Carel humiFog multizone User Manual

High Efficiency Solutions
humiFog multizone
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
User manual
3
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
WARNINGS
CAREL INDUSTRIES Hq humidifiers are advanced products, whose operation is specified in the technical documentation supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com. Each CAREL INDUSTRIES Hq product, in relation to its advanced level of technology, requires setup/configuration/programming/commissioning to be able to operate in the best possible way for the specific application. The failure to complete such operations, which are required/indicated in the user manual, may cause the final product to malfunction; CAREL INDUSTRIES Hq accepts no liability in such cases. The customer (manufacturer, developer or installer of the final equipment) accepts all liability and risk relating to the configuration of the product in order to reach the expected results in relation to the specific final installation and/or equipment. CAREL INDUSTRIES Hq may, based on specific agreements, act as a consultant for the installation/commissioning/use of the unit, however in no case does it accept liability for the correct operation of the humidifier and the final installation if the warnings or suggestions provided in this manual or in other product technical documents are not heeded. In addition to observing the above warnings and suggestions, the following warnings must be heeded for the correct use of the product:
DANGER OF ELECTRIC SHOCK
The humidifier contains live electrical components. Disconnect the mains
power supply before accessing inside parts or during maintenance and installation;
DANGER OF WATER LEAKS
The humidifier automatically and constantly fills/drains certain quantities of
water. Malfunctions in the connections or in the humidifier may cause leaks;
For isothermal humidiers: DANGER OF BURNS
The humidifier contains high temperature components (100°C/212°F);
For gas-red isothermal humidiers: DANGER OF GAS LEAKS
The humidifier is connected to the gas mains. Malfunctions in the
connections or inside the humidifier may cause gas leaks.
The installation of the product must include an earth connection, using the
special yellow-green terminal available in the humidifier.
The environmental and power supply conditions must conform to the
values specified on the product rating labels.
The product is designed exclusively to humidify rooms either directly or
through distribution systems (ducts). In addition, for adiabatic-water spray­pressure humidifiers, humidification also occurs through the atomisation rack.
Only qualified personnel who are aware of the necessary precautions and
able to perform the required operations correctly may install, operate or carry out technical service on the product.
Only water with the characteristics indicated in this manual must be used
for steam or water vapour production.
Warning, demineralised drinking water must be used for adiabatic-water
spray-pressure humidifiers (as specified in the manual). In addition, the particles of water not absorbed by the air must be removed into the droplet collection tank (in the humidification section) and by the droplet separator (at the end of the humidification section).
All operations on the product must be carried out according to the
instructions provided in this manual and on the labels applied to the product. Any uses or modifications that are not authorised by the manufacturer are considered improper. CAREL INDUSTRIES Hq declines all liability for any such unauthorised use.
Do not attempt to open the humidifier in ways other than those specified
in the manual.
Observe the standards in force in the place where the humidifier is installed.
Keep the humidifier out of the reach of children and animals.
Do not install and use the product near objects that may be damaged when in
contact with water (or condensate). CAREL INDUSTRIES Hq declines all liability for direct or indirect damage following water leaks from the humidifier.
Do not use corrosive chemicals, solvents or aggressive detergents to clean
the inside and outside parts of the humidifier, unless specifically indicated in the user manual.
Do not drop, hit or shake the humidifier, as the inside parts and the linings
may be irreparably damaged.
For adiabatic-water spray-pressure humidifiers: the atomised water must
be distributed using a special atomising ‘rack’ or through distribution systems specified by CAREL INDUSTRIES Hq
For isothermal appliances: these are designed to produce steam at
atmospheric pressure, and not pressurised steam. CAREL INDUSTRIES Hq does not recommend and waives all liability for the use of distribution devices other than those specified.
CAREL INDUSTRIES Hq adopts a policy of continual development. Consequently, CAREL reserves the right to make changes and improvements to any product described in this document without prior warning. The technical specifications shown in the manual may be changed without prior warning. The liability of CAREL INDUSTRIES Hq in relation to its products is specified in the CAREL INDUSTRIES Hq general contract conditions, available on the website www.carel.com and/or by specific agreements with customers; specifically, to the extent where allowed by applicable legislation, in no case will CAREL INDUSTRIES Hq, its employees or subsidiaries be liable for any lost earnings or sales, losses of data and information, costs of replacement goods or services, damage to things or people, downtime or any direct, indirect, incidental, actual, punitive, exemplary, special or consequential damage of any kind whatsoever, whether contractual, extra-contractual or due to negligence, or any other liabilities deriving from the installation, use or impossibility to use the product, even if CAREL INDUSTRIES Hq or its subsidiaries are warned of the possibility of such damage.
DISPOSAL
The humidifier is made up of metal parts and plastic parts. In reference to European Union directive 2002/96/EC issued on 27 January 2003 and the related national legislation, please note that:
1. WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately;
2. the public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment;
3. the equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the environment;
4. the symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment has been introduced onto the market after 13 August 2005 and that it must be disposed of separately;
5. in the event of illegal disposal of electrical and electronic waste, the penalties are specified by local waste disposal legislation.
Warranty on the materials: 2 years (from the date of production, excluding consumables).
Approval: the quality and safety of CAREL INDUSTRIES Hq products are guaranteed by the ISO 9001 certified design and production system, as well as by the following marks.
WARNING: separate as much as possible the probe and digital input signal cables from the cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance. Never run power cables (including the electrical panel wiring) and signal cables in the same conduits.
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
5
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
Content
1. INTRODUCTION AND ASSEMBLY 7
1.1 Description of humiFog ..........................................................................................7
1.2 Components in the system ..................................................................................7
1.3 humiFog system configurations ........................................................................7
1.4 Supply water characteristics.................................................................................7
1.5 Periodic checks for consumables ......................................................................8
1.6 Dimensions and weights ........................................................................................8
1.7 Components (master/slave) .................................................................................9
1.8 Electrical specifications.........................................................................................10
1.9 Opening the packaging .......................................................................................10
1.10 Positioning the cabinet ......................................................................................11
1.11 Opening the cabinet door ................................................................................12
1.12 Components and accessories .........................................................................12
2. WATER CIRCUIT CONNECTIONS 13
2.1 Water circuit installation: instructions .........................................................13
2.2 Water circuit installation: checklist ................................................................13
3. ELEC TRICAL CONNECTIONS 14
3.1 Power supply .............................................................................................................15
3.2 Remote ON/OFF .......................................................................................................15
3.3 Control signals from external voltage-free contact (humidistat) .....15
3.4 Modulating control signal (J2) .........................................................................16
3.5 Heat recovery signal ...............................................................................................17
3.6 Solenoid valve connection for distribution system ............................17
3.7 Water treatment unit contact ...........................................................................18
3.8 Cumulative alarm relay (J15) .............................................................................18
3.9 Pump state contact ...............................................................................................18
3.10 Pump life signal .........................................................................................................18
3.11 Alarm inputs from external devices ...........................................................19
3.12 Backup/rotation (redundancy) ........................................................................19
3.13 Expansion mode/remote actuator ................................................................19
3.14 Master-slave connection .....................................................................................20
3.15 Supervisor network .................................................................................................20
4. PUMPING UNITS 21
4.1 Pumping unit with flow control configuration .....................................21
4.2 Pumping unit with constant pressure control .......................................21
5. DISTRIBUTION SYSTEM 22
5.1 Air handling unit: distribution, atomisation system and
droplet separator ......................................................................................................22
5.2 Direct humidification into the room: distribution and
atomisation system .................................................................................................22
6. APPLICATIONS 23
6.1 Main advantages of humiFog multizone ..................................................23
7. CONTROL 24
7.2 Evaporative Cooling ...............................................................................................25
8. SINGLE ZONE AND MULTIZONE CONFIGURATION 27
8.1 Single zone ...................................................................................................................27
8.2 Multizone application in AHU or room ......................................................28
8.3 Indirect adiabatic cooling applications ......................................................30
8.4 System operation .....................................................................................................30
8.5 Constant pressure systems: notes on capacity control ....................31
9. START UP 32
9.1 Starting ...........................................................................................................................32
9.2 Stopping ........................................................................................................................32
9.3 First start-up .................................................................................................................32
10. USER INTERFACE 33
11. TABLE OF ALARMS 49
12. WIRING DIAGR AMS 52
12.1 Wiring diagram humiFog multizone - Master - CE -
MONOFASE ...................................................................................................................52
12.2 Wiring diagram humiFog multizone - Master - CE -
TRIFASE
(solo per UA10K***) .......................................54
12.3 Wiring diagram humiFog multizone - Master - UL -
MONOFASE ...................................................................................................................56
12.4 Wiring diagram humiFog multizone - Master - UL - TRIFASE .......58
12.5 Wiring diagram humiFog multizone - Slave - CE ................................60
12.6 Wiring diagram humiFog multizone - Slave - UL ................................62
7
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
1. INTRODUCTION AND ASSEMBLY
1.1 Description of humiFog
humiFog is a humidifier and adiabatic cooler that atomises demineralised water into very fine droplets that evaporate spontaneously in the air, which is humidified and cooled.
humiFog uses a volumetric pump to pressurise the water, which is atomised by special stainless steel nozzles.
The sophisticated control system combines the action of an inverter, which controls the speed and consequently the flow-rate of the pump, with a series of solenoid valves that activate only the nozzles that are necessary, allowing the system to always operate at the ideal pressure to atomise the water, across a wide range of flow-rates (a 5-100 % flow range working with a constant pressure of 14-100% for operating while controlling the flow).
The effect of cooling the air is due to the spontaneous evaporation of the droplets of water: the change in state from liquid to steam occurs by subtracting energy from the air that, as a consequence, is cooled. Each kilogram of water evaporated absorbs 0.69 kWh of heat from the air.
humiFog is a complete humidification and/or adiabatic cooling system that can be used both in AHUs (air handling units) and to humidify or cool industrial environments by spraying water directly into the environments. The term zone refers to both AHUs and industrial environments.
1.2 Components in the system
humiFog is made up of:
a pumping unit that delivers the water at high pressure (25-70 bars).
It also contains the electronic controller that completely manages the pumping unit, controlling the temperature/humidity in a zone (either AHU or environment) and managing any other zones connected to the pumping unit;
The pumping unit can be set to operate:
- with flow control (maximum precision, minimum energy and water
consumption, only single zone applications);
- at constant pressure (suitable for multizone applications where one
pumping unit supplies the humidification and/or cooling system in different zones);
distribution and atomisation system: system of pipes carrying the
pressurised water that house the atomisation nozzles and, in general, the capacity-control solenoid valves and drain solenoid valves;
droplet separator (only when installed in an AHU);
temperature and/or humidity probes (if necessary);
water treatment system: typically this is a reverse osmosis demineraliser
that supplies water with a low mineral salt content to the humiFog.
1.3 humiFog system configurations
The humiFog system can be used in the following configurations:
single zone: for humidification and/or cooling applications in a AHU or
an industrial environment;
multizone: for applications where one pumping unit (master) is
used to supply multiple zones with pressurised water. The master will control one zone, in the sense that in relation to the zone probe readings or the external controller, it will activate and control the distribution and atomisation system so as to maintain the humidity or temperature level. All other zones will have a controller (slave electrical panel) that communicates with the master, and in relation to the zone probe readings or the external controller will activate and control the distribution atomisation system so as to maintain the humidity or temperature level.
One important configuration is for indirect adiabatic cooling applications: a pumping unit can be used to humidify the air in winter and to cool the discharged air in summer before it enters a heat recovery unit. This configuration is explained in detail in the chapters below.
humiFog humidifiers are available for:
maximum flow-rates respectively of 100 l/h,(UA100..) 200 l/h (UA200..),
320 l/h (UA320..), 460 l/h (UA460..), 600 l/h (UA600..);
type of cabinet: H=single zone master; Z=multizone master; S=slave
cabinet;
power supply voltage: D= 230 V 50 Hz; U= 208 V 60 Hz;
shows the version of the launched product (1 - 4)
damper: 0=without damper; 1=with damper (only versions with 100
and 200 l/h flow-rate)
features of the pump and circuits: 0= brass; 1=stainless steel; 2=
stainless steel, silicon free
1.4 Supply water characteristics
Why does humiFog require demineralised water?
Humifog only works with demineralised water, to ensure:
minimum maintenance;
no blockage of the nozzles;
no dust (the droplets that evaporate do not leave mineral salts in the
AHU/environment);
more hygiene.
The use of demineralised water is also required by standards such as UNI8883 , VDI6022, VDI3803
humiFog must only be supplied with treated water, based on the limit values listed below. In normal circumstances, this means that the water must be treated using a reverse osmosis system.
recommended supply water characteristics unit of
measure
limits
min. max.
bH (**)(pH)
6,5 8,5 Specific conductivity at 20°C (**) (σR, 20°C) for steel pump
µS/cm 0 30
Specific conductivity at 20°C (**) (σR, 20°C) for brass pump
µS/cm 30 50
Total hardness (**) (TH) mg/l CaCO3 0 25 Temporary hardness mg/l CaCO3 0 15 Total quantity of dissolved solids (cR) mg/l
(*) (*)
Dry residue at 180° (R180°C) mg/l
(*) (*)
Iron + Manganese mg/l Fe+Mn 0 0 Chlorides ppm Cl 0 10 Silicon dioxide mg/l SiO2 0 1 Chlorine ions mg/l Cl- 0 0 Calcium sulphate mg/l CaSO4 0 5
Tab. 1.a
(*) values depend on the specific conductivity; in general:
CR 0,65 * σ
R, 20 °C
; R
180
0,93 * σ
R, 20 °C
(**) main values to keep in consideration for every type installation.
Important: If the specific conductivity is less than 30 µS/cm, the stainless steel pump should be used.
Important:
(**)
for conductivity values around “0”, contact CAREL
INDUSTRIES for operating suggestions.
Caution: for conductivity higher than 1000 S/cm, it is required to pre-treat the water before subjecting it to reverse osmosis.
Caution: the pump is able to operate at a maximum temperature of 40°C.
8
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
1.5 Periodic checks for consumables
Summary table of checks and maintenance:
Pump Check/Replace monthly every 1000 h
Water filters X Oil level X Replace oil X Check/replacement gasket and valves X
Attention: after the first 50 h of exercise you need to replace the oil pump.
Attention: if the “1000h” check does not identify any leaks or
malfunctions, then the possibility to postpone the replacement shall be assessed. Typically, in optimum operating conditions, this process is necessary around 3000 h of operation.
Rack/distribution system visually check every 1000 h
obstructed nozzles X solenoid valves X accessories X drain and water X droplet separator X
Tab. 1.b
Installations in AHUs or ducts must also comply with national maintenance standards (ASHRAE 12-2000, VDI 6022, UNI 8884, VDI 3803, etc.)
Please note that:
maintenance personnel must reset the hour counter after having
performed the preventive maintenance operations listed in the columns “after 50 hours” and “every 1000 hours”. If the hour counter is not reset, the maintenance warnings will no longer be signalled (to reset the hour counter, see the information under Section 9.8 Maintenance menu/submenu f/screen 02);
maintenance personnel are responsible for any malfunctions due to a
lack of preventive maintenance. The controller will display maintenance warning code “C5” after the first 50 hours and, subsequently, routine maintenance warning code “CL” every 2000 hours, as a reminder for the operations listed;
failure to change the oil after the first 50 hours of operation may cause
oil leaks and serious damage to the pumps, reducing operating life;
maintenance signals do not stop the operation of humiFog.
1.6 Dimensions and weights
Humifog master
front view
1030
20
135
550
70
360
860
1
2
3
4
5
6
Fig. 1.a
detail of cabinet, water inlet/outlet
side view
electrical connection side view
90
554
135
2055
105
2558
3
4
5
6
70
360
430
75
75
4040 40 4040
2
1
Fig. 1.b
Key:
1. power supply inlet;
2. terminal block inlet;
3. water inlet;
4. water outlet;
5. drain
6. drain bypass..
N.B.: inlets for electrical connections ready to be cut out, opening
and cable gland installation to be performed by the installer
Packaging dimensions:
height (H): 1020 mm (40.16 inch);
width (W) 1100 mm (43.30 inch);
depth (D) 455 mm (17.50 inch).
Weight of packaged humidifier:
UA(100,200)(H,Z)4** models: 100 kg (220 lb);
UA(320,460)(H,Z)4** models: 110 kg (240 lb);
UA600(H,Z)4** models: 120 kg (265 lb);
UA1K0(H,Z)4** models: 125 kg (276 lb);
Weight of installed humidifier:
UA(100,200)(H,Z)4** models: 85 kg (190 lb);
UA(320,460)(H,Z)4** models: 95 kg (210 lb);
UA600(H,Z)4** models: 100 kg (220 lb);
UA1K0(H,Z)4** models: 105 kg (230 lb);
Mechanical specifications:
Installation: floor standing;
IP20; (enclosure type 1).
cabinet operating conditions: 1 to 40 °C (34 to 104 °F) <80 % RH non-
condensing;
storage conditions: 1 to 50 °C (34 to 122 °F) <80 % RH non-condensing
9
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Humifog slave
front view
500 28
580
1
22
Fig. 1.c
detail of cabinet, air & water inlet side view
detail of cabinet, outlet side view (to nozzles)
150 8
303030
40110
101
50100
150
123
224
1
2
123 101
50
224
2
Fig. 1.d
N.B.: inlets for electrical connections ready to be cut out, opening
and cable gland installation to be performed by the installer
Packaging dimensions:
height (H): 770 mm (30.14 inch);
width (W) 605 mm (23.82 inch);
depth (D) 255 mm (10.00 inch).
Weight of packaged humidifier:
UA000S(D,U)400 models: 21 kg (46.3 lb);
Weight of installed humidifier:
UA000S(D,U)400 models: 19.5 kg (43 lb);
Mechanical specifications:
Installation: wall mounted;
IP20; (enclosure type 1)
cabinet operating conditions: 1 to 40 °C (34 to 104 °F) <80 % RH non-
condensing;
storage conditions: 1 to 50 °C (34 to 122 °F) <80 % RH non-condensing
1.7 Components (master/slave)
Electrical components
Master cabinet
F1 F2 F6
F8
F7
F9
1
3
6
4
2
5
9
7
10
8
11
12
Fig. 1.e
Slave cabinet
1
2
8
6
4
3
11
12
Fig. 1.f
Key:
1. terminal rear view.
2. transformer B.
