CaptiveAire 5JA0902B User Manual

STEAM SELECTION 4.23.21.999
Customer: Date: 4/1/2004 Contact: From: Telephone: Company: Fax: Return Tel: Job: Return Fax:
G I V E N D A T A Construction
Air Side
Item: SCM1 Air Flow (SCFM) Coils Per Bank: 1 Altitude (FT): Allow Opp. End: No Ent. Air DB (°F): Tube OD (IN): 5/8 Lvg. Air DB (°F): Style: Distributing Total Capacity (MBH): Fins Per Inch: Optimize Max Air PD (IN WG): Rows: Optimize Fin Surface: Optimize ABC
Steam Side
Fin Height (IN): 19.50 Pressure (PSIG): Finned Length (IN): 16.50 Tubing Mat. (IN) 0.020 Copper Fin Mat. (IN) 0.0075 Aluminum
O U T P U T D A T A
Model Number: Air Velocity: Total Capacity: Sens. Capacity: Lvg. Air DB: Lvg. Air WB: Standard APD Condensate: Conn. Size: Weight: Notes:
(SFPM)
(MBH) (MBH)
(°F)
(°F) (IN WG) (LB/HR)
(IN)
(LB)
Specified Coil
5JA0902B
1,006.99
176.49 N/A
72.03 N/A
0.54
183.51
2.50 34
A
Notes:
A) ARI Certified And Rated In Accordance With ARI 410.
2,250.00
0.00
0.00
70.00
0.00
0.00
5.00
CERTIFIED DRAWING
Customer: Date: 4/1/2004 Contact: From: Telephone: Company: Fax: Return Tel: Job: Return Fax:
MODEL NUMBER
ITEM QTY TYPE FPI ROWS FIN FH (IN) FL (IN) HAND
SCM1 1 5JA 09 02 B 19.50 16.50 N/A
MATERIALS OF CONSTRUCTION OPTIONS Fins Tubes Casing Supply Return
.0075 Aluminum .020 Copper Galvanized Steel
2.500 MPT Carbon Steel
2.500 MPT Carbon Steel
Casing Type Vent
Pitched Horizontal .50 FPT on Face
Label Kit Phenolic Coating Mounting Holes Boxed Headers Vacuum Breaker Thermostatic Air Vent
No No No No No No
CONNECTION FLANGES
SIZE A B C D E F H I J L M N R S T W
2.50 2.50 N/A 3.00 N/A 11.17 N/A 22.50 22.75 6.00 19.50 4.75 N/A 1.50 1.50 1.50 5.00
1. All dimensions are in inches.
2. Phenolic coated coils require a longer lead-time since they must be re-tested after coating.
DIMENSIONAL DATA (IN)
GENERAL NOTES
Loading...