Buttons used to activate/deactivate the use of the remote control unit...12
Buttons used to modify the main parameters (directly accessible buttons)...13
Buttons for the remote control of the IR instruments....13
How to use the remote control unit....13
Access without code.....13
Access with code.....14
Further information.....15
Configuration parameters - The password....15
/ = parameters for the management of the temperature sensors...16
r = parameters for the temperature regulation....18
c = parameters for the compressor management....19
d = parameters for the defrost management....21
A = parameters for the alarm control....24
F = parameters for controlling evaporator fans....28
Summary diagram of the evaporator fan operation ....29
Notes for the new release.....31
Wiring diagrams.....34
Wiring diagram for multiple units - IR32 panel mounting connections...34
Operating states of the equipment....38
Sequence of main phases.....38
Alarms and troubleshooting .....39
What to do if the IR32S, IRDRSE/S0 fails to work....41
What to do if the IR32Y fails to work....41
What to do if the IR32P or IR32C, IRDRC fails to work...43
Technical characteristics.....44
Temperature/resistance ratios for NTC thermistors ....48
IR32 dimensions.....50
Code numbers for ordering controls and accessories...51
Description of particular parameters and performances...61
Memorisation of minimum/maximum temperature....61
Functioning of the relay 4.....61
Type of sensor - Digital Inputs Configuration....61
IR96: alarms.....62
Dimensions.....62
GENERAL FEATURES
Models available
The electronic controllers of the Infrared series have been specifically designed for the control and regulation
of refrigeration units. These new instruments are microprocessor based and come complete with a LED
display. Carel offers a wide range of models to ensure that the exact instrument is available for your
application at the most competitive price. In brief, here is a list of the main models available:
IR32M
IR32S
IRDRSE
IRDRS0
IR32Y
An electronic digital thermometer, capable of displaying the temperature from one or two
sensors. It is the ideal solution for applications requiring temperature display. It is possible to
display the temperature of either the first sensor or the second one alternatively by simply
connecting a switch to the thermometer. Additionally, the modification of a specific parameter
will allow you to get the weighted average of the two sensors. For further information see the
parameter '/4' (virtual sensor).
The ideal solution for regulation of 'static' refrigeration units (without evaporator fans) working
at normal temperature ranges (above 0ºC). IR32S works both as a thermometer − it displays
the temperature − and as an electronic thermostat: it activates the compressor (or the
solenoid valve in piped systems) to keep the temperature at the set value. You can select the
time-interval between successive defrosting cycles as well as their duration. IR32S can be
used simply as a thermostat. In this case it proves to be extremely useful in cooling or
heating applications where it activates compressors, heaters, etc. IR32S, in fact, can work
either in the 'Direct' (Cooling) or 'Reverse' (Heating) functioning mode, by simply selecting the
dedicated parameter (see 'r3' below) or acting on the digital input. The operating temperature
range is 40/90ºC (-40 /130 ºC with PTC sensor).
Specifically designed for the control and regulation of 'static' refrigeration units working at low
temperature ranges (below 0ºC), requiring 'active' defrost (that is, electrical or hot gas
defrost). IR32Y, in fact, works not only as a thermometer and a thermostat at the same time,
but it also controls defrost. You can select the time-interval between successive defrost cycles
as well as their duration. Defrosting will be stopped when the defrost end temperature is
reached (it is necessary to connect a defrost sensor to the evaporator). A timed fail safe is
included as standard in the event that the defrost end temperature is not reached. A parameter will
allow you to select the defrost end mode most suitable to your application, i.e.
time/temperature or time/time.
IR32P
IR32C
IRDRC
IR96
Specifically designed for the control and regulation of ventilated refrigeration units (with
evaporator fan) working at low temperatures. It features the same functions described above
for IR32Y plus control of the evaporator fans, thus optimizing their ON/OFF routines in
relation to the specific characteristics of your unit. IR32P has no relays; therefore it is
necessary to add a power card, either the S90RDPW200 or the S90OEM4PWR. The first card
has 3 relays for the control of compressor, fan and defrosting. The compressor relay can
control units up to 1 Hp at 240Vac. The second card has 4 relays; it allows you to enjoy the
benefits of the 'Multifunction output' to operate an auxiliary output (cold room light, de-misting
fan, etc.) or to send a remote alarm signal. Both cards can be powered with either 24 Vac or
240Vac.
It is a complete solution for the control and the management of ventilated units working at low
temperatures. It performs all the functions of the IR32P model complete with the
S90OEM4PWR card, with everything packed into one case. Thanks to the very latest
technology, we have achieved a unique product that integrates the 4 relays (2000 VA) into a
case just 74mm wide, 72mm deep and 33mm height, without sacrificing performance and
reliability.
Ir96 is a microprocessor based controller designed for the management of freezer with gravity
or forced-air evaporators. It has 5 relay outputs available to control all the main actuators:
compressor (directly up to 1Hp single-phase), evaporator fans and defrosting. The fourth relay
allows remote signalling of any malfunctioning (high temperature, faulty sensors,...). The fifth
relay can be used to control the unit lights or other auxiliary functions. Two programmable
digital inputs allow innovative performances: automatic alarm management, real time
defrosting, management of lights subjected to the door switch.
1
Cod. +030220151 - Rel. 2.1 - 04/09/98
Main features of the Infrared series
Power supply
All the instruments of the Infrared series − except IR32P − come complete with WIDE RANGE power
supply, allowing you to power your units with either direct or alternating current, from 12 to 24Volt. The 'S'
model is also available with a UNIVERSAL or a HIGH range power supply that allow to extend the power
supply range: from 24 to 240V or from 110 to 240V respectively. All Infrared instruments fit automatically to
the voltage supplied.
With the UNIVERSAL and HIGH range power supply any external transformer to change from 24Vac to240Vacor from 110 to 240V is not required. Such features simplify your work and provide the maximum
reliability as the controller is capable of adjusting perfectly any fluctuation of supply
IR32P is powered by means of the power card and can be supplied either with 24Vac or 240Vac.
Soft touch keypad
It is made of silicone for both functional reasons (especially when pressing the keys) and aesthetic reasons
(it matches the new lines and structures of the latest refrigeration units). The Infrared series is the result of
specific ergonomic choices designed to simplify all procedures. Setting or modifying a parameter, for
example, now requires the touch of just one button.
LED Display
The LED display shows two and half digits' ranging from -40 to +90ºC (-40/+130 with PTC sensor); the
temperature value appears with one decimal point (you can omit it by acting on the dedicated parameter)
ranging from -19.9 to +19.9. In addition there are up to 4 LED indicators (depending on the model) that light
up when the output they represent is ON. They will flash in case of external problems relative to the output
(see Multifunction input) or during active/current procedures.
Buzzer
All controllers come complete with an alarm buzzer upon request.
Remote control
To make it easier to set and display the working parameters, you can request your controller complete with
the Infrared receiver. In this case you will be able to use the remote control unit to perform any operation.
One remote control unit can be used for several IR32 instruments placed within the same room, with no
interference since each controller can be identified by a specific access code.
Duty setting
A completely new function allows the compressor to run even if the regulation sensor is damaged. In case of
short-circuit or open-circuit sensor, the compressor is instructed to start on the basis of time-intervals
(minutes) selected through the 'duty setting' parameter ('c4') and to turn OFF every 15 minutes (fixed timeinterval).
Multifunction input
The Infrared instruments come complete with a digital input that can be used in different ways, depending on
the value given to the parameter 'A4'. The multifunction input can be used to enable/disable defrost, to act
on serious alarm conditions requiring either the immediate (for example, high pressure alarms) or delayed
lockout of the unit (low pressure alarms).
Multifunction output
Some models come complete with a fourth relay for the remote alarm signal or to drive auxiliary ON/OFF
devices.
Keypad protection
The keypad and/or the remote control unit can be deactivated to prevent unauthorized personnel from
modifying settings (especially when the controller is located in a public area).
Continuous cycle
This function operates the ON routines of the compressor for a 't' time selected through a dedicated
parameter. This is particularly useful when a rapid fall of temperature is required.
2
Cod. +030220151 - Rel. 2.1 - 04/09/98
Serial connection
All instruments can be equipped with a 'serial' card that can be fitted any time, even after the controller has
been installed. The serial output allows you to connect the controller to a supervisory and/or telamintenance
system.
In addition, Carel has developed 'MODÌ, a special program for the trouble-free configuration of the Infrared
instruments via Personal Computer through a serial output. 'Modì’ proves to be extremely useful especially
when you need to configure several controllers.
Virtual sensor
All models equipped with two sensors (all except IR32S) may be adjusted to regulate the unit on the basis of
the weighted average temperature or the two sensors. It is also possible to choose which sensor − either the
first or the second one − will be the most important one for the determination of the final value. The value
relative to the virtual sensor will appear on the display (see parameter '/4').
Dimensions
Even the most sophisticated model has standard dimensions. Panel mountings usually require a 71x29mm
drilling template thus making it extremely simple and fast to replace older controllers with new Infrared
instruments.
Protection index
The O-RING inside the front panel of the instrument and the material of the keypad ensure a very high
protection index (IP65). All controllers come complete with a flat gasket that contributes to increase the
protection index of the panel housing the controller.
Fastening the controller
Fastening the controller is achieved using a small clamp made of plastic. No screws are required.
Test-in-circuit
The instruments of the Infrared series are the result of the most advanced SMD technology. All controllers
are built using high quality components. Quality control includes a rigorous 'TEST-IN-CIRCUIT' on each
single component to ensure that your controller is entirely reliable.
NTC sensor
The Infrared instruments have been designed to be connected to Carel NTC sensors since they give greater
precision than different sensor models. However, special versions capable of receiving the most common
types of PTC sensors are available upon request.
Watch dog
It is a special device that will protect the microprocessor of the controller even in the event of strong
electromagnetic noises. In case of abnormal conditions the watch dog restores the initial functioning status of
your unit. Only Carel controllers come complete with this exclusive safety device.
Immunity against noise
The INFRARED series complies with the EEC standards regarding the electromagnetic compatibility.
& ISO9001 Approvals
Quality and safety of the INFRARED series are assured by the ISO 9001 design and production certificate as
well as the CE labelling.
3
Cod. +030220151 - Rel. 2.1 - 04/09/98
FRONT PANEL AND KEYS
Each Infrared controller comes complete with:
•Wide Range power supply
•display 2 and 1/2 digits
•temperature decimal point
•LEDs indicating the outputs status (the number of LEDs depends on the model)
•4 keys for programming the unit (except IR32M);
The following options are also available upon request:
•Universal power supply (IR32S only)
•alarm buzzer
•infrared receiver for programming the unit via remote control
•serial card for connection to a supervisory and/or telemaintenance system such as Carel MasterPlant
for the control and regulation of refrigeration units.
Note: you are requested to indicate the optional functions you need when placing the order. Only the serial
card can be fitted after the controller has been installed. The IRDRSE and IR32SOU versions are not
equipped with the serial output.
LED display
The display shows the temperature values (range: -40/90 or -40/+130 with PTC sensor). The temperature
measured by the sensor is displayed to a 10th degree resolution ranging from -19.9 to +19.9. It is possible to
exclude the decimal part of the degree by modifying the value of the /6 parameter. The display will show one
of the following values/codes, depending on the function being performed.
• normal functioning: value measured by the ambient sensor;
• parameter selection stage: code of the parameter or its value;
• when an alarm condition occurs: the code of the alarm flashes alternatively to the value of the
temperature.
Indicators
On the display there are some luminous indicators (see ƒ to ˆ above). They indicate:
3current transmission via remote unit (the controller must be equipped with IR receiver);
4compressor ON routine (IR32S, IR32Y, IR32C, IR32P e IRDRC);
if the IR32S as been set to work as the ‘T’ model (see parameter H1=0), this LED indicates the status
(ON or OFF), of the controlled output (compressor or other devices); in the IRDRSE/S0 models comp
indication is replaced with the symbol
4b continuous cycle ON routine (all models except IR32M)
5fan ON routine (models IR32C, IR32P and IRDRC);
second sensor reading (model IR32M);
REVERSE function mode (heating) - models IR32S - configured to work as thermostats (H1=0)
6fourth relay active (IR32C and IR32P only)
7defrost ON routine - models IR32S, IR32Y, IR32C and IR32P; in IRDRS, IRDRSE and IRDRS0 models
the indication def is replaced with the symbol
8decimal point
4
Cod. +030220151 - Rel. 2.1 - 04/09/98
Keypad
The buttons on the front panel of the instrument allow you to perform the following functions:
•- goes to the next parameter;
- increases the value of the parameter;
if pressed simultaneously to the button no. 10 (*):
- activates/deactivates the continuous cycle;
in models IR32C and IR32P complete withS90OEM4PWR:
- activates/deactivates the auxiliary output
‚- silences the buzzer (if present);
if pressed for more than 5 seconds:
- allows you to enter the 'F' parameters section (Frequent);
if pressed for more than 5 seconds together with the button no. 9:
- allows you to enter the 'C' parameters section (Configuration);
if pressed when turning ON the instrument:
- activates the RESET procedure
‰ displays and/or selects the SET-POINT;
- displays the value of the selected parameter;
if pressed for more than 5 seconds together with the button no. 2:
- allows you to enter type 'C' parameters (Configuration);
Š
- goes to the previous parameter;
- decreases the value of the parameter;
if pressed for more than 5 seconds:
- activates a manual defrosting cycle (except version IR32S with parameter H1=0);
if pressed together with the button no. 1 (*):
- activates/deactivates the continuous cycle.
(*) Warning: in order to activate a continuous cycle, press the button no. 10 first and then the button no. 1.
5
Cod. +030220151 - Rel. 2.1 - 04/09/98
INSTALLATION
Standard configuration
All Infrared controllers are supplied ready to use. The values of the main working parameters have been
factory-set on the basis of the most frequent and common requirements to meet the greatest number of
application needs. It is always possible to change the preset values to personalize the unit according to your
requirements. The notes below show the default values as well as the parameters that can be modified in
relation to the type of refrigeration unit to be controlled (set-point, differential, etc.). We will also list all the
parameters whose values should always be carefully checked before starting the unit.
The factory-set program makes your unit perform the following main functions:
IR32M: specifically programmed for the detection of two different temperature values. Connect a switch to
the digital input to switch from the first to the second sensor. IR32M can be connected to either NTC or PTC
sensors, as specified when placing the order.
IR32S, IRDRSE and IRDRS0: configured as a thermostat with DIRECT functioning mode (to control
cooling), set-point = 0 ºC and differential= 2 ºC. The default values also include a high temperature alarm set
at 10 ºC above the set-point and a low temperature alarm set at -10 ºC below the set-point. Should you
change the default set-point (0 ºC), the deviation values relative to the alarms will remain +/-10 degrees
above and below the new set-point. When the continuous cycle functioning mode is ON, it will last 4 hours.
After this cycle the temperature alarm will be delayed for two hours.
IR32Y: features the same functions as IR32S. In addition, it is programmed to control timed electric defrost
(duration = 30 minutes) and 8-hour intervals between successive defrost cycles. The temperature displayed
during the defrost cycle will be that acquired before the beginning of the cycle. At the end of the defrost cycle
the evaporator will drain down for 2 minutes and the high temperature alarm will be inhibited for 1 hour.
IR32P: performs the same functions as IR32Y plus the control and regulation of the evaporator fans, these
will be stopped when the compressor is off and during each defrost cycle. At the end of the drain-down time,
the fans will remain off for 3 minutes; this time-delay is necessary to restore the normal temperature of the
evaporator before re-starting the fans. In the IR32P models the defrost cycle will be interrupted as soon as
the evaporator sensor measures a temperature corresponding to 4ºC (defrost based on temperature). The
defrost cycle, however, will last max. 30 minutes. If your controller is complete with the S90OEM4PWR
card, the fourth relay will change state thus indicating an alarm condition.
IR32C, IRDRC: has the same configuration as IR32P plus the 4-relay card. For IR96, please see on page 36.
The following operations should be perform to ensure trouble-free operation of the Infrared unit:
1)installation;
2) connection to sensors, power supply and output contactors;
3)working parameters selection.
Installation
1) insert the instrument into the previously adjusted hole.
2) fasten the instrument to the panel by means of the dedicated clamp.
Connection
1) carry out all electrical connections following the instructions given in this guide (see “Caution”at the end
of this chapter);
2) connect the sensors following the installation instructions carefully.
NOTE: all IR32 and IRDR instruments have been designed for NTC sensors. However, should your system
comprise PTC sensors, ask for a PTC model when placing the order (it is available only for panel mounting
IR32).