3. main switch G.
4. power supply terminal block.
5. VFD inverter.
6. transformer primary fuse carrier (TRA: F1,F2; TRB:F3,F4).
7. inverter fuse carrier (F6, F7).
8. transformer B secondary fuse carrier (F8).
9. transformer A.
10. start relay K.
11. electronic controller;
12. control terminal block plus fuses
10
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Water circuit components
12
7
5
6
8
9
11
10
13
23 4
1
Fig. 1.g
16
15
14
17
Fig. 1.h
Key:
1. inlet water pressure reducer with filter;
2. 1st pressure gauge, inlet;
3. water filter;
4. minimum pressure switch (1 bar);
5. 2nd pressure gauge, downstream of the water filter;
6. conductivity sensor;
7. water supply solenoid valve;
8. motor;
9. pulsation damper;
10. outlet pressure gauge, high pressure side;
11. piston pump;
12. maximum pressure switch (95 bars);
13. high pressure control valve;
14. thermostat (70 °);
15. bypass solenoid valve;
16. temperature probe;
17. pressure transducer
18. drain bypass.
1.8 Electrical specifications
MASTER 50 HZ
model UA100*D4** UA200*D4** UA320*D4** UA460*D4** UA600*D4** UA1K0*HL4*
VAC 230 V 230 V 230 V 230 V 230 V 400 V phases 1 1 1 1 1 3 Hz 50 -60 Hz 50 -60 Hz 50 -60 Hz 50 -60 Hz 50 -60 Hz 50-60 Hz power 0,955 kW 0,955 kW 1,150 kW 1,150 kW 1,95 kW 4 kW current 7,0 A 7,0 A 9,2 A 9,2 A 12,0 A 4,6 A
Product in compliance with EN55014, EN61000, EN60204. Insulation grade III
MASTER 60 HZ
model UA100*U4** UA200*U4** UA320*U4** UA460*U4** UA600*U4** UA1K0*HM4*
VAC 230 V 230 V 230 V 230 V 230 V 460 V phases 1 1 1 1 1 3 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz power 0,955 kW 0,955 kW 1,150 kW 1,150 kW 1,95 kW 2.75 kW current 8,00 A 8,00 A 10,20 A 10,20 A 13 A 4.8 A FLA 1HP/8 A 1HP/8 A 2HP/12 A 2HP/12 A 3HP/17 A 3HP/6.1 A SCCR 5KA 5KA 5K A 5K A 5KA 5K A
Product in compliance with UL998
SLAVE
model UA000SD400 UA000SU400
VAC 230 V 208 V phases 1 1 Hz 50 Hz 60 Hz power 0,280 kW 0,280 kW current 2,20 A 2,50 A FLA - 3/4HP SCCR - 5KA
Product in compliance with UL998
Tab. 1.c
1.9 Opening the packaging
 make sure the humidifier is intact upon delivery and immediately
notify the transporter, in writing, of any damage that may be due to careless or improper transport;
 move the humidifier to the site of installation before removing from
the packaging, grasping the neck from underneath;
for the master cabinet:
 position the cabinet near the site of installation (still packaged on the
pallet);  remove the packaging;  unscrew the bolts and remove the pallet (the cabinet is secured to the
bottom of the pallet using 4 bolts);
for the slave cabinet:
 open the cardboard box, remove the protective material and remove
the humidifier, keeping it vertical at all times.
Keep the packaging in a cool and dry environment (cardboard box, pallet, 4 bolts used to secure the cabinet to the pallet) for reuse.
11
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
1.10 Positioning the cabinet
Both cabinets: master and slave, should be positioned so as to guarantee the following:
read the values on the display;
access the keypad on the display;
open the front panels;
access to the inside parts for checks and maintenance;
connection of the water supply lines;
connection to the water distribution lines;
power and control connections;
prepare a base of at least 200 mm.
in particular, for the Master cabinet: It can be positioned wherever the following conditions are ensured:
clearance for routine maintenance as described in Fig. 1.f
humidity 20-80% rH non-condensing
temperature 1-40 °C;
cabinet compliant with seismic testing standards IEC 60068-2-6, IEC
60068-2-57, IEC 60068-2-64, ISO2041. To ensure compliance with the above-mentioned standards, the cabinet must be anchored to the floor using the threaded holes provided (M6 female thread), as shown in Fig. 1.i.
65
900
65
20 20
310
INSERTI FILETTATI M6
FEMMINA
65
900
65
M6 F
20
310
20
M6 F
Fig. 1.i
Important: the maximum distance between the cabinet and rack/ distribution system is 50 metres, for higher distances contact CAREL INDUSTRIES.
Positioning procedure:
after opening the packaging:
position the cabinet in the final position;
level the cabinet horizontally.
TV
3751000
100
1075
55
45
100 100
P
Fig. 1.j
Slave cabinet
Fasten it to a solid support surface using the screws and bracket supplied. Make sure there is enough space for the electrical power supply and control connections.
rear of the cabinet
390
200
440
drilling template
440
200
390
= =
= =
Fig. 1.k
12
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
1.11 Opening the cabinet door
Master cabinet
Opening Fig. 1.h:
1. Release the water circuit panel:
use a flat-head screwdriver (max. 8 mm); turn anticlockwise until releasing the panel.
2. Remove the panel:
tilt the panel and lift it. Closing Fig. 1.h:
3. Reposition the water circuit panel:
Important: insert the bottom pins of the panel in the corresponding holes (F).
4. Lock the panel:
use a flat-head screwdriver (max. 8 mm); turn clockwise until the panel is secured
Fig. 1.l
Slave cabinet
1. press and turn anticlockwise with a flat-head screwdriver (max 8 mm)
until releasing the panel;
2. open the cabinet door by turning it to the left.
1
2
Fig. 1.m
1.12 Components and accessories
Once having opened the packaging and removed the front cover of the humidifier, make sure the following are included:
for master units:
tool for opening the water inlet filter casing;
PG13 and PG21 cable glands for the electrical connections (CE versions
only).
yellow/black pump motor oil cap, to replace the red cap on the pump.
for slave units
kit of screws with plugs for wall-mounting;
PG13 and PG21 cable glands for the electrical connections (CE versions
only).
13
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
2. WATER CIRCUIT CONNECTIONS
2.1 Water circuit installation: instructions
The water connections are
water inlet;
high pressure water outlet to the rack (see ”connecting the cabinet to
the rack” in the distribution manual);
water drain.
Water circuit installation: instructions
To simplify installation and maintenance, install a manual valve immediately before connecting the water inlet to the cabinet (this valve is not supplied by CAREL). humiFog only operates on demineralised water, preferably from a reverse osmosis system. The specifications and the limits of the water are described in detail in chap. 1.4 “supply water characteristics”.
1. open the water circuit (vedi par. 1.10 “Opening the cabinet door”):
2. connect the water supply hose:
the supply hose connection fitting is G1/2”F (NPT1/2”F - UL 60 Hz
version).
the inside diameter of the supply hose must not be less than
13 mm.
run the water supply hose through hole “3” Fig. 1.a.
Water drain connection
1. connect the drain “5” Fig. 1.a to the drain system:
use a hose with inside diameter 10 mm, resistant to demineralised
water.
connect the hose to the drain connection underneath the cabinet
using a hose clamp.
N.B.: the hose and the clamp are not supplied by CAREL, to
tighten clamp, lift the cabinet.
2. connect the drain bypass “6” Fig. 1.a to the drain system.
Replacing the top oil cap on the pump
1. replace the top oil cap on the pump:
replace the TOP oil cap ( (Fig. 2.a, A), used for transport only, with
the CAP WITH THE VENT HOLE (Fig. 2.a, B) used in normal operation;
keep closed cap for future transport.
2. reposition the front panel on the water circuit and close it.
Fig. 2.a
CE versions
model UA100*D4** UA200*D4** UA320*D4** UA460*D4** UA600*D4** UA1K0*HL4* max flow rate (l/h; lb/h;Gd)
100 200 320 460 600 950 220 441 705 1014 1323 2095
634 1268 2028 2916 3805 6023 inlet pressure (Mpa,Bar, PSI)
0,3…0,8 Mpa
3…8 Bar
40…100 PSI
temperat. 1T40 ºC / 34T104 ºF input G1/2”F G1/2”F adapter outlet (pump)
M16,5m DIN 2353 (G3/8”F) M22,5m
DIN 2353
(G1/2”F) main drain
G1/2”F
drain tray
External stainless steal pipe φ 10 mm/ 0.4 inch
Tab. 2.a
UL versions
model UD100*U4** UD200*U4** UD320*U4** UD460*U4** UD600*U4** UA1K0*HM4* max flow rate (l/h; lb/h;Gd)
100 200 320 460 600 950 220 441 705 1014 1323 2095
634 1268 2028 2916 3805 6023 inlet pressure (Mpa,Bar, PSI)
0,3…0,8 Mpa
3…8 Bar
40…100 PSI
temperat. 1T40 ºC / 34T104 ºF input NPT 1/2”F (with adapter G1/2” M - NPT 1/2” F)
adapter outlet (pump)
NPT3/8F NPT1/2F
main drain
NPT 1/2”F (with adapter G1/2” M - NPT 1/2” F)
drain tray
External stainless steal pipe φ 10 mm/ 0.4 inch
Tab. 2.b
2.2 Water circuit installation: checklist
humiFog system name: _____________________________________
Description / notes
 Cabinet level  Distance between cabinet-rack/water distribution system: ≤50 m.  Water supply connection  Water inlet pressure ≥3 bars (0.3 MPa, 40 PSI)  Filters filled with water  Drain connected to the water drain system  drain bypass: TFN8x10 NYLON WHITE hose connected to the water
drain  Pump: oil cap replaced with the cap featuring the vent  Supply water within the limit values See the section on “Supply water
characteristics””
Date: _______________ Signature: _______________________________________
14
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
3. ELECTRICAL CONNECTIONS
Master version
F1 F2 F6
F8
F7
F9
1
J15
4
5
J20
J19
J6
J2
3
2
J3
Fig. 3.a
Slave version
J15
4
1
5
J6
3
2
J3
J2
Fig. 3.b
Legenda:
1 L/N/GR Power supply
Important
make sure that the cable glands
are fitted
do not run the control and signal
cables through this cable gland.
J2 U1 Main humidity/temperature probe
U2 Limit humidity/temperature probe U3 AUX probe (temperature display
only)
J3 U5 Segnale recuperatore di calore per
EC, uscita configurabile sia analogi-
ca che digitale J6 U8 rack temperature probe J15 NO8 Cumulative alarm relay J19 NO24 Pumping unit signal J20 NO27 Pumping unit enable signal 2 PEN/G0A Pumping unit remote enabling
signal
ROAL/G0A Water treatment system control BKUP/G0A Back up cabinet signal ROEN/COM comand for water treatment system ON-OFF/G0A Control signals from external con-
tact type humidistat ON/OFF
RKEN/G0A RACK production enable FLUX/G0A Air flow
3 NC1÷NC6/GOB Slicing solenoid valves step
NO1÷NO6/GOB Drain solenoid valve step NOL Drain solenoid valve line NOV Fan solenoid valve (rack)
4 Field card Field card input for Master Slave
connection 5 Serial Card Serial card input for BMS (Building
Management Systems)
N.B.: feature adequate protection on all activation
outputs to external devices.
15
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
3.1 Power supply
Depending on the model:
UA****D4** voltage 230 V 1~ 50Hz
UA****U4** voltage 230 V 1~ 60Hz
UA1k0*HL4* voltage 400 V 3~ 50Hz
UA1k0*HM4* voltage 460 V 3~ 60Hz
Important: The cables must conform to local standards. Install a power switch outside the humidifier to completely isolate
the mains power supply, with earth fault protection (30 mA).
GR
L
N/W
GR
N/W
L
L
N/W
GR
L
N/W
GR
MASTER
SLAVE
GR
L2
L1
GR
L1
L2L3L3
400V Trifase
230V Monofase
Fig. 3.c
CONNECTIONS
Cabinet master - slave 230V Monophase Powersupply cable L L/F (fase) AWG13 (2,5 mm) N N/W (neutro) AWG13 (2,5 mm) GR GR/PE (terra) AWG13 (2,5 mm)
Cabinet master 400/460V Threephase Powersupply cable L1 L1 (fase 1) AWG13 (2,5 mm) L2 L2 (fase 2) AWG13 (2,5 mm) L3 L3 (fase 3) AWG13 (2,5 mm) GR GR/PE (terra) AWG13 (2,5 mm)
3.2 Remote ON/OFF
Cables • up to 30 m: two-wire cable AWG20/22 electrical specifications of the contact:
voltage-free contact
GR
PEN
GR
PEN
ROAL
ROAL
BKUP
BKUP
ROEN
ROEN
COM
COM
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0A
G0A
G0A
G0A
G0A
G0A
G0B G0B G0B G0B G0B
G0B G0B G0B G0B G0B
21
Fig. 3.d
Key:
1. Pump remote ON/OFF
2. Zone remote ON/OFF
CONNECTIONS
humiFog Master cabinet Remote ON/OFF
PEN (enable pump) NC/NO RKEN (enable master rack) NC/NO G0A COM
humiFog Slave cabinet Remote ON/OFF
RKEN (enable slave rack) NC/NO G0A COM
N.B.: the Master unit is supplied with contacts PEN-G0A and RKEN­G0A jumpered, the Slave unit is supplied with contact RKEN-G0A jumpered
3.3 Control signals from external voltage­free contact (humidistat)
a) ON/OFF (C control)
Cables • up to 30 m: two-wire cables cross-section 0.5 mm2
(AWG20)
• greater than 30 m: shielded cables cross-section 1.5 mm
2
(AWG15) electrical specifications of the contact
voltage-free contact
GR
PEN
GR
PEN
ROAL
ROAL
BKUP
BKUP
ROEN
ROEN
COM
COM
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0A
G0A
G0A
G0A
G0A
G0A
G0B
G0B
1
Fig. 3.e
Contact open: humiFog deactivated Contact closed: humiFog activated
humiFog Master cabinet ON/OFF humidistat thermostat ON/OFF NC/NO GOA COM
b) ON/OFF and limit probe (CH/CT control)
J9
J24
J2
J3
GR
PEN
GR
PEN
ROAL
ROAL
BKUP
BKUP
U
U
U
U
U
U
U
ROEN
ROEN
COM
COM
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0A
G0A
G0A
G0A
G0A
G0A
G0B
G0B
1
2
Fig. 3.f
Key:
1. ON/OFF humidistat thermostat
2. limit humidity/temperature probe
16
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
3.4 Modulating control signal (J2)
The control signal input connections depend on the control algorithm activated.
Cables • up to 30 m: two-wire cables cross-section 0.5 mm2
(AWG20) the signal may come from
• modulating control with external controller
• modulating control with ambient humidity probe
• external controller and limit humidity probe
• ambient humidity probe and limit humidity probe
• modulating control with temperature control
• modulating control with temperature control and limit probe
To set the type of operation, control and signal: “installer menu > type of control (see chap. 9.11 Installer menù).”
N.B.: shielded cables should be used. The cables must not run near the 230 V/208 V power cables nor near the contactor cables: this avoids measurement errors due to electromagnetic disturbance.
a. Modulating control with external controller (P control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA.
SERIAL CARD
J9
J24
J2
J3
J4
J5
FIELD CARD
p
1
U
U
U
U
U
U
U
Fig. 3.g
Key:
1. external controller
Connections:
humiFog cabinet External controller
J2 B1 OUT
GND Reference, shield
b. Modulating control with ambient humidity probe (H control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
FIELD CARD
1
U
U
U
U
U
U
U
Fig. 3.h
Key:
1. humidity sensor
Connections:
humiFog cabinet Ambient humidity probe
J2 B1 OUT H
+Vdc +(G) GND M
c. Modulating control with controller and limit probe (PH/PT control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
J
FIELD CARD
p
1
2
/T
U
U
U
U
U
U
U
Fig. 3.i
Key:
1. limit humidity/temperature probe;
2. external controller.
Connections:
humiFog cabinet External controller Limit humidity
probe
J2 B1 OUT
B2 OUT H/T +Vdc +(G) GND Reference M
d. Modulating control with ambient humidity probe and limit humidity and temperature probe (HH/HT control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
J5
FIELD CARD
p
1
2
/T
U
U
U
U
U
U
U
Fig. 3.j
Key:
1. limit humidity/temperature probe;
2. ambient humidity probe.
Connections:
humiFog cabinet External controller limit humidity probe
J2 B1 OUT H
B2 OUT H/T +Vdc +(G) +(G) GND M M
e. Modulating control with temperature control (T control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
J5
U
U
U
U
U
U
U
FIELD CARD
p
1
Fig. 3.k
Key:
1. ambient temperature probe;
17
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Connections:
humiFog cabinet Ambient temperature probe
J2 B1 OUT T
+Vdc +(G) GND M
f. Modulating control with temperature control using NTC probe (T control)
SERIAL CARD
J9
J24
J2
J3
J4
FIELD CARD
U
U
U
U
U
U
U
Fig. 3.l
Connections:
humiFog cabinet NTC probe
J2 B1 NTC
GND NTC
g. Modulating control with temperature control and limit humidity probe (TH control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
J
FIELD CARD
p
1
U
U
U
U
U
U
U
Fig. 3.m
Key:
1. ambient temperature probe and limit humidity probe;
Connections:
humiFog cabinet Ambient temperature probe + limit humi-
dity probe
J2 B1 OUT T (main)
B2 OUT H (limit) +Vdc +(G) GND M
h. Modulating control with temperature control and limit humidity and temperature probe (TT/TH control)
0 to 1 V; 0 to 10 V; 2 to 10 V; 0 to 20 mA; 4 to 20 mA
SERIAL CARD
J9
J24
J2
J3
J4
J5
FIELD CARD
p
1
2
H/T
U
U
U
U
U
U
U
Fig. 3.n
Key:
1. limit humidity/temperature probe;
2. ambient temperature probe.
Connections:
humiFog cabinet Ambient temperature
probe
limit probe
J2 B1 OUT T
B2 OUT T/H +Vdc +(G) +(G) GND M M
3.5 Heat recovery signal
J3 inlet U5 terminal, analogue or digital configurable signal associated with the position of the recovery damper
Fig. 3.o
3.6 Solenoid valve connection for distribution system
For the management of the distribution system, the cabinet controls four types of solenoid valves:
normally closed “NC” for capacity-control of the manifolds.
normally open “NO” for draining the manifolds.
normally open vent valves.
normally open line drain valves.
