Campbell Scientific SDM-SIO4 User Manual

INSTRUCTION MANUAL
SDM-SIO4 4-Channel
Serial I/O Interface
Revision: 2/04
Copyright (c) 1996-2004
Campbell Scientific, Inc.

Warranty and Assistance

Products may not be returned without prior authorization. The following contact information is for US and International customers residing in countries served by Campbell Scientific, Inc. directly. Affiliate companies handle repairs for customers within their territories. Please visit www.campbellsci.com to determine which Campbell Scientific company serves your country. To obtain a Returned Materials Authorization (RMA), contact CAMPBELL SCIENTIFIC, INC., phone (435) 753-2342. After an applications engineer determines the nature of the problem, an RMA number will be issued. Please write this number clearly on the outside of the shipping container. CAMPBELL SCIENTIFIC's shipping address is:
CAMPBELL SCIENTIFIC, INC.
RMA#_____ 815 West 1800 North Logan, Utah 84321-1784
CAMPBELL SCIENTIFIC, INC. does not accept collect calls.
SDM-SIO4 Table of Contents
PDF viewers note: These page numbers refer to the printed version of this document. Use the Adobe Acrobat® bookmarks tab for links to specific sections.
1. Introduction....................................................................
1.1 What is the SDM-SIO4?....................................................................... 1-1
1.2 Specifications........................................................................................ 1-3
1.2.1 Serial Ports.................................................................................. 1-3
1.2.2 SDM Port.................................................................................... 1-4
1.2.3 Case............................................................................................. 1-4
1.2.4 Power Requirements................................................................... 1-4
1.2.5 Environmental Operating Range................................................. 1-5
1.2.6 Other Key Features ..................................................................... 1-5
1.3 'Talk-Through' Mode............................................................................ 1-5
2. Installation and Hardware Set-Up ...........................2-1
2.1 Setting the SDM Address ..................................................................... 2-1
2.2 Selecting RS232 or 5V Logic for Each Port......................................... 2-2
2.3 Connections to the SDM-SIO4............................................................. 2-2
2.3.1 Transient Protection and Grounding........................................... 2-2
2.4 Power-on Tests — the Status LED....................................................... 2-3
3. Understanding How the SDM-SIO4 Handles Data .3-1
3.1 Introduction........................................................................................... 3-1
3.1.1 Method of Entering Special / Control Characters....................... 3-1
3.2 Input Filters........................................................................................... 3-2
3.2.1 Filter Types................................................................................. 3-2
3.3 Output Formatting.................................................................................3-6
3.3.1 Simple Output Formatter............................................................. 3-6
3.3.2 Output Format Strings................................................................. 3-7
4. Programming the SDM-SIO4....................................4-1
4.1 Command Line Operation and Structure.............................................. 4-1
4.2 Entering Commands............................................................................. 4-1
4.3 Basic Commands.................................................................................. 4-2
4.4 Advanced Commands........................................................................... 4-3
5. Programming the Datalogger ..................................5-1
5.1 Instruction 113 Parameters ................................................................... 5-1
5.1.1 Parameter 1 — Reps ................................................................... 5-1
5.1.2 Parameter 2 — Address.............................................................. 5-1
5.1.3 Parameter 3 — Mode.................................................................. 5-1
5.1.4 Parameters 4, 5 and 6 — SDM-SIO4 Command........................ 5-2
5.1.5 Parameter 7 — Values per Rep................................................... 5-2
5.1.6 Parameter 8 — Starting Input Location...................................... 5-2
5.1.7 Parameters 9 and 10 — Multiplier and Offset ............................ 5-2
i