6
Cod. +030220151 - Rel. 2.1 - 04/09/98
Cautions
Warning: Before making any electrical installation read the instructions and take careful note of the
diagrams on the following pages. Remember that all safety devices necessary to correct operation must be
fitted in advance.
Installation should be avoided in the following circumstances:
1. Relative humidity greater than 85%.
2. Heavy vibration or shocks.
3. Exposure to continuous water sprays.
4. Exposure to corrosive or pollutant gases (e.g. sulphurous or ammoniacal fumes, saline mist, smoke) so
as to avoid corrosion and oxidisation.
5. Strong magnetic and/or radio interference (therefore installation of the equipment near transmitter aerials
should be avoided).
6. Exposure of controls to direct solar radiation and other climatic influences.
The following must be observed when connecting the controllers:
1. Connecting a power supply of the incorrect voltage can seriously damage the system.
2. Use the correct type of connectors. Slacken each screw, insert the lead and then tighten the screws.
Finally, tug gently to make sure there is a secure grip.
3. So as to avoid any possible electro-magnetic interference, separate as far as possible the signal leads
from the sensors, and the digital inputs from the induction and power leads. Do not place power leadsand sensor leads in the same channels. Furthermore, avoid placing sensor leads in the immediate
vicinity of powered components (thermo-magnetic contacts or others).
Keep the sensor leads as short as possible and avoid their sharing routes with power leads. As defrost
sensors use only guaranteed IP67 sensors; place the sensors with the bulb upright in a position to assist
drainage of any condensation which may occur. Note that thermistor temperature sensors (NTC or PTC)
have no polarity and the terminals may therefore be connected either way.
4. Sensors can be located at distances of up to a maximum of 100 meters from the control. To connect
sensors, leads with a minimum cross-section of 1 square millimetre should be used, and may be
screened. In this case the screening should be connected to terminal 7 on the control; it should not be
connected to earth or to any fitting at the other end of the screening (i.e. the end nearer to the sensor).
5. Whatever may be provided for through the IR32SER board, it is necessary to take care when earthing the
system. In particular:
a) the secondary side of transformers supplying the equipment must not be earthed. If it should be
necessary to connect to a transformer which has a secondary earth, an insulating transformer must be
interposed. If necessary, Carel has available an insulating transformer with the following characteristics:
24Vac to 24Vac, 20VA, reference no. 0907651AXX.
b) if several controls are connected to the same transformer, care must be taken with polarity when
wiring: terminals "4" of all controls must all be connected to the same terminal on the transformer;
terminals "5" of the controls must all be connected to the other transformer terminal. See diagram for
further details.
6. Avoid touching with the fingers the electronic components mounted on the boards, so as to avoid
electrostatic discharges from the operator to the components, as these could become seriously damaged.
7
Cod. +030220151 - Rel. 2.1 - 04/09/98
Selection of the main working parameters
Setting the main working parameters - Ambient set-point
The factory set-point is 0ºC. Should you need a different value, more suitable to your specific application
requirements, observe the following instructions:
•press
•after a while, the value will begin to flash;
•increase or decrease the set-point using theand/orkeys until you reach the requested
value;
•press
for 1 second: the set-point value will appear on the display;
again to confirm the new value;
Setting the differential (hysteresis of the regulator)
The factory-set differential is 2ºC. Should you need a different value, more suitable to your specific
application requirements, operate as follows:
•press for more than 5 seconds (in case of active alarm, silence the buzzer first);
•the code of the first modifiable parameter (/C) appears on the display;
•press either or
•press to display the relative value;
•increase or decrease the value using either the or buttons until you reach the requested
value;
until the code 'rd' appears;
•press again to confirm temporarily the new value and display the code of the parameter;
•press to memorize the new value and exit the procedure.
Other important parameters
For all the models:
As indicated above, all Infrared instruments have been programmed to detect both the high and the low
temperature alarm. In the event of abnormal conditions the internal buzzer (if present) will sound and the
display will show the code of the alarm, that is 'HI' for high temperature, 'LO' for low temperature.
High/Low temperature alarms are generated by abnormal temperature conditions:
•high temperature alarm: the temperature measured by the ambient sensor is 'AH' degrees (or more)
above the set-point: ambient temperature > set-point + AH;
•low temperature alarm: the temperature measured by the ambient sensor is 'AL' degrees (or more)
below the set-point: ambient temperature < set point - AL.
On the basis of the default values, AL = 10 and AH = 10.
In the event of a temperature alarm, the relative message will be delayed for 120 minutes (Ad = 120). After
that the 'HI' or 'LO' alarm will be generated. No alarms will be generated if normal temperature conditions are
restored within the Ad time-interval (the temperature should range within +/-10 degrees of the selected set
point).
While installing the unit, the temperature might take more than 120 minutes (Ad time) to range between the
set limits. Consequently the temperature alarm will be generated. In order to avoid this problem, we suggest
- during this stage only - increasing the Ad time-interval, by increasing the value of the Ad parameter.
8
Cod. +030220151 - Rel. 2.1 - 04/09/98
Models IR32S, IRDRS, IRDRSE and IR32Y
Configuration of the 'type' of instrument
The INFRARED series comprises two models - IR32S and IR32Y - with different operating modes. Both
models feature the H1 parameter (see below) allowing you to select one of the two operating modes. IR32S,
IRDRS and IRDRSE can operate either as a simple thermostat (H1=0, default value) or as a thermostat and
defrost controller for static units operaring at normal temperatures (the defrost cycle starts when the
compressor stops, H1=1). For the second type of operating logic, it is necessary to configure the instrument
and give H1 the value '1' (H1=1, see below 'How to modify the working parameters').
IR32Y controls and regulates both temperature and defrost for static units working at low temperature
ranges. The defrost cycle can use the timed ('X' functioning mode) or temperature end (evaporator
temperature, 'Y' functioning mode). In the second case the instrument requires another sensor - called the
defrost end sensor - to be placed on the evaporator (when in the 'X' functioning mode, the input for the
'defrost end sensor' remains free). The 'H1' parameter allows you to select either the 'X' or 'Y' functioning
logic. When H1=0 (default value), the instrument works in the 'X' logic (end of defrost based on time). If you
want the end of defrost based on temperature, select the 'Y' logic, that is H1=1 (see below 'How to modify the
working parameters').
Defrost parameters
When using the Infrared unit to control defrost, check the following parameters before starting the unit:
Models IR32S, IRDRS and IRDRSE (with H1=1), IR32Y, IR32C, IRDRC and IR32P:
dI: Time-interval between defrost cycles: defrost cycles occur periodically, depending on the time-
intervals (hours) set through the 'dl' parameter. When the time-interval is 0 (dl=0), the defrosting cycle is
never carried out unless it is forced via keypad (manual defrost) or via the digital input (see A4 parameter).
Temperature alarms are inhibited during each defrost. Def.: 8 (hours)
dP: Maximum defrost time: the dP parameter determines the maximum duration of the defrosting cycle
(minutes). In the models without evaporator fan (IR32S with H1=1 and IR32Y with H1=0) this parameter
indicates the actual duration of the defrost. Def.: 30 minutes
Models IR32Y, IR32C, IRDRC and IR32P
d0: Type of defrost: in the models equipped with defrost relay (IR32Y, IR32C and IR32P) 'dO' determines the
type of defrost, that is: 0 = electrical defrosting, 1 = hot gas defrosting. Def.: d0=0, electrical defrosting
dt: Defrosting end SET-POINT: in the models equipped with defrost end sensor (IR32Y with H1=1,
IR32C, IRDRC and IR32P) 'dt' allows you to set the defrost end temperature. Remember, however, that the
maximum duration of the defrost cycle corresponds to the value (in minutes) given to the dP parameter.
When the temperature measured by the defrost end sensor is higher than the defrost end set point set by the
User, the defrost cycle will be omitted. Def.: 4 ºC
LIST OF THE WORKING PARAMETERS TO BE CHECKED
BEFORE STARTING THE UNIT
CodeParameterTypeMinMaxM.u.Def
PARAMETERS OF THE REGULATOR
rdControl differentialF0.1+19.9 °C/°F2
DEFROST PARAMETERS
d0Type of defrost (0=electrical, 1=hot gas)C01flag0
dITime-intervals between def. cyclesF0199hours8
dtDefrost end set-pointF-40+199°C/°F4
ALARM PARAMETERS
AdTemperature alarm delayF0+199min120
OTHERS FUNCTIONS
H1Model [IR32Y: 0=type X; 1=type Y]
[IR32S, IRDRSE/S0: 0=type T; 1=type S]
C01flag0
9
Cod. +030220151 - Rel. 2.1 - 04/09/98
HOW TO MODIFY THE WORKING PARAMETERS
The microprocessor of the INFRARED instruments allows you to configure the functions of your controller
according to the application requirements. To simplify this operation, we have divided the Working
Parameters into two main groups:
•frequently used parameters (indicated as 'F' parameters in the tables below);
•configuration parameters ('C'), protected by a code or password to prevent unauthorised access to the
data.
All parameters can be modified via keypad (except IR32M, with no keys) as well as via remote control unit or
serial line. In order to modify the parameters via front panel keypad, observe the following instructions:
Gaining access
To gain access to the 'F' parameters:
•press the
•the display shows the code of the first modifiable parameter (/C);
To gain access to the 'C' parameters:
•press the
•the display shows 00;
•press either the or button until '22' (the password) appears;
•confirm pressing ;
•the display shows the code of the first modifiable parameter, that is '/C'.
for more than 5 seconds (in case of alarm condition, silence the buzzer first);
and
buttons simultaneously for more than 5 seconds;
How to modify the parameters
Modifying parameters: after having displayed the first parameter, either 'C' or 'F', follow these instructions:
•press either or until you reach the parameter whose value needs to be changed;
•press to display its current value;
•increase of decrease its value using the or key until you reach the requested value;
•press to memorize temporarily the new value and display the code of the parameter again;
•press again either or to go to the next parameter you want to change;
then repeat the operations as indicated above, starting from "press .."
How to exit the procedure
How to memorize the new set values
•Press
Important: it is necessary to press to memorize the new values. In case of power failure before
has been pressed, all modifications will be lost. Whenever you modify the value of a parameter, we strongly
recommend writing it down in the dedicated column situated on page 46 of this guide (see column 'New value').
to memorize the new values and exit the procedure.
How to exit the procedure without memorizing the modified data
•do not press any key for at least 60 seconds (TIME OUT). The instrument will return to its normal
functioning mode.
10
Cod. +030220151 - Rel. 2.1 - 04/09/98
RESET PROCEDURE
In case of abnormal conditions - strong electromagnetic noises, for example - there might be errors when
storing data. Consequently the unit might not work correctly. When the microprocessor identifies an error in
the process of storing data, one of the following groups of letters will be displayed:
EA, EB or EE
In order to restore normal working conditions, it is necessary to RESET the instrument (for the instruments
having serial number < 5,000 see the note at the end of this guide). Please note that RESETTING the
instrument is quite an unusual procedure, as well as the causes that can make it necessary. We would also
like to point out that competitive controllers are not capable of dealing with such serious conditions which
would normally lead to inevitable damages to the instrument. This is the reason why Carel have
implemented the RESET function in all the controllers of the INFRARED series, thus providing safer and
more reliable instruments, always capable of restoring their normal functions without any problem. Should
this error message appear without any apparent reason, we strongly recommend inspecting the unit carefully
and finding out the causes that generated it. (Please also find useful information at the end of the
“Installation” chapter);
To reset the controller:
••turn off the instrument;
•press and, keeping it pressed, turn on the controller;
•the display shows "_c_";
•after a few seconds, the instrument automatically allows you to gain access to the 'C' parameters where
you can modify the default values according to your specific requirements. Also the /0 parameter will be
displayed thus allowing you to select the type of sensor you want to use (NTC or PTC):
Important: after the RESET procedure the values of each single parameter will be exactly the
factory-set ones (default values). Any modification made before the reset procedure will therefore
be lost.
If you are using an instrument set to receive a PTC sensor, it is necessary to set the parameter /0=1
because the default value appearing after the reset procedure will be 0 (/0=0, NTC sensor).
For further information see the parameters relative to the sensors.
•if your instrument requires default values, normal working conditions will be restored by simply
pressing
•if the instrument requires a different configuration, it is necessary to modify all parameters whose values
are different from the factory-settings.
After having modified the parameters, press to exit the procedure and come back to the normal working
mode.
Note: the reset procedure should be carried out by expert personnel only. We would like to point out,
however, that such a procedure does not damage the instrument but it simply restores its factory-set
configuration. As a result, you can resort to this in the event of confused or incorrect modification of the
working parameters. In this case, in fact, resetting the controller will allow you to recover the factory-set
configuration and restart the modification procedure, without any problem.
.
Should 'EE' persist, even after the above procedure has been carried out, press until the message
disappears. If you do not manage to clear the EE error, it will be necessary to replace the controller. If the
EE message occurs frequently or disappears with difficulty, it is better to get in contact with the nearest
service centre to check the precision of the instrument.
11
Cod. +030220151 - Rel. 2.1 - 04/09/98
REMOTE CONTROL UNIT
The IR32 Infrared instruments can be easily and quickly programmed by means of the remote control unit.
Until now programming multi-function instruments dedicated to refrigeration was a very complex procedure.
This is why Carel have enhanced the IR32 series with the remote control unit, used not only to program the
controller from a remote position but also to allow the End-User to set the main working parameters easily
and fast. Today, modifying any parameter of an IR32 instrument is as easy as turning the volume ofyour TV 55or 66.. An interesting feature of the Infrared series is the possibility of selecting the access code
(H3) for each controller to further simplify the use of the remote control. In fact, if your installation includes
several controllers, selecting a specific access code will allow you to modify only the parameters of the unit
the code refers to, without interfering with the other controllers. Changing the value of a parameter requires a
special procedure (see 'START' button). Further safety is also provided by the 'H2' parameter that allows you
to protect your system from unwilling or unauthorised access or modification of all set data.
On the basis of the function performed, the buttons on the remote control unit, have been grouped as
follows:
•buttons to activate/deactivate the use of the remote control unit;
•pre-programmed buttons for the modification of the values of the main parameters;
•buttons for the remote control of the IR32 keypad.
Buttons used to activate/deactivate the use of the remote control unit
The buttons shown on the left are the remote control unit ON/OFF buttons. They
also allow you to memorize any new parameter value.
MEMO1) ends the programming procedure and memorizes the new
values given to the parameters;
2) silences the buzzer when programming the IR controller
via remote control unit;
CANCELinterrupts the transmission without memorizing the modifications;
STARTenables the use of the remote control unit;
NUMERIC BUTTONS: allow you to select the access code. We advise you to
give each controller a specific access code, especially when your
control panel includes several IR instruments or when all of them
are exposed to the beam of the remote control unit. In this way you
will be able to modify exactly the parameters you want to change,
without interfering with the data of the other controllers. (See also
'How to use the remote control unit' and 'How to select the
password').
12
Cod. +030220151 - Rel. 2.1 - 04/09/98
Buttons used to modify the main parameters (directly accessible buttons)
The most frequently used parameters are indicated on the remote control
unit. They are grouped in three light-grey zones:
•temperature parameters;
•defrost parameters;
•continuous cycle parameters.
For the correct use of the buttons see 'How to use the remote control unit'
below.
Buttons for the remote control of the IR instruments
The green zone of the remote control unit reproduces exactly the keypad of the
IR instruments and allows you to perform the same operations, as you would
perform if you were using the keypad.
Here are the main functions of the buttons:
SEL displays the value of the selected parameter;
1) goes to the next parameter;
2) increases the displayed data (parameters selection phase);
AUX activates/deactivates the auxiliary output;
1) goes to the previous parameter;
2) decreases the displayed value (parameters selection phase).
HOW TO USE THE REMOTE CONTROL UNIT
Access without code
1)How to enable the controller to receive the remote control unit transmission
•press the 'START' button to operate the remote control unit;
•the controller's LED indicator above the digits flashes and the first parameter - '/C' - is immediately
displayed.
2)Modifying the main parameters
•press either the + or - button relative to the parameter you want to modify. The display will show the
code of the selected parameter (see the codes of the parameters listed in the Instruction Sheet of the
instrument). Press the button again to display the value associated to the selected parameter and
•press + to increase it;
•press - to decrease it.
