit probe
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
1
GR
2
GR
1
Limit humidity probe 2Ambient humidity probe
Connections:
MC cabinet limit humidity probe amb. humidity probe
J24
+V term +(G) +(G)
GND M M
J2
B1 - out H B2 out H -
e. Modulating control with temperature control
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA NTC
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
1
GR
1
Ambient temperature probe
Connections:
MC cabinet Ambient temperature and limit humidity probe
J24
+V term +(G)
GND M
J2 B1 out T
or
J4
J3J2
VG
VG0Y1Y2
Y3
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
NTC
f. Modulating control with temperature control and humidity limit probe
0 to 1 V 0 to 10 V 2 to 10 V 0 to 20 mA 4 to 20 mA NTC
J4
J3J2
ID1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
GR
1
1
Ambient temperature and limit humidity probe
Connections:
MC cabinet Ambient temperature and limit humidity probe
J24
+V term +(G)
GND M
J2
B1 out T B2 out H
Or:
J4
J3J2
ID1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V
term
GND
+5V
ref
GND
+VDC
1
GR
2
GR
1
Limit humidity probe 2 Temperature probe
Connections:
MC cabinet (1) limit hum. probe (2) temperature probe
J24
+V term +(G) +(G)
GND M M
J2
B1 - out T B2 out H -
3.4 Control signals from ext. voltage-free contact i.e. ON/OFF humidistat (ID & COM)
Cables:
up to 30 m: shielded cables, size 0.5mm2 (AWG20) over 30 m: shielded cables, size 1.5 mm
2
(AWG15)
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
1
Contact open: MC unit off Contact closed: MC unit on
1
ON/OFF humidistat
MC cabinet ON/OFF humidistat
ID2 ON/OFF
COM1 COM
GR shield
15
ENG
cabinetdistributionmaintenance
3.5 Control signals from air line pressure transducer (J2)
Transducer:
CAREL (for the codes of the probes see chap. 16.2 “Maintenance“) -0 to 4 bars/ 4 to 20 mA (-11 to 60 psi). Supplied with cable in diff erent lengths, depending on the code (10 m, 50 m, 100 m)
J5
J4
J3J2J1
serial card
field card
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V term
GND
+5V
ref
GND
+VDC
G
G0
input: 24 V / V ; 50 to 60 Hz max. power: 40 VA / 15 W
1
GR
1
Pressure probe
Connections:
MC cabinet cable pressure probe
J2
B3 white C GR shield -
+ VDC black A
3.6 Connection of NO drain solenoid valve at end of water line (group of ID terminals)
NO solenoid valve (normally open):
CAREL code MCKDVWL000 or code MCKDVWL001 (20 VA 24 Vac)
Recommended connection cables
up to 100 m: shielded cables, size 1.5 mm
2
(AWG1.5) up to 200 m: shielded cables, size 2.5 mm
2
(AWG13)
Electrical speci cations of the contact
power 500 VA voltage 250 V current 2 A resistive/inductive
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
1
NO
1
NO solenoid valve (normally open) water line
Connections:
MC cabinet solenoid valve
G0 1
NO4 2
GR 4
3.7 External utility control (J13)
Cable shielded AWG 15/20 Control to interface MC with:
compressors water treatment systems
Electrical specifi cations of the contact
power 500 VA voltage 250 V current 2 A resistive/inductive
Status of the contact in function of MC status:
MC cabinet OFF or in standby
contact open
cabinet with production request
contact closed
1
NO8
C7
C4
NO7
NO4C7NO5
NO6
C4
J13 J14
L
N/W
GR
COM2
COM3
COM3
F1 1A
F2 1A
1
Start compressor / water treatment
Connections:
MC cabinet Output
J13
NO5 ON/OFF
C4 COM
GR shield
3.8 Cumulative alarm relay (J14)
Activated when one or more alarms is detected via a contact/output that can be transferred to a supervisory system
Cable shielded AWG 15/20
Electrical specifi cations of the relay
power 500 VA voltage 250 V
current 2 A resistive/inductive Status and operation of the relay:
contact open no active alarms
contact closed active alarm/alarms
1
NO8
C7
C8
NO7
NC8
C7
J14 J15
L
N/W
GR
COM2
COM3
COM3
F1 1A
F2 1A
1
Alarm relay
Connections:
MC cabinet Output
J14
C07 COM N07 ON/OFF
GR shield
16
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
3.9 Alarm inputs from external devices
Inputs for signalling the status of external devices such as:
air fl ow sensor air compressor alarm
water treatment system alarm Cable: shielded AWG 15/20 Confi guration of type of contact:
see installer menu > external alarms
Connections:
water treatment system
contacts: ID3 & COM1
air compressor
contacts: ID4 & COM1
air fl ow switch
contacts: ID6 & COM2
1
2
ID3
COM1
ID4
COM1
3
ID6
COM2
G0
NO4
ID1
ID2
ID3
ID4
ID6
ID7
COM1 COM2 COM3
F1 1A
F2 1A
1
Alarm relay from water treatment
2
Compressor alarm relay
3
Flow switch alarm relay
Connections:
MC cabinet Relay
ID3 ON/OFF
Alarm relay from water treatment
COM1 COM
ID4 ON/OFF
Compressor alarm relay
COM1 COM
ID6 ON/OFF
Air fl ow switch alarm relay
COM2 COM
GR shield
3.11 Enable wash water line on external signal
Manages the washing of the water line based on an external signal. To do this, set: installer menu > operating options > valve at the end of the line (YES) > special functions > wash > manual
Cable: shielded AWG 15/20
Status and operation of the contact:
contact open
wash line not enabled externally
contact closed
wash line enabled externally
G0
NO4
L
N/W
GR
G0
NO4
ID1
ID1
ID2
ID2
ID3
ID3
ID4
ID4
ID6
ID6
ID7
ID7
COM1
COM1 COM2
COM2
COM3
COM3
F1 1A
F2 1A
1
1
External contact for activating the wash function
Connections:
MC cabinet Relay for activating wash on ext. signal
ID7 ON/OFF
COM1 COM
3.12 Supervisor network
J5
J4
J3J2J1
serial card
field card
service card
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V term
GND
+5V
ref
GND
+VDC
G
G0
NO8
C7
C4
C1
C8
NO7
NO4
NO1
NC8
C7
NO5
NO2
NO3
C4
C1
Rx-/Tx-
Rx+/Tx+
GND
J9 J10
J11
J12 J13 J14 J15
input: 24 V / V ; 50 to 60 Hz max. power: 40 VA / 15 W
J
3J2
J1
f
ield card
s
ervice car
d
III
ID8ID
C1
B4BC4B5B
C5B1B2B3
J2
4
V
te
rm
ND
V
ND
VD
C
NO
8
4
N
O7NO
4
N
O1
NC
8
N
O5NO2NO3
4
x-
/
Tx-
Rx+
/
Tx
+
ND
J9
J
10
J11
J12J13
J14
J15
input: 24 V / V ; 50 to 60 Hz
max. power: 40 VA / 15 W
DDDDD
D
CAREL optional cards
network/card protocol supported
PCOS004850 RS485 CAREL, Modbus®
PCO100MDM0
RS232 (external modem)
CAREL for remote connections
PCO1000WB0 Ethernet™
TCP/IP SNMP v1 &v2c BACnet™ Ethernet™ ISO8802-2/8802-3 BACnet/IP
PCO10000F0 LON in FTT10 (*) LON-Echelon
PCO1000BA0
Ethernet™ (Modbus®)
BACnet™ MS/TP
(*) When suitably programmed
Important: Follow the instructions provided with the optional cards as regards the technical specifi cations, connections and expansions.
3.13 Proportional 0 to 10 Vdc output (J4)
Parallel output to the 0 to 10 Vdc signal sent to the proportional valve.
J5
J4
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG0Y1Y2Y3Y4
BC5
0...10 Vdc
Rif.
MC cabinet Outputs
VG0 REF.
Y1 0 to 10 Vdc
Output speci cations: maximum load 1 kΩ (10 mA)
17
ENG
cabinetdistributionmaintenance
4. MASTER/SLAVE APPLICATIONS
MC master cabinet: unit fi tted with display to manage the operation
of the unit itself and the other units connected
MC slave cabinet: unit without display that normally works based on
the controls received from the master
pLAN: serial communication system to connect the master unit to the
slaves across a local network
each master unit can be connected to up to 5 slave units
serial address: numeric code that automatically identifi es each unit
cabinet in the installation. Master unit: address 1, Slave unit: address
2. The serial address is already stored in the controller on the unit, and should only be modifi ed on the Slave unit when there are multiple units (see paragraph 4.3)
for the software confi guration of the pLAN net work, see installer menu
> pLAN con guration
4.1 Applications for one large space or AHU (single point)
Ideal for large rooms (or air handling units) where the required water
capacity exceeds the output of a single MC cabinet.
Only the master unit is fi tted with a probe, and the values saved are
applied to all the units connected.
pLAN
Sla
ve
1
Maste
rSl
ave 5
W
ater & Air line
s
up to 5 Slave units
AHU /Room 1
AHU - Air Handling Unit
4.2 Applications for multiple spaces or AHUs (multizone)
Ideal for applications in a series of separate rooms (or air handling
units).
Each MC cabinet is fi tted with a probe, the values saved by each probe
are managed by the cabinet this is connected to.