SDM-SIO4 Table of Contents
5.2 Commands and Options (Parameters 4, 5 and 6)..................................5-2
5.2.1 Understanding Parameter Options and Returned Values ............5-3
5.2.2 Command 1: Poll of Available Data...........................................5-3
5.2.3 Command 2: Signatures............................................................. 5-4
5.2.4 Command 3: Flush all Receive Buffers......................................5-4
5.2.5 Command 4: Send Data to Datalogger.......................................5-4
5.2.6 Command 5: Status....................................................................5-4
5.2.7 Command 6: Flush Transmit Buffer...........................................5-5
5.2.8 Command 7: Activate Command Line.......................................5-5
5.2.9 Command 8: Poll Tx Buffers for Data .......................................5-5
5.2.10 Command 9: Flush Converted Data Buffer.............................. 5-6
5.2.11 Command 66: Send Single-Byte Data to Datalogger................5-6
5.2.12 Command 67: Get Return Code...............................................5-6
5.2.13 Command 320: Send Data to SDM-SIO4 .................................5-6
5.2.14 Command 321: Execute Command Line Command................5-6
5.2.15 Command 1024: Send String to Device...................................5-9
5.2.16 Command 1025: Transmit a Byte.............................................5-9
5.2.17 Command 1026: Serial Port Status...........................................5-9
5.2.18 Command 1027: ‘Manual’ Handshake Mode.........................5-11
5.2.19 Command 2049: Set Communications Parameters .................5-11
5.2.20 Command 2054: Set Up Receive Filter..................................5-13
5.2.21 Command 2304: Transmit String and/or Data to Device.......5-13
5.2.22 Command 2305: Transmit Byte(s).........................................5-15
5.3 SDM-SIO4 Configuration Examples.................................................5-15
5.3.1 Sensors Where the Datalogger Can Request Data by Sending a
Prompt or Using a Handshaking Line:................................................5-17
5.3.2 Sensors Which Send Data Out Without Prompting...................5-20
5.4 Outputting Datalogger Data................................................................5-27
5.5 Flushing the Input and Output Buffers................................................5-29
5.6 Return Error Codes.............................................................................5-29
6. Data Error Detection................................................ 6-1
6.1 Error detection with the SDM-SIO4 .....................................................6-1
6.2 Received Data....................................................................................... 6-1
6.2.1 Example of Using Received Data Filters.....................................6-3
6.2.2 CR10X Program Example...........................................................6-4
6.3 Transmitted Data...................................................................................6-7
6.3.1 Example of Using Transmitted Data Filters................................6-8
6.3.2 CR10X Program Example...........................................................6-8
6.3.3 Alternative CR10X Program.......................................................6-9
Appendices
Appendix A. ASCII Table.............................................A-1
Appendix B. Serial Port Data Transfer Modes...........B-1
B.1 Baud Rates........................................................................................... B-1
B.2 Stop Bits.............................................................................................. B-1
B.3 Data Length......................................................................................... B-1
B.4 Parity Bits............................................................................................ B-2
B.5 Serial Handshake Modes..................................................................... B-2
ii
SDM-SIO4 Table of Contents
Appendix C. Limitations of the Talk-Through Mode.C-1
C.1 Limitations...........................................................................................C-1
Figures
1-1. Schematic Diagram of the SDM-SIO4................................................ 1-2
Tables
1-1. SDM-SIO4 Serial Port Pin Configuration........................................... 1-3
2-1. Address Settings.................................................................................. 2-1
2-2. Status LED Error Codes...................................................................... 2-3
3-1. Fixed Strings Currently Allocated....................................................... 3-8
iii
SDM-SIO4 Table of Contents
This is a blank page.
iv