13
Cod. +030220151 - Rel. 2.1 - 04/09/98
The section including directly accessible buttons also comprises 3 buttons that activate/deactivate the
function they represent:
DEFROST SECTION:
STARTactivates/deactivates a manual defrost cycle;
°C evap.displays the temperature value measured by the defrost end sensor (if present) or the
value measured by the second sensor (IR32M model).
Important: this function is always active. Consequently the temperature measured by the second sensor will
be always displayed without having to press the 'START' button or select the access code (see point 5
below).
CONTINUOUS CYCLE SECTION:
C.cont. activates a continuous cycle;
•to exit the programming procedure see point 4 below.
3) How to modify the parameters not directly indicated by a specific button
The other parameters - not directly associated to a specific button on the remote control unit - can be easily
modified as follows:
•perform the same operations described in point 1 above until the first parameter '/C' appears on the
display;
3.1)
•press either or
•press SEL to display the value of the selected parameter;
•press either or to increase/decrease its value;
•press SEL to confirm temporarily the new value and display again the code of the parameter;
•to modify another parameter repeat the operations described above starting from point 3.1;
•exit the programming procedure as described in point 4 below.
until the display shows the parameter you want to modify;
4) How to exit the programming procedure
•press PRG to exit and memorize all modifications;
•press CANCEL to exit without memorizing the previous modifications;
•do not press any button for at least 60 seconds (TIME OUT).
In this way the previous modifications will be cancelled.
Access with code
5) How to enable the controller to receive the remote control unit transmission
•press 'START' to operate the remote control unit;
•all the controllers exposed to the beam of the remote control unit will display their own access code;
•select the access code of the controller whose parameter you intend to modify using the numeric section
on the remote control unit. Select the code correctly (if the code of the controller is 05, press 0 and 5).
•the controller's LED indicator above the digits flashes and, simultaneously, the code of the first
parameter '/C' appears on the display.
•perform the same operations described in point 2) or 3) above.
How to select the access code
Setting the access code
All IR32 controllers have no factory-set access codes. The User can choose and set his own access
codes by simply modifying the H3 parameter as follows:
•press 'START' to operate the remote control unit;
•the controller's LED indicator above the digits flashes and the first parameter ('/C) appears immediately.
•press to display the H3 parameter;
•press SEL to display its value (default 00);
•press to select the requested value (from 01 to 199);
•press SEL to confirm the new value and display again the H3 code;
•press MEMO to memorize the access code and exit the procedure.
Removing the code
•repeat the operations described above and give the H3 parameter the value 00 (H3=00). In this way you
can program your controller/s without selecting the access code.
14
Cod. +030220151 - Rel. 2.1 - 04/09/98
FURTHER INFORMATION
Configuration parameters
As already mentioned, (see chapter 'How to change the operating parameters'), there are two types of
parameter:
•parameters used frequently (indicated by 'F' in the following tables)
•configuration parameters (type C) which are protected by a password to prevent unwanted modification.
Categorisation of parameters
Besides being divided into TYPES, the parameters are grouped into logical categories labelled by letters
indicating their function. The categories and their identifying letters are given below:
Category Description
Flashing 00 Does not indicate a category, but merely that the password must be
entered in order to gain access to the configuration parameters.
/ parameters relative to the temperature sensor
r parameters relative to the temperature regulation
C parameters relative to the compressor management
d parameters relative to the defrost management
A parameters relative to the alarm management
F parameters relative to the evaporator fan management
H general parameter configuration
NEW RELEASE
The instruments with serial number greater than 100,000 have a new software release − compatible with the
previous one − offering new functionalities described in detail in the following chapter.
The password
Flashing 00: PASSWORD
This is a protective device which intentionally "complicates" access to Configuration parameters in order to
prevent accidental changes or any that might be made by unauthorised persons. Type C parameters are in
fact those which alter the control configuration. Once the configuration parameters have been entered by use
of the password, the system allows the user to alter type F parameters as requested.
The password request (flashing 00) appears when the two buttons and are pressed at the same
time. Access to type C parameters is gained as follows:
•press or to produce 22 or the correct password;
•confirm with ;
•the code of the first modifiable parameter is displayed, that is '/C'. (On controls with serial number
less than 5,000, '/O' is displayed instead of '/C' . See the relative note on page 49).
In the following paragraphs all the parameters will be described, indicating in which versions they are
available and what values can be assigned to them. (Remember that on version IR32M the parameters are
modifiable only through the remote controller and the serial input).
There will also be indicated the default value (Def.), which is the value given to the parameter in the factory.
Furthermore it will be stated whether the parameter is modifiable through the remote controller with "directaccess", that is, whether there is a specific button for modifying it on the remote controller. It should be
remembered that ALL the parameters are modifiable through the remote controller; the 16 most frequent
parameters can however be modified directly by means of a dedicated button ("direct access").
15
Cod. +030220151 - Rel. 2.1 - 04/09/98
/ = Parameters for the management of the temperature sensors
°C / °F (0=°C,1=°F)
/6Decimal point (0=yes, 1=no)C01flag0
Note: for the set times to become operative, the instrument must be switched off and on again.
Short descriptive note about sensors with thermistors types NTC and PTC:
Equipment of the IR32 series is designed to work with NTC Carel temperature sensors, or sensors using
thermistors with a negative characteristic (NTC stands for Negative Temperature Coefficient). This type of
thermistor modifies an electrical parameter (its own resistance) in inverse proportion to any change in
temperature; that is, the resistance falls as the temperature rises, and vice versa. Other types of thermistor
are on the market. Widely available are PTC thermistors with a resistance of 985 Ohms at 25°C. PTC stands
for Positive Temperature Coefficient; by contrast with the NTC, these increase their resistance directly
according to the temperature increasing. As you can see in the diagram below, (the horizontal axis
represents the operating range, the vertical axis the error), the NTC type of sensor shows greater accuracy
than the PTC version. This is why the NTC sensors have been adopted as standard.
C01flag0
Maximun variation shown by types NTC and PTC temperature probes in
-30-25-20-15-10-5051015202530
Variation of PTC 985 Ohm probe at 25°C
relation to intended theoretical values .
3
2
1
0
-1
-2
-3
-4
Variation of Carel NTC probe
It is nevertheless possible to use Infrared equipment with PTC sensors of the 985 Ohm, 25°C type by
specifying the model required.
/0: Type of sensor
This parameter is displayed only during the reset procedure (see relative chapter). On equipment with a
serial number less than 5000 the parameter /0 is displayed whenever access is gained to type C parameters.
On this point please refer to the specific note at the end of the manual. The parameter /0 allows users to
specify the type of sensor being used, i.e. whether NTC (/0=0) or PTC (/0=1). As indicated previously, it is
emphasised that IR32 equipment is normally designed to work with NTC sensors. To be able to work with
PTC sensors rather than NTC, a modification is required which can only be carried out in the factory, and it
is not enough to shift the parameter /0 to =1. If PTC sensors are to be used, therefore, it is essential to
specify the requested code at the time of ordering (see chapter 'Ordering codes 'I).
Parameter /0 is useful in only one situation: that is where the equipment has been acquired to work with a
PTC sensor and, in addition, due to serious malfunction, it has been reset (see "Reset procedure"). After the
reset, the microprocessor installs the parameter /0=0, which is the value intended for the NTC sensor and
therefore incompatible with hardware designed for a PTC sensor. In such an event it is necessary to operate
manually to set the parameter /0 to the correct value, i.e. /0=1 (operation with PTC sensor). Any other use
can cause malfunctioning.
Default for standard models /0=0
Default for PTC models /0=1. Available on all panel mounting models
16
Cod. +030220151 - Rel. 2.1 - 04/09/98
/C: Calibration offset
This parameter allows the temperature shown on the display to be corrected. The value assigned to this
parameter is added to (if positive) or subtracted from (if negative) the temperature transmitted by the sensor.
For example, if it is wished to reduce the temperature displayed by 2.3 degrees, /C should be set to = -2.3.
The calibration offset can be varied from -20 to +20 with a precision to a tenth of a degree, from -19.9 to
+19.9. Default is 0.0, i.e. no offset is applied to the sensor's reading.
This parameter can be accessed directly from the remote control.
/2: Stability of measurement
This parameter is employed to control the stability with which the temperature is measured. Low values
assigned to this parameter produce a prompt response by the sensor to variations in temperature; however,
the display becomes correspondingly sensitive to changes. High values slow down the response, causing
less fluctuation and a more stable reading. Default value is 4. Available on all models.
/3: Sensor reading speed
This parameter stabilises the maximum temperature variation within a period equal to 200ms (equipment
cycle period). Small values of this parameter restrict the variation in temperature within the short period, and
thus reduce the equipment's susceptibility to erratic impulses.
Note: If it is wished to alter both this parameter and the previous one, it is recommended to operate in a
consistent manner: if /2 is increased, it is correct to leave /3 unchanged or to reduce it. Vice versa if /2 is
decreased. Default value is 8. Available on all models.
/4: Virtual sensor
In equipment with two sensors (IR32M, IR32Y, IR32C, IDRDC and IR32P), this parameter allows a choice as
to whether temperature is regulated by reference to one sensor alone (P1 on the IR32M) or by reference to a
weighted average of the two sensors. This parameter is useful in special applications. For example, it is
possible to place the ambient sensor in the suction and the defrost sensor in series. Control can be effected
via the weighted average of the two values read. The formula used by the microprocessor is:
virtual sensor = ambient - (ambient - defrost) x (value of /4)
100
When /4=0, control is effected using the ambient sensor. This is the typical situation.
When /4=100, control is effected by reference to the values read by the defrost sensor (sensor P2 on
IR32M).
When /4=50, control is effected by reference to a "virtual" sensor, which is given by the average between
the ambient sensor (or P1) and the defrost sensor (or sensor P2). With values above 50 the defrost sensor
exerts greater influence; with lesser values the ambient sensor does. If the defrost sensor suffers a failure,
the equipment is controlled by the ambient sensor. On the IR32M version, the parameter must remain at
zero (0), as this control system has no second sensor. Default: 0, control by ambient sensor (P1 on the
IR32M).
Available on IR32M, IR32Y, IR32P, IR32C and IRDRC).
/5: Selection of °°F or °°C
Defines the unit of measurement.
0 = for working in degrees Celsius,
1 = for working in degrees Fahrenheit.
In passing from one to the other there is automatic conversion of set and differential into the new unit.
Default = 0, working in degrees Celsius. Available on all models.
/6: Decimal point
Allows the display of temperature with or without tenths of degrees ranging from -19.9 to +19.9.
0= data displayed with tenths of degrees;
1= data displayed without tenths of degrees.
Default: 0, decimal place shown. Available on all models.
Note: for the set times to become operative, the instrument must be switched off and on again.
rd: Regulation delta
Sets the value of the differential, or hysteresis, used in regulating the temperature. A narrow differential, i.e.
one with a low number, ensures a temperature which differs little from the setpoint (or optimal operating
temperature), but which requires frequent switching on and off of the main operating components (normally
the compressor). It is possible to prolong the life of the compressor by appropriately setting the parameters
to define the number of start-ups per hour and the minimum switch-off period (see the Compressor
parameters).
In all Infrared refrigeration equipment the differential is placed to the right of the setpoint as indicated below
(DIRECT operation):
Default: rd=2. Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC. Parameter with direct
access from remote commander.
r1: SET minimum allowed
This parameter sets the minimum value that can be given to the setpoint. Using this parameter prevents the
user from fixing a setpoint lower than the value assigned to r1. Default: -40. Available on IR32S,
IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
r2: SET maximum allowed
This parameter sets the maximum value accepted as a setpoint. Use of this parameter prevents the user
from fixing a setpoint greater than the value assigned to r2. Default: +90. Available on IR32S, IRDRSE/S0,
IR32Y, IR32P, IR32C and IRDRC.
r3: DIRECT/REVERSE
Model IR32S is also designed to operate as a thermostat (parameter H1=0, see below). In "thermostat"
operation it is possible to select the function "cooling" (or DIRECT, as typically used in refrigeration) or the
function "heating" (or REVERSE, as used typically in heating). It should be remembered that in the
REVERSE mode the differential is to the left of the setpoint as indicated in the diagram below. Model IR32S
has a further parameter in the "r" category for selecting the mode of operation, parameter r3.
When r3=0 you have the DIRECT operation (refrigeration). When r3=1 you have the REVERSE operation
(heating). See also the description of parameter A4. Default: r3=0 (DIRECT) with H1=0 on model IR32S,
IRDRSE/S0. This parameter is not available on other models. Available on IR32S, IRDRSE/S0.
For the r3, r4, r5, rt, rH, rL parameters: see the following chapter “Notes for the new release” to a more detailed
description of this parameter functionalities, effective for the instrument with serial number greater than 100,000)
18
Cod. +030220151 - Rel. 2.1 - 04/09/98
c = parameters for the compressor management
COMPRESSOR PARAMETERSTypeMin.Max.U.m.Def.
c0Delay in compressor insertion after switching on equipmentC015mins0
c1Minimum time between two successive insertions of
compressor
c2Minimum compressor down timeC015mins0
c3Minimum compressor operating timeC015mins0
c4Duty setting (compressor safety: 0=OFF, 1=ON)C0100mins0
ccDuration of continuos cycleC015hrs4
c6Alarm cut-out after continuos cycleC015hrs2
Note: for the set times to become operative, the instrument must be switched off and on again.
c0 Delay in switching on compressor and fans (if controlled) after switching on the equipment.
From the moment when the equipment receives its power supply, start-up of the compressor is delayed by a
period equivalent to the value assigned to this parameter. This delay serves to protect the compressor from
repeated start-ups when there is some interruption in the power supply. For example, if the paramater is set
at c0=6, the compressor will wait for six minutes after power is restored before starting up. Thus if there are
several power failures close together (in this case at intervals of less than six minutes), the compressor will
not start up. In the case of installations with more than one compressor, the parameter A0 can also be used
to avoid simultaneous start-ups of several compressors; it is sufficient to assign a different value to A0 for each
compressor.
C015mins0
Default: c0=0 (no minimum period is assigned to the
delay between switching on equipment and activation of
the compressor). Available on IR32S, IRDRSE/S0,
IR32Y, IR32P, IR32C and IRDRC
c1: Minimum time between two start-ups of compressor.
This sets the minimum time in minutes which must elapse between two insertions of the compressor,
independently of the temperature and of the setpoint. By setting this parameter it is possible to restrict the
number of start-ups per hour. For example, if the greatest number of start-ups permitted in an hour must be
10,
it is sufficient to set c1=6.
Default: c1=0 (No minimum interval between two
insertions is set.)
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C
and IRDRC.
c2: Minimum compressor down-time: this sets the minimum time in minutes for which the compressor
may remain inactive. The compressor will not be started up if the minimum time selected has not elapsed (c2). This parameter is
useful for equalising pressure after switch-off in the case of installations with hermetic and capillary compressors.
Default: c2=0 (No minimum down-time for the compressor is
set.)
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and
IRDRC.
19
Cod. +030220151 - Rel. 2.1 - 04/09/98
c3: Minimum compressor operating time: this sets the shortest period for which the compressor may
operate. The compressor will not be switched off if it has not been active for a time equivalent to the minimum
selected.
Default: C3=0 (No minimum operating period has
been set).
Available on IR32S, IRDRSE/S0, IR32Y, IR32P,
IR32C and IRDRC
c4: Duty setting or safety relay: if the Control sensor alarm is activated, (or if the ambient sensor is
short-circuited or disconnected), this parameter allows the compressor to function while the fault is being
repaired. As the compressor is unable to function on the basis of temperature (because of the faulty sensor),
it is activated cyclically with an operating time ("ON time") in minutes equivalent to the value assigned to c4
and a fixed OFF time of 15 minutes. There are two values of c4 which produce particular functioning. If
c4=0, the compressor will remain permanently OFF in case of a defective sensor; if c4=100, the compressor
will remain permanently ON, the 15 minutes off-time being cancelled. The following particular situations should
also be considered:
•If the control sensor fault occurs while the compressor is OFF, the compressor will start up (subject to
limits imposed by parameters c1 and c2) and remains ON for the period set by c4. At this point the "duty
setting" begins. This mode is indicated by the "COMP" LED which flashes during the compressor's off-time
and
stays permanently lit when the compressor is operating. The fans continue to operate according to the
chosen parameters (see category F).
•If the sensor defect alarm is signalled while the compressor is operating, the compressor is switched off
(without regard to the minimum operating time which may have been selected under parameter c3), and
remains off for 15 minutes; (the "COMP" LED flashes during this phase). After this, periodic operation
commences according to the operating time set under c4.