Recommended connection cables: two-wire plus earth AWG 13 (1.5mm²), maximum length 100 m.
the following table contains the bipolar cable sections suggested in relation to the number of solenoid valves per step for the NC and NO valves
1 EV per step fino a 4 EV per step Fino a 7 EV per step
Sez.cavo AWG 18 AWG14 AWG10
N.B. in cases up to 4 solenoid valves and up to 7 solenoid valves for a
single step it is necessary to provide the accessories box, code UAKDER6000.
N.B. For electrical distances greater than 30 m contact Carel.
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0B G0B G0B G0B G0B G0B
G0B G0B G0B G0B G0B G0B
NC1
NC1
FUSE
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NOL
NOV
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NOL
NOV
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
1 2 3 4 5 6 7 8 91011 12 1413
Fig. 3.p
18
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Rif. Cabinet
terminal block
Solenoid valve connec­tor
Description
Max. no. of solenoid valves per step. Master up to 460
Max. no. of solenoid valves per step. 600/1k0
Max. no. of solenoid valves per step. Slave
1 NC1 – G0B 1 -2
Capacity-control sol.valves 1st step
674
2 NC2 – G0B 1 -2
Capacity-control sol. valves 2nd step
444
3 NC3 – G0B 1 -2
Capacity-control sol. valves 3rd step
444
4 NC4 – G0B 1 -2
Capacity-control sol. valves 4th step
442
5 NC5 – G0B 1 -2
Capacity-control sol. valves 5th step
222
6 NC6 – G0B 1 -2
Capacity-control sol. valves 6th step
222
7 NO1 – G0B 1 -2
Drain solenoid valves 1st step
674
8 NO2 – G0B 1 -2
Drain solenoid valves 2nd step
444
9 NO3 – G0B 1 -2
Drain solenoid valves 3rd step
444
10 NO4 – G0B 1 -2
Drain solenoid valves 4th step
442
11 NO5 – G0B 1 -2
Drain solenoid valves 5th step
222
12 NO6 – G0B 1 -2
Drain solenoid valves 6th step
222
13 NOL – G0B 1 -2 Line drain sole-
noid valves
222
14 NOV – G0B 1 -2 Vent drain sole-
noid valves
11
Tab. 3.c
N.B.: using the solenoid valves supplied by Carel SpA, each individual
cabinet can power up to 22 solenoid valves, divided as follows:
10 NC capacity-control solenoid valves
10 NO manifold drain solenoid valves.
1 line drain solenoid valve.
1 vent drain solenoid valve.
Cabinet master 600 l/h and 1000 l/h
15 slicing solenoid valves NC
15 collector drain solenoid valves NO.
1 line drain solenoid valve.
1 ventilation solenoid valve
3.7 Water treatment unit contact
Cables • up to 30 m: two-wire cable
cross-section 0.5 mm
2
(AWG15) Electrical characteristics allowed by the contact:
• power 50 VA;
• voltage 24 V;
• current 0.5A resistive/inductive Status of the contact accor­ding to master statusr
Master OFF or in standby closed contact Master ON open contact
Tab. 3.d
GR
PEN
GR
PEN
ROAL
ROAL
BKUP
BKUP
ROEN
ROEN
COM
COM
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0A
G0A
G0A
G0A
G0A
G0A
G0B G0B G0B G0B G0B G0B
G0B G0B G0B G0B G0B G0B
NC1
NC1
FUSE
1
Fig. 3.q
Legenda:
1. Pump state contact (can be used for allowing a water treatment plant)
3.8 Cumulative alarm relay (J15)
Activated when one or more alarms is detected via a contact/output that can be transferred to a supervisory system.
Cable two-wire AWG 15/20 Electrical specifications of the relay
power 500 VA; voltage 250 V; current 2 A resistive/
inductive Status and operation of the relay:
contact open no alarm active
contact closed active alarm/alarms
Tab. 3.e
J15
J16
J17 J18
Fig. 3.r
Connections
humiFog cabinet terminal J15 NO8 normally open
C8 COM
3.9 Pump state contact
J19 inlet NO24 terminal, configurable digital and logical outlet that shows the pump status: closed contact “open”, free contact “closed”.
Fig. 3.s
3.10 Pump life signal
The J20 inlet NO27 terminal identifies the life signal of the pumping station. Signal used by humiFog for back-up or pump rotation.
Fig. 3.t
19
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
3.11 Alarm inputs from external devices
Cable two-wire AWG 15/20 Electrical specifications of the relay
voltage-free contact
Status and operation of the relay:
contact open no alarm active contact closed active alarm/alarms
GR
PEN
GR
PEN
ROAL
ROAL
BKUP
BKUP
ROEN
ROEN
COM
COM
ONOF
ONOF
RKEN
RKEN
FLUX
FLUX
G0B
G0B
G0A
G0A
G0A
G0A
G0A
G0A
G0B G0B G0B G0B G0B G
0
G0B G0B G0B G0B G0B G
0
1 2
Fig. 3.u
Key:
1. alarm input from water treatment system;
2. alarm input from AHU pressure sensor (flow switch).
N.B.: the unit is supplied with contacts ROAL-G0A and FLUX-G0A jumpered.
3.12 Backup/rotation (redundancy)
The backup/rotation function on two master cabinets allows two pumping units to be used with one single zone and consequently one rack distribution system. The backup function guarantees continuous production when the cabinet that is currently operating shuts down due to an alarm. The rotation function distributes the number of operating hours equally between the two cabinets.
Electrical connections:
Connect the two pumping units according to the following diagram. To complete the electrical connections in backup & rotation mode, a special junction box with relays (P/N UAKDERBK00) must be installed in the system.
J20
J19
ID15H
ID15
IDC15
ID16
ID16H
C25
NO25
C25
NO26
NO27
NO28
NO29
U6U7U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J7
J8
J6
PEN PEN
ROAL ROAL
BKUP BKUP
ONOF ONOF
RKEN RKEN
FLUX FLUX
ROEN ROEN
COM COM
GR
G0A G0A G0A
G0A G0A G0A
G0B G0B G0B
G0B G0B G0B
GR
J20
J19
ID15H
ID15
IDC15
ID16
ID16H
C25
NO25
C25
NO26
NO27
NO28
NO29
U6U7U8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J7
J8
J6
PEN PEN
ROAL ROAL
BKUP BKUP
ONOF ONOF
RKEN RKEN
FLUX FLUX
ROEN ROEN
COM COM
GR
G0A G0A G0A
G0A G0A G0A
G0B G0B G0B
G0B G0B G0B
GR
G0A
BKUP
Primary Secondary
Backup box UAKDERBK00
Fig. 3.v
Software configuration: access B. Installer menu > b. Zone settings > c. Special functions.
1. On screen Bbc08, enable the backup function by selecting the
priority to attribute to the cabinet when starting. One cabinet must be set as the “Primary cabinet”, while the other must be set as the “Secondary cabinet”. This configuration is needed to define the priority of the cabinet that will attempt to start first when both units are powered on together. Aside from this, there is no functional difference between the two units.
2. If deciding to enable rotation between the cabinets, set the “Rotation”
parameter on screen Bbc08 to “YES”, and select the number of pump operating hours before activating the rotation request (default 8 h). .
A system configured in this way will therefore comprise one cabinet that is operating and one in standby. The cabinet in standby will display “Off from backup” on the main screen if rotation is not enabled, or “Off from rotation” if awaiting the time set for rotation.
Important:
The input signals (external control signal, probes, etc.) must be
connected to both cabinets.
The operating parameters for the two master units (rack parameters,
number of steps, branch flow-rates, etc.) must be configured in the same way.
A “T” connector must be installed in the water circuit to connect the
two pump outlets to the one rack supplied by both units. A non­return valve also needs to be installed on the outlet of each pump (P/N UAKCHV****) upstream of the “T” and the main line drain valve (UAKCD0000*).
If rotation is not enabled, the cabinet that requested changeover due
to an alarm with shutdown can only be reactivated following to an alarm with shutdown on the cabinet that replaced it, even if the alarm condition that caused the unit changeover has been resolved.
When rotation is enabled, in the event of unit changeover due to an
alarm, the rotation hour counters are reset and the next request is ignored.
The two pumping units must belong to the same zone and use the
same rack. In multizone configurations, the backup of the master cabinet (pumping unit that supplies the water line for all the zones) can be implemented, but it will not be possible to have a backup on the slave cabinets.
For further information and details regarding water circuit and electrical installation of humiFog in Backup & Rotation mode, see the official document +050004015 +LEAF INSTAL. BACKUP & ROTATION HUMIFOG (UAKDERBK00) REL. 1.0 ITA/ENG A3 F/R. A copy of this document will always be included with part number UAKDERBK00 (backup junction box).
3.13 Expansion mode/remote actuator
Expansion
The Slave (UA***S****) cabinets can be configured on the Bbc01 screen as Expansion/Remote actuators.
This mode transforms the cabinet in an I/O expansion for another Humifog generic cabinet (pumping station or slave) in order to:
Provide a tool to simplify the wiring if the rack is too far from the
pumping station (Remote Actuator)
Allow the slave cabinet to use a rack with 6 NC valves on step 1 and 4
NC valves on step 4.
20
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Remote rack actuator
This mode allows you to control the solenoid valves of the rack in the area associated with the pumping station via one or two “remote area” cabinets controlled in serial sequence via the J23 port of pCO5+. This configuration is particularly useful if the rack is located away from the pumping station, since it allows to bring the control signal via the only serial cable in the rack area, reducing the number and length of the cables of the solenoid valves between the rack and the device that physically controls it (the remote area cabinet).
To enable the function, proceed as follows:
Electrical connections:
Connect the expansion (or two expansions) serially in port J23 of the
pCO5+ as follows:
FBJ/J23
BMS2
BMS2
pCOe
Fig. 3.w
Connect the control signals used for the cabinet configured as “Remote
expansion/Actuator 1”
Connect the solenoid valves to the remote area cabinet that controls
them. If two cabinets are used, distribute them evenly. For example, in the case of the first step with 6 collectors, connect three solenoid valves to the first expansion cabinet and three solenoid valves to the second cabinet.
Software configuration:
On the pumping station, enable the use of the remote actuator on
the Bbc09 screen: the software automatically establishes the number of required actuators (1 and 2) based on the number of collectors
present, and alerts the user via a dedicated pop-up window Configure the first slave as “Expansion/Remote actuator 1” and the second one (only at request) as “Expansion/Remote actuator 2”
Note: if you are using this mode, the probe readings of the main control (U1), limit (U2), auxiliary (U3), heat recovery signal (U5), rack temperature (U8) and the ventilation solenoid valve are transferred to the remote area cabinet configured as “Expansion/Remote actuator 1”.
Remote area expansion
The software installed on the remote area cabinet, based on the number of set collectors, automatically determines whether it is necessary to add a second cabinet, used as an expansion for the proper management of the solenoid valves. The system is pre-configured based on the number of set collectors. The following are necessary to enable the feature: Electrical connections:
Connect the J23 port of the remote area cabinet that requires
expansion to the BMS2 port of the cabinet configured as expansion, as follows:
Connect the adjustment probes and the ventilation valve (if present)
to the remote area cabinet and distribute the solenoid valves between the two cabinets. For example, in case of a step with 6 solenoid valves, connect three to the first cabinet and three to the second cabinet.
Software configuration:
The remote area cabinet, based on the number of set collectors,
establishes if it is required to expand and alerts the user via a dedicated pop-up window
Configure the slave used for the expansion as “Expansion/Remote
actuator 1”
3.14 Master-slave connection
The multi-zone master-slave configuration is serial and done through optically-isolated integrated Field-bus 485 present in the humiFog unit.
Cable section
Use twisted and shielded two wire cables, AWG20/22 with clamp sections of 2 mm min 0.2 – max 2.5
Connections:
Fieldbus card humiFog master BMS2 humiFog slave ++
-­GND GND
+
-
GND
+
-
GND
FieldBus RS485
Fig. 3.x
Note: if the optional card is in the last position on the supervisor serial line and the line is longer than 100 m, connect the 120 Ω - 1/4 W line terminal resistors to the pins, as shown in the following figure.
3.15 Supervisor network
J5
J4
J3J2J1
serial card
field card
service card
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG0Y1Y2Y3Y4
B4
BC4B5BC5
B1B2B3
J24
+V term
GND
+5V
ref
GND
+VDC
G
G0
NO8
C7
C4
C1
C8
NO7
NO4
NO1
NC8
C7
NO5
NO2
NO3
C4
C1
Rx-/Tx-
Rx+/Tx+
GND
J9 J10
J11
J12 J13 J14 J15
input: 24 V / V ; 50 to 60 Hz
max. power: 40 VA / 15 W
J3J
2
J1
field card
service car
d
D8D
C
1
4
4
5
1
J24
+
V
t
er
m
N
D
+
5
Vr
ef
N
D
+VD
C
7
7
472
x-
/
Tx-
Rx+
/
Tx
+
N
D
J9
J10J11J12
J13J14J15
input: 24 V / V ; 50 to 60 Hz
max. power: 40 VA / 15
W
DDDDD
D
Fig. 3.y
Optional CAREL cards
network/card protocol supported
PCOS004850 RS485 (standard) CAREL, Modbus® PCO100MDM0 RS232 (external modem) CAREL for remote connections
PCO1000WB0 Ethernet™
TCP/IP SNMP v1 &v2c BACnet™ Ethernet™ ISO8802-2/8802-3 BACnet/IP
PCO1000BA0 Ethernet™ (Modbus®) BACnet™ MS/TP
Important: Follow the instructions shown on the optional cards
for the technical specifications, connections and expansion boards.
Default: CAREL supervisor protocol.
21
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
4.2 Pumping unit with constant pressure control
The humiFog controller manages the water pressure generated to ensure it remains at a constant level, typically 70 bars.
This configuration is used in the following applications:
humidification and/or adiabatic cooling (direct) in an AHU (the flow
control configuration is recommended);
humidification and indirect adiabatic cooling in an AHU fitted with
heat recovery unit (the two distribution systems can atomise water at the same time);
humidification and/or adiabatic cooling (direct) in an industrial
environment;
humidification and/or adiabatic cooling (direct) in multiple zones,
whether AHUs, AHUs fitted with heat recovery units, industrial environments, or any combination of these.
Note that in the case of humidification and/or cooling adiabatic directly into rooms, constant pressure control is preferred over flow control: as the droplets are atomised directly into the environment, to minimise the space required for evaporation, the smallest possible diameter should be achieved and therefore the water must be atomised at maximum pressure. This is represented by constant pressure control, which maintains the pressure at 70 bars.
humiFog is fitted with an inverter to control the speed of the pump and maintain the pressure at the rated value set by parameter, typically 70 bars.
The humiFog system will be made up of a pumping unit (master) that also controls its own zone, as well as a series of zone electrical panels (slaves) corresponding to the number of remaining zones. Note that for humidification and indirect adiabatic cooling in an AHU fitted with heat recovery unit (the two distribution systems may atomise the water at the same time) a zone panel (slave) will be required.
The water distribution system/systems have nozzles organised into groups, called steps, which in general each have different capacities. Based on the flow-rate of water to be atomised in one or more zones, the humiFog system will activate the required steps until the nozzles atomise the required quantity of water. Each zone can have up to 6 modulation steps.
The groups of nozzles are normally configured when selecting the humiFog system, and the procedure is clearly described in the documents supplied with the water distribution system (rack or room distribution and atomisation system)
Constant pressure control rationalises operation of the humiFog pumping unit as, despite the lower precision, it can treat a number of zones at the same time without installing a pumping unit for each AHU or industrial environment.
4. PUMPING UNITS
4.1 Pumping unit with flow control configuration
humiFog controls the humidification and/or cooling capacity by continuously controlling the atomised water flow-rate across a wide range of modulation.
This configuration is used in the following applications:
humidification and/or adiabatic cooling (direct) in an AHU;
humidification and indirect adiabatic cooling in an AHU with heat
recovery unit (one atomisation system at a time atomises the water). In this case, a zone electrical panel will be required, see the next chapters for further information.
humiFog is fitted with an inverter to continuously and precisely control the speed of the pump and, consequently, the flow-rate.
The outlet pressure is kept within the optimum water atomisation limits by the range of modulation of the pump speed and control of the number of nozzles that atomise the water.
In detail, the nozzles must be supplied at a pressure in the range from 25 to 70 bars, to ensure that the droplets generated have an average equivalent diameter of 10-15 µm.
Based on the flow-rate of water to be atomised, humiFog will activate the number of nozzles that ensures the pressure is within the range indicated above.
It is clear that if the required flow-rate is low, just a few nozzles will be needed to atomise the water; if the request increases, the increase in flow-rate will cause an increase in pressure that, if it exceeds 70 bars, will activate other atomising nozzles, consequently decreasing the pressure and returning it within the range of optimum values. Similarly, if the humidification request decreases, the flow-rate and thus the pressure will decrease and, if the latter falls below 25 bars, some nozzles will be closed so that the pressure returns within the optimum atomisation range. This is possible because the nozzles are assembled into groups of up to four, with different capacities; when suitably activated, these guarantee continuous modulation of the flow-rate across a wide range, nominally from 14 to 100% of the maximum flow-rate, with a pressure from 25 to 70 bars.
The groups of nozzles are normally configured when selecting the humiFog system, and the procedure is clearly described in the documents supplied with the water distribution system (rack).
The pumping unit in the flow control configuration can only be used for single-zone applications: one pumping unit supplies just one zone at a time. Multizone configurations are not possible.
The flow control configuration guarantees maximum humidification and adiabatic cooling precision as capacity is controlled continuously and across a wide range.
22
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
5. DISTRIBUTION SYSTEM
This paragraph briefly describes the distribution and atomisation systems for AHUs (rack and droplet separator) and for rooms. These are described in detail in the “humiFog – distribution systems” manual.
5.1 Air handling unit: distribution, atomisation system and droplet separator
The rack is supplied made-to-measure based on the AHU/duct and is made up of various vertical manifolds with atomisation nozzles, each with activation and drain solenoid valves. Each rack is also fitted with a main drain solenoid valve installed at the lowest point of the piping that connects the rack to the pumping unit. In addition, it is fitted with a vent solenoid valve on the horizontal manifold so as to completely empty the pipelines. The manifolds house the required number of atomising stainless steel nozzles located in specific positions, calculated during the system configuration phase and described in the documents supplied with the rack.