To ensure continuity of operation in the event of interruption of the
serial communication see installer menu > type of control > stop slave offl ine.
pLAN
Sla
ve 1
aster
Slave
5
W
a
ter &Air lin
es
up to 5 Slave units
AHU /Room
2
AHU /Room
1
AHU /Room
1
AHU - Air Handling Unit
4.3 Setting the serial address for units with multiple slaves
The serial address is used to automatically identify each MC unit in the
installation.
The address is already confi gured: for the master unit=1; for the slave
unit=2.
The slave units do not have terminals.
In systems with a series of slaves, the serial address must be changed
to avoid having the same address (2) on all the units (causing confl ict in the event of pLAN communication).
To set the pLAN address, use the kit PGD0002F0K.
Important: The serial addresses must be changed before
connecting the pLAN network.
Instructions for changing the serial address on the slave units using the kit PGD0002F0K:
complete the power supply connections (see paragraph 3.1);
switch off the MC cabinet (make sure the power supply is
disconnected);
connect the cable in the terminal kit to output J10 on the cabinet
switch the cabinet on;
press the ALARM and UP buttons together until the display shows the
message “self test please wait” (displayed for a few seconds, before the address setting screen) ;
set the required address using UP or DOWN (to a value higher than 2)
and press ENTER to confi rm and exit;
the MC slave unit has now been confi gured with a new serial address,
switch the unit off , disconnect the cable and repeat for the other units.
Once confi guration has been completed, connect the pLAN serial line (see the following paragraph)
Important: only change the serial address on the slaves, and not
on the master.
Table of serial addresses (installer’s responsibility, see installer
menu > pLAN confi guration):
unit unit name room or AHU
serial
address
master ................................................ ................................................ 1
slave 1 ................................................ ................................................
.......
slave 2 ................................................ ................................................
.......
slave 3 ................................................ ................................................
.......
slave 4 ................................................ ................................................
.......
slave 5 ................................................ ................................................
.......
18
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
4.4 pLAN network connection (J11)
Use two-wire cables plus earth, AWG 20/22, maximum distance between two cabinets: 200 m (219 yd).
MASTER
SLAVE
GR
GR
service card
Rx-/Tx-
Rx+/Tx+
GND
J9 J10
J11
service card
Rx-/Tx-
Rx+/Tx+
GND
J9 J10
J11
Connections:
MC Master cabinet J11 MC Slave cabinet
J11
RX+/TX+
J11
RX+/TX+
RX-/TX- RX-/TX-
GND GND
In multizone mode, by disabling the “stop slave off line” function, if the pLAN is interrupted the slaves operate independently according to the signals from the probes or/and controllers. In this mode, the values will not be shown on the master display.
19
ENG
cabinetdistributionmaintenance
5. STARTING AND USER INTERFACE
Before starting the humidifi er, check:
water and air connections (chap. 2). In the event of water leaks do not
start the humidifi er before having resolved the problem;
electrical connections (chap. 3)
5.1 Starting
1
0
O
N
5.2 Stopping
1
0
OFF
Note: if the system is stopped for an extended time, open the
valve at the end of the water line to assist drainage. If the system is fi tted with drain solenoid valves at the end of the line (optional), this is done automatically.
5.3 First start-up (setting the language)
On power-up, the following screen is displayed:
Select language:
1. English
2. Italiano
3. Deutsch
4. Francais
5. Espaniol
Press ENTER to go the list of languages, then UP to select the desired language and ENTER to confi rm. This screen remains displayed for 60 seconds.
Subsequently, the following screen will be displayed:
Show language mask at unit start-up Yes/No
YES: the screen for choosing the language will be displayed when the
humidifi er is started the next time;
NO: the screen for choosing the language will no longer be displayed
on power-up.
Note: The language can also be changed from the maintenance
menu (maintenance menu > system info > language).
5.4 Keypad
6
4
5
3
2
1
button function (1)
alarm list active alarms and reset any alarms present
(2)
PRG return to the “main” screen
from the “main” screen access the main menu
(3)
ESC return to the previous screen/display
(4)
UP circular navigation inside the menus, the screens, the
parameters and the values of the parameters from the “main” screen, access an “INFO menu”
(5)
ENTER select and confi rm (like the “Enter” key on a computer
keyboard) from the main menu, access the “SET” screen
(6)
DOWN circular navigation inside the menus, the screens, the
parameters and the values of the parameters from the main screen, access the pLAN screens and connect to the SLAVE cabinets
5.5 “Main” screen
1 2
3
4
6
5
7
8
9
(1) description of unit status (*) (2) line 2 description of unit status (**) (3) value read according to the type of signal connected (4) status of the atomising nozzles:
atomising nozzles operating
atomising nozzles off
(5) time bands set (6) access the “INFO” screen (UP button) (7) access the “SET” screen (ENTER button) (8) access the “pLAN” screen (DOWN button) (9) Symbol on display:
no image: master unit not connected to a network (stand alone)
master unit connected to a pLAN network for multiple spaces
master unit connected to a pLAN network for single spaces
slave unit
20
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
(*) Types of descriptions:
IN OPERATION: atomised water production in progress,
SHUTDOWN ALARM: production stopped due to an alarm,
OFF FROM SUPERVISOR: production stopped by supervisor,
OFF FROM SCHEDULER: production stopped during the set time
band,
OFF FROM REMOTE: production stopped due to opening of the
“Remote ON/OFF” contact,
OFF FROM KEYPAD: production stopped from the keypad (see “SET”
screen),
MANUAL MODE: manual mode activated (see maintenance menu)
NO REQUEST: unit on without production request.
(**) Types of unit status description, line 2:
DRAIN: unit draining;
FILL: unit fi lling the water line;
CLEANING: unit cleaning the heads on the air line;
WASHING: unit washing the water line.
5.6 “INFO” screens (read-only)
Series of read-only screens for displaying the main humidifi er status values. To access, press UP from the “Main” screen. There are two “INFO” screens; to move from one screen to the next, press UP or DOWN. Press ESC to return to the “Main” screen.
Info (1/2)
display UOM
Request
50-100 %
Air line
ON/OFF
Water line
ON/Drain
Type of op..
ON/OFF or Modulating
Press. sensor
bar/psi
Date & time
dd/mm/yy 00:00
Info (2/2)
display UOM
Humidifi er model
In production
YES/NO
Hours production
h
Date & time
dd/mm/yy 00:00
5.7 “SET” screen
Used to set the main values for the humidifi er. From the main screen press:
ENTER to access the menu;
ENTER to move from one value to the next;
UP & DOWN to modify the selected value;
ENTER confi rm and go to the next value.
Parameter range default UOM
Set point 0 to 100
50 %rH- °C/°F
Humidifi er AUTO / OFF
OFF -
Max. prod. 50 to 100
100 %
Prop. band 2 to 19.9
5 %rH- °C/°F
Limit set (
limit probe set
point)*
0 to 100
80 %rH
Prop. band* 2 to 19.9
5 %rH
* visible only if the limit probe is enabled
5.8 “pLAN” screen
From the main screen press:
DOWN to access the menu;
ENTER to select the unit;
UP & DOWN to move from one unit to the next;
ENTER to confi rm.
Units connected
1 (master)
2 (slave)
3 (slave)
4 (slave)
5 (slave)
6 (slave)
Current: Network:
21
ENG
cabinetdistributionmaintenance
5.9 Main menu
To access press PRG from the main screen
Buttons:
UP & DOWN: navigation inside the submenus, screens, and range of
values and settings;
ENTER: confi rm and save the changes made;
ESC: to go back (pressed repeatedly returns to the “Main” screen).
1. User (no password)
1. Alarm thresholds Main probe thresholds
High alarm Low alarm Limit probe thresholds High alarm Alarm delay
2. Clock Clock Hour Day Month Year Format Day
3. Enable scheduler Enable scheduler Scheduler On/Off Variable set point
4. Set scheduler Set scheduler P1-1 P1-2 P2 P3 P4
5.Weekly scheduler Weekly scheduler Monday Tuesday Wednesday Thursday Friday Saturday Sunday
6. Scheduled setp. Scheduled set points Z1 Z2 Z3 Z4
2. Installer (password 77)
1. Type of control Type of operation Type of signal or probe Type of signal or probe Main Limit Unit of measure Stop slave offl ine
2. Probe confi guration Main probe confi g. Min value Max value Offset Limit probe confi g. Min value Max value Offset
3. Operating options Operating options (1/2) Remote p. sensor Max. air press. Min air press. Max air press. offset Min air press. offset Operating options (2/2) Valve at end of line Alarm relay logic Prop. s. set point:
4. Special functions Special func. (1/3) Independent cleaning Enabled Period Duration Special func. (2/3) Washing Start washing Washing period Washing duration Enable fi lling Filling duration Special func. (3/3) Select main screen display Language Show language choice at start-up?
5. Supervisor Supervisor confi g.
ID number for BMS network) Com. speed Type of protocol Enable ON/OFF from supervisor
6. External alarms External alarms Water treatment Logic Compressor Logic Flow switch Logic
7. pLAN confi g. pLAN confi g. (1/2) pLAN Mode Press down arrow to set unit pLAN confi g. (2/2) M1: S2: S3: S4: S5: S6: Alarm delay:
3. Maintenance (password 77)
1. Reset conf. Confi guration Save confi g. Load confi g Default parameters Restore default parameters code: Type of humidifi er
2. System info System info Boot (read only) Bios (read only) Code: Version: Date:
3. Manual procedure Manual controls (1/2) Manual procedure Air valve Water valve Drain valve Valve at end of line Production status Manual controls (1/2) Alarm relay Prop. output Prop. valve
4 Hour counter Hour counter
Hours of production Reset hours
5. Alarm log Alarm log Alarm (read only) Log deleted Time (read only) Date (read only)
22
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
6. USER MENU
From the main screen press:
PROG to access the main menu;
ENTER to select and access the selected menu;
UP/DOWN to move between the submenus;
ENTER to enter the submenus
ENTER to select the parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confi rm selected parameter and go to the next parameter;
ESC to return to the previous menu.