•If the sensor defect alarm is signalled while the equipment is defrosting or in continuous cycle, control
immediately leaves the state in which it happens to be and initiates the duty setting. To re-start
defrosting
or continuous cycle operation it is necessary to replace the ambient sensor. Since it is not possible to
effect defrosting by manual means, a replacement sensor should be available in case of any
malfunction.
If the sensor fault disappears, the equipment will return to normal operation. If at the moment of
disappearance the compressor is operating, it will continue for a period equivalent to the value of c3; if it
is off, it will remain off for a period equivalent to the value of c2
Default: 0 (Compressor always off in case of
defective ambient sensor.)
Available on IR32S, IRDRSE/S0, IR32Y, IR32P,
IR32C and IRDRC.
cc: Duration of the continuous cycle: it is the period in hours for which the compressor remains in
operation so as to lower the temperature even below the setpoint. If cc=0, the continuous cycle is not
activated. Control leaves continuous cycle mode when the period set under parameter cc has elapsed, or
when the minimum temperature set has been reached (see minimum temperature alarm, parameter AL).
Default: 4 (hours). Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC. Parameter with direct
access from remote control.
c6: Alarm cut-out after continuous cycle operation: the time in hours for which the temperature alarm
is de-activated after continuous cycle operation. If the temperature of the refrigerated unit should drop, after
continuous cycle operation, to a level below the minimum temperature (setpoint AL), the activation of the low
temperature alarm is delayed for the period set under parameter c6. It should be remembered that at that
temperature (setpoint AL), the continuous cycle is automatically de-activated. Default: 2 (hours). Available on
IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
20
Cod. +030220151 - Rel. 2.1 - 04/09/98
d = Parameters for the defrost management
DEFROSTING PARAMETERSTypeMinMaxUnitDef
d0Type of defrosting (0=resistance, 1= hot gas)C01flag0
dlInterval between defrostsF0199ore8
dtEnd of defrost temp setpointF-40+199°C/°F4
dPMax duration of defrostF1199min30
d4Defrost at power ON (0=no, 1=yes)C01flag0
d5Defrost delay from power ON or start of MultifunctionC0199min0
d6Interrupt display during defrostC01flag1
ddDripping timeF015min2
d8Alarm cut-out time after defrost and/or open doorF015ore1
d9Defrost priority over compressor protection (0=no, 1=yes)C01flag0
d/Reading defrost sensorF--°C/°FdCTime basis (0=hours/min, 1=minutes/seconds)C11flag0
Note: for the set times to become operative, the instrument must be switched off and on again.
d0: Type of defrosting
This parameter sets the type of defrosting for equipment fitted with defrosting relays:
0 = defrosting by resistance;
1 = defrosting by hot gas.
Default: d0=0, resistance defrosting. Available on IR32Y, IR32P, IR32C and IRDRC.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
dI: Interval between two defrost cycles
Defrosting is effected periodically at intervals equivalent to dI (in hours or minutes, see parameter dC). The
dI period is counted from the END of the previous defrost. If the period equals 0 (dI=0), defrosting will not
begin unless commanded by the keypad or a digital input. Temperature alarms are over-ridden during
defrosting.
Default: 8 (hours). Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
Parameter with direct access from remote control.
dt: SETPOINT for temperature at end of defrost
On equipment supplied with an end of defrost sensor (IR32Y with H1=1, IR32C and IR32P), this parameter
allows the temperature of the evaporator requested at the end of defrosting to be set. (The temperature of
the evaporator is taken from the defrosting sensor.) If, at the start of a defrosting cycle, the temperature
indicated by the defrosting sensor is higher than the temperature set for the end of defrosting, the cycle will
not be effected. In the case of a malfunction of the defrosting sensor, control will effect a defrost lasting for a
period equivalent to the value set for dP. Thus if the end of defrost setpoint can not be reached, the
defrosting will be interrupted after a maximum period equivalent to the value in minutes of dP, and the fault
will be displayed Ed. This will remain displayed until a "correct" defrosting cycle is effected, or there is a
change in temperature.
Default: 4°C. Available on IR32Y, IR32P, IR32C and IRDRC.
Parameter with direct access from remote control.
dP: Maximum duration of defrosting
This parameter determines duration of the defrosting in minutes (or seconds, see parameter dC). On
equipment without defrost sensors on the evaporator (IR32S with H1=1 and IR32Y with H1=0), this
parameter represents the actual duration of the defrost.
Default: 30 minutes. Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
Parameter with direct access from remote control.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
21
Cod. +030220151 - Rel. 2.1 - 04/09/98
d4: Defrosting at power ON
It activates a defrost as the power supply is switched on. A request to defrost on start-up has priority over
insertion of the compressor and over activation of a continuous cycle. Possible values are:
0 = no, defrosting on start-up of equipment;
1 = yes, defrost is effected on start-up.
Commanding a defrost as the power supply is switched on can be useful in certain particular situations, for
example if the installation suffers from frequent power break-downs. If there is a power failure, the internal
clock which calculates the intervals between two defrosts will be set back to zero. In an extreme case, if the
frequency of power failure were to be greater than the frequency of defrosting (for example a power failure
every 8 hours with a defrost interval of 10 hours), control would never command a defrost. In such a
situation it is better to activate defrosting as the power comes on, especially if defrosting is set at a
temperature (evaporator sensor) intended to avoid unnecessary defrostings or if their duration is reduced.
In the case of multi-unit installations, if defrosting at power-on is chosen, it can happen that when power is
restored, all units begin defrosting at the same time, therefore the supply can be overloaded. To avoid this
consequence, use can be made of parameter d5, which permits an initial delay in defrosting; this delay
obviously has to be different for each unit. Default: d4=0 (no defrost at power-on). Available on IR32S,
IR32Y, IR32P and IR32C.
d5: Delay of defrost at power-on or start of Multi-function
This parameter sets the time which is to elapse between the controller power on and the start of defrosting.
When digital input is used, either to initiate defrosting (see parameter A4=3) or to convey a defrosting
command from an external contact (see parameter A4=4), this parameter represents the delay occurring
between the initiation of defrosting, or a request for it, and its actual commencement. The digital input for
defrosting (see parameter A4) can be usefully employed to carry out defrosting in real time. It is sufficient to
connect a timer at the multifunction digital input (see parameter A4). Defrosting will be activated when the
timer contacts close. Where several units are connected to the same timer, we suggest to use the parameter
d5 to delay the various defrostings, so as to avoid any overload on the supply. Furthermore, to avoid
unwanted defrosting being commanded by the equipment internal clock, we suggest set at 0 to the
parameter dI, (defrosts only from keypad or from multi-function contact).
Default: d5=0 (no delay in defrost at power-on or from multi-function input).
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
d6: Blocking display during defrosting
This parameter gives consent to block the display of ambient temperature at the last value read before
defrosting began. Display resumes normally when the measurement first reaches the setpoint o, or in any
case within the time set as "alarm cut-out during defrost (parameter d8). If the display is not blocked during
defrosting the equipment will display the signal dF rather than the value received from the control sensor.
This is to indicate that a possibly high temperature is due to the defrosting process.
Default: d6=1 (during defrosting the display shows the last temperature read before defrosting began).
Available on IR32S, IR32Y, IR32P and IR32C.
dd: Dripping time
This parameter makes it possible to close down the compressor and the evaporator fans after a defrosting,
so as to hasten the dripping from the evaporator. The value of the parameter indicates the minutes of shutdown. If dd=0, no dripping time is provided for, with the result that the compressor will be re-activated
immediately defrosting is over.
Default: dd=2 minutes. Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
Parameter with direct access from remote control.
d8: Period of alarm cut-out after defrosting and/or open door
This indicates the time for which a high temperature alarm will be inhibited at the end of a defrosting and/or
after the door of a store-room has been opened; in the case of Multi-function input being connected to the
door-switch (see parameter A4).
Default: d8=1 hour of cut-out. Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
22
Cod. +030220151 - Rel. 2.1 - 04/09/98
d9: Defrost priority over compressor protection
This parameter cancels the compressor protection times (c1: minimum time between two successive startups, c2: minimum shut-down time and c3: minimum operating time) at the start of defrosting.
0= protection times are observed;
1= protection times are not observed; defrosting has greater priority and takes no account of the compressor
timings.
As an example, it is useful for avoiding delay in hot gas defrosting when the compressor has only just shut
off and has been restarted with a minimum time between two insertions. It must be remembered however
that in this event the maximum number of compressor start-ups per hour may not be observed.
Default: d9=0 (defrosting is subject to the compressor's timings - it should be remembered that in the default
state these are set at zero). For equipment with serial number less than 5,000 d9=1 in default state.
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
d/: Reading defrost sensor
By choosing this parameter it is possible to display the value being read by the defrost sensor, in equipment
where that is fitted. When the parameter d/ has been selected, pressing will not allow the value to be
changed, but the value registered by the defrost sensor can be read.
Available on IR32Y, IR32P, IR32C and IRDRC.
Parameter with direct access from remote control.
dC: Time bases
Consent to alter the units of measurement used in counting times for parameters dI (interval between
defrosting) and dP (duration of defrosting).
0 = dI is expressed in hours and dP in minutes;
1 = dI is expressed in minutes and dP in seconds.
The parameter dC=1 can be useful for speedily testing the operation of defrosting with reduced times.
It is however considered that if defrosting requires insertion of the compressor (hot gas defrosting)
and the parameter d9=1 there can be a risk of damaging the compressor by too many start-ups at
short intervals.
On the other hand, the parameter dC=1 can be very useful when it is wished to use the IR32Y version for
controlling air dehumidifiers. The defrosting cycle then becomes the condensate discharge cycle, which
needs to be initiated at short intervals (minutes) and for very brief periods (seconds). Contact your Carel
agent for further information.
Default: dC=0, that is, the defrost interval dI is expressed in hours, and dP, the maximum duration of
defrosting, in minutes.
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
23
Cod. +030220151 - Rel. 2.1 - 04/09/98
A = parameters for the alarm control
ALARM PARAMETERSTypeMinMaxUnitDef
A0Alarm and fan differentialsC0.1+20°C/°F0.2
ALLow temp alarm (relative to set)F0+199°C/°F10
AHHigh temp alarm (relative to set)F0+199°C/°F10
AdTemperature alarm delayC0199min120
A4Multifunction input configuration IR32S, IRDRSE/S0, IR32Y,
IR32P, IR32C, IRDRC, IR32M
A5(should be kept at zero)C05-0
A6Duty setting in case of external alarm (0=OFF, 1=ON)C0100min0
A7External alarm delay (A4=2 multi-function input)C0199min0
Note: for the set times to become operative, the instrument must be switched off and on again.
A0: Alarm and fan differentials
This parameter represents the differential used for activating the high and low temperature alarms (AL and
AH - see the diagram below) and for the control of the fans (see F parameters). In the case of the alarms,
as can be seen from the diagram, the value A0 contributes to determining the points at which the
temperature alarms actually occur.
Default: 0.2 degrees. Available on IR32S, IRDRSE/S0 and IR32Y (alarm differential), and IR32P and IR32C,
IRDRC alarm and fan differential).
C05-0
3
AL: Minimum temperature alarm
This parameter allows the low temperature alarm to be selected. The value of AL does not indicate the
temperature at which the alarm will sound, but rather the maximum deviation from the setpoint (i.e. the
requested operating temperature) that is permitted. The low temperature alarm is given as follows:
Low temperature alarm = (setpoint) - (value of AL) - A0
Note that changing the setpoint automatically changes the temperature at which the low temperature alarm
will be given, while the maximum differential permitted (AL) remains as set. The low temperature alarm is
automatically re-instated. This means that if the temperature returns above the minimum value set, the
alarm signal is automatically cancelled. Finally, it should be remembered that the low temperature alarm is
also operative in the continuous cycle mode (see relevant section). if the temperature drops to the alarm
level, the continuous cycle is automatically de-activated, even if the period of time selected has not been
completed. De-activation does not disable the alarm signal.
Default: AL=10
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C, IRDRC. Parameter with access from remote control.
AH: High temperature alarm
It allows the high temperature alarm to be set. The value of AH does not indicate the temperature at which
the alarm is given, but rather the maximum deviation allowed from the setpoint (i.e. the requested
operating temperature). Therefore:
High temperature alarm = (setpoint) + (value of AH) + A0
Note that changing the setpoint automatically changes the high temperature alarm, while the the maximum
deviation permitted remains the same. The high temperature alarm is also automatically re-instated.
Default: AH=10.
Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC. Parameter with access from remote
control.
24
Cod. +030220151 - Rel. 2.1 - 04/09/98
Ad: Temperature alarm delay
This indicates how many minutes of delay are requested before a registered deviation is signalled. If during
the delay Ad the temperature returns to permitted limits, the alarm will not be signalled. If there is a further
alarm state, the delay will begin again at zero.
Setting a delay in signalling temperature alarms can help to avoid false alarms due to interference with the
sensor or situations lasting only a limited time, such as briefly opening the door of a store-room. Alarm
delays do not affect two particular functions: defrosting and continuous cycle. To delay any temperature
alarms after these functions, parameters d8 for defrosting and c6 for continuous cycle must be adjusted.
Remember that temperature alarms are not generated during defrosting and continuous cycle operation.
Default: Ad=120 (120 minutes' delay in signalling temperature alarms). The default for equipment with serial
numbers below 5000 is Ad=0. See note at end of manual. Available on IR32S, IRDRSE/S0, IR32Y, IR32P,
IR32C and IRDRC. Parameter with direct access from remote control.
A4: Configuration of Multi-function digital input
This defines the effect of MULTIFUNCTION digital input.
MULTIFUNCTION digital input can have varying significance, according to the values given to this
parameter and as a function of the type of control employed. The various functions are described below:
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
A4=0: INPUT NOT ACTIVE: MULTIFUNCTION digital input is not used. This is the value set in the factory
for all versions except model IR32M.
A4=1 IMMEDIATE EXTERNAL ALARM: it is possible to connect to the digital input an external alarm which
will request immediate intervention (for example a high pressure or compressor temperature alarm). In
particular the alarm is registered when the contact is opened (normal operation being in the closed state).
Activation of the alarm produces a display signal (see alarm A1), sound the buzzer if so designed and
initiates the following actions:
compressor:functions according to values under parameter A6 (blocking compressor by external
alarm);
fans:continue to work according to fan parameters (F). If the external alarm is registered during
defrosting or a continuous cycle, control exits from the procedures.
When the alarm ceases the equipment resumes operation as follows:
Defrost: the opportunity to defrost is reinstated. The next defrosting is effected after the interval dI
(interval between defrosting) that has been set;
Compressor:If the compressor is operating at the moment when the alarm ceases, it remains operating
and follows the minimum on-time that has been set (parameter c2). If the compressor is
off, it is kept off for a minimum equivalent to that set under parameter c3.
Important note: it should be remembered that to guarantee the safety of the unit in case of serious alarms it
is necessary always to fit the unit itself with all the electro-mechanical safety devices needed to ensure correct operation.
A4=2 Delayed external alarm
The significance, connection and mode of operation are similar to those already indicated for the parameter
A4=1. However, when A4=2 it is possible to delay the alarm signal for a period in minutes equivalent to
value chosen for A7 (see below). This arrangement is particularly useful for controlling the low pressure
alarm. In fact it often happens that on first starting up, the unit registers a low pressure alarm due to ambient
conditions rather than to any malfunctioning of the equipment. By setting a delay on the alarm, false alarms
are avoided. In fact, by calculating the delay appropriately, if the low pressure is due to environmental
factors (low temperature), the alarm will be automatically re-instated before the delay set has elapsed. After
the set delay period, effects on the compressor, fans, defrosting and continuous cycle are the same as when
A4=1.
If A4 is set to equal 3, the effect varies according to the model of equipment in use:
Version IR32M:
A4=3: SENSOR SELECTION
Allows the digital input to be used to display the temperature registered by sensor 1 or sensor 2. When the
contact is open the reading on P1 is displayed, when contact is closed, P2. Default: A4=3 digital input for
sensor selection.
25
Cod. +030220151 - Rel. 2.1 - 04/09/98
Version IR32S with H1=0 (thermostat function):
t
A4=3: DIRECT/REVERSE OPERATION
The digital input is used to choose the DIRECT function (for refrigeration) or the REVERSE function (for
heating - see also parameter r3). When the contact is open the equipment works in DIRECT mode, when the
contact is closed, in REVERSE. It is therefore possible to connect, for example, a switch which will
command, according to its position, heating or cooling.