Section 1. Introduction

The SDM-SIO4 has four configurable serial RS232 ports which allow it to be connected to intelligent serial sensors, display boards, printers or satellite links. It can also be used in many other applications where the data is transferred in a serial fashion. This device is designed to send data to and receive data from the sensors, and process it in parallel with the datalogger’s own program sequence, thus making the complete datalogging system faster and more efficient.
The SDM-SIO4 can handle the incoming and outgoing data in many different ways. It can either send data in the same format as sent from the datalogger or it can be programmed to send pre-stored data strings to the sensor. Combinations of data sent from the datalogger and pre-stored strings can be sent, allowing complex formatted data to be sent. For input, the SDM-SIO4 can transfer data in the same form as received from a sensor to the datalogger, or it can be programmed to filter out critical data from a sensor and only pass back the data the datalogger requires.
NOTE
This manual assumes that you have a basic knowledge of the terminology and theory of serial communications. For further information please refer to one of the standard textbooks on this subject.

1.1 What is the SDM-SIO4?

The SDM-SIO4 i s a device that is connected to a datalogger through the datalogger SDM port. The SDM port is specific to Campbell Scientific dataloggers and acts as a high-speed data exchange mechanism. On some dataloggers it is a dedicated port; on others it is implemented using control ports C1, C2 and C3.
Figure 1-1, on the next page, is a Schematic Diagram giving an overview of the functions of the SDM-SIO4. When used in conjunction with the following sections of this manual, it may help you to understand how the SDM-SIO4 operates.
The datalogger program controls the sequence and timing of data exchange with the sensors. However, unlike most other Campbell Scientific interfaces the SDM-SIO4 can be configured in two ways:
1. By inserting commands in the datalogger program
2. By connecting a computer running a terminal emulation program to serial
port 1 on the SDM-SIO4. Pressing a switch on the SDM-SIO4 temporarily switches this port to allow you to access a ‘command line’ (for entering command strings in much the same way as entering commands at the DOS prompt on a PC).
The ‘command line’ option allows you to store complex output strings and data filters in the SDM-SIO4. This set-up information is stored in battery-backed,
1-1
Section 1. Introduction
g
write-protected memory, which allows you to set up the SDM-SIO4 in the office and then move it to the site of installation in an unpowered state.
Handshake Line
Handshake
Control
To Other Ports
½ ¾
¿
PORT
Rx
¿
Tx
Tx Buffer Rx Buffer
¿
0
1
¿ À
CRC/SIG
Driver
¿
¿
À
Format
Driver & User Strin
s
¾
À
1
0
½ ½
CRC/SIG
Driver
À
Filter Driver
À
Converted
Data Buffer
Switches -
Go to 1 if command
line active
¾
¿
À
Command Line
Switch
Status
LED
Command Line
Control
¿
Datalogger can
Execute Command
Line Commands
K K K
To Other Ports
À
¾
¾
½
Control Lines
Data Lines
FIGURE 1-1. Schematic Diagram of the SDM-SIO4
¿
Datalogger
Command
Control
¿ À
Data HS SDE C1 C2 C3
¿ ¿
to SDM port of datalogger
1-2

1.2 Specifications

1.2.1 Serial Ports

The SDM-SIO4 has four serial ports which can b e configured independently to use different serial data formats and baud rates (from 25 to 115,200 baud). These ports are 0-5V logic or ±5V for RS232 and are configured similar to a PC ‘AT’ style DTE serial port.
Handshaking, to control the flow of data to and from a sensor, can be done by the datalogger or SDM-SIO4 if needed, and can be in the form of hardware or software protocols.
Pin No. SDM-SIO4 Port
1. RI ring indicate/DCD in
2. RX in
3. TX out
4. DTR data terminal ready out
5. Ground
6. DSR in
7. RTS request to send out
8. CTS clear to send in
9. +5V if internal link fitted, otherwise no connection
Section 1. Introduction
TABLE 1-1. SDM-SIO4 Serial Port Pin Configuration
NOTE
Serial Port Buffers
If you have an older SDM-SIO4 which has female ‘D’ type connectors, your connections will be different from those shown above. Please either refer to your earlier Manual or contact Campbell Scientific for further details.
Each serial port has a receive (Rx) buffer, a transmit (Tx) buffer and a processed data storage buffer. It is important to understand these buffers as their size can determine how often data must be collected from the SDM-SIO4 by the datalogger. It is important to avoid letting these buffers fill up. They are of the ‘fill and stop’ type, i.e. if they fill up, and more data is sent into the buffer, the extra data will be lost.
The receive and transmit buffers for each port are 981 bytes long and there is an additional 16-byte hardware buffer for each port.
The processed data storage buffer (used to store converted data ready for the datalogger to collect) is 891 bytes long, which is large enough for 222 4-byte Campbell Scientific floating point values (refer to the datalogger manual for more details of this format).
1-3
Section 1. Introduction

1.2.2 SDM Port

There is one more buffer, which is used only when the datalogger outputs floating point data via the SDM-SIO4. This buffer is 241 bytes — long enough for 60 floating point values. (The size of this buffer is rarely a limitation as it is emptied quickly.)
This serial port is to connect to the SDM port of the datalogger, e.g. via C1, C2 and C3 on a CR10X. The port is a set of screw terminals marked C1, C2, C3, I/O, +12 and G. C3 is the Synchronous Device Enable line, C1 is the Data line, C2 is the Clock line and I/O is a special-purpose Interrupt line.
The Interrupt line can be used with some dataloggers to tell the datalogger to collect data from the sensor. The SDM-SIO4 pulses the I/O line for 50ms every 250ms if there is data available for the datalogger to collect. This can be used for sensors which send out data without prompting. For dataloggers which support interrupt-driven subroutines this can simplify program operation.
The SDM port is used by the datalogger to communicate with the SDM-SIO4 and other SDM peripherals. The speed at which data is transferred is under the control of the datalogger and this can vary with other activities in the datalogger and also the length of the SDM cables. The typical transfer speed to and from the SDM is one byte per millisecond.
Multiple SDM-SIO4s can be connected to the datalogger in parallel with other SDM-SIO4s or other SDM devices. The only difference would be the SDM address of each device.
NOTE
For high-speed c ommunications the SDM cable should be kept as short as possible and connections made using screened cable. The cable between the SDM-SIO4 and the datalogger should not exceed 3m in length.