The droplet separator has the purpose of trapping the droplets of water that are not completely evaporated, so as to prevent objects located downstream from getting wet. The droplet separator is supplied in standard modules that can be assembled on a support structure to cover the cross-section of the AHU. The structure is always in stainless steel, and guarantees fast and effective draining of the water trapped by the droplet separator. The modules are available with glass wool or stainless steel filters, the latter required for hygiene-certified installations, such as VDI6022, UNI8884, etc.
The width and height of the rack and the droplet separator vary with approximately 152 mm within the following limits:
width: 508…2,788 mm;
height: 516…279 mm.
If the droplet separator does not exactly cover the cross-section of the AHU, the free spaces must be sealed to prevent air from bypassing the droplet separator.
Flexible or stainless steel hoses are supplied for connecting the pumping unit to the rack.
Note that a droplet collector tank with drain connection must also be fitted, containing the rack, droplet evaporation chamber and droplet separator. This tank is not supplied by CAREL.
5.2 Direct humidification into the room: distribution and atomisation system
This system consists of
hoses and/or stainless steel pipes for the distribution of pressurised
water;
capacity-control solenoid valves to shut off the branches of the system
that don’t need to atomise water (on/off operation, N.C.);
drain solenoid valves to empty the installation and prevent stagnation
of water (on/off operation, N.O., opening pressure 13 bars);
main drain solenoid valve installed on the lowest point of the piping
that connects the rack to the pumping unit, so as to completely empty the system and avoid stagnation of water. The solenoid drain valves are also used to quickly discharge water pressure when the line stops atomising, avoiding dripping. In addition, the solenoid drain valves are used for the automatic periodical washing function managed by humiFog;
stainless steel manifolds (pipes with holes) with atomising nozzles;
blower units: compact units featuring manifolds with atomising
nozzles, on-off solenoid and drain valve, plus a fan that creates a stream of air that carries the droplets and ensures they evaporate completely before falling in the environment.
The distribution and atomisation system can have up to 6 capacity modulation steps, where, obviously, each step can have a series of branches with pipes, manifolds and/or blower units.
Special attention must be paid to the position of the nozzles and the blower units inside the environment: observe the installation limits (minimum installation height and minimum horizontal distance from objects/machinery/people that must not be wetted), as shown in the “humiFog multizone: distribution system” manual.
23
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
6. APPLICATIONS
humiFog for AHU/ducts is suitable for all applications in which the air can be humidified and/or cooled adiabatically, atomising demineralised water. Below are some possible applications of humiFog:
office buildings
hotels and call centers
printing and paper industries
cleanrooms
libraries and museums
textiles industry
food industry
direct/indirect adiabatic cooling
timber industry
other industrial applications.
The possibility of using an atomising rack for indirect adiabatic cooling is especially interesting: the air to be discharged is cooled adiabatically (bringing it to saturation) and is then used to cool the fresh outside air using an air-air heat exchanger, as shown in the following figure.
1
HE
7
2
3
4
5
6
Fig. 6.a
Key:
1. recirculated air;
2. exhaust air;
3. saturated and cooled air;
4. outside air inlet;
5. heated exhaust air;
6. cooled outside air;
7. fresh air.
6.1 Main advantages of humiFog multizone
The main characteristic of humiFog for AHUs is compliance with the European standards on air hygiene, as certified by the Institut für Lufthygiene in Berlin, which has declared it as compliant with the following standards:
Standard climatisation Hospitals
VDI 6022, page 1 (7/2011) 9 DIN 1946, part 4 (12/2008) 9 VDI 3803 (02/2010) 9 ONORM H 6020 (09/2003) 9* ONORM H 6021 (09/2003) 9 SWKI 99-3 (05/2003) 9 SWKI VA104-01 (04/2006) 9 DIN EN 13779 (09/2007) 9
Tab. 6.a
*: In accordance with H6020 (02/07), chapter 6.13.2 the use of steam humidifiers or equivalent humidification systems is required in Austria.
Please note:
VDI6022/2006: “Hygiene requirements for ventilation and air-
conditioning systems and units“
DIN EN 13779: “Ventilation for non–residential buildings – Performance
requirements for ventilation and room conditioning systems”
DIN1946 - Ventilation and air conditioning - part 4: Ventilation in
hospitals
Further advantages of the humiFog system include:
extremely low electricity consumption: around 4 Watts for each litre/
hour of humidification capacity;
high maximum capacity: 600 kg/h (customised versions are available
with capacities up to 5000 kg/h);
high precision, thanks to models with continuous modulation from
14% to 100% of maximum capacity;
complete distribution rack, supplied already assembled and tested;
extremely fine atomisation with consequently very little space required
for evaporation, due to high water pressure (25 to 75 bars);
optimum humidification and cooling effect in the AHU thanks to
custom racks made to measure based on the cross-section of the AHU;
very low maintenance requirements
automatic washing and emptying cycles to avoid stagnation of water
no dripping;
silent nozzles
modularity: one pumping unit can supply up to 6 zones
connectivity: humiFog can be connected to external systems, for
example BMS, using the MODBUS, TCP/IP protocols etc. (see paragraph
3.10).
24
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
7. CONTROL
The electronic controller fitted in the humiFog features different control algorithms, which can be selected from the installer menu.
• HH control:
modulates the capacity (water flow-rate) using two humidity probes, one control probe normally installed in the AHU in the return air, and one limit probe, usually installed downstream of the droplet separator.
• HT control:
modulates the capacity (water flow-rate) with two probes, one humidity control probe and one limit temperature probe. This configuration is recommended for systems in which a certainly humidity level is required without however excessively cooling the air.
• H control:
like the HH algorithm but without the limit humidity probe;
Below is the diagram of operation using humidity control probes
100%
Set point
1
3
4
2
6
5
Fig. 7.a
The following chart shows the control probes with humidity control with differential P+I
100%
Set point
1
3
4
2
6
5
7
Fig. 7.b
Key:
1. production
2. humidity control probe
3. maximum production
4. minimum production
5. proportional band
6. hysteresis (10% of “5”)
7. differenziale
• TH control:
modulates the capacity (water flow-rate) with a temperature probe normally installed in the AHU in the return air, and a limit humidity probe, usually installed downstream of the droplet separator. In room applications, both probes are installed so that the temperature and relative humidity represent the average ambient values (for example, not near windows or the nozzles where the cooling and humidification effect do not correspond to the averages in the room)
• TT control:
modulates the capacity (water flow-rate) with a temperature control probe and a limit temperature probe. This configuration is recommended for adiabatic cooling systems in rooms where the control probe is usually installed in the centre of the room and the limit probe at another “critical” point where the temperature must absolutely not fall below a set limit value.
• T control:
like the TH algorithm, but without the limit humidity probe;
Below is the diagram of operation using temperature control probes
Set point
C°/F°0
1
3
4
2
5
6
Fig. 7.c
Key:
1. production
2. probe control temperature
3. maximum production
4. minimum production
5. proportional band
6. hysteresis (10% of “5”)
• PH/PT control:
capacity is modulated proportionally to an external control signal and is limited based on the value measured by the limit temperature or humidity probe. This is the typical configuration used in humiFog installations connected to a Building Management System that generates a control signal;
• P control:
like the PH/PT algorithm but without the limit humidity probe;
Below is the diagram of operation with proportional control.
100%
max
1
2
3
4
5% 5%
Fig. 7.d
Key:
1. production
2. external request
3. maximum production
4. minimum production
25
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
• CH/CT control:
operation in on/off mode, based on a voltage-free external contact (for example, a humidistat). The capacity will thus be either the maximum set or nothing, depending on the status of the external contact, and is limited based on the value measured by the limit probe.
• C control:
like the CH/CT algorithm but without the limit probe;
The HH and TH algorithms are the most commonly-used, and recommended for humiFog installations.
The limit humidity probe described above is usually set to high values, e.g. 80% rH, so as to limit the maximum moisture in the air introduced into the duct and into the room. This is especially recommended in installations where air flow-rate and operating, temperature and humidity conditions, may change over time and, consequently an additional safety system is required to prevent the humidifier from over-humidifying the air and, in the worse case scenario, condensing in the ducts downstream.
Below are the two diagrams of operation with humidity or temperature probes
100%
Set point
1
3
4
2
6
5
Fig. 7.e
Key:
1. production
2. limit probe
3. maximum production
4. minimum production
5. proportional band
6. hysteresis (10% of the set point)
N.B.: for convenience, the diagrams show continuous modulation of the flow-rate while, depending on the model, control may be
continuous or in steps.
7.2 Evaporative Cooling
If optiMist is used as an application dedicated to evaporative cooling, the possible controls are:
TT Control
TH Control
TF Control
T Control
PH/PT/PF Control
P Control
C Control
CH/CT/CF Control
IMPORTANT: All of these controls require a consent signal that lets the humidifier know when it can operate. This indication corresponds with the activation of the recovery unit in the Air Treatment Unit (ATU); this information can be sent to the humidifier through:
a modulating 0-10V signal (corresponding to the opening of the
renewal air locks) or
a digital contact or
a digital variable via supervision (DIG 63).
A delay in the humidifier activation can be set, starting from the activation signal from the recovery unit previously described.
T CONTROL
This type of control consists of a Proportional+Integral type control of the temperature detected by a probe located in the return air, downstream from the exchanger. The proportional action will allow for the control of the flow-rate as a function of the distance between the temperature detected and the setpoint. The integral action, on the other hand, will act on the reaction speed of the system.t. L’azione integrale, invece, agirà sulla velocità di reazione del sistema.
Grafico 1
Temp.
Fatt.P
SET
SET
+ ∆
Band
Hyst=10%Band
Fig. 7.f
As seen in the figure, increasing factor P (dashed red line) reduces sensibility to temperature variations, resulting in a decreased reduction request in correspondence to the same temperature variation. The integral contribution, on the other hand, reduces the request to a greater extent the longer the deviation from the control temperature setpoint remains.
• controllo TH:
This type of control is used to modulate the capacity (water flow-rate) with a temperature probe, installed in the return air, downstream from exchanger, an a limit humidity probe, usually installed downstream from the droplet separator. In order to enable this configuration, a droplet separator is NECESSARY, otherwise there is a risk that the probe could get wet, thus constantly detecting humidity values close to the saturation point. The humidity probe will further limit the maximum request.
TT CONTROL
This type of control is used to modulate the capacity (water flow-rate) with a temperature control probe and a temperature limit probe. The control probe is usually installed in the centre of the room and the limit probe in another “critical” point where the temperature must absolutely not be lower than a settable limit value.
TF CONTROL (T + air flow/flow-rate limit)
This type of control is used to modulate the capacity (water flow-rate) with a temperature control probe and an air flow modulator, which can correspond to:
the modulating opening signal of the recirculation air lock;
the modulating signal from the fan
In this case, the limit signal will function as:
a temperature limit signal, in the event of a modulating signal from
the fan
a humidity limit signal, in the event of a air lock opening modulating
signal.
PH/PT/PF CONTROL
The modulation of the capacity is proportional to an external control signal and limited based on the measured value of the temperature, humidity or flow limit signal. This is the typical configuration when the control is entrusted to a Building Management System that generates a control signal.
26
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
P Control
This control is like the PH control, but without humidity limit probe. The following is a graphic with proportional control.
100%
max
1
2
3
4
5% 5%
Fig. 7.g
Key:
1. production
2. external request
3. maximum production
4. minimum production
CH/CT/CF control
This control mode corresponds to the ON/OFF operation, from a non­powered external contact (for example, a humidistat). The capacity will therefore be the maximum set or nothing (no modulation) according to the status of the external contact and limited based on the limit signal. See sections TT/TH/TF for more information regarding limit signals.
C control
This control corresponds to the ON/OFF operation mode without any limit probe. The request directly follows only the control contact.
Note: Whenever the activation signal from the recovery unit is a digital signal, the control contact will NOT be the same signal; they will be two distinct signals.
Limit probe
In the following graphics, the first represents the limitation of the maximum production with a temperature limit probe or an activation signal from the IEC ventilator. The second graphic, on the other hand, represents the case in which the limit probe is a humidity probe or an opening signal from the recirculation air lock.
H=10%Band
Band
SET °C/°F
% Fan
Y
Fig. 7.h
H=10%Band
Band
SET %RH or
% Opening
Y
Fig. 7.i
27
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
8. SINGLE ZONE AND MULTIZONE CONFIGURATION
The humiFog system can be used in the following configurations:
8.1 Single zone
For humidification and/or cooling applications in AHUs or industrial environments. The pumping unit has just one distribution system, a rack in the case of AHUs or a room distribution system with simple manifolds and nozzles or blower units. The humiFog control system (single zone version UAxxxxxxxx) controls both the pumping unit and the connected distribution system. In particular, it receives signals from the probes and/ or the external control system, calculates the required humidification/ cooling capacity, starts the pump to pressurise the water and manages the solenoid valves in the distribution system. In addition, it manages the filling, wash and drain cycles.
Single zone application in AHU
As can be seen in the figure, humiFog is a complete system for humidification/cooling in AHUs. humiFog can be set for:
- capacity/flow-rate control: As described in detail in the paragraph “humiFog with flow control”, the humiFog controller managers the humidification and/or cooling capacity by controlling the water flow-rate atomised continuously across a wide range of modulation. The outlet pressure is kept within the optimum water atomisation limits by the range of modulation of the pump speed and control of the number of nozzles that atomise the water. For example, if low capacity is required, only the first group of nozzles is activated and the pump speed will be controlled to ensure the required capacity (Fig. 8.a point 1). If the request increases, the pump speed will increase and, as a consequence, the flow-rate and outlet pressure will increase. If the pressure exceeds the maximum limit (75 bars, settable) humiFog will activate a further group of nozzles (max 4 groups), Fig. 8.a point 2, so that, for the same flow-rate, the operating pressure will drop and fall within the limits (25-75 bars, settable). If the request increases further, the pump will increase the flow-rate and the pressure until activating a further, third, group of nozzles (Fig. 8.a point 3). The process is repeated until the maximum flow-rate is reached, corresponding to all the groups of nozzles being active and the pump operating at the maximum rack flow-rate (Fig. 8.a point 4). Similarly, the system will behave in reverse if the request decreases, reducing the speed and consequently the flow-rate of the pump and deactivating the groups of nozzles one after the other. The groups of nozzles on the rack are configured automatically during humiFog system selection procedure using the “humiFog excel tool” and is described in detail in the documents supplied with the water distribution system (rack). The flow control configuration guarantees maximum precision of humidification and adiabatic cooling as capacity is controlled continuously and across a wide range.
- constant pressure control: As better described in the paragraph “humiFog with constant pressure”, humiFog is fitted with an inverter to control the speed of the pump, so as to maintain the pressure at the rated value set by parameter, typically 70 bars.
bar
20
bar
20
80 70
50
30
10
0
0
20 40 60 80 10 0 120 14 0 16 0 180
bar
kg/h
60
40
20
38%25%
58%38%25%17%
17%
25%17%
100%
2
3
4
80 70
50
30
10
0
0
20 40 60 80 10 0 120 14 0 16 0 180
bar
kg/h
60
40
20
80 70
50
30
10
0
0
20 40 60 80 10 0 120 14 0 16 0 180
kg/h
60
40
80 70
50
30
10
0
0
20 40 60 80 10 0 120 14 0 16 0 180
kg/h
60
40
17%
1
Fig. 8.a
The water distribution system/systems have nozzles organised into groups, called steps, which in general each have different capacities. Based on the flow-rate of water to be atomised in one or more zones, the humiFog system will activate the best combinations of steps until the nozzles atomise the required quantity of water. For example, if the system has three steps with the following capacities: step 1 - 30kg/h, step 2 - 30kg/h; step 3 - 20kg/h, and the request is 30 kg/h, then step 1 is activated, if the request is 50 kg/h then step 1 and step 3 are activated, while if the request is 60 kg/h then step 1 and step 2 will be activated. In AHU applications, it is useful to suitably distribute the capacity of the steps so as to allow good resolution of capacity modulation. For example, a humiFog with a 180 kg/h rack, using 4 modulation steps and 4 kg/h nozzles, may have steps with the following capacities: step 1 96kg/h step 2 48kg/h step 3 24kg/h step 4 12kg/h Note that the resolution is 12/180=6.6%, therefore very good, with just 4 modulation steps! The technique involves assigning around half of the capacity to one step, half of this to the next step, half of the latter to the following step and so on, according to the following formula:
S=
M
t2
T-1
2N-1
With: S= capacity of step T M= rack capacity T= index of the step, 1 to N N= step number
N.B.: the maximum flow-rate of one step is 120 l/h.
28
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Obviously, the capacity calculated above should be rounded off based on the capacity of the nozzles (in this example, 4 kg/h), the number of nozzle manifolds that can be installed, etc. Each zone may have up to 6 modulation steps.
The groups of nozzles are normally configured when selecting the humiFog system, and the procedure is clearly described in the documents supplied with the water distribution system (rack or room distribution and atomisation system).
Single AHU application
1
2
MASTER CABINET
3 4
5
6 7
Fig. 8.b
Key:
1. water from REVERSE OSMOSIS system;
2. atomising nozzles;
3. vent valve;
4. water fill valve;
5. water drain;
6. main drain valves;
7. high pressure stainless steel or rubber hoses.
Single zone room applications
As can be seen in the figure, humiFog is a complete system for humidification directly into rooms. As better described in the paragraph on “humiFog with constant pressure”, humiFog features an inverter to control the speed of the pump, so as to maintain the pressure at the rated value set by parameter, typically 70 bars.
Note that in the case of humidification and/or cooling adiabatic directly into rooms, constant pressure control is preferred over flow control: as the droplets are atomised directly into the environment, to minimise the space required for evaporation, the smallest possible diameter should be achieved and therefore the water must be atomised at maximum pressure. This is represented by constant pressure control, which maintains the pressure at 70 bars.
The water distribution system/systems have nozzles organised into groups, called steps, which in general each have different capacities. For simple installation and operation, however it is recommended to use steps of the same capacity. For example, a 100 kg/h system may have two 50 kg/h steps, where necessary made up of two or more lines with nozzles/blower units. Based on the flow-rate of water to be atomised, the humiFog system will activate the steps required for the nozzles to atomise the necessary quantity of water. The zones can have up to 6 modulation steps. humiFog also manages rotation of the lines, emptying, washing etc, better described in the following paragraphs.