If A4=3 the state of the digital input takes priority over parameter r3; that is, the value assigned to r3
becomes immaterial and only the state of (open or closed) of the digital input counts.
All other versions, including IR32S with H1=1:
A4=3: PREPARATION FOR DEFROSTING
It is possible to connect an external contact to the multi-function input to prepare for or to inhibit defrosting.
When the contact is open, defrosting is inhibited, and when closed, defrosting becomes possible. If the
contact is closed, but defrosting has not been requested by the controller, obviously defrosting will not occur.
If the contact is closed and defrosting is under way, any opening of the contact will cause defrosting to be
interrupted immediately, and the equipment will resume normal operation (without carrying out the dripping
or post-dripping phases). The "DEF" LED begins to flash, indicating that the request for defrosting remains
unsatisfied and will await the next consent signal (the closure of the contact).
This function is useful, for example, with refrigerated cabinets fitted with hot gas defrosting. With these
installations it is necessary to defrost an "island" at a time, so at anyone moment, some islands will be
empowered to defrost and others inhibited.
Another use for this function is to inhibit defrosting of those units exposed to the public during shopping
hours. A request for defrosting which arises when the contact is open will remain in waiting until the contact
is closed.
A4=4: INITIATION OF DEFROSTING BY EXTERNAL CONTACT
This function allows activation of defrosting by an external contact. This defrosting has priority over "internal"
defrosting ordered by parameter, or from the keypad. Where defrosting occurs through external contact all
the "d" parameters selected remain valid. In particular it can be useful to set dI=0 so as to permit only
manual or externally ordered defrosting, and excluding defrostings ordered by the internal clock.
This function is useful if is necessary to carry out a defrosting in real time. To do this it is sufficient to
connect a mechanical or electronic timer to the digital input. When the timer contact changes from open to
closed, a request for defrosting is passed. As described under parameter d5, it is possible to link more than
one unit to the same timer. By choosing the value of parameter d5 appropriately for each unit it is possible to
avoid simultaneous defrosting by more than unit.
timer
Explanation:
defrost
dP(1)unit 1
d5(2)
defrost
dP(2)unit 2
t = impulse from timer to initiate
defrosting; minimum duration must be
0.5 seconds;
dP(1) = maximum duration of
defrosting, unit 1;
d5(2) = external contact's defrost delay
for unit 2. This must be greater than
richiesta sbrinamento
defrost request
d5(3)
defrost
dP(3)
unit 3
dP(1) if two units are not to defrost at
the same time.
Similarly for d5(3) and dP(3).
26
Cod. +030220151 - Rel. 2.1 - 04/09/98
A4=5: DOOR SWITCH
By setting A4 = 5 it is possible to control the switch at the store-room door. When the switch is opened the
compressor is switched off. If the IR32C or IR32P versions with S90OEM4PWR are being used, the control
automatically also cuts off the evaporator fan (often positioned above the door), and, if the parameter H1=0
referring to the room light automatically goes on via output AUX. When the door is closed (and also the
Multifunction contact), the equipment resumes the previous operation, delaying any temperature alarm by a
number of hours equivalent to the value of d8. On re-starting the compressor however, any protective time
constraints selected will be respected (see c parameters). Note: even if the fan is controlled by the fan
controller (see category F), the fans will be shut down.
The table below summarises the functions served by the digital input according to the values assigned to A4
and to the equipment version being used.
Parameter valueFunctionMT (*)SX (**)YCP
0Input not active
1Immediate external alarm
Contact open = alarm active
closed = inactive
2External alarm with delay
Contact open = alarm active
closed = inactive
3Sensor selection
Contact open = first sensor
closed = second
Direct/Reverse
Contact open = direct
closed = reverse
Ready to defrost
Contact open = defrost
possible
closed = impossible
4Start of defrost
5Door switch
Contact open = door open
closed = door closed
Default values3000000
Note: (*) T refers to the IR32S version when used in thermostatic operation, i.e. with parameter H1=0.
(**) X refers to the IR32Y version with time defrost as well as temperature, i.e. with parameter H1=0.
•••••••
••••••
••••••
•
•
•••••
•••••
••
A5: This parameter is not controlled on the versions being considered and must be lept at 0.
Default: A5=0 Refers to models IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
A6: Cut-out of compressor by external alarm
The function of this parameter is similar to that of parameter c4 (duty setting). As well as acting on the
sensor alarm, it acts on the external alarm via the multi-function input (A4=1 or A4=2). When an external
alarm occurs (whether immediate or delayed), the compressor works for a period equivalent to the value
given to parameter A6 (in minutes), while remaining off for a fixed period of 15 minutes. When given two
particular values A6 serves the following functions: A6=0: the compressor always remains off; A6=100: the
compressor always remains on. The fans continue to be controlled by according to the selected parameters
(see category F). If the duty setting for the sensor alarm (parameter c4) is also active, controil uses
the value of c4.
Default: A6=0 (compressor cuts out if there is an external alarm). Available on IR32S, IRDRSE/S0, IR32Y,
IR32P, IR32C and IRDRC.
A7: Delay in registration of external alarm (multi-function input)
Sets the delay (in minutes) in registering the external alarm when A4=2.
Default: A7=0 Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.
27
Cod. +030220151 - Rel. 2.1 - 04/09/98
F = parameters for controlling evaporator fans
FAN PARAMETERSType MinMaxUnitDef
F0Fan control LED by fan controller (0=no, 1=yes)C01flag0
F1Fan cut-out temperature (relative to ambient temperature)F0+20°C/°F5
F2STOP fans when compressor idle (0=no, 1=yes)C01flag1
F3Stop fans during defrost (0=no, 1=yes)C01flag1
FdStop after drippingF015min1
Note: for the set times to become operative, the instrument must be switched off and on again.
F0: Fans controlled by fan controller
Fans can be put under the control of the fan controller, which manages them according to the temperature
registered by the defrost and control sensors. Alternatively, the fans can work constantly, with the possibility
of switching them off when the compressor is idle (see parameter F2), during defrosting (see parameter F3),
during a period of dripping (see parameter dd) and for a further period after dripping (see parameter F1).
Permitted values for this parameter are: F0=0 (=no). In this case fans are not controlled by the fan
controller, but by parameters F2, F3 and Fd. F0=1 (=yes). In this case the fans are managed by the fan
controller (see parameter F1). It should be remembered that if a dripping period has been provided for (dd
not=0), the fans will be cut out all the same. Default: F0=0 (not managed by fan controller). Available on IR32P,
IR32C and IRDRC.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
F1: Fan cut-out temperature (operative only when F0=1)
The controller activates the fans only when the temperature of the evaporator is far enough below the
ambient temperature. Parameter F1 sets the minimum difference which there must be between the ambient
and evaporator temperatures for the fans to be activated. Once switched off, the fans will start up again
when the difference between the two sensors is equal to F1+A0, where A0 is the fan controller differential.
(See diagram.)
Default: F1=5, i.e. the fans remain operative until the evaporator temperature is 5 degrees below the
ambient temperature. Available on IR32P, IR32C and IRDRC.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
F2: STOP fans when compressor idle (parameter operative only when F0=0).
It allows a choice to be made as to whether the fans should operate continuously (except F3, dd and Fd) or
only when the compressor is working. If F0=1 the fans are managed by the fan controller and therefore
working or idle according to the difference between evaporator and ambient temperatures, independently of
the state of the compressor.
F2=0 (=no): Fans operate even if compressor is idle.
F2=1 (=yes): Fans are idle when the compressor is not working.
Default: F2=1, fans are off when compressor is off.
Available on IR32P, IR32C and IRDRC.
28
Cod. +030220151 - Rel. 2.1 - 04/09/98
F3: Stop fans during defrosting (parameter operative only when F0=0)
Allows a choice to be made as to whether the fans should operate during defrosting. Inactive if the fans are
managed by the fan controller. F3=0 (no): fans working during defrosting; F3=1 (yes): fans do not work
during defrosting. Note that during dripping time, if provided for, fans are always off. Default: F3=1,
evaporator fans off during defrosting. Available on IR32P, IR32C and IRDRC.
Fd: Cut-out after dripping (operative under both F0=0 and F0=1)
After defrosting, the fans can be blocked for a further period, in minutes, defined by the value given to Fd.
This is useful for allowing the evaporator to return to temperature after defrosting, thus avoiding forcing
"warm" air into the interior of the refrigerator. Where the fan controller is in command, it is not necessary to
select a time for Fd, as the controller starts the fans when the evaporator is at the right temperature. If the
fan controller is
in command (i.e. F0=1), assigning any value other than zero to Fd causes the fans to remain off for a period
equivalent to the value of Fd, independently of the temperature of the evaporator. Default: Fd=1 minutes of
cut-out after dripping. Available on IR32P, IR32C and IRDRC. Parameter with direct access from remote control.
DIAGRAM OF THE EVAPORATOR FAN OPERATION
N.B. The broken lines of the diagram refer to the instruments with serial number greater than 100,000; see
the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000).
29
Cod. +030220151 - Rel. 2.1 - 04/09/98
H = other settings
OTHER SETTINGSTypeMinMaxUnitDef
H0Serial addressC015-0
H1Particular configurations: IR32S, IRDRSE/S0 and IR32Y
IR32C, IRDRC and IR32P
H2Possibility of changing parameter set from keypad (0=no, 1=yes)C01flag1
H3Remote commander readiness codeC0199-0
Note: for the set times to become operative, the instrument must be switched off and on again.
H0: Serial address
It allows equipment to be provided with an address to which it will respond when connected to a control or
remote assistance system. Also known as serial or network connection. Default: H0=0; Available on all
models.
H1: Special configurations
This parameter allows particular functions which vary with different models to be defined. These are:
IR32S, IRDRSE/S0: the IR32S can operate as a simple thermostat (H1=0 is set in the factory), or as a
thermostat and defrost controller for static units at normal temperature (defrosting by shut-down of
compressor, H1=1). If the second type of operation is required, it is necessary to change the unit's
configuration by setting H1=1. Default: H1=0, thermostatic operation.
IR32Y: the IR32Y is a thermostatic model with defrost control for static low temperature units. Defrosting can
be effected by time ("X" operation) or can be initiated on the evaporator reaching the requested temperature
("Y" operation). In this second case it is necessary to fit the equipment with a second sensor, known as the
"defrost sensor". By setting parameter H1, X or Y operation can be selected. With H1=0 (the value set in the
factory), the equipment operates in the X mode (defrost by elapsed time). To choose Y mode (defrost by temperature)
H1=1 must be set. Default: H1=0, mode X operation.
IR32P, IR32C and IRDRC: decides whether the fourth relay is used as an auxiliary output (for lighting, antimist fan or other on/off function) or as an alarm output.
C01flag0
1
In the first case (auxiliary output) it is possible to start and stop the item connected by pressing button. If
the relay is connected to the equipment's light it is possible to switch it on and off not only by pressing the
button, but also automatically when the door is opened or shut by connecting the door switch (see parameter
A4). In the second case the relay signals any alarm situations, allowing a siren or other remote alarm
indicator to be activated. The possibilities are: 0 = auxiliary output; 1 = alarm output. Default: H1=1, alarm
relay.
H2: Inhibit the Keypad and/or the Remote Control
Using H2 parameter is possible to prevent modification of the SET POINT and every parameters, when the
controller is exposed:
If the Keypad is inhibited it is no possible to modify SET POINT and the "F" parameters, but it is possible
to visualise their value. "C" Parameters, accessible by means of a password, can be modified also with the
procedure above described. With the remote control inhibited it is possible only to visualise the value of
parameters, but no change them.
Note: if H2 is setted to "2" or "3" by the remote control, it is immediately inhibited (pushing "MEMO" button is
not required). To enable again the remote control, set H2 to "0" or "1" using the keypad
H3: Remote programming enabling0 code
Parameter H3 allows an access code to the control. As already indicated, this makes use of the remote
control possible when there are several controls on the same panel without danger of interference. For more
detail, see the section on remote programming. Default: H3=00, parameters can be changed from the
keypad. Available on all models.
Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)
30
Cod. +030220151 - Rel. 2.1 - 04/09/98
NOTES FOR THE NEW RELEASE
The instruments of the Infrared series with the serial number greater than 100,000 offer new useful
functionalities (see the following description) and at the same time they maintain the compability with the
previous series, retaining all their parameters.
Memorization of the minimum and maximum temperature. For all the models
This instrument allows the registration of the minimum and maximum temperature read by the ambient
sensor during an interval which can reach up to 199 hours (more than 8 days). To activate this function, operate as
follows:
1.select the parameter 'r5'=1. This is a ‘Configuration’ parameter.
2.Visualize the parameter 'rt' (type F parameter). By pressing the button ‘SEL’, the instrument visualizes
how long (hours) the minimum and maximum temperature memorization has been active (if the
memorization has just been enabled, rt will be associated to the value '0'). If you want to restart the
memorization of the temperatures, press the ‘66’ button during the visualization of memorization hours.
The instrument will clear the memorization hours and will start with monitoring again.
3.To visualize the max. temperature detected by the sensor, refer to the value associated with rH.
4.To visualize the min temperature detected by the sensor, refer to the value associated with rL.
After a maximum interval of 199 hours, the rH and rL values are cleared and the memorization will start
again.
Description of the new parametersTypeMinMaxU.M.Def
r5Enabling min. and max. temperature monitoring (0=no, 1=yes)C01flag0
rtEffective interval of min and max. temperature monitoringF0199hoursrH Max. temperature monitored on the rt intervalF-50+90°C/°FrLMin temperature monitored on the rt intervalF-50+90°C/°F-
These functions are now available on the IR32M model which – in addition to the insertion of the Ad delay–
allows – on the version with the infrared receiver – the modification of the high and low temperature alarms
by IR remote controller.
Particularly, the management of the energization delay of the temperature alarms (Ad) has been improved
on all the models here enclosed. Notice that it is possible to reset a temperature alarm simply by pressing
the ‘66’ button for 5 seconds.
Warning: if the instrument is not connected to a UPS, a short power failure will clear the values rt, rL and rH.
When the voltage is supplied again, the controller will automatically start the monitoring again with rt =0.
Time defrosting. IR32Y, IR32C, IR32P and IRDRC models
The duration of the defrosting can be controlled by:
3 temperature according to the defrost sensor located on the evaporator. In any case the defrosting will be
deactivated after a max. security duration (selectable).The alarm Ed (defrost end for ‘max. security
duration’) can be disabled.
3 time, useful for special applications, like ‘water defrost method’.
If the Ed alarm has not been deactivated, in case of intervention it is possible to clear it by pressing the
button ‘6’ for 5 seconds at least. Notice that if you utilize the defrost by time, the second sensor can monitor
the air-off temperature. It is also possible to control the unit by a virtual sensor, that is proportional both to
the air-on and air off temperature. Important note: with the time defrosting, possible defaults of the second
sensor are non detected.
Description of the new parametersTypeMinMaxU.M.Def
r3Enabling Ed alarm (defrosting inhibited as the max. duration is
reached, dP parameter) 0=no, 1=yes.
d0Type of defrosting (0= resistance, 1= hot gas,
2= water or resistance by time, 3= hot gas by time)
dPMax. duration of the defrosting or effective duration if d0=2 or 3F1199min30
C01flag0
C03flag0
31
Cod. +030220151 - Rel. 2.1 - 04/09/98
Interval between 2 defrosting. For all the models except IR32M
The defrost duration does not affect the interval between two defrosts. In fact the defrost interval is
calculated starting from the beginning of the defrost cycle (so, not from the end of the cycle, as in the
previous series).
Curtain-switch control. For all the models excepted IR32M
The digital input of the instrument can be programmed to control the ‘curtain -switch’. When the curtain is
closed – and consequently the digital input connected to the ‘curtain -switch’ is closed – the control increases
automatically the set-point of a selectable value. If the auxiliary output (AUX) controls the unit light, the light
is automatically switched off when the curtain is closed and switched on when it is open.
Description of the new parametersTypeMinMaxU.M.Def
r4Automatic variation of the set-point during the night (or when
the Curtain-switch is closed, with A4 or A5=7)
A4Configuration of the digital input No 1C07-0
A5Configuration of the digital input No. 2 (only IRDR* models)C07-0
Management of the evaporator fans. IR32C, IR32P e IRDRC models
During the normal functioning, the controls of the Infrared series can control the evaporator fans as follows:
C0+20°C/°F3.0
3 continuously;
3 only when the compressor is active;
3 according to the temperature difference between the evaporator and the ambient temperature.
Now a new option is available: the evaporator fans can be driven also according to the absolute temperature
of the evaporator. The F3 parameter is now fully operative.