User menu screens:
1. Alarm thresholds
2. Clock
3. Enable scheduler
4. Set scheduler
5. Weekly scheduler
6. Scheduled set point
6.1 Alarm thresholds
parameter par. name range default UOM
Main probe alarm thresholds
high alarm 0 to 100.0 100.0 %
low alarm 0 to 100.0 0.0 %
Limit probe alarm thresholds
high alarm 0 to 100.0 100.0 %
Alarm delay
0 to 999 1 min
6.2 Clock
Used to set the timed activation of the humidifi er
parameter range
hour / min
0 to 23 / 0 to 59
day
1 to 31
month
1 to 12
year
00 to 99
format
dd/mm/yy - mm/dd/yy
weekday
Monday to Sunday
6.3 Enable scheduler
Enable control of the time bands and the set points
parameter enabled
Scheduler On/Off
YES / NO
variable set point
YES / NO
When the time bands are set, the display shows the symbol.
6.4 Set scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled
(see the enable scheduler screen).
Setting of the intervals for the operation of the humidifi er over one day (24h):
time band
ON OFF
P1 P1-1
09:00 13:00
P1-2
14:00 21:00
P2
14:00 21:00
P3
always ON
P4
always OFF
Parameters P1 to P4 can be used set how many times atomised water production is enabled/disabled over a 24h period:
P1 Two daily ON time bands
0 24h
ON
P1-1 P1-2
OFF OFF OFFON
P2 Individual ON time band
0 24h
P2
OFF OFFON
P3 Always ON
0 24h
ON
P4 Always OFF
0 24h
OFF
6.5 Weekly scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled
(see the enable scheduler screen).
Setting of the weekly operation of the humidifi er, using parameters P1 to P4 (confi gured in the previous screen)
parameter type of time band
Monday
P1 to P4
Tuesday
P1 to P4
Wednesday
P1 to P4
Thursday
P1 to P4
Friday
P1 to P4
Saturday
P1 to P4
Sunday
P1 to P4
23
ENG
cabinetdistributionmaintenance
6.6 Scheduled set points
Note: this screen is visible if “variable set point” has been enabled (see the enable scheduler screen).
Setting of diff erent levels of set points throughout the day (24 h):
parameter
ON SETP.
hours %rH
Z1
00:00 0.0 to
Z2
00:00 0.0 to
Z3
00:00 0.0 to
Z4
00:00 0.0 to
Parameters Z1 to Z4 can be used to confi gure up to four diff erent temperature set points at diff erent times of a day (parameters Z1, Z2, Z3, Z4).
Z1 Z2
20% U.R
50% U.R
30% U.R
Z3 Z4
0 24h
By setting the “daily” and “variable set point” time bands, atomised water production can be programmed according to the needs of the utility.
Note:
during the “OFF” time band, the humidifi er is NOT actually off , but
rather atomised water production is temporarily disabled, even when setting manually;
the “daily” time bands have priority over the “variable set point” bands.
For example, setting P4 each Monday (humidifi er off ), parameters Z1, Z2, Z3, Z4 (diff erent set point values) will not be observed, as the humidifi er is not programmed to operate on that day.
24
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
From the main screen press:
PRG to access the main menu;
DOWN to move to the installer menu;
ENTER to move to the password;
UP/DOWN to enter the password “77“
ENTER to access the selected menu;
UP/DOWN to move between the submenus;
ENTER to select the parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confi rm the selected parameter and go to the next parameter;
ESC to return to the previous menu.
Installer menu screens:
1. Type of control
2. Probe confi guration
3. Operating options
4. Special functions
5. Supervisor
6. External alarms
7. PLAN confi guration
To navigate inside the screens:
UP or DOWN to change the value (within the options/range),
ENTER to confi rm and move the cursor to the next value
ESC to return to the installer menu.
7.1 Type of control
Settings: type of operation (ON/OFF or modulating), type of signal or probe, main probe, limit probe, unit of measure & stop slave offl ine.
parameter options/range description
Type of operation
ON/OFF modulating
Type of signal or probe
External contact External proportional signal External proportional signal & limit probe Humidity probe Humidity probe & limit probe Temperature probe Temperature probe & limit probe
Main probe
select between:
NTC; 0-1 V; 2-10 V; 0-10 V (default);
0-20 mA; 4-20 mA; 0-135 ohm; 135-1k ohm
Limit probe
Unit of measure
°C - bar (default) °F - psi
Stop slave offl ine
YES default
if the pLAN network is offl ine the slave units stop
NO if the pLAN network is offl ine the slave units
continue
7.2 Probe con guration
Setting of the minimum value, maximum value and off set for the probes used.
parameter settings range default UOM
Main probe confi g.
Min value 0 to 100 0 %rH °C/ °F Max value 0 to 100 100 %rH °C/ °F Off set -10 to 10 0 %rH °C/ °F
Limit probe confi g.
Min value 0 to 100 0 %rH °C/ °F Max value 0 to 100 100 %rH °C/ °F Off set -10 to 10 0 %rH °C/ °F
7.3 Operating options
Operating options (1/2)
parameter description range default UOM
Remote p. sensor
pressure sensor at end of line for balancing compressed air system
YES/NO NO
max. air pressure
0 to 4 2.1 bar
min. air pressure
0 to 4 1.2 bar
max air press. offset
0 to 9.9 0
min air press. offset
0 to 9.9 0
Operating options (2/2)
parameter description range default UOM
valve at end of line
to allow automatic emptying and periodical washing of the water line
YES/NO YES
logic alarm relay
alarm relay status setting
NO/NC NO
proportional signal set point:
3 to 60 10 %
7.4 Special functions
Special functions: automatic cleaning (1/3)
Nozzle self-clean cycles to reduce the frequency of maintenance.
parameter range default UOM
Enabled
YES/NO YES
Period
0 to 999
30 min
Duration
60 to
999
160 s
Special functions: washing (2/3)
Automatic periodical washing of the water line to increase the hygiene of the installation.
parameter range default UOM
washing
manual/
automatic
man.
start washing
NO/YES NO
washing period
1 to 99 6 h
washing duration
0 to 15 10 min
enable fi lling
NO/YES NO
fi lling duration
1 to 1000 5 s
Special functions (3/3)
parameter range default UOM
select display on main screen
% signal;
Hours; %rH;
°C/°F
%rH
Language
Italian, English,
French,
German,
Spanish
Show language choice at start­up?
YES/NO YES
7. INSTALLER MENU
25
ENG
cabinetdistributionmaintenance
7.5 Supervisor
parameter range def. UOM
ID number for BMS network
0 to 200 1
communication speed
1200; 2400; 4800;
9600; 19200
19200 bps
type of protocol
Carel; Modbus®; Lon;
RS232; Winload
Carel
enable ON/OFF from supervisor
YES/NO NO
7.6 External alarms
parameter range def. UOM
water treatment
NO/YES NO
logic
NC/NO NC
compressor
NO/YES NO
logic
NC/NO NC
fl ow switch
NO/YES NO
logic
NC/NO NC
7.7 pLAN con guration
pLAN con guration : mode (1/2)
parameter range def. UOM
pLAN master/master+slave
master
Mode multizone/single
point
multizone
pLAN con guration: units present and names (2/2)
parameter range def. UOM
M1(*)
YES/NO YES
S2/S3/S4/S5/S6(*)
YES/NO NO
Alarm delay
0 to 99
30 S
The MASTER and SLAVE units are named by default, however they can be renamed using the list of the characters shown below.
ABCDEF GHI J KL MNOP QR S T UV WX YZ0123456789 +-*:;,()/#%
To modify the character in the space selected, use UP and DOWN, to confi rm the character and move to the next space press ENTER.
26
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
Important: the operations described in this menu must only be
carried out by qualifi ed personnel.
From the main screen press:
PRG to access the main menu;
DOWN to move to the maintenance menu;
ENTER to move to the password;
UP/DOWN to enter the password “77“
ENTER to access the selected menu;
UP or DOWN to move between the submenus;
ENTER to select parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confi rm the selected parameter and go to the next
parameter;
ESC to return to the previous menu.
Maintenance menu screens:
1. Reset conf.
2. System info
3. Manual procedure
4. Hour counter
5. Alarm log
8.1 Reset con gurations
Con guration
Functions:
save the set confi gurations,
recall the saved confi guration
parameter range default
save confi gurations
YES/NO NO
load confi guration
YES/NO NO
Default parameters
Functions:
restore default parameters
code
parameter range default
restore default parameters
YES/NO NO
code
display only
8.2 System information (read only)
information display
Boot
read only
Bios
read only
Code
read only
Version
read only
Date
read only
8.3 Manual procedure
Important: these operations must only be performed by qualifi ed personnel, incorrect use may cause serious damage.
These procedures are used to manually test the main functions and operations of the humidifi er.