The groups of nozzles are normally configured when selecting and sizing the humiFog system.
Single room application
1
2
MASTER CABINET
3
4
5
6
7
8 9
Fig. 8.c
Key:
1. water from REVERSE OSMOSIS system;
2. air inlet;
3. drain valves;
4. ambient probe;
5. fill valves;
6. blower;
7. main drain valves;
8. high pressure stainless steel or rubber hoses.
8.2 Multizone application in AHU or room
For standard humidification and/or cooling applications in AHUs or industrial environments. The humiFog controller manages the water pressure generated so as to keep it at a constant level, typically 70 bars. As illustrated in the following figure, the pumping unit has a distribution system, a rack in the case of AHUs or a room distribution system with simple manifolds and nozzles or blower units. The humiFog control system (multizone zone version UAxxxxxxxx) controls both the pumping unit and the connected distribution system. All the other zones, whether an AHU or an industrial environment, has a zone control cabinet fitted with electronic controller that manages its own distribution system, a rack in the case of AHUs or a room distribution system with simple manifolds and nozzles or blower units. In addition, it communicates with the Master for all the common system procedures, such as washing, emptying, etc. Each cabinet, both Master and Slave, receives the signals from the probes and/or the external control system, calculates the required humidification/cooling capacity and, when the water has reached the rated pressure, manages the solenoid valves in the distribution system to generate the required capacity.
Constant pressure control rationalises operation of the humiFog pumping unit as, despite the lower precision of stepped modulation, it can treat a number of zones at the same time without installing a pumping unit for each AHU or industrial environment.
For the configuration of the steps, see the instructions provided in the previous paragraph “Single zone applications in AHUs – constant pressure control” and “Single zone applications in rooms”.
29
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Multi-room application
1
2
3
3
4
4
4
5
3
2
2
MASTER CABINET
SLAVE CABINET
SLAVE CABINET
Fig. 8.e
Key:
1. water from REVERSE OSMOSIS system;
2. drain valves (one in each zone);
3. fill valve;
4. ambient probe;
5. main drain valve.
Multi-AHU application
1
2
2
2
3
MASTER CABINET
RACK
SLAVE CABINET
SLAVE CABINET
RACK
RACK
Fig. 8.d
Key:
1. water from REVERSE OSMOSIS system;
2. air handling unit;
3. main drain valve
30
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
8.3 Indirect adiabatic cooling applications
One important function involves indirect adiabatic cooling applications (summer): a pumping unit can cool the exhaust air before it enters a heat recovery unit. This function is often complementary with the use of humiFog for air humidification in winter. The configuration in question is illustrated in the figure. The system can be configured in two ways:
capacity/flow-rate control: just one rack at a time atomises the water,
with continuous system capacity control and consequently maximum precision. See paragraph “4.1 Pumping unit with flow control configuration” for further information on capacity control.
constant pressure control: two racks can atomise the water at
the same time or individually. This maximises energy saving by simultaneous indirect (cooling the air before the heat recovery unit) and direct adiabatic cooling (cooling the air before this is introduced into the environment), however with less precise control (stepped capacity modulation, see paragraph “4.2 Pumping unit with constant pressure control” for further information on capacity control).
For example, an indirect system with 100 kg/h of water sprayed can cool the exhaust air with an equivalent cooling capacity of 68 kW; this, in the heat exchanger/heat recovery unit, will cool the fresh air with an equivalent cooling capacity of 34 kW, for a power consumption of just
1.2 kW! In addition, this reduces the capacity required of the cooling coil and the chiller. For a detailed and complete description, see “Air humidification” by Lazzarin - Nalini, chapter 11.
Indirect and direct adiabatic cooling
1
HE
7
2
3
4
5
6
Fig. 8.f
Key:
1. recirculated air;
2. exhaust air;
3. saturated and cooled air;
4. outside air inlet;
5. heated exhaust air;
6. cooled outside air;
7. fresh air.
8.4 System operation
humiFog multizone independently manages the production of pressurised water, the distribution and filling, drain and wash cycles. This paragraph illustrates the latter functions.
Filling: before starting the production/atomisation phase, the piping must be filled with water and, then, vented of air. This ensures correct pressurisation of the lines and minimises the possibility of pressure swings due to air trapped in the piping. The system is empty when first started and following draining due to extended inactivity (see the rest of the paragraph for further information). Before starting production, the system is filled by starting the pump, which generates the rated capacity of the pumping unit and fills the piping with water for a time set by parameter. This time must be established by trial and error when starting the system. When filling, all the capacity-control and drain valves in all the zones are open, while the vent and main drain valves are closed. The distribution system must be sized so that, in these conditions, the water pressure does not exceed 5 bars, thus avoiding situations where the nozzles atomise/spray water (each nozzle contains a valve that prevents atomisation at pressures below 7 bars).
Washing: this is performed periodically and involves flushing water through the piping for a time set on the menu. The purpose is to completely wash the system and avoid stagnation of water. It is performed in the same way as filling, but lasts longer: the time should be set so that the water used for washing is at least 3 times the volume of water contained in the complete installation. The wash cycle is performed every day at the same time (e.g. every day at 4 in the morning) or periodically at an interval set by parameter. At the end of the first wash cycle, the system remains full, while, starting from the second consecutive wash cycle without operation, the installation will be left empty. In addition, a wash cycle is also performed at start-up. If the wash cycle is disabled, then the system will be left empty after a period, set by parameter, during which it has remained full and without operation.
Pressure relief: this last function is used to save water and limit the filling and emptying cycles, without affecting the hygiene features of the system, nor its performance. The pressure relief function, when a branch (piping with nozzles or blower units) is disabled (stops atomising), the capacity-control valve is obviously closed and the drain valve is opened. The latter, however, will be closed again a few seconds later so that the pressure falls below 7 bars (and then the nozzles no longer spray) however the branch remains almost completely full of water. This avoids emptying the branch (saving water) and having to fill the system when production is required again in the branch. Note that opening the drain valve is required to achieve a rapid decrease in pressure from 70 bars to virtually 0, preventing the nozzles from spraying water at intermediate pressure values and generating large droplets that would wet the AHU/room.
Clearly, it is recommended to enable pressure relief. Indeed, thanks to the emptying procedure described above, in this case too there will not be stagnation of water in the piping for a time greater than the set value.
Rotation (only if “Pressure relief” is enabled): in constant pressure systems, humiFog periodically “rotates” the branches (piping with nozzles or blower units) that atomise the water. For example, if the zone has four branches and only two are in production, then the first and the third will be activated, for example, for 20 seconds, and then deactivated; at the same time, branches two and four will be activated. After a further 20 s, branches two and four will be deactivated (with pressure relief), and one and three will be activated simultaneously. The example in the diagram with six branches gives a better idea: this shows an activation sequence where each configuration (row) lasts 20 s. “A” indicates the active branch, “d” the inactive branch:
t=0
A
dd
A
dd
t=20s d
A
dd
A
d
t=40s d d
A
dd
A
t=60s
A
dd
A
dd
t=80s d
A
dd
A
d
t=100s d d
A
dd
A
Rotation is feasible if system operates with constant pressure and all the branches have the same rated capacity. Obviously, pressure relief must be enabled, otherwise each rotation would require a filling cycle.
31
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
8.5 Constant pressure systems: notes on capacity control
In constant pressure systems, humiFog keeps the pressure at the desired value when the required capacity changes (that is, the sum of the capacities required by each zone). Capacity required increases: whenever a zone requires an increase in capacity, the pumping unit does not respond immediately: the flow­rate/capacity of the pump is modified to generate the required capacity and only then is the signal sent to the zone, which suitably controls the solenoid valves (overboost cycle). For example, if a zone has 4 branches, 25 kg/h in each branch, two branches are active and the request increases to 75 kg/h, then the zone controller sends the request to the pumping unit, which increases the flow-rate to 75 kg/h and, only when this has been reached, sends the signal to the zone to activate the third branch and consequently spray 75 kg/h. In the delay until the signal is received, the water pressure rises above the pressure set point, however this guarantees that, when the third branch is activated, the pressure will not fall below the required value and cause the nozzles to spray coarse droplets. During this transient period, the excess water is recirculated by the bypass valve. Subsequently, when the zone is in the final status (solenoid valves suitably activated, third branch open, as in the example) the water pressure drops for a few seconds to around 60 bars, to ensure complete closing of the bypass solenoid valve (underboost cycle). Capacity required decreases: in this case, the pumping unit responds immediately to the request from any one of the zones to decrease the capacity. As a consequence of the reduction in atomised water in the zone/zones, the pressure will increase and the bypass valve may be activated. There will also be a reduction in the pump rotation speed (to reduce the flow-rate to the new value required by the zone) and, if the bypass valve has been activated, an underboost cycle will be performed (see the description above).
In the general case where there are multiple zones that require variations in capacity, these will be satisfied one at a time, in order, and only at the end of the last variation will the underboost cycle be performed, if necessary.
32
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
9. START UP
Before starting the humidifier check:
 water and air connections (chap. 2). In the event of water leaks do not
start the humidifier before having resolved the problem;
 electrical connections (cap. 3)
9.1 Starting
1
0
ON
9.2 Stopping
1
0
OFF
Note: if the system is stopped for an extended time, open the
valve at the end of the water line to assist drainage. If the system is fitted with drain solenoid valves at the end of the line (optional), this is done automatically.
9.3 First start-up
HumiFog is fitted with a guided procedure for the first start-up, which guides the user step by step on how to set the humidifier. The first screen is dedicated to language, as shown in the following screen
Press ENTER to select the desired language. Once finished press ESC to return to the startup procedure. This screen is displayed for 60 seconds.
Successively, a series of “wizard” screens shall appear, which will guide the user on fillig-in all the parameters required for the proper setting of the humidifier
YES: the screen for selecting the language displays at the next start-up
of the humidifier;
NO: the screen for selecting the language does not display any more
at start-up.
Note: the language can be changed at any time by following the
instructions in Chapter 9.7 Installer menu.
33
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
10.1 Keypad
1
2
4
6
5
3
Ref. Function 1 alarm list active alarms and reset any alarms present
2 PRG
from the “main” screen, access the main menu
3 ESC return to the previous screen/display 4 UP circular navigation inside the menus, the screens, the parame-
ters and the values of the parameters from the “main” screen, access an “INFO menu”
5 ENTER select and confirm (like the “Enter” key on a computer keyboard)
from the main screen, access the “SET” screen
6 DOWN circular navigation inside the menus, the screens, the parame-
ters and the values of the parameters
from the main screen, access the “ALARM HISTORY” screen
10.2 “Main” screen
6
5
7
1
2
3
4
8
9
Ref.
Function
1 description of the area status:
“OFF” state area “IN Function” state area “READY” state area (is in standby) “WASHING” state area “FILLING” state area The descriptions of the missing areas are grouped in the supervision table
2 value read from the main control signal
3 limit probe reading (if enabled) 4 pump state:
• pump in Function (the triangle in the center of the icon flashes);
• pump not in Function (the triangle in the center of the icon does not flash, empty);
5 Access to the “INFO” screen (UP key) 6 Access to the “SET” screen (ENTER key) 7 Access to the “HISTORY ALARM” screen (DOWN key) 8 State of spray nozzles:
• spray nozzles in Function
• spray nozzles not in Function
• disabled area
9 Time frame in “ACTIVE” state
10.3 “INFO” screens
Series of read-only screens for displaying the main humidifier status values. To access, press UP from the “Main” screen. There are four “INFO” screens; to move from one screen to the next, press UP or DOWN. Press ESC to return to the “Main” screen.
1. INFO screen - Information area (read-only)
5
1 2 3 4
Ref.
Parameter and UM Status
1 Request [kg/h]
2 Production [kg/h]
3 AUX Probe (if enabled) 4 Valve state:
Refill valve F Drain valve D Ventilation V
A” Opened (atomizing branch); “ - “ closed ”?” Opened (drain branch) ; “. - ” closed ”B” Opened (in ventilation); “ - ” closed
5 Date and hour
2. INFO screen - Remote information area (read-only)
Indicates the current status of each remote location connected to the cabinet
• Off to flow state
• In production
• No request
• Etc...
3. INFO screen - Pump information (read-only)
1
3
5
2
7
4
6
Ref.
Parameter and UM Status
1 Request [kg/h] Represents the total requests of each area
2 Pump pressure [bar] Pressure generated by the pump
3 Conductivity [µS/cm] Conductivity measured at the inlet of humiFog 4 Pump hours [h] Hours of operation occurred since the last reset
of the hour meter
5 Total hours [h] Total hours of operation only 6 Bypass temp. [°C/°F] Temperature of the water recycled in the pump 7 Rack temp. [°C/°F] Temperature detected by the probe in the ato-
mization area (optional). Setpoint set from CTA
10. USER INTERFACE
34
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
10.4 “SET” screen
Used to set the main values for the humidifier. From the main screen press:
ENTER to access the menu;
ENTER to select the parameter you want to set;
UP and DOWN to modify the value of the selected parameter;
ENTER to confirm and go to the next value.
1
3
5
2
4
Ref.
Parameter and UM Status
1 Enabling the pump set [Yes/No] to the no
parameter to completely disable the system
YES
2 Setpoint (T or %rH) [°C/°F or %U.R] represents
the requested humidity or temperature (avai­lable if the control is fitted with a probe)
28°C/82°F or 50%rH
3 Auto Operation [Auto/OFF] following the
request of the area; OFF the non-atomized area even in the presence of a request
Auto
4 Maximum pressure [%] setting of the maxi-
mum production from the area
100 %
5 Proportional band (T or %rH) [°C/°F or %U.R] 5 °C/°F or 5% rH
.... Differential (present only if P/I) 2 °C/°F or 5% rH
1
2
Ref. Parameter and UM Default
1
Limit probe setpoint (T or %rH) [°C/°F or %U.R] 10°C/50°F or 90 %rH
2
Limit probe proportional band 5 °C/°F or 5% rH
10.5 ”Alarm History” screen
The alarm history screen displays the messages generated by warnings or alarms that are solved.
1
2
Ref.
Parameter
1 number, hour and date of warning/alarm
2 Description of warning/alarm
10.6 “Main” Menu
To access press PRG from the main screen Buttons:
UP and DOWN: navigation inside the submenus, screens, and range of
values and settings;
ENTER: confirm and save the changes made;
ESC: to go back (pressed more than once returns to the “Main” screen)
Menù 1° level 2° level Indexing
A. User a. Alarm Threshold -- Aa01
b. Clock -- Ab01...2 c. Sched uler -- Ac01...2
B. Installer a. Pump setup a. Pump setup Baa01...2
b. Water supply Bab01...2 c. Special fun­ctions
Bac01...6
b. Zone setpu a. Configura-
tion
Bba01...6
b. Distr. sy­stem
Bbb01...3
c. Special funct.
Bbc01...10
d. Supervisor Bbd01...2 e. External allarms
Bbe01
c. Remote zones Remote zones Bc01 d. Change Language Language Bda01...2
C. Ma intenance a. System config -- Ca01...2
b. Unit info -- Cb01...3 c. Probe readings -- Cc01 d. Manual request -- Cd01...11 e. Unit Status -- Ce01 f. Working hours -- Cf01...2 g. Alarm log -- Cg01
10.7 “User” Menu
From the main screen press:
PROG to access the main menu;
ENTER to select and access the selected menu;
UP/DOWN to move between the submenus;
ENTER to enter the submenus
ENTER to select the parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confirm selected parameter and go to the next parameter;
ESC to return to the previous menu.
To navigate inside the screens:
UP or DOWN to modify the value (within the options/range),
ENTER to confirm and move the cursor to the next value
ESC to return to the installer menu.
35
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
User Menu Screens:
Menù 1° level 2° level Indexing
A. User a. Alarm Threshold -- Aa01
b. Clock -- Ab01...2 c. Sched uler -- Ac01...2
Submenu: a. 01 Alarm thresold
1
2
3
Ref. Display Description Range Default Unit
Main
1
Alarm-high
Alarm threshold for high humidity or temperature
0...100 o
-20...70
100 o 40
U.R. o °C
2
Alarm-low
Alarm threshold for low humidity or temperature
0...100 o
-20...70
0 o 20
U.R. o °C
Limits
3
Alarm-high
Alarm threshold for high hu­midity or temperature limits
0...100 o
-20...70
100 o 10
U.R. o °C
4
Alarm-delay
Minutes beyond which the alarm is triggered
0...99 1 min
Submenu: b. Clock b. Clock 01 CLOCK Day, date and hour setup
1
2
3
4
Ref. Display Description Range 1
Giorno
Setting the week day Monday to Sunday
2
Formato data
Setting the European or Ameri­can date format
dd/mm/yy - mm/dd/yy
3
Ora
Setting the hour 0 - 24
Data
Setting according to date format
b. Clock 02 Clock Gestione ora solare/legale
1
4
3
2
Ref. Display Description Range 1
Ora legale
“ENABLE”, defines the automatic switching between standard time and daylight saving time
Enable/disable
2
Transition time:
Determine the number of minutes by which the clock will be adjusted during the activity time of the transition.
-60 min
3
Start
Defines the start of the daylight saving time period
4
End
Defines the end of the daylight saving time period
Same type of setting and requested for the end transition threshold. This is expressed relatively, not based on the number of days but on the day of the week. Setting this parameter requires entries in four different fields:
Week selection (available options: First, Second, Third, Fourth, Last):
Day selection;
Month selection
Transition start time
The same type of setting is required for the transition end threshold
Note: the default configuration includes changing the standard time/daylight saving time according to the European standard and the UTC +1 time zone
Submenu: c. Scheduler c. Scheduler 01 SCHEDULER Enabling the scheduler (operation time frames)
1
Ref. Display Description Range Default Unit 1
Enable scheduler:
Abilita/ disabilita
Note:
if the unit is configured with the “On/Off” setting or the “Proportional
external signal”, the scheduler manages the switching on and off of the unit, while the actual regulation is delegated to the external signal:
if the unit is in “Off by scheduler” the request from the external signal is
ignored, while it is satisfied if the unit is placed in “On” by the scheduler.