Description of the new parametersTypeMinMaxU.M.Def
F0Management of fans: 0 = fans always ON – specific phases
excluded (see F2, F3 and Fd parameters)
1= thermostatic fans on the basis of the difference between
ambient and evaporator temperature,
2= thermostatic fans according to the evaporator temperature
F1Starting temperature of the fans: if F0=1 the fans are ON if
evaporator temperature<(ambient temperature - F1 - A0); the fans
are OFF if evaporator temperature>ambient temperature - F1. if
F0=2, the fans are ON if evaporator temperature<(Setpoint + F1-
A0); the fans are OFF if evaporator temperature>(Setpoint + F1)
Management of the new algorithm ‘switch door’. For all the models excepted IR32M
When the door is open:
C02flag0
F0+20°C/°F5
3 the light is open (only IR32C and IRDRC models with an AUX output programmed to control the
management of light);
3 the compressor is OFF and the evaporator fans are OFF;
3 the measure displayed flashes;
3 the temperature alarms are disabled.
After a selectable time (d8) has elapsed, the controller returns to its normal functioning, and the temperature
alarms are activated. The new algorithm solves any problem due to a switch-door malfunctioning.
Description of the new parametersTypeMinMaxU.M.Def
normally closed, 2= alarm normally energized
d8If A4 or A5=5, max. stop time of the unit with door open.
Furthermore time to exclude the alarm after the defrost.
C01flag0
F015hours 1
32
Cod. +030220151 - Rel. 2.1 - 04/09/98
‘Smart’ remote On/Off. For all the models
The digital input can be programmed also as remote On/Off.
When the controller is OFF:
3 the temperature is displayed;
3 the compressor anti-cycling protection (min. time between 2 switch on) is active;
3 the AUX output remains operative;
3 the measure displayed is visualized alternatively with two horizontal lines.
N.O. and N.C. alarm relay. IR32C, IR32P and IRDRC models
The AUX output working in alarm in the IR32C and IRDRC models can operate both as Normally Open and
as Normally Closed. The functioning with the N.C. alarm relay ensures the maximum security because the
alarm is active also in case of power failure or disconnection of cables.
Description of the new parametersTypeMinMaxU.M.Def
H1Selection of relay 4 functioning: 0=auxiliary output,
1=alarm N.C., 2= alarm N.O.
Functioning up to - 50°C (for all the models) and sensor calibration (IR32Y, IR32C, IR32P and IRDRC).
The instrument can work up to -50°C. Therefore it can be used to control the temperature reducer.
The calibration is operative in the ambient temperature sensor only, that is on the displayed value.
Programmable digital inputs: list of the options
C02flag0
Value
A4 / A5
0not active input
1immediate external alarmContact open=alarm active
2external alarm with delayContact open=alarm active. Delay: see parameter A7
3enabling of defrostContact open =defrost not enabled
4start of defrostDefrost is activated when the contact closes. It can be used for
5door switchContact open=door open. When the door is open the
6remote On/OffContact close=ON. (On the IRDR models, if A4 =6 and A5=6
MeaningFunctioning
real time defrosting. You only need to connect to the digital
input a real clock with power back-up, select A4=4 (if the
chosen input is Id1) or A5=4 (if the chosen input is Id2, only for
the IRDR model). To exclude cyclic defrost automatically
activated by the control, set dI=0.
compressor and the fan are turned off. If H1=0 (models IR32C,
IR32P and IRDRC only) Aux output is activated to switch on
the lights. If the door stays open for a time longer than d8, the
display will begin to flash and the controller will restart the
normal functioning (compressor and fan ON, in case of need).
the control is ON with both the contacts OFF).
7curtain switchContact closed= curtain down. If the input is selected as
curtain switch, when the contact closes the control modifies
the set point adding the value of the parameter r4. With r4=3.0
(pre-programmed value), the set is increased of 3 degrees
compared to the value used with open curtain. If the auxiliary
output is used for the light management (only for IR32C,
IR32P and IRDRC models) the curtain lowering automatically
switches off the light while the curtain raising switches it on.
33
Cod. +030220151 - Rel. 2.1 - 04/09/98
WIRING DIAGRAMS
Wiring diagram for multiple units:
MAIN
TRF
TRF
TRF
INS
TRF
INS
TRF
4
5
4
5
4
5
4
5
SER
MAIN = mains power supply
TRF = transformer
INS TRF = insulating transformer
=earth
SER = multiple connection to the control system.
IR32
IR32
IR32
IR32
IR32 panel mounting connections:
34
Cod. +030220151 - Rel. 2.1 - 04/09/98
35
Cod. +030220151 - Rel. 2.1 - 04/09/98
36
Cod. +030220151 - Rel. 2.1 - 04/09/98
37
Cod. +030220151 - Rel. 2.1 - 04/09/98
OPERATING STATES OF THE EQUIPMENT
As indicated above, the display LEDs can be in three states:
•off, when the function indicated or the actuator is not operative;
•on, when the function indicated or the actuator is operative;
•flashing, when the function is held up by an alarm situation, by a delay, or by a particular state of the
Multifunction input.
There are however various particular operating states not directly indicated by the displays. This can lead to
erroneous interpretation of the equipment's operating state. For convenience, the state of the display in such
situations is given below:
"PARTICULAR" STATECOMP LEDFAN LEDDEF LEDC.CYCLE LED
è signifies that the LED may be on, off or flashing as a function of other parameters and ambient factors
(temperature, operating set, differential etc.). General remarks made earlier on the state of LEDs should
be borne in mind.
SEQUENCE OF MAIN PHASES
For easy reference we give below a diagram showing the sequence of all the possible phases in the process
of defrosting. It should be remembered that some phases (e.g. dripping or post-dripping) can be activated or
inhibited by an appropriate choice of parameters. The type of activators being controlled and the type of
control depend on the type and configuration of equipment selected.
PHASEnormal
operation
Models
applicable
Actionunit's
(*) The thermometer version IR32M is obviously excepted.
all (*)IR32S, IRDRSE/S0
when H1=1, all others
evaporator defrosted
temperature
controlled
as chosen
The sequence progresses from left to right.
defrostdrippingpost drippingresumption of
normal
IR32S, IRDRSE/S0
when H1=1,all others
compressor and
evaporator fans
(latter on IR32C,
IRDRC and IR32P
only) are shutdown
in order to help
drainage of water
after defrosting.
IR32C, IRDRC
and IR32P
fans are shut off
to allow the
evaporator
again operating
temperature
all (*)
control of
temperature
resumed
38
Cod. +030220151 - Rel. 2.1 - 04/09/98
ALARMS AND TROUBLESHOOTING
Defective or incorrect operation
Equipment in the Infrared range are able to signal most incorrect operation automatically. When any
malfunction occurs the microprocessor initiates the following actions:
•the malfunction is signalled on the display with an appropriate alarm signal. More specifically, the
display shows alternatively the alarm code and the temperature read by the sensor. If more than one alarm
occurs at the same time, they are signalled successively.
•For some alarms an internal buzzer, if fitted, gives an audible warning.
•For these alarms, the AUX relay, where fitted and if configured as an alarm output, will operate.
By pressing the button the buzzer will stop and the relay disconnect, while the alarm code will
disappear only when the cause has been eliminated. The alarm codes are listed in the table below:
Edinactivedefrost end by time-outIR32Y, IR32C, iRDRC, IR32P
dFinactivedefrost in progressALL
CAUSEMODELS APPLICABLE
Description of the main alarm signals
FLASHING LED
Initiation of the relative function is delayed for a period while awaiting an external consent or while held up
by another process still in progress. For example, if a defrost is requested during continuous cycle operation,
the defrost will be held up until the continuous cycle is complete, and the appropriate LED (Def) will flash.
E0 FLASHING: control sensor error
•sensor not working because the signal has been interrupted or there is a short-circuit
•sensor not compatible with the equipment
•parameter /0 does not correspond to unit's hardware set-up.
E1 FLASHING: evaporator sensor error
•Sensor not working because the signal interrupted or there is a short circuit
•sensor not compatible with the equipment
•parameter /0 does not correspond to unit's hardware set-up.
AI FLASHING: immediate Multi-function digital input
•check Multi-function input and parameter A4.
Ad FLASHING: delayed Multi-function digital input
•Check Multi-function input and parameters A4 and A7.
LO FLASHING: low temperature alarm.
The sensor has registered a temperature further below the set value than the value given to parameter AL.
•Check parameters AL, Ad and A0.
The alarm will cease as soon as the temperature returns within the limits selected (see parameter AL).
39
Cod. +030220151 - Rel. 2.1 - 04/09/98
HI FLASHING: high temperature alarm.
The sensor has registered a temperature further above the set value than the value given to parameter AH.
•Check parameters AH, Ad and A0.
The alarm will cease as soon as the temperature returns within the limits selected (see parameter AH).
EA, EB, EE DISPLAYED DURING OPERATION OR SWITCHING-ON
Data acquisition error. See the section "Reset procedure".
Ed FLASHING:
the last defrost has stopped due to expiry of the maximum time rather than because the end of defrost set
has been reached.
•Check parameters dt, dP and d4.
•Check effectiveness of the defrost.
If the next defrost ends on temperature the signal will disappear automatically.
dF FLASHING; defrosting in progress.
•This is not an alarm signal but an indication that that the equipment is carrying out a defrost. Appears
only if parameter d6=0.
Note: The following pages list some other incorrect operating situations, model by model. The most likely
causes and corrective action are indicated. The CAREL organisation remains at your service with
suggestions and information.
What to do if the remote commander does not work:
•see that there are batteries and that they are correctly inserted;
•see that the batteries are not discharged;
•see that the equipment is designed for remote control (the last letter but one of the code must be R);
•see that there are no obstacles between the remote control and the controller;
•see that the transmitter on the remote control and the infra-red receptor on the control are not dirty;
•see that the distance between the remote commander and the control is not more than 3 metres.
If you can enter the parameters without the possibility to modify their value, check that the protection
procedure is not active (see the description of the H2 parameter).
40
Cod. +030220151 - Rel. 2.1 - 04/09/98
What to do if the IR32S, IRDRSE/S0 fails to work
PROBLEMS CAUSECHECK
compressor will not start :
•power on
•compressor LED off
if H1=0
wrong mode: heating instead of
cooling or vice versa
parameter r3
if A4=3, check state of digital input
compressor will not start :
•power on
•compressor LED flashing
temperature is outside set limits but
no alarm signalled and buzzer, if
fitted, does not sound
AL or Ad alarm signalled (Multifunction input) without in fact being
active
alarm connected to Multi-function
input does not operate
defrost not activated :
•power on
•defrost LED off
manual defrost not activated and
defrost LED flashing
high temperature alarm given after
defrosting
compressor delay operatingparameter c0, c1 and c2
alarm delay operatingcheck Ad
Multi-function input generates
alarm as power goes on
alarm delay operating or
programming error
if H1=1
•defrost cycle too short (dp)
•interval between defrosting
dl=0: in this case defrost will
not be activated
compressor protection delays
operating
alarm delay after defrost too short
or alarm threshold too low
check connection of input and
whether it is off in normal operation
see whether A4=1 or A4=2;
if A4=1 check state of digital input;
if A4=2 check A7
parameter dP and dl
parameter d9 (select d9=1, see
instructions)
parameters d8 and AH
when H1=1, display override
remains even after defrost
after changing a value, or
programming continues to work with
old values
cycle continuos is not actived
With the factory settings it can happen that within the 120 minutes delay set (Ad) the unit fails to
reach the range of +/- 10 degrees (AL and AH) around the set-point selected for the temperature
alarm. If this occurs we suggest to increase the delay by changing parameter Ad.
ambient temperature has not yet
reached value set, or time d8 has
not yet elapsed
unit has not yet updated of re-start
unit, parameters has not been
satisfactorily completed, pressing
it is necessary to press before
.
wait or reduce d8
switch off and parameter, control or
programme again correctly
see note on page 8
What to do if the IR32Y fails to work
41
Cod. +030220151 - Rel. 2.1 - 04/09/98
PROBLEMS CAUSECHECK
compressor will not start :
•power on
•compressor LED flashing
•compressor delay in operation if
A4=3
•post-defrost dripping in progress
parameters c0, c1, c2 and dd
temperature is outside set limits but
no alarm signalled and buzzer, if
fitted, does not sound
AL or Ad alarm signalled (Multifunction input) without in fact being
active
alarm connected to Multi-function
input does not operate
defrost not activated :
•power on
•defrost LED off
defrost not activated:
•power on
•defrost LED flashing
manual defrost not activated and
defrost LED flashing
high temperature alarm given after
defrosting
alarm delay operatingcheck Ad
Multi-function input generates alarm
as power goes on
alarm delay operating or parameter
programming error
check connection of input and
whether it is off in normal operation
see whether A4=1 or A4=2;
if A4=1 check state of digital input;
if a4=2 check A7
if H1=0
parameter dp and dl
•defrost cycle too short (dp)
•interval between defrosting dl=0:
in this case defrost will not be
activated
if H1=1 end defrost temperature is
parameter dt and d/ defrost sensor
too low. Suggest checking defrost
sensor and temperature reading on
evaporator (parameter d/)
compressor protection delays
operating
alarm delay after defrost too short or
parameter d9
(select d9=1, see instructions)
parameters d8 and AH
alarm threshold too low
display override remains even after
defrost
ambient temperature has not yet
reached value set, or time d8 has not
wait or reduce d8
yet elapsed
after changing a value, or
programming continues to work with
unit has not yet updated of re-start
unit, parameters has not been
switch off and parameter, control or
programme again correctly
old values
satisfactorily completed, pressing
cycle continuos is not actived
see note on page 8
it is necessary to press before
.
With the factory settings it can happen that within the 120 minutes delay set (Ad) the unit fails to
reach the range of +/- 10 degrees (AL and AH) around the set-point selected for the temperature
alarm. If this occurs we suggest to increase the delay, by changing parameter Ad.
42
Cod. +030220151 - Rel. 2.1 - 04/09/98
What to do if the IR32P or IR32C, IRDRC fails to work
PROBLEMS CAUSECHECK
compressor will not start :
•power on
•compressor LED flashing
temperature is outside set limits but no
alarm signalled and buzzer, if fitted,
does not sound
AL or Ad alarm signalled (Multi-function
input) without in fact being active
alarm connected to Multi-function input
does not operate
defrost not activated:
•power on
•defrost LED flashing
manual defrost not activated and
defrost LED flashing
high temperature alarm given after
defrosting
after changing a value, or programming
continues to work with old values
•compressor delay in operating
•post-defrost dripping in
progress
alarm delay operatingcheck Ad
Multi-function input generates
alarm as power goes on
alarm delay operating or parameter
programming error
end defrost temperature too low.
Suggest checking defrost sensor
and temperature reading on
evaporator (parameter /d)
compressor protection delays
operating
alarm delay after defrost too short
or alarm threshold too low
unit has not yet updated of re-start
unit, parameters has not been
satisfactorily completed, pressing
parameters c0, c1, c2 and dd
check connection of input and
whether it is off in normal
operation
see whether A4=1 or A4=2;
if A4=1 check state of digital input;
if A4=2 check A7
parameter dt and d/ defrost sensor
parameter d9
(select d9=1, see instructions)
parameters d8 and AH
switch off and parameter, control
or programme again correctly
display override remains even after
defrost
•fans do not start
•fan power on
•compressor LED flashing
•fan LED flashing
cycle continuos is not actived
With the factory settings it can happen that within the 120 minutes delay set (Ad) the unit fails to
reach the range of ±10 degrees (AL and AH) around the set-point selected for the temperature alarm.