Manual procedure (1/2)
parameter range default
manual procedure (*)
YES/NO NO
air valve
ON/OFF OFF
water valve
ON/OFF OFF
drain valve
ON/OFF OFF
valve at end of line
ON/OFF OFF
production status
ON/OFF OFF
Manual procedure (2/2)
parameter range default
alarm relay
YES/NO NO
proportional output
ON/OFF OFF
proportional valve
ON/OFF OFF
(*) To activate the individual manual procedures, fi rst enable the manual procedure parameter.
8.4 Hour counter
parameter range/display
hours production
display
reset hours
YES/NO
8.5 Alarm log
Recorded trace of the alarms (events) that have been activated. The humidifi er memory can record up to 200 events (complete with description and date, press DOWN to scroll the list).
parameter display
Alarm
event description
Log deleted
Time
hh:mm
Date
dd/mm/yy
8. MAINTENANCE MENU
27
ENG
cabinetdistributionmaintenance
alarms displayed
meaning cause solution reset alarm
relay
action notes
high humidity humidity
outside of set limits
value measured by the probe greater than the humidity alarm threshold
check the set parameter manual inactive signal only on
low humidity humidity
outside of set limits
value measured by the probe less than the humidity alarm threshold
check the set parameter manual inactive signal only on
humidity probe broken or disconnected
humidity probe broken or disconnected
main humidity probe disconnected or broken
check the connection & the operation of the probe
manual active stop
production
on
high humidity limit probe
limit humidity outside of set limits
value measured by the probe greater than the humidity alarm threshold
check the set parameter manual inactive signal only fl ash can only be
reset switching the unit off from “set”, signalled only in sequence after other alarms but not when
forced. limit probe broken or disconnected
limit probe broken or disconnected
limit humidity probe disconnected or broken
check the connection & the operation of the probe
manual active stop
production
on
slave (2-3-4-5-6) unit offl ine
slave unit not connected to the pLAN
pLAN network disconnected
check connection of pLAN cable to terminals on controller
manual active signal only on
master unit offl ine
master unit not connected to the pLAN
pLAN network disconnected
check connection of pLAN cable to terminals on controller
manual active signal only on
low pressure alarm
insuffi cient air pressure
insuffi cient air pressure
check air line pressure manual active stop
production
on for ON/OFF
units compressor alarm from air
compressor
compressor fault alarm
check air compressor manual active signal only on
fl ow switch alarm from AHU
fl ow switch
no air in AHU alarm
check AHU manual active signal only on
water treatment system
alarm from water treatment system
water treatment system fault alarm
check water treatment system manual active signal only on
pressure sensor faulty or disconnected
pressure sensor faulty or disconnected
pressure sensor faulty or disconnected
check pressure sensor manual active stop
production
on for proportional
units with air
pressure sensor pressure off scale
air pressure outside of set limits
insuffi cient air pressure
check air supply pressure manual active stop
production
on for proportional
units with air
pressure sensor clock fault clock error backup battery
completely discharged or generic clock fault
replace clock manual inactive signal only off
9. TABLE OF ALARMS
When an alarm is activated, the alarm button starts fl ashing intermittently. In these conditions, pressing the alarm button once displays the type of alarm .
In the case of potentially dangerous alarms, the controller automatically stops production. For some alarm events, the alarm relay is also activated at the same time as the signal (see the table below).
28
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
10. ADVANCED FUNCTIONS
10.1 Wiring diagrams
Wiring diagram for ON/OFF version, Master codes: MC***C*M**
PS
PRESSOSTATO LINEA ARIA
PRESSURE SWITCH AIR LINE
29
ENG
cabinetdistributionmaintenance
Wiring diagram for ON/OFF version, Slave codes: MC***C*S**
PS
PRESSOSTATO LINEA ARIA
PRESSURE SWITCH AIR LINE
30
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
Wiring diagram for modulating version, Master codes: MC***H*M**
31
ENG
cabinetdistributionmaintenance
Wiring diagram for modulating version, Slave codes: MC***H*S**
32
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
10.2 Operating principle
The humidifi er controller - based on the input signal from a probe, an ON/OFF contact or external controller - activates the cabinet to start the production of atomised water (at maximum capacity), and stops the production when the set point is reached. As well as the room probe, the limit probe for humidity control is fi tted in a signifi cant point of the installation to avoid excessive condensation. Normally the humidity control probe is located in the ducts of the air handling unit.
ON/OFF operation
The activation logic is:
Request ON (contact closed)
J
Humidifi er in production
No request OFF (contact open)
J
Humidifi er in stand by (not in production)
Status of the outputs:
Humidifi er in production:
Water line active (NO drain solenoid valves active, NC fi ll solenoid valve
active)
Air line active (NC air line activation solenoid valve active)
Humidifi er off (not in production):
Water line inactive (NO drain solenoid valves deactivated, NC fi ll
solenoid valve deactivated)
Air line inactive (NC air line activation solenoid valve deactivated)
Operation in modulating versions
The humidifi er controller - based on the input signal from a temperature or humidity probe, or external controller - activates and modulates the quantity of compressed air so as to achieve a humidifi cation capacity proportional to the request from the external controller, or to the diff erence between the desired value (set point) and the value measured by the probe.
In this case too, the limit probe is also used to measure the humidity in a signifi cant point of the installation and avoid excessive condensation. In modulating operation, the system MANAGES a humidity set point, with an optional limit signal from the second probe, a temperature set point or a request signal (proportional).
Standard control of humidity production is performed using a proportional valve (AO2) controlled by a 0 to 10 V signal. The system behaves as follows:
Status of the outputs:
Humidifi er in production:
Water line active (NO drain solenoid valves active, NC fi ll solenoid valve
active)
Air line active (NC air line activation solenoid valve active, Proportional
valve controlled proportionally to required pressure)
Humidifi cation not request:
Water line inactive (NO drain solenoid valves deactivated, NC fi ll
solenoid valve deactivated)
Air line inactive (NC air line activation solenoid valve deactivated,
proportional valve closed)
The use of the request signal and the extent of control of the proportional air valve depends on the type of control selected. ON/OFF and modulating control share the ratio between the values, that is, the maximum signal applicable to the proportional solenoid valve corresponds to the rated production (Pnom).
10.3 Control principles
ON/OFF control from contact
The action is all or nothing, activated by an external contact that consequently determines the control set point and diff erential. The external contact may be a humidistat, whose status determines the operation of the humidifi er:
contact closed: the humidifi er produces atomised water if the remote
ON/OFF contact is also closed;
contact open: production ends.
ON/OFF control with humidity probe
The action is all or nothing, activated based on the reading of the probe, production starts and reaches the maximum when the relative humidity is lower than the set point by the set diff erential. To set the set point and diff erential for the main control probe: SET menu. To check that the value measured by the probe is within certain preset values, two alarm thresholds can be set:
high humidity alarm threshold;
low humidity alarm threshold.
When these thresholds are exceeded, an alarm is activated, after a set delay.
Hy
Set point
%rH
Request
0
0
P. Ma x
100
ON/OFF control with temperature probe
The action is all or nothing, activated based on the reading of the probe, production starts and reaches the maximum when the temperature is lower than the set point by the diff erential. To set the set point and diff erential for the main control probe: SET menu. To check that the value measured by the probe is within certain preset values, two alarm thresholds can be set:
high temperature alarm threshold;
low temperature alarm threshold.
When these thresholds are exceeded, an alarm is activated, after a set delay.
H
Set point
°C/°F
Request
0
0
P. Ma x
100
33
ENG
cabinetdistributionmaintenance
Proportional control
The production of atomised water is proportional to the value of a signal “Y” from an external device. The type of signal can be selected between the following: 0 to 1 Vdc, 0 to 10 Vdc, 2 to 10 Vdc, 0 to 20 mA, 4 to 20 mA, 0 to 135 Ohm, 135 to 1000 Ohm (installer menu > type of control > type of signal) The entire range is indicated as BP (proportional band). The maximum production of the humidifi er, corresponding to the value maximum of the external signal, can be set from 50% t 100%. The minimum production corresponds to 10% (default, range 3-60%) of the external signal:
if set point < 10%, hysteresis of 2%;
if set point > 0 = 10%, hysteresis of 5%.
H
Set point
BP
Request
0
0
P. Ma x
(50%) P. Min.
100
Segnale proporz.
Proportional control with limit probe
See “proportional control”, with the addition of a limit probe, generally installed in the air duct downstream of the humidifi er. This type of control is used to reduce production if the relative humidity, downstream of the humidifi er, is within the proportional band set for the limit probe. Production is stopped if the relative humidity, downstream of the humidifi er, reaches the limit set point %rH2. To set the set point and diff erential for the limit probe: “quick set menu”.
H
Di_Humid
Set point
%rH
Request
0
0
P. Ma x
P. Min.
100
Independent control with relative humidity probe
The production is related to the reading of the probe and increases as the relative humidity value read decreases. The production reaches the maximum when the relative humidity is lower than the set point (St) by a value at least equal to the diff erential. The maximum production can be programmed between 50% and 100% of the rated value of the humidifi er. To set the set point and diff erential for the main control probe: “quick set menu”. The minimum production has an activation hysteresis, “hy”, equal to 0.2% rH To check that the relative humidity measured by the probe is within certain preset values, two alarm thresholds can be set in independent control:
high humidity alarm threshold;
low humidity alarm threshold.
When these thresholds are exceeded, an alarm is activated, after a set delay.
