Campbell Scientific SDM-SW8A User Manual

SDM-SW8A 8 Channel
8 CHANNEL SWITCH CLOSURE INPUT MODULE
TO DATALOGGER
C2
C3
12V
Switch Closure Module
Revision: 7/10
MADE IN USA
SDM - SW8A
IN 8
5V
IN 7
5V
IN 6
5V
IN 5
5V
IN 4
5V
5V
5V
5V
C1 OUT
C1 IN
Copyright © 1987-2010
Campbell Scientific, Inc.

Warranty and Assistance

The SDM-SW8A SWITCH CLOSURE INPUT MODULE is warranted by Campbell Scientific, Inc. to be free from defects in materials and workmanship under normal use and service for twelve (12) months from date of shipment unless specified otherwise. Batteries have no warranty. Campbell Scientific, Inc.'s obligation under this warranty is limited to repairing or replacing (at Campbell Scientific, Inc.'s option) defective products. The customer shall assume all costs of removing, reinstalling, and shipping defective products to Campbell Scientific, Inc. Campbell Scientific, Inc. will return such products by surface carrier prepaid. This warranty shall not apply to any Campbell Scientific, Inc. products which have been subjected to modification, misuse, neglect, accidents of nature, or shipping damage. This warranty is in lieu of all other warranties, expressed or implied, including warranties of merchantability or fitness for a particular purpose. Campbell Scientific, Inc. is not liable for special, indirect, incidental, or consequential damages.
Products may not be returned without prior authorization. The following contact information is for US and International customers residing in countries served by Campbell Scientific, Inc. directly. Affiliate companies handle repairs for customers within their territories. Please visit www.campbellsci.com to determine which Campbell Scientific company serves your country.
To obtain a Returned Materials Authorization (RMA), contact Campbell Scientific, Inc., phone (435) 753-2342. After an applications engineer determines the nature of the problem, an RMA number will be issued. Please write this number clearly on the outside of the shipping container. Campbell Scientific's shipping address is:
CAMPBELL SCIENTIFIC, INC.
RMA#_____ 815 West 1800 North Logan, Utah 84321-1784
For all returns, the customer must fill out a “Declaration of Hazardous Material and Decontamination” form and comply with the requirements specified in it. The form is available from our website at completed form must be either emailed to repair@campbellsci.com 435-750-9579. Campbell Scientific will not process any returns until we receive this form. If the form is not received within three days of product receipt or is incomplete, the product will be returned to the customer at the customer’s expense. Campbell Scientific reserves the right to refuse service on products that were exposed to contaminants that may cause health or safety concerns for our employees.
www.campbellsci.com/repair
. A
or faxed to
SDM-SW8A Table of Contents
PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab for links to specific sections.
1. Function........................................................................1
2. Specifications ..............................................................2
3. Power Supply Considerations....................................3
4. Connections ................................................................. 4
4.1 Connections to Dataloggers and Other SW8As........................................4
4.2 Sensor Connections ..................................................................................4
5. Internal Jumpers..........................................................4
5.1 Address Jumpers.......................................................................................4
5.2 Measurement Jumpers ..............................................................................6
6. Datalogger Programming............................................ 6
6.1 CRBasic Programming .............................................................................6
6.1.1 SDMSW8A Instruction...................................................................6
6.1.2 SDMSpeed Instruction....................................................................7
6.2 Edlog Programming..................................................................................9
7. Datalogger Program Details .....................................10
7.1 Datalogger Scan Rate .............................................................................10
7.2 First Scan ................................................................................................10
7.3 Watchdog Reset......................................................................................11
8. Measurement Applications ....................................... 13
8.1 SPDT Switch Closure.............................................................................13
8.2 SPST Switch Closure..............................................................................13
8.3 DC Voltage Pulse ...................................................................................14
8.4 Duty Cycle..............................................................................................14
9. Theory of Operation ..................................................15
Appendix
A. Edlog Program Example......................................... A-1
i
SDM-SW8A Table of Contents
List of Tables
List of Figures
1. Datalogger to SDM-SW8A Connections................................................... 2
2. SDM-SW8A to SDM-SW8A Connections................................................ 3
3. Address Jumpers ........................................................................................ 5
4. Measurement Jumpers................................................................................ 6
5. Bit Period Values ....................................................................................... 8
6. Instruction 102 - SDM-SW8A ................................................................... 9
1. SDM-SW8A Front Panel ........................................................................... 1
2. SDM-SW8A Address and Port Configuration Jumpers with
Sensor Wiring Examples......................................................................... 5
3. SPDT Signal Conditioning by SDM-SW8A............................................ 13
A-1. Example Program Flow Chart ...........................................................A-2
ii