If this occurs we suggest to increase the delay by changing parameter Ad.
ambient temperature has not yet
reached value set, or time d8 has
not yet elapsed
•compressor and fan delay
selected
•if F0=1 (fans under fan
controller)
•evaporator is warm:
temperature can be read by
selecting parameter /d
•dripping is in progress
•delta (F1) selected is too high
•a post dripping delay is
operating
•if F0=0
•F2=1 and compressor off
•dripping is in progress
•closing down after dripping
it is necessary to press button
before "aux" Button.
wait or reduce d8
check c0
parameters F0, F1, FD, dd and d/
parameters F0, F2, dd and Fd
see note on page 8
43
Cod. +030220151 - Rel. 2.1 - 04/09/98
TECHNICAL CHARACTERISTICS
ModelsIR32MIR32SIRDRS0IRDRSEIR32YIR32PIR32CIRDRC
Power supply:
Wide range: 12-24Vac/dc, ±10%, 50/60Hz
Universal: 24-240Vac/dc, ±10%, 50/60Hz
24 Vac e 220 Vac on power board
Consumption
Accuracy:
NTC Carel
PTC
Type of sensor used for control:
NTC Carel (10 KΩ a 25°C): standard ON
PTC 985 Ohms a 25 º C, upon request:
Type of sensor used for defrosting:
NTC Carel (10 KΩ a 25°C), standard ON:
PTC 985 Ohms a 25 ºC, upon request:
•
2VA2VA3VA3VA2VA2VA/3VA3VA3VA
±1°C
±3°C±3°C±3°C±3°C±3°C
•
•
12-24 Vac/dc
110-240 Vac/dc
(mod. IR32S*H)
•
•
•
230
•••
•
••
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Range of operation: -40÷90°C (-40÷130 °C with PTC)
Operating conditions: 0÷60°C, with relative humidity less than 80%rH
Storage conditions: -25÷70°C, with relative humidity less than 80%rH
(*) 0/50°C, <80rH%, for IR32S with universal power supply
User interface
LED display with 2 and a half digits
Signal buzzer optional ON
Compressor ON indicator
Defrost ON indicator
Fan ON indicator
Continuous cycle ON indicator
Particular functions
Duty setting
Continuous cycle
Multi-function input
Multi-function output (IR32P only with S90OEM4PWR)
Serial connection
Keypad protection
Virtual sensor
Decimal point
Test in circuit
Watch dog
Immunity from interference according to standards
•••••
•••••
••••••••
IEC 801-2 and 801-4 level 4
GENERAL SPECIFICATIONS (for all models)
ConnectionScrew terminals for cables with min. 0.5mm2 - max. 1,5mm2 cross-section
Classification according to protection against shockClass I
Number of automatic cycles for each automatic action (e.g.: relay)100.000
Ageing period (operating hours)60.000
Type of action-disconnection1C
PTI of materials used for insulation250 V
Period of electric stress across insulating partsLong
Environmental pollutionNormal
Heat and fire resistance categoryD
Category (surge immunity)1
Software class and structureClass A (EN60730-1)
Time constant35 s in forced air
Disposal of the productavoid disposing the device in domestic rubbish. To dispose the device refer to the
environmental protection laws in force in your Country
Electrical characteristics of relays fitted in all models except the
Electrical characteristics of the compressor relay fitted on board S90RDPW200
compressor relay on board S90RDPW200
Maximum peak current: 10AMaximum peak current: 70A
Maximum operating current: 8AMaximum operating current: 20A
Maximum operating power: 2000VAMaximum operating power: 5000VA
Maximum operating resistance load at 220Vac: 1760WMaximum operating resistance load at 220Vac: 4400W
Maximum inductance load 300 W at 220Vac (cos.psi=0.7)
Maximum inductance load 1800 W at 220Vac (cos.ϕ=0.7)
Maximum operating tension: 250VacMaximum operating tension: 250Vac
CONTROL PARAMETERSTypeMinMaxUnitDefNew
rdControl differentialF0.119.9°C/°F2
r1Minimum set allowedC-40r2°C/°F-40
r2Maximum set allowedCr1199°C/°F90
r3Direct / Reverse operation (Direct r3=0, Reverse r3=1)C01flag0
COMPRESSOR PARAMETERSTypeMinMaxUnitDefNew
c0Compressor start-up delay after unit start-upC015min0
c1Minimum interval between two compressor start-upC015min0
c2Minimum compressor off-timeC015min0
c3Minimum compressor on-timeC015min0
c4Duty setting (compressor safety, 0=OFF,100=ON)C0100min0
ccDuration of continuos cycleC015hrs4
c6Alarm cut-out after continuos cycleC015hrs2
DEFROST PARAMETERSTypeMinMaxUnitDefNew
d0Type of defrost (0=resistance, 1= hot gas)C01flag0
dIInterval between defrostF0199hrs8
dtEnd defrost temperature setF-40199°C/°F4
dPMaximum duration of defrostF1199min30
d4Defrost on unit start-up (0=no, 1=yes)C01flag0
d5Defrost delay after unit start-up or multi-function inputC0199min0
d6Display override during defrost (0=no, 1=yes)C01flag1
ddDripping timeF015min2
d8Duration of alarm cut-out after defrost and/or opening doorF015hrs1
d9Defrost has priority over compressor protection (0=no, 1=yes)C01flag0
A0Alarm and fan differentialC0.1+20°C/°F0.2
ALLow temperature alarm (deviation from set point)F0199°C/°F10
AHHigh temperature alarm (deviation from set point)F0199°C/°F10
AdTemperature alarm delayC0199min120
A4Multi-function input configuration IR32S, Y and C, IR32MC05-0
A5Multi-function input configuration: IRDRS, SE, IRDRC
C05-0
For Rail Din mounting: must be kept 0
A6Duty setting for external alarm(0=OFF, 100=ON)C0100min0
A7External alarm delay (A4=2, Multi-function input)C0199min0
FAN PARAMETERSTypeMinMaxUnitDefNew
F0Fans under fan regulator (0=no, 1=yes)C01flag0
F1Fan shut-off temperature (relative to ambient)F0+20°C/°F5
F2Stop fans when compressor off (0=no, 1=yes)C01flag1
F3Stop fans during defrost (0=no, 1=yes)C01flag1
FdEnd post-drippingF015min3
OTHER SETTINGTypeMinMaxUnitDefNew
H0Address within networkC015-0
H1Type configuration: IR32S and IR32Y
IR32C and IR32P
C01flag0
1
H2Changing sets by keypad (0=no, 1=yes)C01flag1
H3Code to permit remote programmingC0199-00
47
Cod. +030220151 - Rel. 2.1 - 04/09/98
TEMPERATURE/RESISTANCE RATIOS FOR NTC
THERMISTORS
As indicated in the description of parameter /0, temperature sensors using the NTC thermistors normally
fitted in Infrared control systems change an electrical parameter, i.e. their resistance, as the temperature
varies. Below are listed the resistance values corresponding to the various temperatures. In the case of any
malfunction or any inaccurate control, users are advised to check the operation of the sensors in the
following manner:
•with a standard thermometer determine the temperature sensed by the sensor
•with an ohmmeter measure the resistance at the head of the sensor and compare it with the values in
the table.
In view of the variation shown by thermistors, three resistance values are given in the table for each
temperature.:
•Rstd = the typical resistance value at the temperature indicated;
•Rmin is the minimum value;
•Rmax is the maximum value.
For the sake of simplicity, the values relative to only a limited number of temperatures are given.
Intermediate values can be adequately determined by interpolation.
Temperature/Resistance ratios for the Carel NTC temperature sensor
TemperatureRminRstdRmax
-40 ºC
-30 ºC
-20 ºC
-10 ºC
0 ºC
10 ºC
20ºC
30 ºC
40 ºC
50 ºC
60 ºC
70 ºC
80 ºC
90 ºC
181.10 kΩ188.40 kΩ195.90 kΩ
107.50 kΩ111.30 kΩ115.10 kΩ
65.80 kΩ67.74 kΩ69.74 kΩ
41.43 kΩ42.25 kΩ43.50 kΩ
26.74 kΩ27.28 kΩ27.83 kΩ
17.67 kΩ17.95 kΩ18.24 kΩ
11.95 kΩ12.09 kΩ12.23 kΩ
8.21 kΩ8.31 kΩ8.41 kΩ
5.73 kΩ5.82 kΩ5.92 kΩ
4.08 kΩ4.16 kΩ4.24 kΩ
2.95 kΩ3.02 kΩ3.09 kΩ
2.17 kΩ2.22 kΩ2.28 kΩ
1.62 kΩ1.66 kΩ1.71 kΩ
1.22 kΩ1.26 kΩ1.30 kΩ
48
Cod. +030220151 - Rel. 2.1 - 04/09/98
NOTES FOR CONTROLS WITH SERIAL NUMBERS BELOW 5,000
If the unit has a serial number lower than 5000 (see serial number on the label placed on the back of the
unit), the factory settings of two parameters will differ from other units:
ALARM PARAMETERSTypeMinMaxUnit Def
AdTemperature alarm delayC0199mino
DEFROST PARAMETERSTypeMinMaxUnit Def
AdDefrost has priority over compressor protection (0=no, 1=yes)C01Flag1
In addition, whenever type C parameters are accessed (via the keypad or via remote commander), the unit
displays the parameter /0.
As indicated in the description of the sensor parameters, this parameter can only be modified in exceptional
situations.
Finally, these units have a different reset procedure from that described previously. This is as follows:
Reset procedure for units with serial number below 5000.
In very exceptional operating situations (strong interference impulses of electromagnetic origin), the unit may
reveal errors in its internal memorisation of data. These errors can affect the correct operation of the unit. If
the microprocessor identifies an error in data memorisation, the display will show one of the following:
EE, EB or EE.
To re-start correct operation a particular RESET procedure must be carried out:
•switch off power supply to the unit;
•while pressing the , switch on the unit (Note: RESET procedure returns all parameters to their
default state. Thus any changes made to the working parameters will be lost. In particular, if using a unit
designed for PTC sensor, it is necessary to reprogram the correct value for parameter /0, i.e. /0=1).
•the display will read_C_;
•after a few seconds the unit will begin normal operation.
If the error indicator EE should persist, press the def button to remove the indication. If the error EE persists
further, it will be necessary to replace the unit. If the indication disappears it is possible to continue using the
unit. However, it is wise to have the control checked as soon as possible, since its original accuracy may not
be maintained.
49
Cod. +030220151 - Rel. 2.1 - 04/09/98
IR32
IR32 DIMENSIONS
A7575
B3333
C6472
D6464
IRDR and S90RDPW2
IR32M, IR32S,
IR32P
IR32Y
IR32C
S90OEM4PWR
50
Cod. +030220151 - Rel. 2.1 - 04/09/98
CODE NUMBERS FOR ORDERING CONTROLS AND
ACCESSORIES
NTC Sensors
DescriptionOperating rangeIndex of protectionCode
NTC, bulb 6x15mm-50÷50°CIP67NTC0**HP00
NTC, bulb 6x40mm-50÷100°CIP67NTC0**W*00
NTC for insertion-50÷110°CIP67NTCINF0600
NTC for wall mounting-10÷70°CIP30ASWT011000
NTC for duct mounting-10÷70°CIP55 (*)ASDT011000
NTC for wall mounting
(temperature + humidity)
NTC for duct mounting
(temperature + humidity)
(*) the index of protection above mentioned refers to the case: IP40 refers to the sensor.
IR32P: 2½digits, for remote control (¹)IR32P0LBR0
(¹) IR32P: must be used with S90RDPW200 (24-240 supply voltage, 3 relays, 4 Din modules casing) or
S90OEM4PWR (24-240 supply voltage, 4 relays, PC board) connected by S90CONN000/1/2.
Options
Alarm buzzerIR32***B**
IR receiverIR32***B**
IR32 serial output boardIR32SER000
51
Cod. +030220151 - Rel. 2.1 - 04/09/98
DIN RAIL MOUNTING THERMOSTATS
Din Rail mounting thermostats with defrost timer
IRDRSE: 2½digits, 230Vac,no buzzer, no option for serial interface, 2 digital
inputs, for remote control
IRDRS0: 2½digits, 24-240Vac, buzzer, optional serial interface, 2 digital inputs,
for remote control
Din Rail mounting thermostats and defrost controls for ventilated unit at low temperature
IRDRC0: 2½digits, 12-24Vac/dc, buzzer, optional serial interface, 2 digital inputs,
4 relay outputs, for remote control
Options
Serial output board for IR Din-Rail and IR96IRDRSER000
Remote Control
Italian versionIRTRRI0000
English versionIRTRRE0000
French versionIRTRRF0000
Spanish versionIRTRRS0000
German versionIRTRRG0000
IRDRSE0000
IRDRS00000
IRDRC00000
Transformers
TRA 12 UNI: 3 VA, 110/12 Vac,TRA12UNI11
TRA 12 UNI: 3 VA, 230/12 Vac,TRA12UNI00
TRA 12 UNI: 3 VA, 240/12 Vac,TRA12VDE00
TRA 24 UNI: 3 VA, 230/24 Vac,TRA2400001
TRA DIN: 4 VA, 230/24 VacTRADR4W024
Network components
T-device connectionTCONN60000
52
Cod. +030220151 - Rel. 2.1 - 04/09/98
IR96: MICROPROCESSOR-BASED FREEZER CONTROLLER FOR MEDIUM
OR LOW TEMPERATURE RANGE FORCED AIR UNITS
Ir96 is a microprocessor based controller designed for the management of freezer with gravity or forced-air
evaporators. It has 5 relay outputs available to control all the main actuators: compressor (directly up to 1Hp
single-phase), evaporator fans and defrosting. The fourth relay allows remote signalling of any
malfunctioning (high temperature, faulty sensors,...). The fifth relay can be used to control the unit lights or
other auxiliary functions (for example de-misting fans). Two programmable digital inputs allow innovative
performances: automatic alarm management, real time defrosting, management of lights subjected to the
door switch.
IR96 can be supplied directly with 230 Vac (±15%), since it is equipped with an internal transformer (it is
necessary to protect the instrument with a 1 A protection fuse). Ir96 set-point is selectable from -50 to +90 ºC
and temperature can be displayed with a resolution of a tenth of degree from -19.9 to +19.9. It comes
complete with an alarm buzzer and an infrared receiver for remote control programming. It is moreover prearranged for serial card installation which allows to connect the instrument to supervisory and
telemaintenance systems.
Ir96 is an evolution of Infrared Series for commercial refrigeration. Its software has been up-dated
considering all the suggestions of our customers. Following we will see in detail the new functions.
NEW FUNCTIONS
Min-Max temperature data logging
Ir96 allows to record the minimum and the Maximum temperature values read by the ambient sensor during
an interval which can reach up to 199 hours (more than 8 days).
In any moment it is possible to restart the logging period by pushing a button.
Refer to parameters rt, rH, rL next pages.
Defrost duration also ‘by time’
The defrost duration can be controlled:
• by temperature, according to the defrost sensor, with a Maximum safety duration. In this case the Ed
alarm (defrost end by time) can be disabled.
• only by time. This is useful on special applications like ‘water defrost method’.
Using the defrost by time, the 2nd sensor can monitor the ‘air-off’ temperature.
It is moreover possible to drive the unit according to a virtual sensor, proportional to both the ‘air-on’ and
the ‘air-off’ temperature.
Refer to parameters d0, dP next pages.
Interval between defrosts
On Ir96 the interval between defrosts is constant.
It is calculated starting from the beginning of the defrost cycle.
In this way the defrost duration does not affect the interval between two defrosts.
Refer to parameters dI next pages.
Curtain-switch control
The digital input on Ir96 can be programmed to control the curtain switch.
When the curtain is closed the control automatically increases the set-point of a selectable value.
The light is automatically switched off when the curtain is closed and switched on when it is open.
Refer to parameters A4, A5, r4 next pages.
Evaporator fan management
On normal functioning, the controls of Infrared series can energize the evaporator fan:
• continuously
• only when the compressor is energized
• according to the temperature difference between evaporator and room temperature
Furthermore a special management is possible during defrost and dripping time.
Now on Ir96 a new option is available:
• the evaporator fan can be driven also according to the absolute temperature of the evaporator.
Refer to parameters F0, F1 next pages.
53
Cod. +030220151 - Rel. 2.1 - 04/09/98
New algo for door-switch management
When the door is open
• the light switches ON
• the compressor & the evaporator fan switch OFF
• the temperature alarms are disabled
After a selectable time has elapsed, the control returns to its normal functioning.
The new algo overrides any problems due to a switch- door malfunctioning.
Refer to parameters A4, A5, H1, d8 next pages.
‘Smart’ On/Off button
When the control is OFF
• the temperature is displayed
• the compressor anti-cycling protection is active
• the light-button remains operative
Furthermore
• the ON/OFF state is memorized on EEPROM. In case of power failure the control returns to the previous
state.
• the digital input can be programmed as remote ON/OFF. In this case the ON/OFF button on the front
panel is disabled.
Refer to parameters A4, A5, c2 next pages.
N.O and N.C. alarm relay
On Ir96 the alarm relay can work either with Normally Open or Normally Closed contact.
The latter assures the maximum safety because the alarm is active also in case of power failure or wires
disconnection.
Refer to the parameters H1.
IR96 new functions: -50°C and new algo for calibration
Ir96 can work up to -50°C. In this way it can be used as ‘quick chill’ control.