H
Di_Humid
Set point
%rH
Request
0
0
P. Ma x
P. Min.
100
Independent control with relative humidity probe and limit probe
See control with main probe, combined with a limit probe, installed in the air duct downstream of the humidifi er. This type of control is used to reduce production if the relative humidity, downstream of the humidifi er, is within the diff erential band of the limit probe. Production is stopped if the relative humidity, downstream of the humidifi er, reaches the limit set point %rH2.
Temperature control for cooling applications
When using the humidifi er for adiabatic cooling, instead of the humidity probe in the room, a temperature probe is used. The production of atomised water is related to the temperature T read by the temperature probe (AO1), and increases as the distance from the set point St increases. Maximum production (Pmax), which occurs when the room temperature is greater than the set point by a value equal to the diff erential (T di erential), can be set between 50% and 100% of rated production (Pnom). The activation hysteresis (default 0.2 °C) is indicated in Figure
4.2 as hy.
H
Di_Temp
Set point
°C/°F
Request
0
0
P. Ma x
P. Min.
100
34
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
Temperature control with humidity limit probe
The production of atomised water depends on the reading of the temperature probe, with a second humidity probe (AO3) that limits production, so as to limit the humidity level in the cooled air. The limit probe has a set point (L set point), a diff erential (L diff .) and an activation hysteresis (0.2% rH). Production is the result of the diff erence between the two readings.
10.4 Pressure control
Pressure control in the air line is fundamental as this is used to control production. Depending on the model, pressure may be controlled using:
Manual regulating valve (ON/OFF operation)
Manual regulating valve & pressure transducer in line (ON/OFF operation)
Proportional valve (modulating operation)
Proportional valve & pressure transducer (modulating operation)
MC models with ON/OFF controller
The pressure is controlled using the pressure gauges installed in the air line, which signal if the value is above or below the calibration of the manual pressure regulator. The correct operating pressure will be thus be controlled by the operator, when commissioning the installation, using the pressure gauges in the line and the manual regulating valve.
MC models with ON/OFF controller and pressure transducer (recommended)
The transducer is available as an optional component, upon request, including 10 m, 50 m or 100 m cable. The system works in “all or nothing” mode and displays the signal of the pressure transducer, providing indications to the operator on the calibration of the air line using the manual regulating valve.
MC models with control by proportional valve
The system provides a signal to the proportional valve to modulate the pressure in the air line, from a minimum to a maximum, depending on the request from the humidity probe or the external controller. The minimum and maximum pressure values are set using the related parameters. If there is signifi cant pressure drop along the line - measured by the operator using a pressure gauge installed at the end of the line - a parameter (see installer menu > operating options (1/2) can be used to set a pressure off set as compensation. The pressure off set is summed to the signal sent to the proportional valve to compensate for the pressure drop.
MC models with control by proportional valve & pressure transducer (recommended)
The transducer is available as an optional component supplied upon request by Carel SpA, the kit includes:
transducer
connector
10 m, 50 m or 100 m cable.
In this case, as well as control with the proportional valve, the pressure transducer installed at the end of the line measures the air pressure and tells the electronic controller (which manages the proportional valve) to automatically compensate for pressure drop along the line. In this way, the system can supply the required pressure and automatically manage any pressure drop in the line.
10.5 Drain/ ll
Important: this function requires the installation of a CAREL NO drain solenoid valve at the end of the water line, available as an option.
For hygiene reasons, when the system is not operating the water line is emptied to avoid bacterial formation inside. This is done using the normally-open drain solenoid valves located inside the cabinet and at the end of the line. The fi ll operation is performed as follows, starting from empty:
the NC water fi ll solenoid valve in the cabinet is activated (opened);
the NO drain solenoid valve in the cabinet is activated (closed);
the NO solenoid valve at the end of the line is deactivated (opened).
The duration of the fi ll cycle can be set by parameter and depends on the length of the line. During the fi lling phase, the air line is deactivated. At the end of the cycle, the NO drain solenoid valve at the end of the line will be closed and the air line will be activated so as to resume production. The function can be activated by parameter, and when deactivated, the status is as illustrated in chapters 3 and 4.
10.6 Periodical washing of the water line
Function required for hygiene/health reasons when the humidifi er is not operating. To activate this function: installer menu > special functions > special functions (2/3), can be performed automatically by time or manually. The washing procedure is similar to the fi ll cycle described above, starting from empty
the NC water fi ll solenoid valve in the cabinet is activated (opened);
the NO drain solenoid valve in the cabinet is activated (closed);
the NO solenoid valve at the end of the line is deactivated (opened).
The duration of the wash cycle is longer than the fi ll cycle and, in this case too, depends on the length of the line. The duration and the frequency of the wash cycle can be set by parameter. During the washing phase, the air line is deactivated
10.7 Automatic cleaning of the atomising heads
To activate this function: installer menu > special functions > special functions (1/3); can be performed:
During a production cycle
At the end of a production cycle
Cleaning involves deactivating the water  ll, keeping the air line active (at 100% in the case of modulating operation, or simply activated for ON/OFF operation), activating (opening) the NO water drain solenoid valves at the end of the line and in the cabinet.
The duration of the operation can be set by user parameter, in addition the frequency during the production cycle can also be set, as well as whether or not to perform the operation at the end of the production cycle.
10.8 Pressure overboost
To ensure the correct opening and modulation of the atomising heads, at the start of each production cycle, these are supplied with compressed air only, at a pressure of:
2.1 bars for ON/OFF versions.
3 bars for proportional versions.
During this phase, the water line is not activated. This function is not managed by parameter.
35
ENG
cabinetdistributionmaintenance
Notes:
36
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
11. GENERAL CHARACTERISTICS OF THE DISTRIBUTION SYSTEM
11.1 Atomising head
The atomising heads are available in AISI 316 stainless steel with 5 diff erent fl ow-rates, yet all with the same dimensions and weights. Each atomising head has a marking on the nozzle indicating the model and thus the fl ow-rate.
Marking Code Capacity
A MCAA200000 2.7 l/h B MCAB200000 4.0 l/h C MCAC200000 5.4 l/h D MCAD200000 6.8 l/h E MCAE200000 10 l/h
73
32
11.2 Assembly kit
This is a series of components designed to make the assembly of the atomising heads on the air-water lines simpler and faster; it can be used for both normal water and demineralised water (aggressive).
Only one model is available:
MCK1AW0000 for assembly of the heads on the lines in the room or
in the duct.
Kit MCK1AW0000
1. 1/4” FF elbow connector
2. 1/4” H43 MF column
3. 1/4” nipple
4. 1/4” MF 2-way valve
5. 1/4” PVSF 2-way valve
6. 1/4” 180° M connector
7. B TFN nylon tube dia. 6/8 mm
8. 1/4” FF elbow connector dia. 6/8 mm
9. 1/4” FF hose coupling”
37
ENG
cabinetdistributionmaintenance
12.1 Sizing an MC system
When sizing an MC system, several factors must be considered: air fl ows, fl ow speed, presence of cooling coils, dimensions of the room where the humidifi er will be installed. For correct sizing, given the relative complexity of the factors involved, the applications should be designed using the documents provided by CAREL.
To calculate the humidifi cation requirements of a certain space, a series of factors need to be considered:
volume of the local (m3);
current conditions of the room: temperature (°C) and relative humidity
(% rH);
desired conditions in the room: temperature (°C) and relative humidity
(% rH);
characteristics of the materials inside (quantity, hygroscopic factor,
number of people);
time required to reach steady operation;
inlet of outside air (infi ltration, occasional opening of doors or
windows);
air change (m3/h);
outside design conditions: temperature (°C) and humidity (% rH);
condensation on the cooling coil.
Note: If there is no fresh air inlet, once the required relative humidity
value is reach the humidifi cation system will not need to work much to maintain the humidity level. Consequently, to save running costs when high capacities are required, check the time required to reach steady operating conditions.
12.2 Sizing the compressor
Careful attention needs to be paid to sizing the compressor. The air consumption is determined by the capacity of the installation and not by the maximum fl ow-rate of the cabinet. Consequently, the number of atomising heads in the installation and their fl ow-rate need to be considered. The air fl ow-rate of each head may have the following values:
MCAA2 MCAB2 MCAC2 MCAD2 MCAE2
Nm3/h 3.43 5.08 6.86 8.64 12.7 CFM 2 3 4 5 7.5
The air consumption for all heads is equal to:
- 0.41 m3/h per litre of water at an operating pressure of 2.1 bars;
- 1.27 Nm3/h per litre of water at atmospheric pressure;
- 0.75 CFM per litre of water at atmospheric pressure.
The table below describes the specifi c consumption for each individual head in Normal m3/h and CFM (Cubic Feet per Minute), referred to atmospheric pressure:
Calculation example: Installation of 18 MCAC2 heads supplied by a 230 l/h cabinet.
V = C
head
x n = 6.86x18 = 123.5 Nm3/h = 2058 l/m
(referred to the rated data of the compressor)
where: V = volume of air taken in by the compressor or introduced into the room by the installation (Nm3/h) C
head
= air consumption of each head (Nm3/h)
n = number of heads
Note: In order to guarantee the right air fl ow-rate in all conditions, the size should be overrated by 10%.
12.3 Sizing air/water lines between cabinet & distribution system
The pipes or hoses carrying air and water to the atomising heads must be made from copper or plastic. DO NOT USE GALVANISED STEEL PIPES as these may release impurities that block or damage the heads. When supplying the cabinet with demineralised water, only use plastic or stainless steel pipes. If the cabinet is supplied with demineralised water (aggressive), Tefl on or liquid Tefl on must be used as the sealant.