Scheduler settings (operation time frames)
1 2
3
5
4
Ref. Display Description Range Def. Unit 1
Day
Setting day of the time frame
2 Enable/disable the time frame
3
00:00
Start hour of time frame ora
4
ON+SET
Type of time frame ON
ON+SET OFF
5
00.0%
Setpoint of the humidity or tempera­ture frame (editable only for “ON+SET” frames)
% rH %T
36
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Note: It is possible to set up to 6 time slots in each day of the week to define ON/OFF and setpoint changes over 24 hours, as follows: ON: The unit is ON and the production works respecting the current request (in the case of adjustments in temperature or humidity setpoint is used in the mask “Set”) ON+SET (only regulation in humidity or temperature): The unit is ON following the setpoint defined in the mask of the scheduler. OFF: The unit going in “Off by scheduler”: each production request isn’t consider and there is no production.
Note: reffering to the mask Scheduler AC02 below: The humidifier is in “Off” mode from 0:00 to 10:00 am At 10:00, the humidifier is in ON mode and works with setpoint equal to global setpoint (editable in mask “Set” and reported in mask “scheduler” AC02) At 15, the humidifier is always in ON mode and works with a setpoint other than the global 20% rH At 23:00 the unit is turned off.
10.8 “Installer” Menu
From the main screen press:
PRG to access the main menu;
DOWN to move to the installer menu;
ENTER to move to the password;
UP/DOWN to enter the password “77“
ENTER to access the selected menu;
UP/DOWN to move between the submenus;
ENTER to select the parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confirm the selected parameter and go to the next parameter;
ESC to return to the previous menu.
To navigate inside the screens:
• UP or DOWN to modify the value (within the options/range),
• ENTER to confirm and move the cursor to the next value
• ESC to return to the installer menu.
The installer menu is divided into four submenus:
Menù 1° level 2° level Indexing
B. Installer a. Pump setup a. Pump setup Baa01...2
b. Water supply Bab01...2 c. Special fun­ctions
Bac01...6
b. Zone setpu a. Configura-
tion
Bba01...6
b. Distr. sy­stem
Bbb01...3
c. Special funct.
Bbc01...10
d. Supervisor Bbd01...2 e. External allarms
Bbe01
c. Remote zones Remote zones Bc01 d. Change Language Language Bda01...2
Submenu a. Pump setup a. Pump setup - Pump setup
1...2
Contains the menu with the installer parameters related to the pump station
Pump operation mode
1
2
Define the type of operation of the pumping station - between constant pressure (the atomization occurs when the pressure is set constantly, set the pressure to 70 bar) and flow control, the atomization starts at 25 bar and increases to 70 bar. If the humidity setpoint is not reached at this point, then the next branch is opened, atomizing again between high and low pressure, which are the only two parameters to be set. In the case of a multi-area system, the only possible option is the constant pressure setting.
Constant pressure
Ref. Display Description Default Unit
1 Mode
Set to constant pressure
PC per i codici
UA...ZD....
CP per i codici
UA...HD....
2 Pressure set
Pressure at which the atomization occurs
70 bar
Flow control
Ref. Display Description Default Unit
Mode
Set to flow control PC per i codici
UA...ZD....
CP per i codici
UA...HD....
High pressure
Activation value of the next rack branch
70 bar
Low pressure
Deactivation value of the rack branch
25 bar
Change pump
1
Ref. Display Description Default Unit
1 Change pump?
Activity to be performed only when the pump is replaced, in order to reset the opera­ting hours and the warnings related to them
No
If it is necessary to replace the pump, it is required to set the parameter to “YES” by resetting the hourmeter from the first 50 hours of operation If it is necessary to replace the pump assembly, it is of fundamental importance to signal the replacement on the Baa02 screen, in order to reset the parameters related to the operation of the pump and have the correct maintenance and oil change alerts, particularly that relating to the first 50 hours of operation, which is not restored following the simple reset of the hourmeter on the Cf02 screen.
37
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Submenu a. Pump setup
a. Pump setup ­ b. water supply 1...2
Water alarm settings
In the menu you will find two screens that define the parameters of water supply and the relative signal delay of any warnings
1
2
Ref. Display Description De-
fault
Unit unità
1 Low
pressure alarm delay
The time after the locking alarm is notified, with regard to the low water pressure in the pump outlet of the humidifier, does not exceed the minimum threshold set by Carel at 20 bar
0 - 999 45 sec
2 WTS alarm
input logic
Manages the logic of the ROAL-G0A contact which receives the possible alarm state coming from the water treatment system. In the event that an alarm state occurs, this is also displayed on the cabi­net display as “water treatment plant alarm” The possible logics are the following: N.C. means that the alarm state will occur at the opening of this contact N.A. means that the alarm state will occur at the closing of this contact
N.C./ N.A.
N.C.
1
2
Ref. Display Description De-
fault
Unit unità
1 Conductivity
warning threshold
Conductivity value of the inlet water to the pumping station beyond which a warning is triggered. This threshold does not repre­sent a blocking notification for the system, but only a pre-alarm
100 µS
2 Conductivity
alarm threshold
Conductivity value of the inlet water to the pumping station beyond which the system is blocked. The value set by the “high con­ductivity alarm threshold” parameter must always be greater than the previous parameter
200 µS
Submenu a. Pump setup
a. Pump setup ­ c. Special function 1...6
Washing and filling
1
2
Ref. Display Description De-
fault
Unit unità
1 Enable
filling
When the pumping station should start and detects that the water discharge line is empty before start-up, enabling the pump, seasonal restart etc. , enabling this pa­rameter with Yes, the pump dispenses the minimum flow for a defined time to the next parameter, in order to fill the line before the start of the atomization
Si/No Si
2 Duration
The filling time of the di­scharge line before starting the atomization, only if the discharge line is detected as being empty
1/60 2 min
1
2
3
Ref. Display Description De-
fault
Unit unità
1 Wash mode:
Periodic Giornaliero Solo svuotamento
Washing performed after a set number of inactive hours Washing performed daily at a pre-defined hour Complete emptying of the lines performed after a set number of inactive hours
Perio ­dico giorna­liero solo svuota­mento
Perio ­dico
Tipo
2 Intervallo
Ora Intervallo
Number of inactive hours after which the periodic washing is performed Time of day when you run the daily wash Number of inactive hours after which the complete emptying of the lines is performed
49 0 49
h h h
3 Duration
Duration
-
Number of minutes for which the periodic washing is performed Number of minutes for which the daily washing is performed
1 - 10 1-1022
-
min min
-
Note: if the washing parameter was set to “Periodic” or “Daily”, a
washing will be performed at every start of the pumping station.
38
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
2
Ref. Display Description De-
fault
Unit
unità
1 Fill/Wash
pump speed:
As specified on the Bac01 screen, if the filling or washing is enabled, you have the possibility to set the nominal flow rate in % at which the filling and washing is performed
0...999 14 %
Slowdown pump
1
2 3
Ref. Display Description De-
fault
Unit
unità
1 Slowdown
vent. valve zone
Defines in which area to open the ventilation valve during the slowdown of the pump at the reached setpoint. This phase is required because the normal mechanical inertia of the pump when reaching the setpoint could generate a critical pressure for the next restart
0...6 (Nume­ro della zona da aprire)
1
2 Opening
duration ventilation valve
Time of opening the ventilation valve to ensure the correct pressure of the system at the next restart
1...15 3 sec.
3 Fill/Drain
valves
Time of opening the drain valves of the area defined by the first parameter of the screen to en­sure the proper pressure at the opening of the ventilation valve
1...15 1 sec
Drain-valve status in stand-by
1
2
Ref. Display Description Def. Unit
unità
1 close fill valves
in case of empty standby for more than:
Set minutes after which, if the system detects an empty standby, stops the supply towards the load solenoid valves (N.C.)
0...540 15 min
2 Pump status relay
logic:
Set the relay logic that represents the state of the pump through the free ROEN-COM contact. Open contact ON pump (if the set parameter is N.A., otherwise vice versa) Closed contact OFF pump (if the set parame­ter is N.A., otherwise vice versa)
N.A/ N.C.
N.A.
Cooling the water treatment system
In order to preserve the state of the membranes even in limited environmental conditions (for example temperature) it is possible to provide the enabling of the successive parameters which run the water by avoiding overheating
1
2
3
Ref. Display Description Range Default Unit
1 Enable WTS
cooling procedure
Enables at the end of the “T. Inactivity” parameter, the opening of the load solenoid valve of the pumping station for a time defined by the “Du­ration” parameter in order to activate the water treatment system to ensure optimal conditions for maintaing the membranes
SI/NO SI Tipo
2 Inactivity
thr:
Time after which the system opens the load solenoid val­ves of the pumping station
0...999 24 h
3 Duration
Opening time of the load so­lenoid valves of the pumping station
0...99 15 min
Submenu b. Zone setup b. Zone setup ­ a. Input config.1...6
Remote area address
1
Ref. Display Description Range Default Unit 1
Zone address:
Field-bus address of the area
1 -6 1
39
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Operating mode (in this regard consult the chapters xxxx)
1
Ref. Display Description Range Default Unit 1
Unit mode
Defines the operating mode of each area Humidification or D.E.C I.E.C.: Indirect evaporative cooling with temperature setpoint Generator of pressurized water: defines a pressure setpoint according to the pre­set measuring unit. With this operation disable the management of the solenoid valves of the distribution system and the distribution system in general
Humidification I.E.C. Generator of pressurized water (only to a single area UA...HD...)
Umidific Tipo
Regulation type
1
2
Ref. Display Description Range Default Unit
1 Regulation type
Set the adjustment type of the atomised water production Humidity + Lim temp = main humidity probe with temperature limits Humidity+Lim. Humid. = main humidity probe with humidity limits Humidity = main humidity probe ON/OFF+Lim. Temp = humidistat/thermostat + limit temp. probe ON/OFF = humidistat/thermostat ON/OFF = humidistat/thermostat + flow limits (only IEC) Ext. Sign. + Temp. Lim. = analogic signal + limit temperature probe Ext. Sign. + Hum. Lim. = analogic signal + limit humidity probe External signal = analogic signal External signal = analogic signal + flow limits (only IEC) Temp.+Lim. Temp. = main temperature probe with temp. limits Temp.+Lim. Humid. = main temperature probe with temp. limits Temperature = main temperature probe Temperature = main temperature probe + flow limits (only IEC)
Umidità+Lim temp Umidità+Lim. Umid Umidità ON/OFF+Lim. Temp ON/OFF Segn.Ext+Lim.Temp Segn.Ext+Lim.Umid Segnale esterno Temp.+Lim. Temp Temp.+Lim. Umid. Temperatura
Umidità+Lim. Umid tipo
2 Reg. logic
P = proportional P+I = proportional + integral
P P+I
P tipo
Probe confirguration
Main probe confirguration
1
2
4
3
Ref. Display Description Range Default Unit
1 Main probe
Type of main control signal 0 - 10 V
2 - 10 V 0 - 1 V 135 - 1000 Kohm 0 - 135 ohm 4 - 20 mA 0 - 20 mA
0 - 10 V
2 Min:
Correlates the minimum value of the humidity/temperature with the minimum value of the main signal -100 ... +100 0.0 %/°
3 Max
Correlates the maximum value of the humidity/temperature with the minimum value of the main signal --100 ... +100 100 %/°
4 Offset
Humidity correction factor read by the main signal -20 ... +20 0.0 %/°
40
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Limit probe confirguration
1
2
4
3
Ref. Display Description Range De-
fault
Unit
Limit probe
Type of signal of the limit probe
0 -10 V 2 - 10 V 0 - 1V NTC 135 - 1000 ohm 0 - 135 ohm 4 - 20 mA 0 - 20 mA
0 - 10 V
Min
Correlates the mi­nimum value of the humidity/temperatu­re with the minimum value of the limit probe signal
-100 ... +100 0.0 %/°
Max
Correlates the ma­ximum value of the humidity/temperatu­re with the minimum value of the limit probe signal
-100 ... +100 100 %/°
Offset
Humidity correction factor read by the limit probe signal
-20 ... +20 0.0 %/°
Auxiliary probe confirguration
1
2
Ref. Display Description Range Default Unit
1 AUX-probe
Enables the temperature or humidity read-only feature of the auxiliary, without causing any effect on the control of the single area
°C/°F %rH
°C/°F °C/°F
2 Type
Defines the type of signal from the auxiliary reading probe
0 -10 V 2 - 10 V 0 - 1V 135 - 1000 ohm 0 - 135 ohm 4 - 20 mA 0 - 20 mA
0 - 10 V
3 Offset
Correlates the min, max and offset values
Min - Max ­Offset Min - Max ­Offset
0.0 - 100 - 0.0
0.0 - 100 - 0.0
%/°
Some masks were included only the probe-parameters probes that correspond to the type of operation set.
Submenu B. Zone setup b. Zone setup ­ b Distr. system
Within the sub-menu, settings area, “distribution systems”, there are 3 screens which will be different in relation to the chosen “mode” parameter (code Baa01), between flow control or constant pressure, from the first screen of the Pump settings submenu. Below are the steps for the definition of the distribution system in “constant pressure” mode
Definition of the distribution system
1
2
Ref. Display Description Range Def. Unit 1
Step n.
Step no. of the area (as shown in the documentation attached to the rack)
1 - 6 1
2
...kg/h
Flow rate of each single step (as shown in the documentation atta­ched to the rack)
kg/h
1
2
3
Ref. Display Description Range Default Unit 1
Nominal
Setting the nominal flow rate of the RACK in the single area (not to be confused with that of the pumping station). This value can be found in the documentation provided with the Rack
10...1000 10 kg/h
2
Step
Step number (as shown in the documentation attached to the rack)
4n°
3
Min production
Setting the minimal flow rate of the RACK (not to be confu­sed with that of the pumping station!). This value is found in the documentation provided with the rack and ensures that, at the minimum flow rate, the water pressure does not drop below 20 bar, which would generate a blocking alarm.
From the theoretical minimum calculated according to the “Nominal flow” and the “Number of branches” up to 80% of the “Nominal flow”
Theoretical minimum calculated according to the “No­minal flow” and the “Number of branches”
kg/h
1
Ref. Display Description Range De-
fault
Unit
1 Collectors
number
Set the number of vertical collec­tors dedicated to each single step (as shown in the documentation attached to the rack)
41
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Submenu b. Zone setup
b. Zone setup - c. Special functions
Contains nine screens and their parameters, and any notes and clarifications contained in chapter xxxxx
Remote area cabinet mode
1
Ref. Display Description Range Default Unit
Cabinet working mode
Remote zone
Pressure relief
1
2
Ref. Display Description Range Def. Unit 1
Pressure relief duration
Defines the opening time of the load solenoid valves N.A. of the step in closing phase. This parameter is fundamental to let the pressurized water inside the collectors and avoid dripping problems.
0 - 999 3 sec
2
Zone status relay logic
Set the relay logic that represents the state of the area through the free C25 ­NO26 contact J20 terminal. Se N.A. Free contact OFF area - none of the steps of the area are in atomization phase Closed contact ON area - at least one of the steps of the area is in atomization phase
N.A. - N.C. N.A.
Alarm relay logic and fan blower
1
2
3
Ref. Display Description Range Def. Unit
1 Alarm relay
logic
Set the logic of the J15 alarm relay N.A. free contact between the NO8 - C8 terminals N.C. closed contact between the NO8 - C8 terminals
N.A. - N.C. N.A.
2 Flow switch
input logic
Manages the logic of the FLUX­G0A contact which verifies the air passage in the duct. The possible logics are the following: N.C. signifies that there is an air passage in the duct N.A. signifies that there is no air passage in the duct
N.A. - N.C. N..C.
3 fan blower
present
Set to “YES” if you want to enable the environment atomization of the pumping station with the use of ventilating heads
YES-NO NO
Step rotation
1
2
Ref. Display Description Range De-
fault
Unit
Steps rotation
1 Enable
Enable the rotation of the ac­tivation logic only in constant pressure mode and if all the steps have been dimensioned with the same capacity
Si/NO NO
2 Time
Time after which the rotation is performed from one step to another
3...999 60 seconds
Rack temperature probe
It is possible to install a temperature probe immediately before the distribution system in order to verify if the temperature is optimum for the proper absorption of the atomized water.
1
2
3
Ref. Display Description Range Def. Unit
1 Use rak
temperature probe
Enables the detection of the temperature in the atomization area. When the tempera­ture drops below the “rack temp. probe setpoint” a warning video is signalled.
YES - No NO
2 Type
Probe type NTC
0 -10 V 2 - 10 V 0 - 1V NTC 135 - 1000 ohm 0 - 135 ohm 4 - 20 mA 0 - 20 mA
NTC
3 Reduced
production
Enables the reduc­tion of production if the temperature in the atomization area falls below the “rack temp. probe setpoint” proportio­nally with the offset from the ideal atomi­zation temperature
YES-NO NO
42
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
1
2
3
Ref. Display Description Range Def. Unit
1 Rack
temperature probe setpoint
Represents the minimum recommended temperature for atomization
-999.9 - +999.9 20 °C
2 Warning
differential
Defines the interval after which the warning message disappears
-999.9 - +999.9 3 °C
3 Prop. band
Defines a modulation interval equal with the “Rack temp. probe setpoint” ­“band prop.”. The production will be mo­dulated within this interval Below this interval the production comes to a minimum Above this interval the pro­duction restarts according with the std. Displayed only if the produc­tion reduction is enabled
-999.9 - +999.9 5 °C
The Function, configurable on the FUNZ. SPECIALI Bbc05 and FINZ screens. SPECIALI Bbc06, is formed of two distinct modes: Only Warning: If the temperature is below the setpoint set on the Bbc06 screen, calculated by the system dimensioning, the “Rack low temperature” warning is activated Warning + Production reduction: When the temperature drops below the setpoint in the same time as the activation of the warning, the production is reduced by decreasing the temperature until it is completely stoped when the difference between the setpoint of the temperature probe on the rack and the measured temperature is higher than the “Prop. band” parameter Set on the Bbc06 screen.
The operation of the warning and production reduction is summarized in the following graph where all the specified parameters are settable from the FUNZ SPECIALI Bbc06 screen
Setpoint sonda temp. Rack – Prop. Band
Setpoint sonda temp. Rack + Diīerenziale warning
Fig. 10.a
Alarm delay of control probes
1
2
Ref. Display Description Range De-
fault
Unit
1 Delayed
reg. probes alarms at pump ON
Inhibits if set to YES, the alarm sensor is disconnected for a defined time by the following parameter “activation delay”. This time is measured starting from the start-up of the pump
YES
-NO
NO
2 Actovation
delay
Activation delay time of the disconnected probe alarms
2 min
If the characteristics of the application can bring the control probe readings - particularly the humidity - too low, it is possible to temporarily disable the alarm “Sensor broken or disconnected” at the start of the control, avoiding the presence of false positives, setting in a timely manner the parameters of the Bbc07 screen.
