CaptiveAire A1-IBT 200-G10 User Manual

Modular IndIrect FIred Bent tuBe Heater (IBt)
closed view
The Modular Indirect Fired Bent Tube Heater (Model IBT) is designed to deliver clean
air into an indoor environment. The push-through design of the unit ensures that
combustion fumes will not enter the fresh air stream being delivered into the space.
The standard unit includes a blower module and the indirect heater module with multiple options for discharge and
intake. Five housing sizes are available in our modular design with up to four furnaces available in one unit. The air
volume range is from 800 to 15,000 CFM and up to a maximum of 3 inches wg. for static pressure. The unit can
deliver a constant 83% efficiency over the entire gas-firing range.
Features & BeNeFIts
Bent Tube In-Shot Style Furnace with Type 409 Stainless-Steel Heat Exchanger
High Turndown Ratio Ranging from 6:1 to Maximum of 28:1
Fully Modulating Gas Output Control Standard
Constant 83% Efficiency Over Entire Gas Firing Range — Variable Power­Vent Blower Speed Control
Standard High Fire Start to Ensure Optimum Light-Off
Standard Inlet & Manifold Pressure Gauges
Light Weight Design with Condensed Footprint
Isolated & Insulated Electrical Controls Vestibule
Fully Insulated Cabinet and Power-Venter Post Purge for Condensation Prevention
End Discharge or Integral Down Discharge
Discharge, Space or Building Automation System (BAS) Temperature Control
aDDItIONaL OPtIONs
5:1 Turndown for Propane (LP) to Maximum of 23:1
Blower on Delay for Heat Exchanger Reheat
Motorized Intake Damper
Single Point Electrical Connection
Freeze-stat Option
Roof Curbs or Indoor Hanging Cradle
Variable Air Volume (VAV) Controls
Dedicated Combustion
DX and Chilled Water Cooling Section
CertIFICatIONs
ETL listed to the ANSI Z83.8-2006 and CSA 2.6-2006 standards.
The furnace is certified by the American Gas Association and approved by the Canadian Gas Association.
4641 Paragon Park Rd, Raleigh, NC 27616 | p. 919.882.2410 | p. 800.334.9256 | f. 919.882.5204 | www.captiveaire.com
Modular IndIrect FIred Bent tuBe Heater (IBt)
Unit Dimensions
(all dimensions nominal & given in inches)
Model A B C D E F (NPT)
A1-IBT 150-G10 817 92-1/4 49-1/2 39-9/16 44-3/8 71 3/4 150 20.8 124.5 6 7” WC 14” WC
A1-IBT 200-G10 847 92-1/4 49-1/2 39-9/16 44-3/8 71 3/4 200 27.7 166 6 7” WC 14” WC
A1-IBT 300-150-150-G10 902 92-1/4 49-1/2 39-9/16 44-3/8 71 3/4 300 20.8 249 12 7” WC 14” WC
A1-IBT 400-200-200-G10 976 92-1/4 49-1/2 39-9/16 44-3/8 71 3/4 400 27.7 332 12 7” WC 14” WC
A2-IBT 200-G15 1020 100-1/4 49-1/2 39-9/16 53-5/8 79 1 200 27.7 166 6 7” WC 14” WC
A2-IBT 300-G15 1112 100-1/4 49-1/2 53-7/8 53-5/8 79 1 300 41.5 249 6 7” WC 14” WC
A2-IBT 400-G15 1191 100-1/4 49-1/2 53-7/8 53-5/8 79 1 400 55.3 332 6 7” WC 14” WC
A2-IBT 400-200-200-G15 1079 100-1/4 49-1/2 39-9/16 53-5/8 79 1 400 27.7 332 12 7” WC 14” WC
A2-IBT 600-300-300-G15 1233 100-1/4 49-1/2 53-7/8 53-5/8 79 1 600 41.5 498 12 7” WC 14” WC
A2-IBT 800-400-400-G15 1346 100-1/4 49-1/2 53-7/8 53-5/8 79 1 800 55.3 664 12 7” WC 14” WC
A3-IBT 400-G18 1472 105-1/4 57-3/4 57-1/16 51-5/8 84 1 400 55.3 332 6 7” WC 14” WC
A3-IBT-600-300-300-G18 1590 105-1/4 57-3/4 57-1/16 51-5/8 84 1 600 41.5 498 12 7” WC 14” WC
A3-IBT 800-400-400-G18 1728 105-1/4 57-3/4 57-1/16 51-5/8 84 1 800 55.3 664 12 7” WC 14” WC
A3-IBT 1000-300-300-400-G18 2467 165-3/8 57-3/4 57-1/16 51-5/8 84 1 1000 41.5 830 20 7” WC 14” WC
A3-IBT-1200-400-400-400-G18 2579 165-3/8 57-3/4 57-1/16 51-5/8 84 1 1200 55.3 996 18 7” WC 14” WC
A4-IBT 800-400-400-920 2099 124-5/16 57-3/4 57-1/16 76-3/8 42 1 800 55.3 664 12 7” WC 14” WC
A4-IBT 1000-300-300-400-920 2982 184-7/16 57-3/4 57-1/16 76-3/8 42 1 1000 41.5 830 20 7” WC 14” WC
A4-IBT 1200-400-400-400-920 3094 184-7/16 57-3/4 57-1/16 76-3/8 42 1 1200 55.3 996 18 7” WC 14” WC
A4-IBT 1400-300-300-400-400-920 3206 184-7/16 57-3/4 57-1/16 76-3/8 42 1 1400 41.5 1162 28 7” WC 14” WC
A4-IBT 1600-400-400-400-400-920 3318 184-7/16 57-3/4 57-1/16 76-3/8 42 1 1600 55.3 1328 24 7” WC 14” WC
A5-IBT 800-400-400-925 2587 134-5/16 66-3/8 59-15/16 71-3/8 52-3/4 1 800 55.3 664 12 7” WC 14” WC
A5-IBT 1000-300-300-400-925 3359 194-7/16 66-3/8 59-15/16 71-3/8 52-3/4 1 1000 41.5 830 20 7” WC 14” WC
A5-IBT 1200-400-400-400-925 3471 194-7/16 66-3/8 59-15/16 71-3/8 52-3/4 1 1200 55.3 996 18 7” WC 14” WC
A5-IBT 1400-300-300-400-400-925 3583 194-7/16 66-3/8 59-15/16 71-3/8 52-3/4 1 1400 41.5 1162 28 7” WC 14” WC
A5-IBT 1600-400-400-400-925 3695 194-7/16 66-3/8 59-15/16 71-3/8 52-3/4 1 1600 55.3 1328 24 7” WC 14” WC
Weight (lbs)
BTU Range* (MBH)
Burner
Input
BTU Low
BTU High
Turndown
Ratio
*All models are fully electronically modulating.
Gas Pressure
Min Max