In alternative to the above, polypropylene hoses can be used, which allow faster and simpler connections by welding.
To determine the diameters of the air/water outlet lines, refer to the tables below. Make sure that the inside diameter of the pipes/hoses selected is as described in the table under the item “ID”.
Always make sure that the rated pressure of the pipes/hoses is suitable for the operating pressure of the installation, in any case PN8 or higher diameter pipes/hoses are recommended.
12. DESIGNING A SYSTEM
system  ow-rate l/h
type of heads line length
A B C D E 5 m 10 m 25 m 50 m
no. heads installed per
type
air water air water air water air water
ID mm ID mm ID mm ID mm ID mm ID mm ID mm ID mm
30 11 8 6 4 3 15 12 20 14 20 15 25 18
60 22 15 11 9 6 20 12 25 14 30 15 30 18
120 44 30 22 18 12 30 12 30 14 35 15 40 18
230 85 58 43 34 23 35 12 40 14 45 15 55 18
38
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
system  ow-rate lb/h
type of heads line length
A B C D E 16 feet 32 feet 80 feet 160 feet
no. heads installed per type
air water air water air water air water
ID mm ID mm ID mm ID mm ID mm ID mm ID mm ID mm
65 11 8 6 4 3 5/8 1/2 3/4 5/8 3/4 5/8 1 3/4
130 22 15 11 9 6 3/4 1/2 1 5/8 1 1/4 5/8 1 1/4 3/4
260 44 30 22 18 12 1 1/4 1/2 1 1/4 5/8 1 3/8 5/8 1 1/2 3/4
500 85 58 43 34 23 1 3/8 1/2 1 1/2 5/8 1 3/4 5/8 2 1/4 3/4
Note: If the air line is more than 50 metres log, size the line so that
the pressure drop does not exceed 0.2 bar. Try to limit the number of connections in the air and water lines to the minimum possible. The use of elbow or “T” connectors and reducers/adapters will increase the pressure drop in the lines. The diameters shown in the tables have been selected considering the use of a pair of connectors in each line, if the number of connectors doubles choose the next largest diameter.
39
ENG
cabinetdistributionmaintenance
13. INSTRUCTIONS FOR INSTALLATION IN ROOMS
13.1 Tips for correct installation
Note: see Chapter 2 for the connection of the atomising heads.
The air line also acts as the support for all the heads. The water line must always be lower than the atomising heads to ensure emptying and drying when the installation is off . Size the water and air lines as shown in the table in paragraph 4.3
13.2 Assembling the atomising head
For each atomising head, a kit for assembly in the room is available that makes installation simpler and faster. The assembly kit can be used both for normal water and for aggressive water. The drawing (paragraph 3.2) illustrates how to fi t the kit.
All the atomising heads must be installed at the same height to avoid
variations in pressure that would make the sprays of atomised water less uniform.
The assembly kit allows the head to be turned vertically so as to aim
the spray as desired.
A readily accessible ball valve should be installed at the end of each
line for cleaning (bleeding) the lines when fi rst starting and at the start of each season.
The water lines must not have “pockets” along the path so that the
installation can be drained completely by gravity when stopped.
Make sure not to reverse the water/air inlets on the atomising heads;
the air inlet is always marked by a label showing “AIR”.
13.3 Positioning the humidity probes
The cabinet control system can be connected to:
signal from an external controller.
ambient humidity probe.
signal from external controller plus limit probe.
two humidity probes: ambient plus limit
one temperature probe and one limit probe.
If installing humidity and temperature probes:
The ambient humidity control probe must be located inside the
return air duct. This sensor can also be positioned in the room being humidifi ed. Make sure, however, that the place where it is installed is away from fl ows of air that are hotter or colder than the environment, or is not in contact with perimeter walls.
The temperature probe must follow the same rules as described
above for the humidity probe.
The high humidity limit probe should be located downstream of the
atomisation manifold in a position where it cannot be wet by the jet of atomised water (e.g. after the cooling coil, or after a droplet separator, or near the fan).
13.4 Important rules to be followed
There are a number of important rules to be observed when installing an MC humidifi cation system:
1. The jet of atomised water must not come into contact with any
object along its path so as to avoid condensation and thus dripping. Any obstacles in the trajectory of the jet of water can be avoided by suitably aiming the atomising heads. Table shows the length and the maximum diameter of the jet in relation to the humidity in the room. The heads must also be installed so as to avoid two separate sprays from overlapping. It is recommended to install them, inside the area being humidifi ed, as high as possible, without however wetting the ceiling.
no
Luce/Light
sì/yes
no
no
sì/yes
sì/yes
head  ow-rate minimum installation height max spray diameter visible spray distance <50% rH visible spray distance >50% rH
2.7 l/h 4 m 0.75 m 3.00 m 4.55 m
4.0 l/h 4 m 0.75 m 3.35 m 4.90 m
5.4 l/h 4.6 m 0.90 m 3.65 m 5.20 m
6.8 l/h 6.1 m 1.20 m 4.00 m 6.10 m
10.0 l/h 9.4 m 1.50 m 4.60 m 7.00 m
40
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
2. The air/water lines must not have variations of height.
3. If the fi lling and washing functions are featured, install the NO
drain solenoid valve supplied as an option at the end of the line. The drain hose connected downstream of the solenoid valve must have a diameter that is greater than or equal to diameter of the line upstream. If this is not installed, fi t an easily accessible ball valve for cleaning (bleeding) the line when commissioning and restarting each season.
4. At the end of the air line, an easily accessible ball valve should be
fi tted for cleaning (bleeding) the line when commissioning and restarting each season.
5. To control the pressure in the air line, use one of the following devices,
installed at the end of the line:
Pressure gauge (supplied as an option)
Pressure transducer (supplied as an option)
With the devices listed above, depending on the type of cabinet
used, refer to the following:
for ON/OFF cabinets:
With a pressure gauge installed at the end of the line, the pressure
drop in the line can be displayed and, if necessary, the pressure
increased to 2.1 bars using the manual pressure regulator located
inside the cabinet.
With the pressure transducer, the pressure at the end of the line
can be shown on the controller display and, if necessary, increased
using the manual pressure regulator.
for cabinets with modulating control:
With a pressure gauge installed at the end of the line, the pressure
at the end of the line can be read and, if necessary, increased using
the corresponding parameter on the electronic controller.
With the pressure transducer, the cabinet automatically controls
the pressure in the installation to the optimum value so as to
compensate for any pressure drop in the line.
6. The cabinet drain line must be connected directly to a drain cycle at
a height of at least 50 mm below the level of the heads.
7. The position of the cabinet must be selected so as to guarantee
the shortest path to the lines. If the lines are very long (>50 m), the cabinet should be positioned in the centre of the line, so as to balance the pressure.
8. The atomising heads must be distributed so as to uniformly cover the
entire area involved. The control cabinet must always be located in a central position in reference to the layout of the heads.
9. The humidity sensor must be positioned where possible in a central
area of the space being humidifi ed, in a point in which there are no fl ows of humidifi ed air and atomised water from the atomising heads. In addition, avoid fi tting the humidity sensor on a perimeter wall of the building, as the temperature of the wall may be aff ected by the outside temperature and thus infl uence the reading.
10. Shielded cables should be used to connect the control cabinet to the
following devices:
humidity, limit and temperature probes, air line pressure sensor
(optional)
water line drain solenoid valve (optional).
Avoid running these cables near other power cables (electric motors, contactors, high voltage wires, etc...)
41
ENG
cabinetdistributionmaintenance
14. INSTRUCTIONS FOR INSTALLATION IN DUCTS
For duct applications, the solution with two probes is recommended:
humidity probe or signal from external controller
limit probe
this solution can be used indiff erently for both types of cabinet:
ON/OFF
Modulating
The modulating cabinet is recommended for this type of application. By modulating the capacity of the atomisation system, the maximum possible production can be delivered without ever reaching saturation conditions inside of the duct. The atomisation manifold (Fig. 11) is made up of an air line and a water line located below. At the end of the lines, two ball valves should be installed for bleeding the lines.
-
-
R
I
L
SAN PA1
1 O 6 8 x 6 DIN 74324 AIM 29 --
-
-
R
I
L
SAN PA1
1 O 6 8 x 6 DIN 74324 AIM 29 --
-
-
R
I
L
SAN PA1
1 O 6 8 x 6 DIN 74324 AIM 29 --
-
-
R
I
L
SAN PA1
1 O 6 8 x 6
DIN 74324 AIM 29 --
air ow
duct
front view
duct
front view
water line
air line
cabinet air line water line
230 l/h 22 mm (1/2”G) 22 mm (1/2”G) 60 l/h 14 mm (1/2”G) 14 mm (1/2”G)
14.1 Positioning the atomisation manifold
Figure 12 shows the possible positions for the atomised water manifold. The control cabinet must where possible be installed near the manifold with the atomising heads. Critical measurements for the assembly of the manifold in the duct:
1. Distance of the heads from the surfaces of the duct::
The maximum distance H reached by the jets of atomised water is shown in the under table. The distance H is very important for preventing the jet of atomised water from wetting the duct; this is the most typical installation the manifold (Fig. 14.a).
air ow
H
Fig. 14.a
Maximum distance H in mm reached by the jet
air speed in m/s
2.7 l/h 4.0 l/h 5.4 l/h 6.8 l/h 10 l/h distance H in mm
2.0 660 737 914 1219 1792
3.0 610 686 838 1092 1605
4.0 559 610 737 965 1419
5.0 508 559 660 838 1232
6.0 457 508 559 711 1045
7.5 406 432 483 584 859
10.0 356 381 406 432 635
If the height available is not suffi cient, the manifold can be installed as shown in Fig. 14.b. This type of installation is used to humidify in smaller ducts. Any losses due to condensation and removed by the droplet separator will however be greater.
air ow
Fig. 14.b
Never fi t the heads against the fl ow If, based on the top table, the height of the duct is not suffi cient, one solution may be to fi t the manifold outside the duct, with the ends of the nozzles spraying inside, as can be seen in Fig. 14.c. This saves around 20 cm.
air ow
Fig. 14.c
42
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
14.2 Important rules to be followed
1. The minimum distance between two adjacent heads must never be
less than 100 mm. This is also the minimum distance between the heads at the end and the side of the duct.