When the Function is enabled, the electronic control ignores the presence of alarms for the preset time, calculated from the start of the control.
Enable back-up
For clarifications refer to chapter xxxx
1
2
3
Ref. Display Description Range De-
fault
Unit
1 Enable
backup primary cabinet
Defines the cabinet as “main cabinet”, “secondary cabinet” or it does not define the cabinet if set to “NO”. This parameter is fundamental because, if the rotation or redundancy is provided, the system needs to understand what is the first cabinet to take precedence at startup
NO Cabinet secon­dario Cabinet primario
NO
2 Rotation
Set the parameter to “YES” when in the presence of two cabinets you want, even in the normal work phase, to rotate the operatio of the cabinets in order to manage and balance the wear of the two pumps
YES-NO NO
3 Time
If the rotation is enabled define the Function time of the pump after which the pump is rotated
0 - 8 8 h
43
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Remote actuator
1
2
Ref. Display Description Range Def. Unit
1 Use remote
rack actuator
Notification to the pumping station that the directly controlled area is managed by one or more slave cabinets configured as simple actuators. This allows the correct and rational management of large distances between the pumping station and the rack. The “slave” cabinet will be configured automatically by enabling this parameter. If the branches of the step do not observe the limit (1 step > 5 branches and 4° step > 3 branches) managed by a “single actuator”, the system generates the “collector number not set” alarm
YES-NO NO
2 Show
wizard at unit power on
Set to “YES” when you want the wizard to display at start-up, every time the pumping station is supplied with power, as explained in section 9.3 “First start-up”, in order to guide you step by step with regard to the data required for setting the humidifier
SI -NO SI
(*) the humiFog is provided with flow inlet state, thus the machine is enabled.
Submenu b. Zone setup b. Zone setup - d. supervisor
Setting the supervision
1
2
3
Ref. Display Description Range Default Unit
1 Protocol
Set the communication protocol with the supervisor when this is required
Carel, Bacnet Winload Rs232 Lon Modbus
Modbus
2 BMS address
Set the control address within the network
0...207 1
3 Baudrate
Define the speed at which the communication is sent within the network
1200 2400 4800 9600 19200
19200 bps
Supervision adjustment
1
2
Ref. Display Description Range Def. Unit
1 Supervisor
On/Off
set to “YES” if you want to control only the start-up from the super­visor. (N.B. the ON/OFF from the supervisor is independent from the supervisor adjustment)
YES-NONO
2 Supervisor
regulation
Set to “YES” if you want to enable the adjustment from the supervisor, in this case the production of the area shall be adjusted with a variable between 0-1000 % sent by the supervisor via the i156 parame­ter. (N.B. even if the adjustment from the supervisor is activated, it is recommended to also ac­tivate the ON/OF feature from the supervisor, however taking into account that the parame­ters remain independent)
YES-NONO
Zone address
1
Ref. Display Description Range Def. Unit
1 Zone
address
If a remote area is used, identify the address of the area within the system (area connected on the BMS, value set from the Wizard and installer menu/ settings area/ input configuration)
Submenu b. Zone setup b. Zone setup - e. External alarms
1
2
3
Ref. Display Description Range Default Unit
1 Zone
address
Screen visible only to ensure the compatibility with previous versions of humiFog
(*) the humiFog is provided with an alarm input for water treatment, thus the machine is enabled.
44
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Submenu c. Zone remote
c. Zone remote - zone remote 01
Remote area configuration
1
2
Ref. Display Description Range Def. Unit
1 Zone 2:
Yes/No
Activate from the pumping station the presence or absence of remote areas
Yes/No no
2 adr: 2
Also, when remote areas are activated on the pumping station, it allows the user to provide the number of areas and consequently the BMS address. This address will have to coincide with what is set in the same area
1...32 no
Submenu d. Change language d. Change language - language 01...02
Change language
1
Ref. Display Description Range Default Unit
Language
From the following screen select the desired langua­ge. With Enter change the language until you find the desired one. With “ESC” confirm and return to the previous screen
Italian German Spanish French Chinese English
Italian
1
Ref. Display Description Range Def. Unit
Show language mask start-up
Set this parameter to “YES” when you want to view the procedure for selecting the language every time the pumping station is started-up
YES-NO NO
10.9 Menu manutentore
Important: the operations described in this menu must only be
carried out by authorised Carel personnel
From the main screen press:
PRG to access the main menu;
DOWN to scroll to the maintenance menu
ENTER to scroll to the password field;
UP/DOWN to enter the password “77“
ENTER to access the selected menu;
UP/DOWN to move between the submenus;
ENTER to select the parameter and scroll between parameters;
UP/DOWN to modify the parameter;
ENTER to confirm the selected parameter and go to the next parameter;
ESC to return to the previous menu.
Menù 1° level 2° level Indexing
C. Ma intenance a. System config -- Ca01...2
b. Unit info -- Cb01...3 c. Probe readings -- Cc01 d. Manual request -- Cd01...11 e. Unit Status -- Ce01 f. Working hours -- Cf01...2 g. Alarm log -- Cg01
Submenu a. System config 01...02
Factory reset
1
2
Ref. Display Description Range Def. Unit 1
Restore default
Set to “YES” when you want to reset all the humiFog parameters to the default factory settings
NO
2
Model
View one of the choices expressed under “range” and the system code. It is an editable value in that it must be changed after any replacement
Single area Multi area Remote area
Restore configuration
1
2
Ref. Display Description Range Def. Unit 1
Save configuration
Set the parameter to “YES” when you want to save the chosen con­figuration. This option allows you to return to this configuration in any moment without setting the parameters one by one. It is possi­ble to save only one configuration (however, if the system is restored to factory settings, the saved confi­guration shall be removed)
YES-NO NO
2
Load configuration
Set to “YES” when you want to load the saved configuration.
NO
45
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Submenu b. Unit info 01...03
Info of the unit
1
3
5
2
7
4
6
Ref. Display Description Range Def. Unit 1
Model
Represents the code of the device
UA....
2
Flow
Represents the flow rate of the device
kg/h
3
Supply
Identifies the voltage and frequency of the system
V HZ
4
Cabinet
Identifies the cabinet type Master/multi
5
Samper
Identifies the presence or absence of the damper
No
6
Pump
Identifies the type of pump installed
STAINLESS STEEL BRASS SILICON FREE
Steel
7
Measuring unit
Defines the measuring unit International
Imperial
Inter.
1
3
5
2
4
Ref. Display Description Range Def. Unit 1
Code
Identifies the software code
2
Uersion
Identifies the software version and the date on which it was updated
3
Date
Identifies the software launch date
4
Bios
Version of the Bios system
5
Boot
Version of the system’s Boot
Change password
1
Ref. Display Description Range Def. Unit 1
Insert new maintenance password
Defines the new password of the maintainer menu
Submenu c . Letture istantanee 01
Main probe reading
1
3
2
Ref. Display Description Range Def. Unit 1
Principale
Display only the signal value read from the main probe, otherwise viewable from the Installer menu/ settings area 04
Ohm, mA o Volt
2
Limite
Display only the signal value read from the limit probe, otherwise viewable from the Installer menu/ settings area 05
Ohm, mA o Volt
3
Aux
Display only the signal value read from the auxiliary probe, otherwise viewable from the Installer menu/ settings area 06
Ohm, mA o Volt
The signals that are not connected are highlighted as “not present” on the screen.
Submenu d. Manual mode
This is used to control all the outputs and the individual components of the pumping unit or the Zone Control manually. This function is available to test the individual components on the unit. This mode is activated automatically by modifying the status of the outputs from normal operation, indicated as “AUTO” (“0.0 for the production request or analogue outputs). To exit manual mode, simply reset the status of the outputs to “AUTO” (or 0.0). Manual mode is disabled automatically after 30 minutes of inactivity.
Manual request (screen Cd01)
This is used to override cabinet output so as to test complete operation of the zone. To do this, simply change the value of “Zone prod.request” and set the desired request, expressed as a percentage of the rated rack output.
Display Description Range Def. Unit
Zone prod. Request:
Zone production request 0-100.0 0 %
F
Fill solenoid valve status step 1-6 (-> = Open, - = closed)
---
D
Drain solenoid valve status step 1-6 (| = Open, - = closed)
---
46
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Digital Output (screens Cd02- Cd05)
This is used to individually activate the digital outputs on the device so as to test the individual components connected to these.
Display Description Range Def. Unit
NC1… NC6
Spray solenoid valve status setting (NC) step 1-6
---
Display Description Range Def. Unit
NO1… NO6
Drain solenoid valve status setting (NO) step 1-6
---
Display Description Range Def. Unit
Alarm
Alarm relay status setting - - -
Bypass
Bypass solenoid valve status setting
Drain/Vent.
Rack vent and drain valve status setting solenoid
---
Pump status:
Pump relay status setting - - -
Display Description Range Def. Unit
Rack on/off
Zone status relay setting - - -
Antifreeze
Frost protection activation relay setting
Backup req.
Backup sign of life relay setting - - -
Fill Ev.
Fill solenoid valve status setting - - -
SmartZ. Drain
Drain solenoid valve status setting in “SmartZone” mode
---
Analog Output (screen Cd06)
This is used to individually set the status of the analogue outputs on the controller. Set the function on “ON” to enable control of the desired analogue output, then set a value other than 0.
Display Description Range Def. Unit
1:
Enable manual control of analogue output 1
---
Prod.r:
Override current request (analogue output 1)
0-1000 - -
2:
Enable manual control of analogue output 2
---
VFD-FR
Override inverter speed request (analo­gue output 2)
0-1000 - -
Digital input (screens Cd07-Cd08)
Displays the current status, open (ON) or closed (OFF), of the digital inputs.
Display Description Range Def. Unit
3-PEN
Enable pump input status - - -
4- ROAL
Water treatment system alarm input status
---
5- LP
Low pressure switch status - - -
6- HT-DVB
Safety thermostat status - - -
Display Description Range Def. Unit
7- VFD-MB
Inverter alarm status - - -
8- HP
High pressure switch status - - -
9- BKUP
Request backup activation input status - - -
10- ONOF
Zone on/off input status - - -
11- RKEN
Enable rack status - - -
12- FLUX
Air handling unit flow switch status - - -
47
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Analog input (screens Cd09-Cd10)
Displays the status of the analogue inputs on the controller. The value read directly by the input Is displayed, net of any probe limits and offsets.
Display Description Range Def. Unit
1- Main probe
Value read by the main probe - - -
2- Limit probe
Value read by the limit probe - - -
3- Aux probe
Value read by the auxiliary probe - - -
4- Temp.
Value read by the water tempera­ture probe
---
5- Heat rec.
Heat recovery unit damper status (if configured as analogue)
---
6- Conductivity
Value read by the conductivity meter
---
Display Description Range Def. Unit
7- S. pressure
Value read by the pressure probe - - -
8- Rack temp
Value read by the rack temperature probe
---
Bypass calibration (screen Cd11)
This is used to start the bypass calibration procedure, needed when replacing the pumps. For details, see the technical leaflet for the UAKCV0HP* kit.
Display Description Range Def. Unit
Start calibrat:
Start calibration procedure (Y) - - -
Open/Close NC solenoid valves
Close (Y) the system NC solenoid valves so as to pressurise
---
Pressure
Current pressure - - bar/psi
Flow
Current production - - kg/h –
lb/h
Submenu e. Unit Status 01
Unit state
Views detail information of humiFog
1
2
Ref. Display Description Range Def. Unit
1 System
status
View installa­tion status
StandbyEmpty / StandbyFull / Filling / Washing / Emptying / Production
2 Standby
empty
View pump state
Standby / Production incre­ase / Bypass closing / Filling pressure / Washing pressure / Load reduction (production decrease ramp to obtain a single EV unload) / Load clo­sing / At regime (production as well as emptying)
Submenu f. Working hours 01...02
Working hours
1
2
Ref. Display Description Range Def. Unit
1 Pump
View the operating hours of the pump from the last reset in read-only mode
000000 h
2 Unit
View the operating hours of the pump from the last reset in read-only mode
000000 h
N.B. Within the Maintainer Menu, f submenu, Operating hours, the 02 screen allows to reset the operating hours and shows the date of the last reset.
1
2
Ref. Display Description Ran-geDef. Unit
1 Reset
pump counter
Resetting the hourmeter for pump operation
Si/No
2 Last
reset date
View the date of the last resetting
gg/mm/aaaa
48
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Submenu g. Alarm log
Alarm log
1
2
Ref. Display Description Range Def. Unit
1 N° xxx hour
date
Succession of screens that contain the two rows displayed on the left: number of alarm messages, alarm hour, alarm date and alarm message.
YES/ No
2 Zona xxx
offline
The history contains 200 alarms, the older ones being overwritten.
49
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
11. TABLE OF ALARMS
When an alarm is activated, the alarm button starts flashing. In these conditions, pressing the alarm button once displays the type of alarm. In the case of potentially dangerous alarms, the controller automatically stops production. For some alarm events, the alarm relay is also activated at the same time as the signal (see the table below).
Alarm Cause Solution Reset Alarm
relay state
Action Note
No valid model selected After replacing the
control, the software was not configured correctly
Configure the unit model in use on the Ca01 screen Automatic Active Disabled pro-
duction
It is possible to access the Ca01 screen directly from the alarm screen
Nominal rack capacity = 0 The flow rate of the
distribution system has not been set correctly
Configure the capacity of the rack on the Bbb01/ Bbb02 screen (according to the pump control type)
Automatic Active Disabled pro-
duction
Bbb01 is used for a system with flow rate modulation control, Bbb02 for a system with constant pressure It is possible to access the configuration screen directly from the alarm
screen The number of collectors is not set
The number of collectors by which the steps of the rack are formed of has not been set
Set the number of collectors on the Bbb03 screen Automatic Active Disabled pro-
duction
It is possible to access
the Bbb03 screen directly
from the alarm screen
Water treatment plant ID4-IDC1 digital
input on the opened control.
Check the proper operation of the water treatment plant. If correct, check on the Bab01 screen that the input logic coincides with that of the plant alarm signal - If correct, manually close or open the entrance with a plank; if the alarm persists, replace the control
Automatic Active Stop produc-
tion
Low pressure alarm Low pressure at
water inlet
Check the circuit and the pressure of the supplied water
Automatic Active Stop produc-
tion High conductivity warning
The conductivity of the water has reached the warning threshold
Check the water treatment system. If absent, increa­se the warning threshold on the Bab02 screen
Manual Not active Solo segnala-
zione
High conductivity alarm The conductivity
of the water has reached the alarm threshold
Check the water treatment system. If absent, increa­se the alarm threshold on the Bab02 screen
Manual Active Stop produ-
zione
Bypass high temperature alarm
Excessive recycling of the water on the bypass
Check the operating temperature of the installation (environment and water); Check if the distribution system is not obstructed in such a way to cause the recycling of the water
Automatic Not active Only warning
Inverter alarm Malfunction of
inverter
Check, based on the signalling on the display, the status of the inverter and eventually replace it
Automatic Active Stop produc-
tion
The alarm is automatical­ly reset on the control. For the inverter, see chapter 7 of the inverter’s
manual High temperature alarm at the thermostat bypass
Excessive recycling of the water on the bypass
Check the proper operation of the water treatment plant. If correct, check on the Bab01 screen that the input logic coincides with that of the plant alarm signal - If correct, manually close or open the entrance with a plank; if the alarm persists, replace the control
Manual Active Stop produc-
tion
Low temperature at the cabinet pump
Water temperature at inlet lower than 2°C
Reheat the supplied water or the cabinet with a proper dimensioned heater
Automatic Active Stop produc-
tion
High pressure alarm from the pressure switch
Flow pressure excee­ding 90 bar
Contact CAREL for instructions on checking the conditions of the bypass valve
Manual Active Stop produc-
tion
High pressure warning from the presure probe
Flow pressure higher than 30% of the nominal pressure
Contact CAREL for instructions on checking the conditions of the bypass valve
Automatic Not active Only warning
Low pressure warning from the presure probe
During production, the flow pressure is lower than 20 bar
Check the tightnes of the hydraulic circuit at discharge
Manual Active Stop produc-
tion
Remote area # offline On the Multi-area
pumping station, the slave unit is not connected to the fieldbus network
Check the correct setting (address, enable) of the re­mote areas connected to the pumping station and that there are no more areas with the same address. Then check the wiring and the correct operation of the optional fieldbus card
Automatic Active Stop produc-
tion
It is possible to check the correct addressing on the Bc01 screens (Pumping station), Bbc01 and Bbd03 (Remote area)
Offline pumping station On the “Remote area”
cainet, the master unit is not connected to the BMS2 port
Check if the address of the remote area correspon­ds with the one set on the pumping station and that there are no more other areas with the same address. Then check the wiring and the correct operation of the optional fieldbus card
Automatic Active Stop produc-
tion
It is possible to check the correct addressing on the Bc01 screens (Pumping station), Bbc01 and Bbd03 (Remote area)
50
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Alarm Cause Solution Reset Alarm
relay state
Action Note
Broken or disconnected pressure probe
Faulty or incorrectly connected pressure probe
Check the connection and the status of the pres­sure probe
Manual Active Stop produc-
tion
Broken or disconnected main probe
Broken or incorrectly connected main probe
Check the connection and the status of the main control probe
Manual Active Stop produc-
tion
Broken or disconnected secondary probe
Broken or incorrectly connected secondary (limit) probe
Check the connection and the status of the secon­dary control probe
Manual Active Stop produc-
tion
Broken or disconnected auxiliary probe
Broken or incorrectly connected auxiliary probe
Check the connection and the status of the auxiliary probe
Manual Not active Only warning
Broken clock The clock card is not
working properly
Replace the control Manual Active Stop produc-
tion Faulty or disconnected bypass temperature probe
Broken or discon­nected bypass temperature probe
Check the correct coupling and operation of the probe
Manual Active Stop produc-
tion
High humidity alarm The humidity value
detected by the main probe is higher than the high humidity threshold alarm
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
Low humidity alarm The humidity value
detected by the main probe is lower than the low humidity threshold
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
High temperature alarm The temperature
value detected by the main probe is higher than the high tempe­rature threshold
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
Low temperature alarm The temperature
value detected by the main probe is lower than the low tempe­rature threshold
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
High humidity alarm from the limit probe
The humidity value measured by the limit probe is higher than the high humidity threshold of the limit probe
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
Low temperature alarm from the limit probe
The temperature value detected by the limit probe is lower than the low tempe­rature threshold of the limit probe
Check the control parameters to understand if the production is reduced or increased. Eventually change the threshold on the Aa01 screen
Manual Not active Only warning The viewing of the alarm
depends on the type of control used
Maintenance: Change oil The pump has
worked for a number of hours higher than the maintenance threshold
Change the oil of the pump Manual Not active Only warning After changing the oil,
reset the operating hours of the pump from the Cf02 screen in order to
reset the alarm The requested flow exceeds the maximum available flow
In controlled systems (Single and Multi­Area) with constant pressure, the total demand exceeds the nominal flow of the pump by 10% or more
Check if the flows of the steps are correctly set. If correct, check the dimensioning of the installation
Manual Not active Only warning
pCOe Offline The pCOe is not con-
nected to pCO5+
Check if pCOe is correctly supplied. Then check the wiring between pCOe and pCO5+.