1.2.3 Case

The case is made of anodized aluminum. It has four slots for 9-way ‘D’ connectors and one slot for the SDM 6-way screw terminals. There is a momentary push-button switch for command line activation. The size of the case is 184 x 88 x 34mm. There is a tab at each end to allow for vertical mounting.

1.2.4 Power Requirements

The SDM-SIO4 has a typical quiescent current consumption of about 0.7mA. This increases to about 29mA with all 4 ports active. The quiescent state is entered if there has been no SDM or port activity for approximately 30ms.
1-4
The unit can be powered from an unregulated 12V supply (acceptable range 9 ­18V DC).

1.2.5 Environmental Operating Range

-25°C to +50°C (contact Campbell Scientific for extended temperature
0 - 95% RH (non-condensing)

1.2.6 Other Key Features

An internal lithium battery which retains configuration information
(estimated life 10 years)
A built-in system watchdog which will reset the processor in the event of a
crash caused by transients, etc.
A multi-tasking operating system allowing concurrent transmission and
receipt of data on all ports. This allows the receipt and processing of data from all four serial ports concurrently at 9600 baud.
A built-in status LED to give an indication of system function on power-up.

1.3 ‘Talk-Through’ Mode

Section 1. Introduction
requirements)
Recent versions of the CR10X and CR23X datalogger operating systems allow a user, while connected to the datalogger, to switch to a ‘talk-thr ough’ mode via either a direct or a remote telecommunication connection. This allows users to communicate with a device connected to one of the four serial ports of the SDM-SIO4 as if they were directly connected to that device. This can be very useful for diagnosis or configuration of the remote device(s).
Users can also ‘talk through’ to access the command line mode of the SDM-SIO4, enabling them to check the status of, or even to reconfigure, an SDM-SIO4 via a remote connection.
Full details on using the command are given in the appropriate datalogger manual – see the section on ‘Telecommunication’.
See Appendix C of this manual for limitations on the use of the talk-through mode.
1-5
Section 1. Introduction
This is a blank page.
1-6

Section 2. Installation and Hardware Set-Up

The SDM-SIO4 is designed to be mounted on an enclosure chassis plate using the two mounting
Before installation, it is necessary to set up the address of the SDM-SIO4 and also the mode of operation of each serial port. These settings are determined by jumpers inside the case. To access these, remove the four M3 screws and lift the lid off. With the connectors facing you, you will see two blocks of jumpers on the right hand side of the circuit board.
holes in the tabs on the side of the case.
CAUTION
Turn off the 12V supply and take static prevention precautions before removing the lid.

2.1 Setting the SDM Address

The 4 x 2-way block of jumpers close to the ‘D’ connectors selects the SDM address of the SDM-SIO4. This address ranges from 0 to 15. The four selector blocks are numbered on the PCB silk screen as 1, 2, 4, and 8; ‘8’ is closest to the ‘D’ connectors. This is in binary format as shown in Table 2-1.
TABLE 2-1. Address Settings
Selector Block Settings SDM Address 8421
0000 0 0001 1 0010 2 0011 3 0100 4 0101 5 0110 6 0111 7 1000 8 1001 9 1010 10 1011 11 1100 12 1101 13 1110 14 1111 15
NOTE: A ‘1’ means the selector block shorts both pins. ‘0’ means the selector is only connected to one pin (for storage).
2-1
Section 2. Installation and Hardware Set-Up

2.2 Selecting RS232 or 5V Logic for Each Port

The output voltage levels of each serial port can be set to either:
Logic level output: +5V (high) / 0V (low) or
RS232 output: +5V (high) / -5V (low) (compatible with RS232 driver
requirements).
The logic level output is used when driving a logic level compatible device, e.g. an SC32A, or where quiescent current is a concern. This mode is lower power because the idle state is 0V, while the idle state of the RS232 output is -5V which results in current flow to ground via the input resistance of the RS232 device’s inputs. However, in practice, this logic level output mode can be used with the majority of RS232 sensors as most accept a logic level drive signal as a valid input signal.
The output levels are configured via a 4 x 3-way block of jumpers at the back of the unit. There is one jumper for each port. Text is printed on the circuit board to indicate the port and the relevant position for the two modes. If the jumper is fitted on (shorts) the two pins close to the right hand side of the unit, the port will be in RS232 mode and if the two pins close to the left hand side are shorted, the port is set to 5V logic.
The inputs to the SDM-SIO4 are compatible with either logic level or RS232 signals.