2. To determine the distance between heads, divide the width of the
duct by the number of heads plus one. If the distance is less than 100mm, more manifolds should be used, and if possible, larger capacity heads.
3. If the height of the duct (D) is greater than::
D = 2 x H + 100 mm
(where H is the maximum distance in mm reached by the jet sprayed by the heads to the top of the duct, as in Table 4), then the manifold can be placed in the centre of the duct with the heads facing alternately up and down.
4. The minimum height of the duct (M) to be able to install the
distribution manifold with a 90° jet is equal to:
M = H + 180 mm
If this space is not available, then the heads must be installed outside of the duct with the jet spraying inside (Fig. 14.c) or lower capacity heads used.
5. The jet of atomised water must never come into contact with
obstacles (wall reinforcement bars) before total evaporation (free path of evaporation - PL).
6. Never fi t the heads in the opposite direction to the air fl ow.
7. If the fi lling and washing functions are featured, install the NO
drain solenoid valve supplied as an option at the end of the line. The drain hose connected downstream of the solenoid valve must have a diameter that is greater than or equal to diameter of the line upstream. If this is not installed, fi t an easily accessible ball valve for cleaning (bleeding) the line when commissioning and restarting each season.
8. At the end of the air line, an easily accessible ball valve should be
fi tted for cleaning (bleeding) the line when commissioning and restarting each season.
9. To control the pressure in the air line, use one of the following devices,
installed at the end of the line: Pressure gauge (supplied as an option) Pressure transducer (supplied as an option) With the devices listed above, depending on the type of cabinet used, refer to the following:
for ON/OFF cabinets:
With a pressure gauge installed at the end of the line, the pressure
drop in the line can be displayed and, if necessary, the pressure increased to 2.1 bars using the manual pressure regulator located inside the cabinet.
With the pressure transducer, the pressure at the end of the line
can be shown on the controller display and, if necessary, increased using the manual pressure regulator.
for cabinets with modulating control:
With a pressure gauge installed at the end of the line, the pressure
at the end of the line can be read and, if necessary, increased using the corresponding parameter on the electronic controller.
With the pressure transducer, the cabinet automatically controls
the pressure in the installation to the optimum value so as to compensate for any pressure drop in the line.
14.3 Positioning the humidity probes
If installing humidity and temperature probes:
The ambient humidity control probe must be located inside the
return air duct. This sensor can also be positioned in the room being humidifi ed. Make sure, however, that the place where it is installed is away from fl ows of air that are hotter or colder than the environment, or is not in contact with perimeter walls.
The temperature probe must follow the same rules as described above
for the humidity probe.
The high humidity limit probe should be located downstream of the
atomisation manifold in a position where it cannot be wet by the jet of atomised water (e.g. after the cooling coil, or after a droplet separator, or near the fan).
14.4 Manifolds for installation in ducts
Special manifold kits are available for installations in ducts, sized according to the number of atomising heads required and the dimensions of the AHU/ducts.
43
ENG
cabinetdistributionmaintenance
There are fundamentally three components that require adjustments:
atomising heads;
air and water lines;
electronic controller.
Heads
The screw on the rear of the head is used to adjust the atomised water fl ow-rate. This is calibrated in the factory to the reference values (2.1 bars air, 0.35 bars water) for the design fl ow-rate, which may be 2.7; 4.0; 5.4; 6.8 or 10 l/h. If the spray is visibly diff erent in intensity from the other similar heads, or the environmental conditions mean higher or lower absorption, the screw can be adjusted to increase or decrease the water fl ow-rate. This operation should only be performed by authorised personnel (CAREL service centres).
Air and water line
The air and water pressure in the respective lines must have the following values:
Cabinet air inlet: 5 to 7 bars
Cabinet air outlet: 2.1 bars
Cabinet water inlet: 3 to 7 bars
Water outlet:
0.35 bars if the heads and cabinet are at the same height;
(0.35+Hx0.1) bars if the heads and cabinet are at diff erent heights.
H is the height between the heads and the cabinet water line in metres.
Note: maximum height between the cabinet and the water line is 20 m.
The MC modulating humidifi cation system can modulate the production of atomised water by adjusting the air pressure at the heads, allowing a proportional variation in fl ow-rate.
The minimum pressure is set as default to 1.2 bars.
The maximum pressure is set as default to 2.1 bars
These values can be modifi ed so as to optimise:
the minimum pressure according to the type of atomising head used
the maximum pressure according to the pressure drop in the line (also
see chapters 5.3; 6.2). in the case of modulating units with pressure transducer at the end of the air line, the maximum pressure is controlled automatically (the transducer is supplied by CAREL as an option).
15. MAIN ADJUSTMENTS
44
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
16. MAINTENANCE
16.1 Maintenance procedures
Even if the MC humidifi cation system does not generally require special
maintenance, preventive maintenance should be performed regularly,
annually or before starting each season. The richer the water in salts or
impurities, the more frequently checks are required.
Devices requiring checks:
Compressor: follow the manufacturer’s instructions
Atomising heads: once a year remove and clean the nozzle,
lubricate the
o-ring with silicone grease and in case change them. Air and water line: once a year the air and water lines should be bled to remove any sediments, traces of oil and dirt. To do this, follow the system start-up procedure. Pressure regulators and solenoid valves: once a year open and clean to remove any debris and deposits. pCO3 electronic controller + pGD terminal and humidity probes: once a year check the condition of the probes and recalibrate if necessary. Do not use compressed air or solvents to clean the probe sensor.
16.2 Kits & optional accessories for the air/ water line (see chap. 2)
NO solenoid valve at end of line for NW (normal water) M C K D V W L 0 0 0 NO solenoid valve at end of line for AW (aggressive water) M C K D V W L 0 0 1
pressure transducer l=10 m MCKPT01000 pressure transducer l=50 m MCKPT05000 pressure transducer l=100 m MCKPT10000
air outlet pressure gauge 0 to 4 bars MCKMA04000 water outlet pressure gauge AW 0 to 2.5 bars M C K M W 0 2 5 0 1
UV lamp sanitising kit MCKSUV0000 UV lamp MCKUV00000
5” water fi lter container MC F I LWAT 0 5 5 water fi lter cartridge MCC05PP005 1/2” air fi lter MC F I LA I R 0 1 3/8” oil fi lter for air MC F I LO I L 0 1
humidity probes for ducts 10 to 90% rH D P D C 112000 humidity probes for ducts 0 to 100% rH D P D C 212000 ambient humidity probes 10 to 90% rH D P W C 112000 temperature-humidity probes for industrial environments -10 to 70 °C/ 0 to 100% rH D P P C 212000 temperature-humidity probes for industrial environments 0 to 50 °C / 10 to 90% rH D P P C 112000
16.3 Kits & optional accessories for the atomising heads (see chap. 11)
Atomising head assembly kit MCK1AW0000
Atomising head mod. A 2.7 l/h MCAA200000 Atomising head mod. B 4.0 l/h MCAB200000 Atomising head mod. C 5.4 l/h MCAC200000 Atomising head mod. D 6.8 l/h MCAD200000 Atomising head mod. E 10 l/h MCAE200000
45
ENG
cabinetdistributionmaintenance
16.4 Spare parts for air/water line (see paragraph 1.4)
line drawing code & description exploded drawing component code component description n.