On Ir96 the calibration is operative only on ambient temperature sensor, that is on the displayed value.
Refer to the parameters r1,r2
Programmable digital inputs: summary of the options
• real time defrost
• immediate input alarm
• delayed input alarm
• door switch control
• curtain switch control
• remote ON/OFF
54
Cod. +030220151 - Rel. 2.1 - 04/09/98
TECHNICAL FEATURES
Set-point:-50T90 (-50/+90°C; -58/+194°F)
Power supply230 ±15%
Consumption4 VA
Precision
Caseplastic,
Installationincorporated
Working temperature0÷50°C; 32÷122°F
Storage conditions-10/+70°C; 14/158 °F
Connectionsdigital inputs and sensor on plug-in connectors, outputs on faston
Display2 and a half digits
Signalling:
luminous
acoustic
Inputsrefrigerating room sensor, defrosting sensor, multi-function inputs
Type of sensor:
Relay outputs (all)Disconnection of type 1B according to ECC EN 60730-1
NTC CAREL 10KΩ a 25ºC (for codes see Carel price-list)
Important warning: the cables to be connected to the controller contacts should resist to the maximum
operating temperature which is determined by considering the expected maximum ambient temperature +
the controller overheating equal to 20°C. Moreover, it is necessary to protect the controller with a 1A,
250Vprotection fuse should be placed.
CONNECTIONS
230 V~
AMB. DEF
cc
ir96
Dig.In1 Dig.In2
Caution: with respect to safety rules follow the
below quoted instructions carefully:
7 85 63 4
• The cables to be connected to the controller
contacts should resist the maximum operating
temperature which is determined by considering
c
the maximum ambient temperature expected +
the controller auto-heating equal to 20 °C.
• Moreover, it is necessary to protect the
controller with a 1A, 250V fuse.
1 2
POWER
SERIAL LINK
c
c
9 1013 1411 1219 2017 1815 16
Power Supply
Power Supply
• Connect the terminals 12, 15 and 17 to the
same electric potential, as shown in the picture
55
Cod. +030220151 - Rel. 2.1 - 04/09/98
IR96: BUTTONS FUNCTIONING
LIGHTS BUTTON:
•activates/deactivates the unit lights (or any other aux. output connected to the 4th relay)
•increases the value of data on display during selection of set-point and parameters
MANUAL DEFROST BUTTON:
•decreases the value of data on display during selection of set-point and parameters
•if pressed during an alarm signalling, it resets the relay, silences the buzzer and deletes
the alarm code on display even if the cause of the alarm remains.
if pressed for more than 5 seconds:
•forces a manual defrosting cycle
SET BUTTON:
•selects the set-point (see section “set-point”)
•displays the value of the selected parameter (see section “parameters modification”)
if pressed for more than 5 seconds together with the PRG button:
•allows access to the configuration menu (see section “parameters second level”)
PRG BUTTON:
•silences the buzzer, while the alarm code remains as long as the alarm condition remains
if pressed on turning On the instrument:
•allows selection of default parameters (see section “alarms and signalling”)
if pressed for more than 5 seconds:
•allows access to the frequent parameters selection menu
if pressed for more than 5 seconds together with the sel button:
•allows access to the configuration menu (see section “parameters second level")
CONTINUOUS CYCLE BUTTON:
if pressed for more than 5 seconds:
• activates/deactivates a continuous cycle, that is the forced activation of the compressor
for a period to be selected (see parameter “duration of continuous cycle”)
ON/OFF BUTTON:
•allows the switching On/Off of the refrigerating unit
Warning: when the controller is OFF all outputs, with the exception of the light button and the
lights output, will be deactivated and the OFF led will be flashing. The ON/OFF button can be
deactivated and the unit can be switched On/Off by using a digital input (see digital inputs
configuration). It is necessary to select the ‘c2’ parameter to ensure that, between one switching
Off and the following switching On, the minimum time the compressor is Off is maintained.
LED INDICATORS
cooling inserted
fan evaporator activated
defrosting in progress
lights On
'continuous cycle' functioning
unit deactivated
if one of the LED is flashing, see the section “alarms and signalling
FUNCTIONING
56
Cod. +030220151 - Rel. 2.1 - 04/09/98
During normal functioning the display shows the value read by the ambient sensor. In case of alarm the
temperature values will flash alternately to the alarm code. When the controller is deactivated (OFF status)
the 'OFF' led flashes while the display shows the temperature read by the sensor.
SET-POINT:
1.press for one second the button to visualise the set-point value;
2.after some seconds, the selected value will flash;
3.either increase or decrease the set-point value by pressing the buttons and
4.press the button again to confirm the newly set value.
MANUAL DEFROSTING:
press the button for more than 5 seconds to force a defrosting cycle which will be activated only if
the conditions are favourable (for example, the defrost sensor should be lower than the selected defrost end
temperature. For further information see the technical manual)
BUZZER SILENCING:
press the button . Besides silencing the buzzer, the alarm relay is reset, while the alarm code remains
memorised until the cause of the alarm has been removed.
ENABLING OF AUXILIARY OUTPUT:
press the button to activate/deactivate the lights or any other auxiliary output.
CONTINUOUS CYCLE:
To activate the 'continuous cycle' functioning press the button for at least 5 seconds (compressor
activated for the time selected with the 'cc, parameter = duration of ‘continuous cycle').
So as to deactivate the continuous cycle functioning, press the button again for 5 seconds.
57
Cod. +030220151 - Rel. 2.1 - 04/09/98
IR96: PARAMETERS
The parameters have been organised on two levels:
FIRST LEVEL: frequent parameters. They are indicated with F in the table and the password is not
necessary to gain access to them. To modify them operate as follows:
1.press the button for more than 5 seconds (in case of alarm, first silence the buzzer);
2.the display shows the code of the first parameter to be modified.
3.To modify the parameters see the section “parameters modification”.
SECOND LEVEL: configuration parameters. They are indicated with C in the table and it is necessary to
insert the password for any modification, as indicated here below:
1.press simultaneously the buttons and for more than 5 seconds;
2.the display shows 00;
3.press the buttons and until 22 (password) is displayed;
4.confirm by pressing ;
5.the display shows the code of the first parameter to be modified.
To modify the parameters see the following section “parameters modification”.
Parameters Modification:
To modify a parameter operate as follows:
1.press and/or until the parameter to be modified is displayed (see the parameters table);
2.press the button to visualise the value associated to the parameter;
3.modify its value by pressing the buttons and/or until you reach the requested value;
4.press the button to confirm temporarily the newly set value and to go back to the parameter code
visualisation;
5.repeat all operations from the point "press and/or " to modify other parameters values;
New-Set Values Memorisation:
Press the button to memorise all newly-set values and exit the procedure.
To exit without modifying the parameters: do not press any button for at least 60 seconds ( TIME OUT exit).
Warning: if the button is not pressed after modifying operations, all effected modifications will be lost.
58
Cod. +030220151 - Rel. 2.1 - 04/09/98
LIST OF PARAMETERS
ParameterKind MinMaxU.M.Def
PASSWORD
PA
SENSOR PARAMETERS
/
/0Type of sensor (must be 0)[Accessible only after RESET]01-0
/CAmbient sensor calibrationF-20+20°C/°F0.0
/2Measurement stabilityC115-4
/3Sensor reading speedC115-8
/4Sensors average (see installation manual)C0100-0
/5°C /°F (0=°C, 1=°F)C01flag0
/6Enabling of decimal point (0=yes, 1=no)C01flag0
CONTROL PARAMETERS
r
rdControl differential (hysteresis)F0.1+19.9°C/°F2
r1Minimum set allowedC-50r2°C/°F-50
r2Maximum set allowedCr1+199°C/°F90
r3Enabling of Ed alarm (defrost interrupted because maximum
duration has been reached, param. dP) 0=no, 1=yes
r4Automatic set-point variation during night functioning (that is when
the curtain switch is closed, with either A4 or A5=7)
r5Enabling of min./max. temp. monitoring (0=no, 1=yes)C01flag0
rtActual interval in max./min. temperature readingF0199hoursrHMaximum temperature read in the rt intervalF-50+90°C/°FrLMinimum temperature read in the rt intervalF-50+90°C/°F-
C00+199-22
C01flag0
C0+20°C/°F3.0
COMPRESSOR PARAMETERS
c
c0Compressor start-up delay after unit start-upC015min0
c1Minimum interval between two compressor start-upC015min0
c2Minimum compressor off-timeC015min0
c3Minimum compressor on-timeC015min0
c4Relay safety (0=OFF, 100=ON). See Duty settingC0100min0
ccDuration of continuous cycleC015hours4
c6Alarm cut-out after continuous cycleC015hours2
DEFROST PARAMETERS
d
d0 Type of defrost (0= heater, 1= hot gas, 2= water/resistance by time,
3= hot gas by time)
dIInterval between two defrost phasesF0199hours8
dtEnd defrost temperature setF-50+199°C/°F4
dPMaximum duration of defrost or real duration for d0=2 or 3F1199min30
d4Defrost on unit start-up (0=no, 1=yes)C01flag0
d5Defrost delay after unit start-up or digital input (A4 or A5 =4)C0199min0
d6Display override during defrost (0=no, 1=yes)C01flag1
ddDripping time after defrostF015min2
d8Duration of alarm cut-out after defrost and, if A4 or A5=5, after door opening F015hours1
d9Defrost has priority over compressor protection (0=no, 1=yes)C01flag0
d/Defrost temperature sensor readingF--°C/°FdCTime basis (0=hours/min,1=min/sec)C01flag0
C03flag0
59
Cod. +030220151 - Rel. 2.1 - 04/09/98
ALARM PARAMETERS
A0Alarm and fan differentialC0.1+20°C/°F0.2
ALLow temperature alarm (indicates the max. allowed deviation from
F0+199°C/°F0
the set- point). If = 0 disables the low temperature alarm
AHHigh temperature alarm (indicates the max. allowed deviation from
F0+199°C/°F0
the set-point). If = 0 disables the high temperature alarm
AdTemperature alarm delayC0199min120
A4Digital input n.1 configurationC07-0
A5Digital input n.2 configurationC07-0
A6Cut-out of compressor by external alarm: 0=OFF, 100=ON Enabled
C0100min0
if either A4 or A5= 1 or 2, see Duty setting and digital input
A7Delay in registration of the input <<delayed alarm>> (A4 or A5 = 2)C0199min0
FAN PARAMETERS
F
F0Management of fans: 0 = always activated fans except on specific
C02flag0
phases (see parameters F2, F3, and Fd)
1= fans controlled by a thermostat according to the difference
between ambient temp. and evap. temp.,
2= fans controlled by a thermostat according to the evaporator
temperature
F1Fans activation temperature: if F0=1 it is the minimum difference
F0+20°C/°F5
between ambient temp. and evap. temp. (t. evap. < t.amb.)
if F0=2, the fan is ON if Evap.temp<Setpoint + F1 - A0
the fan is OFF if Evap.temp. > Setpoint + F1
F2Stop fans when compr. is Off (0=no, 1=yes). Active if F0=0C01flag1
F3Stop fans during defrost (0=no,1=yes).
C01flag1
This parameter is active for any value of F0
FdStop after dripping. Active for any value of F0F015min1
OTHER SETTING
H
H0Address within networkC015-0
H1Selection of relay 4 functioning: 0= auxiliary output, 1=normally de-
H20= buttons inhibited; 2= buttons & IR inhibited; 3=IR inhibitedC03flag1
H3Code to enable remote programmingC00199-00
60
Cod. +030220151 - Rel. 2.1 - 04/09/98
DESCRIPTION OF PARTICULAR PARAMETERS AND
PERFORMANCES
Memorisation of Minimum/Maximum Temperature:
IR96 allows to record the minimum and the maximum temperature read by the 'ambient' sensor during an
interval which can reach up to 199 hours (more than 8 days). To activate this function, operate as follow:
1.select parameter 'r5'=1. This is a 'Configuration' parameter
2.visualise the parameter 'rt' (type F parameter). By pressing the button the instrument displays how
long the min./max. temperature memorisation has been active (if the memorisation has just been
enabled, rt will be associated to the value '0'). If you want to restart the temperature memorisation, press
the button during the visualisation of memorisation hours. The instrument will clear the memorisation
hours and will start with monitoring again.
3.to see the maximum temperature read by the sensor, refer to the value associated to rH
4.to see the minimum temperature read by the sensor, refer to the value associated to rL
Warning: if the instrument is not connected to a UPS, a short power failure will clear the values rt, rL e rH.
When voltage is supplied again, the controller will automatically start the monitoring again with rt =0.
Functioning of the relay 4
With H1 = 0 relay 4 can be used as auxiliary output. If either A4 or A5=5 the output allows the automatic
lights management if the connection of the door switch to the selected input has been effected (Dig.In1 if
A4=5 or Dig.In2 if A5=5, see wiring diagram).
If H1 = 1 the fourth relay becomes an alarm output. The relay is normally de-energised and on alarm
condition the contact will close. If H1 = 2 the fourth relay is still an alarm output, but the relay is normally
energised (contact closed) and on alarm condition the contact will open. By pressing the button Mute the
relay commutes only if the cause of the alarm has been removed. The fifth relay is always active as an
alarm output: by pressing the button Mute this relay, unlikely the relay 4 with H1=1 or H2=2, always resets even
with an alarm pending.
Type of sensor (Accessible Only After Reset, See Ea, Eb, Ee)
The value of parameter /0 should be absolutely 0
Selection of Duty Setting (Parameters A6 and C4)
If the control sensor alarm (E0 flashing) is activated, the parameter c4 allows the compressor to function:
c4= value between 1 and 99: states the compressor On-time (expressed in minutes), followed by a fixed Offtime equal to 15 min.;
c4=0: compressor always Off;
c4=100: compressor always On.
If an external alarm (Al or Ad flashing) is activated on the digital input (A4=1; A4=2), the parameter A6
allows the compressor to function:
A6= value between 1 and 99: states the compressor On-time (expressed in minutes), followed by a fixed Offtime equal to 15 min.;
A6=0: compressor always Off;
A6=100: compressor always On.
Digital Inputs Configuration
Digital input 1 and 2 can take on different functioning modes according to the value given to the parameter
A4, relative to the ID1 input, and to A5 relative to Id2. The main: see the table “programmable digital inputs:
list of the options” at 33 page.
61
Cod. +030220151 - Rel. 2.1 - 04/09/98
IR96: ALARMS
•
FLASHING LED: actuator set delay
Insertion of the relative function is delayed for a period while awaiting an external consent or while held up
by another process still in progress.
TEMPERATURE FLASHING: door open or door switch broken.
Close the door or control the door switch.
E0 FLASHING: control sensor error
Sensor not compatible with the equipment; sensor cable interrupted or short circuit.
Faulty sensor: disconnect the sensor from the instrument and measure the resistance (NTC: 0ºC=27K
Ohms)
E1 FLASHING: evaporator sensor error
Sensor not compatible with the equipment; sensor cable interrupted or short circuit.
Faulty sensor: disconnect the sensor from the instrument and measure the resistance (NTC: 0ºC=27KΩ)
IA FLASHING: alarm from digital input
Check 'Multi-function' inputs and parameters A4 and A5
Ad FLASHING: delayed alarm from digital input
Check 'Multi-function' inputs and parameters A4, A5 and A7
LO FLASHING: low temperature alarm (temperature lower than SET-AL-A0)
Check parameters AL, Ad and A0
The alarm will cease as soon as the temperature returns within the limits selected.
HI FLASHING: high temperature alarm (temperature higher than SET +AH + A0)
Check parameters AH, Ad and A0
The alarm will cease as soon as the temperature returns within the limits selected.
EA, EB, EE: data acquisition error. RESET procedure
In order to restore normal working conditions, reset the default value of the parameters with this procedure:
•turn off the instrument;
•press the PRG button and, keeping it pressed, turn on the controller;
•the display shows "-c-";
after a few seconds, the instrument enters the RESET procedure and allows the modification of parameters. (*)
•should EE persist, press the button 66 until the message disappears.
(*) Any modification made before the reset procedure will be lost
Ed FLASHING: defrost end by timeout
•check parameters dt, dP and d4
•check effectiveness of the defrost
•in case inhibit the alarm Ed through the r3 parameter
dF FLASHING: defrosting in progress
This is not an alarm signal, but it indicates that the instrument is carrying out a defrost. Appears only if
parameter d6=0.
DIMENSIONS
Carel reserves the right to alter the features of its products without prior notice.
62