CaptiveAire 27120-22 Installation Manual

Series 27100, 28000
Vertical DETECT-A-FIRE® Units Installation Instructions
12.01.D
DESCRIPTION
DETECT-A-FIRE¨ thermal detectors are UL Listed, UL of Canada available upon request, and FM Approved detec­tion and release devices used with fire detection systems to activate alarms and actuate extinguishing systems. This Rate Compensated device combines the best features of both fixed temperature and rate-of-rise detectors.
ELECTRICAL RA TING
tcatnoC
rebmuNledoM
nonoitarepO
erutarepmeT
esiR
*gnitaRlacirtcelE
)ylnOevitsiseR(
Effective: August 1999
02172
02082
12172
12082
*Although incandescent lamps are considered resistive, their inrush cur­rent is 10 - 15 times their steady current. Do not exceed ratings.
snepO
o
054(
)xaMF
sesolC
spmA0.5 spmA5.0
spmA0.5 spmA5.0 spmA0.2 spmA0.1
CAV521
CDV521
CAV521
CDV521 CDV42 CDV84
LOCATION
DETECT-A-FIRE® Units are precision temperature sensors. They must be mounted in an area (normally a ceiling) so that:
1. The detector spacing complies with both system require­ments and requirements of the agency having local ju­risdiction.
2. The thermal air path to the shell is not obstructed.
Spacing per UL, FM, and UL of Canada is shown in T able 1. Distances given are for between units on smooth ceilings. Distances from partitions or walls are half that shown. To assure that all spacing requirements are met, consult the authority having local jurisdiction.
MOUNTING
Detect-A-Fire units are not position sensitive. Horizontal and vertical detectors refer to the most common mounting con­figuration for that unit. However, each type can be mounted either horizontally or vertically depending on the application and installation requirements.
Table 1.
o
F
0418-/7+050552kcalB 0618-/7+525252kcalB 0918-/7+050552etihW 0128-/7+520552etihW 5228-/7+520552etihW 57201±520552eulB 52301±050552deR 06301±520552deR 05451±520552neerG 00551±050552egnarO 00602±A/N0552egnarO 52752±A/N0552egnarO
o
gnitteS
F
ecnareloT
U
®
L
)teefni(SGNICAPS
roloC
gnidoC
Note: For clean agents and CO2 suppression systems,
ceiling spacing 20 ft. (6.1 meters) apart unless oth­erwise specified.
Not all units are suitable for all hazard location applications. Refer to Table 2 and markings on the detector for hazard­ous location suitability .
1
suodrazaH
noitacoL
spuorG,*IssalC ;DdnaC,B,A
spuorG,*IIssalC
GdnaF,E
spuorG,*IssalC
;DdnaC,B
spuorG,*IIssalC
GdnaF,E
*Division 1 and 2.
INSTALLATION
Table 2.
ledoM rbmuN
3-02082 5-12082
0-02172 0-12172 0-12082
roFderiuqeRgnittiF
sgnitsiLCLU,LU
lavorppAMFdna
22-02172 02-12172
aotrotcetedtnuoM
nignittifdetsil-ylbatius
htiwecnadroca
edoCcirtcelElanoitaN
ytirohtualacolro/dna
.noitcidsirujgnivah
Series 28000 units are similar to Series 27100 units except they have two 1/2-14 NPT threads for mounting.
The unit may be mounted as described above or may be threaded into a 1/2-14 NPT tapped hole in the vessel wall or threaded into a coupling brazed or welded to the vessel wall.
FIELD WIRING REQUIREMENT
Field wiring must be capable of withstanding the maximum anticipated ambient temperature in the application.
FUNCTIONAL TEST
When used with automatic fire extinguishing systems first disconnect the initiator/solenoid leads from the panel and connect a 24 VDC bulb to initiator terminals in the control unit. Heat the D-A-F units with a heat lamp or other conve­nient source. When the bulb in the control unit changes state, remove heat source and allow D-A-F unit to cool. Reset con­trol unit. Test lamp must change state and stay changed after system is reset. Do not reconnect initiator/solenoid leads until all D-A-F units have cooled below set point as indicated by test lamp. When D-A-F units are used in other types of systems, disconnect them from the system, connect a 24 VDC lamp and power source in series with the D-A-F units and test with heat source as above. Make sure that contacts have reset to normal condition before reconnecting to sys­tem circuit.
Figure 1
Figure 2
1. Kidde-Fenwal recommends that standard 4-inch oc­tagonal outlet boxes be used to mount detectors.
2. Attach detector to outlet box cover through a 0.875 inch diameter hole and using two 1/2-14 NPT retainer nuts as indicated.
3. Connect system wiring to detector per Figure 3 and ap­plicable electrical codes.
4. Ordinary Locations: The DETECT-A-FIRE Units are to be installed in grounded metallic junction boxes only . They are to be secured to the boxes using two lock nuts, one on either side of the mounting plate. DETECT­A-FIRE Units are not to be installed in non-metallic junc­tion boxes.
5. Hazardous Locations: For Class I, Division 1 and 2 locations, install the DETECT-A-FIRE Unit in a listed explosion-proof enclosure with a minimum thread en­gagement of five full turns. No non-conductive material is to be placed on the threaded joint of the DETECT-A­FIRE Unit or in the listed explosion-proof enclosure. For Division 2 locations, assure that a protective ground terminal is provided in the listed explosion-proof enclo­sure when flexible metal conduit is used.
6. Do not exceed a maximum torque without thread lubri­cant of 20 foot-pounds (27.1 Newton Meters).
2
Loading...
+ 2 hidden pages