49
ENG
“humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015
installeruserservice
11. TABLE OF ALARMS
When an alarm is activated, the alarm button starts flashing.
In these conditions, pressing the alarm button once displays the type of alarm.
In the case of potentially dangerous alarms, the controller automatically stops production. For some alarm events, the alarm relay is also activated at the
same time as the signal (see the table below).
Alarm Cause Solution Reset Alarm
relay state
Action Note
No valid model selected After replacing the
control, the software
was not configured
correctly
Configure the unit model in use on the Ca01 screen Automatic Active Disabled pro-
duction
It is possible to access
the Ca01 screen directly
from the alarm screen
Nominal rack capacity = 0 The flow rate of the
distribution system
has not been set
correctly
Configure the capacity of the rack on the Bbb01/
Bbb02 screen (according to the pump control type)
Automatic Active Disabled pro-
duction
Bbb01 is used for a
system with flow rate
modulation control,
Bbb02 for a system with
constant pressure It is
possible to access the
configuration screen
directly from the alarm
screen
The number of collectors
is not set
The number of
collectors by which
the steps of the rack
are formed of has not
been set
Set the number of collectors on the Bbb03 screen Automatic Active Disabled pro-
duction
It is possible to access
the Bbb03 screen directly
from the alarm screen
Water treatment plant ID4-IDC1 digital
input on the opened
control.
Check the proper operation of the water treatment
plant. If correct, check on the Bab01 screen that
the input logic coincides with that of the plant
alarm signal - If correct, manually close or open the
entrance with a plank; if the alarm persists, replace
the control
Automatic Active Stop produc-
tion
Low pressure alarm Low pressure at
water inlet
Check the circuit and the pressure of the supplied
water
Automatic Active Stop produc-
tion
High conductivity
warning
The conductivity
of the water has
reached the warning
threshold
Check the water treatment system. If absent, increase the warning threshold on the Bab02 screen
Manual Not active Solo segnala-
zione
High conductivity alarm The conductivity
of the water has
reached the alarm
threshold
Check the water treatment system. If absent, increase the alarm threshold on the Bab02 screen
Manual Active Stop produ-
zione
Bypass high temperature
alarm
Excessive recycling
of the water on the
bypass
Check the operating temperature of the installation
(environment and water); Check if the distribution
system is not obstructed in such a way to cause the
recycling of the water
Automatic Not active Only warning
Inverter alarm Malfunction of
inverter
Check, based on the signalling on the display, the
status of the inverter and eventually replace it
Automatic Active Stop produc-
tion
The alarm is automatically reset on the control.
For the inverter, see
chapter 7 of the inverter’s
manual
High temperature alarm at
the thermostat bypass
Excessive recycling
of the water on the
bypass
Check the proper operation of the water treatment
plant. If correct, check on the Bab01 screen that
the input logic coincides with that of the plant
alarm signal - If correct, manually close or open the
entrance with a plank; if the alarm persists, replace
the control
Manual Active Stop produc-
tion
Low temperature at the
cabinet pump
Water temperature at
inlet lower than 2°C
Reheat the supplied water or the cabinet with a
proper dimensioned heater
Automatic Active Stop produc-
tion
High pressure alarm from
the pressure switch
Flow pressure exceeding 90 bar
Contact CAREL for instructions on checking the
conditions of the bypass valve
Manual Active Stop produc-
tion
High pressure warning
from the presure probe
Flow pressure higher
than 30% of the
nominal pressure
Contact CAREL for instructions on checking the
conditions of the bypass valve
Automatic Not active Only warning
Low pressure warning
from the presure probe
During production,
the flow pressure is
lower than 20 bar
Check the tightnes of the hydraulic circuit at
discharge
Manual Active Stop produc-
tion
Remote area # offline On the Multi-area
pumping station,
the slave unit is not
connected to the
fieldbus network
Check the correct setting (address, enable) of the remote areas connected to the pumping station and
that there are no more areas with the same address.
Then check the wiring and the correct operation of
the optional fieldbus card
Automatic Active Stop produc-
tion
It is possible to check the
correct addressing on the
Bc01 screens (Pumping
station), Bbc01 and
Bbd03 (Remote area)
Offline pumping station On the “Remote area”
cainet, the master
unit is not connected
to the BMS2 port
Check if the address of the remote area corresponds with the one set on the pumping station and
that there are no more other areas with the same
address. Then check the wiring and the correct
operation of the optional fieldbus card
Automatic Active Stop produc-
tion
It is possible to check the
correct addressing on the
Bc01 screens (Pumping
station), Bbc01 and
Bbd03 (Remote area)