M C K A 0 6 0 D 0 0
ON/OFF air line 60 l/h
36421
5
2
M C K M A 1 2 0 0 0
pressure gauge 0 to 12 bars 1
M C K M N F D 0 0 0
manifold 2
M C K M R 0 A 0 6 0
manual air pressure regulator 60 l/h
3
M C K A 0 6 0 D U 0
ON/OFF air line 60 l/h UL
M C K F S V B C 0 0
NC air solenoid valve 60 l/h/water NW
4
M C K M A 0 4 0 0 0
air outlet pressure gauge 0 to 4 bars
5
M C K P S 0 0 0 0 0
pressure switch 6
M C K A 2 3 0 D 0 0
ON/OFF air line 230 l/h
34 62152
M C K M A 1 2 0 0 0
pressure gauge 0 to 12 bars 1
M C K M N F D 0 0 0
manifold 2
M C K M R 0 A 2 3 0
manual air pressure regulator 230 l/h
3
M C K A 2 3 0 D U 0
ON/OFF air line 230 l/h UL
M C K F S V A C 0 0
NC air solenoid valve 230 l/h 4
M C K M N F D 0 0 0
manifold 2
M C K P S 0 0 0 0 0
pressure switch 6
M C K A 0 6 0 H 0 0
modulating air line 60 l/h
1 3
4
52
M C K M A 1 2 0 0 0
pressure gauge 0 to 12 bars 1
M C K M N F D 0 0 0
manifold 2
M C K A M V A 0 0 0
modulating valve 3
M C K A 0 6 0 H U 0
modulating air line 60 l/h UL
M C K F S V B C 0 0
NC air solenoid valve 60 l/h/water NW
4
M C K M N F D 0 0 0
manifold 2
M C K A 2 3 0 H 0 0
modulating air line 230 l/h
1 2 345
M C K M A 1 2 0 0 0
pressure gauge 0 to 12 bars 1
M C K M N F D 0 0 0
manifold 2
M C K A M V A 0 0 0
modulating valve 3
M C K A 2 3 0 H U 0
modulating air line 230 l/h UL
M C K F S V A C 0 0
NC air solenoid valve 230 l/h
4
M C K M N F D 0 0 0
manifold 2
M C K W 0 0 0 0 0 0
ON/OFF normal water line 230 l/h
2345
6
12
M C K M A 1 2 0 0 0
pressure gauge 0 to 12 bars 1
M C K M N F D 0 0 0
manifold 2
M C K M R 0 W 0 0 0
manual water pressure regulator
3
M C K W 0 0 0 0 U 0
ON/OFF normal water line 230 l/h UL
M C K F S V B C 0 0
NC air solenoid valve 60 l/h/water NW
4
M C K M W 0 2 5 0 0
water outlet pressure gauge NW 0 to 2.5 bars
5
M C K D S V W C 0 0
NO solenoid water valve NW
6
M C K W 0 0 0 0 0 1
ON/OFF aggressive water line 230 l/h
236415
2
M C K M W 1 0 0 0 1
inlet pressure gauge AW 0 to 10 bars
1
M C K M N F D 0 0 0
manifold 2
M C K M R 0 W 0 0 0
manual water pressure regulator
3
M C K W 0 0 0 0 U 1
ON/OFF aggressive water line 230 l/h UL
M C K F S V W C 0 1
NC water solenoid valve AW 4
M C K M W 0 2 5 0 1
water outlet pressure gauge AW 0 to 2.5 bars
5
M C K D S V W C 0 1
NO solenoid water valve AW 6
46
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinetdistributionmaintenance
NC air solenoid valve 60 l/h/water for NW M C K F S V B C 0 0 NC air solenoid valve 230 L/h MC K F S V AC 0 0 NO water solenoid valve for NW MC K D S VWC 0 0 NC water solenoid valve for AW MC K F S VWC0 1 NO water solenoid valve for AW MC KD S VWC 0 1
pressure gauge 0 to 12 bars MCKMA12000 inlet pressure gauge AW 0 to 10 bars MCKMW10001 air outlet pressure gauge 0 to 4 bars MCKMA04000 water outlet pressure gauge NW 0 to 2.5 bars M C K M W 0 2 5 0 0 water outlet pressure gauge AW 0 to 2.5 bars M C K M W 0 2 5 0 1
manual air pressure regulator 60 l/h MCKMR0A060 manual air pressure regulator 230 l/h MCKMR0A23 0 manual water pressure regulator MCKMR 0W0 0 0 modulating valve MC K AMV A 0 0 0
16.5 Pre-programmed pCO3 controllers
pre-programmed pCO3 controller, 60 l/h ON/OFF Master CE M C K C 0 6 C D M 0 pre-programmed pCO3 controller, 60 l/h ON/OFF Master UL M C K C 0 6 C 1 M 0 pre-programmed pCO3 controller, 60 l/h ON/OFF Slave CE M C K C 0 6 C D S 0 pre-programmed pCO3 controller, 60 l/h ON/OFF Slave UL M C K C 0 6 C 1 S 0 pre-programmed pCO3 controller, 230 l/h ON/OFF Master CE M C K C 2 3 C D M 0 pre-programmed pCO3 controller, 230 l/h ON/OFF Master UL M C K C 2 3 C 1 M 0 pre-programmed pCO3 controller, 230 l/h ON/OFF Slave CE M C K C 2 3 C D S 0 pre-programmed pCO3 controller, 230 l/h ON/OFF Slave UL M C K C 2 3 C 1 S 0 pre-programmed pCO
3
controller, 60 l/h modulating Master CE M C K C 0 6 H D M 0
pre-programmed pCO
3
controller, 60 l/h modulating Master UL M C K C 0 6 H 1 M 0
pre-programmed pCO
3
controller, 60 l/h modulating Slave CE M C K C 0 6 H D S 0
pre-programmed pCO
3
controller, 60 l/h modulating Slave UL M C K C 0 6 H 1 S 0 pre-programmed pCO3 controller, 230 l/h modulating Master CE M C K C 2 3 H D M 0 pre-programmed pCO3 controller, 230 l/h modulating Master UL M C K C 2 3 H 1 M 0 pre-programmed pCO3 controller, 230 l/h modulating Slave CE M C K C 2 3 H D S 0 pre-programmed pCO3 controller, 230 l/h modulating Slave UL M C K C 2 3 H 1 S 0
16.6 Electrical panel kit and spare parts (see paragraph 1.4)
manifold MC KMN F D 0 0 0 pressure switch MCKPS00000 power supply 110/230 Vac 12 Vdc 0.5 A M C K A L 00000 transformer MCKTR00000 fuses MC K F U S E 0 0 0 modulating valve regulator MC K A R V A 0 0 0 pGD0 kit for setting pLAN address PGD0002F0K
47
ENG
cabinetdistributionmaintenance
17. TROUBLESHOOTING
17.1 Troubleshooting table
line problem cause solution
1 alarm status displayed C1 active alarm S1 check the alarm in “table of alarms” 2 unit powered and enabled, the switch
on the front is in position “1” yet the humidifi er won’t start.
C1 no power to the cabinet S1 check that there is power at terminals LN C2 the fuses are blown S2 check the fuses
4 saturation and condensation inside the
duct caused by the fan stopping.
C1 failure to detect the fl ow switch alarm S1 make sure the fl ow switch is connected to
terminals ID6-COM on the unit
S2 check the correct confi guration of the fl ow
switch alarm contact: installer menu>external alarms.
5 the air outlet pressure doesn’t reach 2.1
bars
C1 compressor undersized S1 check the fl ow-rate of the compressor in
relation to the to the consumption expected for the installation
C2 for proportional units, without the transducer at
the end of the line: maximum limit pressure too low.
S2 check the maximum pressure set: installer
menu>operating options
C3 for ON/OFF units, pressure regulator set too low. S3 check the calibration of the pressure regulator
6 in proportional systems: the air outlet
pressure swings
C1 air line long and made from deformable material S1 decrease inlet pressure to the cabinet while
ensuring the pressure at the heads reaches 2.1 bars
7 air line active yet the heads don’t atomise
water.
C1 the air outlet pressure is too low S2.1 ON/OFF unit: check the inlet air pressure and
the air pressure regulator
S2.2 proportional unit, without pressure transducer
end of the line: check air pressure limit, installer
menu>operating options C2 water line NC solenoid valve not powered S2 check 24 V power to the solenoid valve. C3 water line NO solenoid valve not powered S3 check 24 V power to the solenoid valve. C4 water pressure regulator closed (fully unscrewed) S4 adjust the pressure regulator so the outlet
pressure is 0.35 bars C5 regulator not adjusted according to the height of
the heads
S5 adjust the pressure regulator so the outlet
pressure is 0.35 bars plus 0.1 bars for each
metre of diff erence in height between the
cabinet and distribution line C6 water pressure regulator dirty S6 remove the water pressure regulator and clean
any impurities.
8 water pressure reaches high values and is
not controlled.
C1 water pressure regulator dirty S1 remove the water pressure regulator and clean
any impurities.
9 for duct installations: low absorption
of atomised water and area under the atomisation heads wet
C1 air speed in the duct too high in relation to the
free path between the atomising heads and droplet separator.
S1 check the sizing of the installation
C2 overlapping sprays of atomised water or contact
between the spray of atomised water and the walls of the duct
S2 optimise the positioning of the heads
10 water leaks from the NO solenoid valve in
the cabinet or at the end of the line
C1 impurities in the solenoid valve that prevent
complete closing.
S1 remove the solenoid valve, remove the coil,
unscrew the sleeve, remove the impurities,
clean the body and sleeve and reassemble.
11 with the unit off or in stand-by with the
NC solenoid valve closed, water leaks
C1 impurities in the solenoid valve that prevent
complete closing.
S1 remove the solenoid valve, remove the coil,
unscrew the sleeve, remove the impurities,
clean the body and sleeve and reassemble.
12 atomising heads with abnormal fl ow,
adjusting the calibration screw brings no improvement.
C1 atomising heads dirty S1 remove the head and clean. C2 air and water pressure at the heads outside the
limits
S2 check the air and water pressure in the cabinet
and at the end of the line C3 oil in the air line S3 check the oil separator fi lter upstream of the
cabinet.
13 the heads produce a jet of water when
there is no air
C1 air/water connections reversed S1 reverse the connection observing the markings
on the heads
14 the ambient humidity stabilises at values
below the set point
C1 the capacity of the installation is not suffi cient to
meet the requirements
S1.1 review the sizing of the installation S2.1 adjust the heads to increase production
increase the number of the heads in relation
to the maximum fl ow-rate of the cabinet. See
points 8 and 9.
CAREL reserves the right to modify the features of its products without prior notice.
Notes:
Notes:
Notes:
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: carel@carel.com - www.carel.com
Agenzia / Agency:
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
Loading...