Manual Active Stop produc-
tion
Actuator 1 offline Remote actuator/
expansion 1 not connected
Check if the slave cabinet used as a slave is configu­red correctly. Then check the correct wiring betwe­en the J23 port of pCO5+ of the main cabinet and the BMS2 port of pCO5+ of the cabinet configured as actuator.
Manual Active Stop produc-
tion
Actuator 2 offline Remote actuator/
expansion 2 not connected
Check if the slave cabinet used as a slave is configu­red correctly. Then check the correct wiring betwe­en the J23 port of pCO5+ of the main cabinet and the BMS2 port of pCO5+ of the cabinet configured as actuator.
Manual Active Stop produc-
tion
Offline supervision system If the On-Off control
by supervisor is used, the supervisor has not received requests for more than 30 seconds.
Check if the supervisor network settings (protocol, baud rate and slave address) coincide with those of the Humifog
Automatic Not active Stop produc-
tion
The production is
stopped only if the
adjustment is enabled by
the supervisor
51
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
Alarm Cause Solution Reset Alarm
relay state
Action Note
Broken or disconnected heat recovery signal
In IEC mode with analogic heat recove­ry signal status, the si­gnal is not connected or out of range
Check the correct connection of the recuperator at the U5 input, then check that the signal is set correctly
Manual Active Stop produc-
tion
The signalling is reset manually: the production is resumed automatically as soon as it detects a valid signal from the recuperator.
System block With backup and/or
rotation enabled: it was not possible to start any of the two pumping stations following four consecutive switch requests for less than 15 minutes from one to the other without any Humifog starting
Check in the Alarm history what the switch has generated and based on the viewed alarm, follow the instructions in this table
Manual Active Stop produc-
tion
The alarm that has cau­sed the switch is easily indetified in the alarm history (Cg01 screen or main screen shortcut) as it is saved immediately before the “Unit Switch” event
Rack low temperature The temperature
measured on the rack is lower than the set threshold
Check the environment conditions in the vicinity of the rack, possibly increase the threshold
Manual Active View only If the production reduc-
tion is enabled in case of rack low temperature (Bbc05 screen), the current production is reduced based on the
measured temperature Broken or disconnected rack temperature probe
The rack temperature probe is broken or improperly con­nected
Check the connection and the status of the rack temperature probe
Manual Not active View only If the production reduc-
tion is enabled in case
of rack low temperature
(Bbc05 screen), the
production reduction
feature is disabled
52
P
VFD
GR
N
L
PE
N
L
GR
N
L
U
V
W
GR
S1S2S3S4S5FSA1
AC
AC
SC
AM
MA
MB
MC
U
V
W
FAN
S1
K_EVFILL(nc)_1
SC
TB - GOB
K (no)
ID6
G0A
FVD - FR
FVD - FC
GA
G0A
GA
NO13
FVD - MC
G
GR N
L
F3 F4F5F1 F2
L1
T1
TR-B
TR-A
L2
T2
400 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [GA]
F6 F7
24V [GA]
P P
F9
24 (GB)
C
C
C
C
H
C
C
C
C
C
F
F
F F
E
E
E
E
E
AAA
B B
D
D
C
K (nc)
TB - COM
TB - ROEN
TB-G0A
HT-DVB
LP
HP
FVD - MB
TB - PEN TB - ROAL
TB - RKEN TB - FLUX
TB - ONOF
pCO (H) P
pCO (H)
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO4-NO5-NO6
NO7-NO9
NO11
NO12
NO16-NO17
NO21
NO22
GR
G0BG0BG0BG0BG0BG0B
COM
ROEN
K (COM)
K (NO)
G0AG0AG0A
TRA - 0V
(second.)
(second.)
FLUX
RKEN
ONOF
BKUP
ROAL
PEN
J7 - ID12
J7 - ID11
J7 - ID10
J7 - ID9
J5 - ID4
J5 - ID3
NOL
GR
H
C
NO1-NO2-NO 3- NO1(pCOe)
NO10- NO3(pCOe)
NO18-NO19
NO14-NO1 5- NO2(p COe)
NO20- NO4(pCOe)
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12. WIRING DIAGRAMS
12.1 Wiring diagram humiFog multizone - Master - CE - MONOFASE
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINAL: 5,3 min -> 7 max DOUBLE TERMINAL: 5,3 min -> 7 max TERMINAL WITH FUSE: 13 min -> 16 max GROUND TERMINAL: 13 min -> 16 max
53
GA
TB - NC4
TB - NC5
TB - NC6
TB - NC3
TB - NC2
TB - NC1
DVB
TB - NOL
TB - NO6
TB - NO5
TB - NO4
TB - NO3
TB - NO2
TB - NO1
TB - N C1
TB - NO1
TB - NC4
TB - NO4
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Nm) = 0,5 min -> 0,6 max
FUSES TABLEI:
F1-F2 -> 1A T 5x20 250V F3-F4 -> 4A T 5x20 250V F5 -> 4A T 5x20 250V F6-F7 -> 12A T 10,3x38 500V (UA100/200*****) F6-F7 -> 20A T 10,3x38 500V (UA320/480*****) F6-F7 -> 25A T 10,3x38 500V (UA600*****) F9 -> 16A T 10,3x38 500V (UA100/460****) F9 -> 25A T 10,3x38 500V (UA600*****)
54
P
VFD
GR
U
V
W
GR
S1S2S3
S4
S5
FSA1AC
AC
SC
AM
MA
MB
MC
U
V
W
FAN
S1
K_EVFILL(nc)_1
SC
TB - GOB
K (no)
ID6
G0A
FVD - FR
FVD - FC
GA
G0A
GA
NO13
FVD - MC
F3
F4
F5
F1
F2
TR-B
TR-A
600 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [GA]
24V [GA]
P P
F9
24 (GB)
C
C
C
C
C
C
C
F
F
F F
E
E
E
E
E
AAA
B B
D
D
C
K (nc)
TB - COM
TB - R OEN
TB-G0A
HT-DVB
LP
HP
FVD - MB
TB - PEN TB - ROAL
TB - RKEN TB - FLUX
TB - ONOF
pCO (H)
P
pCO (H)
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO4-NO5-NO6
NO7-NO9
NO11
NO12
NO16-NO17
NO21
NO22
GR
G0B
G0B
G0BG0B
G0BG0B
COM
ROEN
K (COM)
K (NO)
G0AG0A
G0A
TRA - 0V
(second.)
(second.)
FLUX
RKEN
ONOF
BKUP
ROAL
PEN
J7 - ID12
J7 - ID11
J7 - ID10
J7 - ID9
J5 - ID4
J5 - ID3
NOL
GR
H
C
NO1-NO2-NO3- NO1(pCOe)
NO10 - NO 3( p COe)
NO18-NO19
NO14-NO15- NO2(pCOe)
NO20 - NO 4( p COe)
L3 L2
GR
L1
L2
T2
C
C
C
H
T3
L3
G
L1
T1
C
B
F6
F8
F7
C
L3
L2
L1
PE
GR
L3
L2
L1
L1
L2
L3
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12.2 Wiring diagram humiFog multizone - Master - CE - TRIFASE (solo per UA10K***)
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINAL: 5,3 min -> 7 max DOUBLE TERMINAL: 5,3 min -> 7 max TERMINAL WITH FUSE: 13 min -> 16 max GROUND TERMINAL: 13 min -> 16 max
55

GA
TB - NC4 TB - NC5
TB - NC6
TB - NC3
TB - NC2
TB - NC1
DVB
TB - NOL
TB - NO6
TB - N O5
TB - NO4
TB - NO3
TB - N O2
TB - NO1
TB - NC1
TB - NO1
TB - NC4
TB - NO4
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Nm) = 0,5 min -> 0,6 max
FUSES TABLEI:
F1-F2 -> 1A T 10,3x38 500V F3-F4 -> 4A T 10,3x38 500V F5 -> 4A T 5x20 250V F6-F7-F8 -> 25A F 10,3x38 500V F9 -> 25A T 10,3x38 500V
56
P
VFD
GR
N
LPEN
L
GR
N
L
U
V
W
GR
S1S2S3S4S5FSA1
AC
AC
SC
AM
MA
MB
MC
U
V
W
FAN
S1
K_EVFILL(nc)_1
SC
TB - GOB
K (no)
ID6
G0A
FVD - FR
FVD - FC
GA
G0A
GA
NO13
FVD - MC
GR N
L
F3 F4F5F1 F2
L1
T1
TR-B
TR-A
L2
T2
400 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [GA]
F6 F7
24V [G A]
P P
F9
24 (GB)
K (nc)
TB - COM
TB - ROEN
TB-G0A
HT-DVB
LP
HP
FVD - MB
TB - PEN TB - R OAL
TB - RKEN TB - FLUX
TB - ONOF
pCO (H) P
pCO (H)
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO4-NO5-NO6
NO7-NO9
NO11
NO12
NO16-NO17
NO21
NO22
GR
G0BG0B
G0B
G0B
G0BG0B
COM
ROEN
K (COM)
K (NO)
G0AG0A
G0A
TRA - 0V
(second.)
(second.)
FLUX
RKEN
ONOF
BKUP
ROAL
PEN
J7 - ID12
J7 - ID11
J7 - ID10
J7 - ID9
J5 - ID4
J5 - ID3
NOL
GR
PONTI AVVITATI / TERMINAL JUMPER
NO1-NO 2-NO3- NO 1(pCOe)
NO10- NO3(pCOe)
NO18-NO19
NO14- NO15- NO2(p COe)
NO20- NO4(pCOe)
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12.3 Wiring diagram humiFog multizone - Master - UL - MONOFASE
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINAL: 5,3 min -> 7 max DOUBLE TERMINAL: 5,3 min -> 7 max TERMINAL WITH FUSE: 13 min -> 16 max GROUND TERMINAL: 13 min -> 16 max
57

GA
TB - NC4 TB - NC5
TB - NC6
TB - NC3
TB - NC2
TB - NC1
DVB
TB - NOL
TB - NO6
TB - NO5
TB - NO4
TB - NO3
TB - NO2
TB - NO1
TB - NC1
TB - NO1
TB - NC4
TB - NO4
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Pound Inches) = 4,4 min -> 5,3 max
FUSES TABLEI:
F1-F2 -> 1A T 5x20 250V F3-F4 -> 4A T 5x20 250V F5 -> 4A T 5x20 250V F6-F7 -> 12A T 10,3x38 500V (UA100/200*****) F6-F7 -> 20A T 10,3x38 500V (UA320/480*****) F6-F7 -> 25A T 10,3x38 500V (UA600*****) F9 -> 20A F 10,3x38 500V (UA100/460****) F9 -> 30A F 10,3x38 500V (UA600****)
58
P
VFD
GR
U
V
W
GR
S1S2S3
S4
S5
FSA1AC
AC
SC
AM
MA
MB
MC
U
V
W
FAN
S1
K_EVFILL(nc)_1
SC
TB - GOB
K (no)
ID6
G0A
FVD - FR
FVD - FC
GA
G0A
GA
NO13
FVD - MC
F3
F4
F5
F1
F2
TR-B
TR-A
600 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [G A]
24V [GA]
P P
F9
24 (GB)
C
C
C
C
C
C
C
F
F
F
F
E
E
E
E
E
AAA
B B
D
D
C
K (nc)
TB - COM
TB - R OEN
TB-G0A
HT-DVB
LP
HP
FVD - MB
TB - PEN TB - ROAL
TB - RKEN TB - FLUX
TB - ONOF
pCO (H) P
pCO (H)
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO4-NO5-NO6
NO7-NO9
NO11
NO12
NO16-NO17
NO21
NO22
GR
G0BG0BG0BG0BG0BG0B
COM
ROEN
K (COM)
K (NO)
G0A
G0AG0A
TRA - 0V
(second.)
(second.)
FLUX
RKEN
ONOF
BKUP
ROAL
PEN
J7 - ID12
J7 - ID11
J7 - ID10
J7 - ID9
J5 - ID4
J5 - ID3
NOL
GR
H
C
NO1-NO2-NO3- NO1(pCOe)
NO10- NO3( p C O e )
NO18-NO19
NO14-NO1 5- NO2 (p COe)
NO20- NO4( p C O e )
L3 L2GR
L1
L2
T2
C
C
C
H
T3
L3
G
L1
T1
C
B
F6F8
F7
C
L3
L2
L1
PE
GR
L3
L2
L1
L1
L2
L3
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12.4 Wiring diagram humiFog multizone - Master - UL - TRIFASE
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINALS: 5,3 min -> 7 max DOUBLE TERMINAL: 5,3 min -> 7 max TERMINAL WITH FUSE: 13 min -> 16 max GROUND TERMINAL: 13 min -> 16 max
59

GA
TB - NC4 TB - NC5
TB - NC6
TB - NC3
TB - NC2
TB - NC1
DVB
TB - N OL
TB - N O6
TB - N O5
TB - N O4
TB - N O3
TB - N O2
TB - N O1
TB - NC1
TB - NO1
TB - NC4
TB - NO4
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Pound Inches) = 4,4 min -> 5,3 max
FUSES TABLEI:
F1-F2 -> 1A T 10,3x38 500V F3-F4 -> 4A T 10,3x38 500V F5 -> 4A T 5x20 250V F6-F7-F8 -> 25A F 10,3x38 500V F9 -> 30A F 10,3x38 500V
60
TB - GOB
G
GR N
L
F3
F4F5F1 F2
L1
T1
TR-B
TR-A
L2
T2
400 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [GA]
F9
24 (GB)
C
C
C
C
H
C
C
C
C
C
D
D
C
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO1-NO2-NO3
NO4-NO5-NO6
NO7-NO9
NO10
NO11
NO12
NO14-NO15
NO16-NO17
NO18-NO19
NO20
NO21
NO22
G0B
G0BG0B
G0B
G0B
G0B
G0AG0A
J4 - VG0
FLUX
RKEN
ONOF
J7 - ID12
J7 - ID11
J7 - ID10
C
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12.5 Wiring diagram humiFog multizone - Slave - CE
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINAL: 0,6 min -> 0,8 max DOUBLE TERMINAL: 0,6 min -> 0,8 max TERMINAL WITH FUSE: 1,5 min -> 1,8 max GROUND TERMINAL: 1,5 min -> 1,8 max
61
TB - N O1
TB - N O2 TB - N O3
TB - N O4
TB - N O5 TB - N O6 TB - N OV
TB - NC4 TB - NC5
TB - NC6
TB - NC1
TB - NC2
TB - NC3
TB - RKEN TB - FLUX
TB - ONOF
TB - BKUP
pCO (H) P
pCO (H)
TB - G0A
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Pound Inches) = 0,5 min -> 0,6 max
FUSES TABLEI:
F1-F2 -> 1A F 5x20 600V F3-F4 -> 4A F 5x20 600V F5 -> 4A T 5x20 250V F9 -> 16A T 10,3x38 500V
62
TB - GOB
G
GR N
L
F3
F4F5F1
F2
L1
T1
TR-B
TR-A
L2
T2
400 VA
100 VA
0 [G0A]
0 (G0B)
24 (GB)
24V [GA]
NOV
G0B
NC1
NO23
NC2
NC3
NC4
NC5
NC6
NO1
NO2
NO3
NO4
NO5
NO6
NO1-NO2-NO3
NO4-NO5-NO6
NO7-NO9
NO10
NO11
NO12
NO14-NO15
NO16-NO17
NO18-NO19
NO20
NO21
NO22
G0B
G0BG0BG0BG0B
G0BG0A
G0A
J4 - VG0
FLUX
RKEN
ONOF
J7 - ID12
J7 - ID11
J7 - ID10
C
F9
24 (GB)
C
C
C
C
H
C
C
C
C
C
D
D
C
TB - RKEN
TB - FLUX
TB - ONOF
TB - BKUP
pCO (H) P
pCO (H)
TB - G0 A
MORSETTIERA UTENTE / USER TERMINAL BOARD (use copper conductor only)
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
12.6 Wiring diagram humiFog multizone - Slave - UL
TORQUE FORCE TERMINALS (Nm)
SINGLE TERMINAL: 0,6 min -> 0,8 max DOUBLE TERMINAL: 0,6 min -> 0,8 max TERMINAL WITH FUSE: 1,5 min -> 1,8 max GROUND TERMINAL: 1,5 min -> 1,8 max
63
TB - N O1
TB - N O2 TB - N O3
TB - N O4
TB - N O5 TB - N O6 TB - N OV
TB - NC4 TB - NC5
TB - NC6
TB - NC1
TB - NC2
TB - NC3
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
FORZA DI SERRAGGIO MORSETTI pCO5+
TORQUE FORCE TERMINALS pCO5+
(Pound Inches) = 0,5 min -> 0,6 max
FUSES TABLEI:
F1-F2 -> 1A F 5x20 600V F3-F4 -> 4A F 5x20 600V F5 -> 4A T 5x20 250V F9 -> 16A T 10,3x38 500V
64
ENG
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
Notes:
CAREL INDUSTRIES - Headquarters
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy) Tel. (+39) 049.9716611 - Fax (+39) 049.9716600 e-mail: carel@carel.com - www.carel.com
Agenzia / Agency:
“humiFog multizone - pumping unit+0300066EN - rel. 1.2 - 10.12.2015
Loading...