SDM-SW8A Switch Closure Input Module

1. Function

The 8 channel SDM-SW8A Switch Closure Input Module (see Figure 1) measures up to 8 channels of switch closure or voltage pulse inputs. Each channel may be configured to read single-pole double-throw (SPDT) switch closure, single-pole single-throw (SPST) switch closure, or voltage pulse. Output options include counts, duty cycle, and state.
The SW8A is addressed by the datalogger, allowing multiple SW8As to be connected to one datalogger (refer to Theory of Operation, Section 9). Sixteen addresses are available, but for most applications, Campbell Scientific, Inc. recommends no more than 4 SW8As be connected to one datalogger. If more SW8As are required, please consult Campbell Scientific's Marketing Department.
In October, 1988, the SDM-SW8A was introduced. Edlog Instruction 102 is used for communication with the SW8A. CRBasic dataloggers use the SDMSW8A instruction. Previous to October, 1988, the SDM-SW8 (no "A") was offered for use only with the CR10, utilizing CR10 I/O Instruction 15.
SDM-SW8As are not compatible with CR10s containing Instruction 15, and SDM-SW8s are not compatible with CR10s containing Instruction
102. Contact Campbell Scientific's Marketing Department for update options
if incompatibilities exist.
FIGURE 1. SDM-SW8A Front Panel
1
SDM-SW8A Switch Closure Input Module

2. Specifications

Operating voltage: 12 VDC nominal (9.6 to 16) Current drain: 3 mA quiescent, 6 mA active (max) Environmental: -25 to +50
Measurement types: Switch closure (SPDT, SPST) DC voltage
Input voltage threshold: From below 0.9 to above 4.0 VDC,±20
Maximum input frequency: 100 Hz (50% duty cycle) Minimum input pulse width: 5 ms high, 5 ms low Maximum bounce time: 3 ms open without counting Output options: State, duty cycle, counts Max count/port: 65535 Internal sampling frequency: 500 Hz Watchdog reset: Yes Total length of connecting cables: 20 feet Dimensions: 0.9"(H), 6.2"(L), 2.7"(W) Weight 0.5 lbs. (0.23 kg) Compatible dataloggers: CR10(X), CR800, CR850, CR1000, 21X,
o
C, 0 to 90% RH,
noncondensing
pulse
VDC max
CR23X, CR3000, CR5000, and CR7
TABLE 1. Datalogger to SDM-SW8A Connections
Datalogger
SDM-SW8A
+12
CR7
CR1000, CR800, CR850, CR23X, CR10(X)
CR3000, CR5000
21X
+12 12 V 12 V +12
(see Note 1)
G G
C3 C3 C3 SDM-C3 C3
C2 C2 C2 SDM-C2 C2
C1 IN C1 C1 SDM-C1 C1
C1 OUT not used
(see Note 2)
not used (see Note 2)
not used (see Note 2)
1H (see Note 2)
2
SDM-SW8A Switch Closure Input Module
TABLE 2. SDM-SW8A to SDM-SW8A Connections
SDM-SW8A
SDM-SW8A that’s connected to a CR10(X), CR800, CR850, CR1000, CR23X, CR3000, CR5000, or CR7
SDM-SW8A that’s connected to a 21X
+12 12 V +12
C3 C3 C3
C2 C2 C2
C1 IN C1 IN C1 IN
C1 OUT not used (see Note 2) C1 OUT (see Note 3)
Notes:
(1) If using an auxiliary power supply, instead of connecting the datalogger’s 12 V or +12 terminal to the SW8A, connect the power supply’s positive “+” wire to the SW8A’s +12 terminal. The power supply’s ground “-” wire connects to the SW8A’s datalogger’s G or
terminal.
terminal along with the wire that connects to the
(2) When using a CR10(X), CR800, CR850, CR1000, CR23X, CR3000, or CR7, a jumper wire is used to connect the C1 IN to the C1 OUT. SDM­SW8As shipped after March 1, 2006, include this jumper.
(3) If you’re using a 21X and the SDM-SW8A was shipped after March 1, 2006, remove the jumper connecting C1 IN to C1 OUT.

3. Power Supply Considerations

Due to the 3 mA continuous and 6 mA active current drain, an auxiliary 12 VDC power supply is recommended for powering the SW8A in remote, long term applications.
For some applications it may be convenient to use the datalogger supply to power the SW8A. For long term applications where AC power is available, or where a solar panel can be used for recharging, the lead acid power supply available with Campbell Scientific, Inc. dataloggers could be used. For short term applications only, the alkaline power supply available with Campbell Scientific, Inc. dataloggers could be used to power the SW8A.
If the 21X power supply is used to power the SW8A, all low level analog measurements (thermocouples, pyranometers, thermopiles, etc.) must be made differentially. This results from slight ground potentials created along the 21X analog terminal strip when the 12 V supply is used to power peripherals. This limitation reduces the number of available analog input channels and may mandate an external supply for the SW8A.
3
SDM-SW8A Switch Closure Input Module

4. Connections

All connections to the datalogger, power supply, and other SW8As are made from terminals located under "TO DATALOGGER" on the SW8A (refer to Figure 1). Sensor connections are made at the remaining terminals.

4.1 Connections to Dataloggers and Other SW8As

The CABLE5CBL or a similar cable is used to connect the SDM-SW8A to a datalogger.
Connections between an SW8A and a datalogger are shown in Table 1. Connections to multiple SW8As are shown in Table 2.
CAUTION
1. The order in which connections are made is critical.
ALWAYS CONNECT GROUND FIRST, followed by 12 V and then the Control Ports.
2. The sum of all the cable lengths connecting SW8As or
other SDM devices and a datalogger should be as short as possible and preferably does not exceed 20 ft. Longer lead lengths may be possible for CRBasic dataloggers if the SDMSpeed instruction is used (see Section 6.1.2). Long lead lengths may prevent communication.

4.2 Sensor Connections

Figure 2 shows the connections between the SW8A and compatible sensor types.

5. Internal Jumpers

Inside the SW8A, jumpers must be set to configure the Module address and the channel measurement type for each channel. Remove the two panel screws and lift the cover to access the jumpers. Figure 2 shows jumper location.

5.1 Address Jumpers

4
Each module can have 1 of 16 addresses (00 to 33, Base 4). The address is factory set to 00. Figure 2 shows the location of the address jumper block. Table 3 lists the jumper settings for each address.
SDM-SW8A Switch Closure Input Module
TABLE 3. Address Jumpers
Pins
Address 1-8 2-7
3-6 4-5
00 c c c c
01 c c c nc
02 c c nc c
03 c c nc nc
10 c nc c c
11 c nc c nc
12 c nc nc c
13 c nc nc nc
20 nc c c c
21 nc c c nc
22 nc c nc c
23 nc c nc nc
30 nc nc c c
31 nc nc c nc
32 nc nc nc c
33 nc nc nc nc
c = connected nc = not connected
FIGURE 2. SDM-SW8A Address and Port Configuration Jumpers with Sensor Wiring Examples