2.3 Connections to the SDM-SIO4

Connect the SDM port to the datalogger SDM terminals as described under ‘SDM Port’ in Section 1. Use a short, low-capacitance, screened cable. The 12V supply can normally be taken from the 12V supply input to the datalogger.
Make up cables for the RS232 devices to match the connections shown under ‘SDM-SIO4 Port’ in Table 1-1 (Section 1). Please refer to your sensor manual for a description of the required connections, including the handshaking requirements. To minimize susceptibility to noise, use screened connectors and cables.

2.3.1 Transient Protection and Groundi ng

The G terminal on the SDM-SIO4 acts both as a ground reference point for digital communications via the SDM port and also as a protective ground for the SDM-SIO4. Usually it can be connected back to the datalogger power ground (G on a CR10/10X). This ground in turn should be connected to the safety ground for the whole system.
The SDM-SIO4 has protection against electrostatic discharge and induced transients on all input and output lines. However, the level of protection offered is limited by the grounding paths within the case. Where long cables are to be run to remote serial devices, especially in areas prone to lightning, external
2-2
Section 2. Installation and Hardware Set-Up
lightning prote ction is recommended on a ll lines connected to the serial ports (contact Campbell Scientific for further details).
The possibility of ground loops being set up between the datalogger and the remote RS232 device via the serial cable should also be considered. Ground loops formed by secondary return earth paths can lead to various problems including:
Electrical noise causing possible loss or corruption of serial data.
Electrical noise being transferred back to the datalogger causing errors on
analogue measurements.
Long term damage in the form of corrosion caused by current flowing along
electro-chemical gradients.
If it is not possible to prevent a ground loop, or if electrical noise is found to be a problem, it may be necessary to add an opto-isolated interface to the output of the SDM-SIO4 serial port. Please contact Campbell Scientific for further details.
Even if ground loops can be prevented, the length of cables that can be used for RS232 signals is limited to a few tens of meters (the exact length depending on the RS232 driver hardware and the cable used). Short-haul modems can be added to the SDM-SIO4 to allow cables up to several kilometers to be used and in addition providing ground isolation (please contact Campbell Scientific for further details).

2.4 Power-on Tests — the Status LED

When the SDM-SIO4 is powered up or has been reset by the internal watchdog hardware it flashes the red LED on the front panel in the following way to indicate status:
TABLE 2-2. Status LED Err or Codes
No. of Flashes Description of error/status.
1 SDM-SIO4 is working correctly. 2 SDM-SIO4 EPROM signature failure. 3 SDM-SIO4 internal battery must be replaced.
NOTE 1: The LED flashes for 1 second on and 1 second off. The LED will also illuminate when the front panel switch is pressed.
NOTE 2: The LED may take up to 4 seconds before it flashes after power up.
2-3
Section 2. Installation and Hardware Set-Up
This is a blank page.
2-4

Section 3. Understanding How the SDM-SIO4 Handles Data

For simple applications the SDM-SIO4 can be configured and controlled from the datalogger alone, using the datalogger program instruction P113 (CR10X and CR7 dataloggers only). Future developments will include support for other dataloggers.
More complicated applications require configuration of the SDM-SIO4 using the ‘command line’ function on a PC running a terminal emulator. This allows you to set up mechanisms to control the transmission of long, formatted output data and filtering of numerical values out of received data. This is done by storing the detailed formatting and filtering configurations in the SDM-SIO4 (see the section about the command line mode below).
Thus when the datalogger needs to send out long or complicated data strings it only needs to send a short command to the SDM-SIO4 to tell it to do this, i.e. it does not have to pass the whole string via the SDM interface. Likewise, by telling the SDM-SIO4 how to process received data, it can strip off the unwanted characters and reduce the data to either binary or floating point numbers. This minimizes the time it takes for the datalogger to get the data and so allows the datalogger to load the data values into its memory with minimal processing.

3.1 Introduction

3.1.1 Method of Entering Special / Contr ol Characters

For collection of data from an intelligent sensor the datalogger programming is typically broken down into several steps, which might be:
1. Set up and co nfigure the serial ports , e.g. baud rate, parity, handshaking.
This can be done by one call of the datalogger instruction either at program compilation (so it is done only once) or perhaps in a subroutine which is called when a flag is toggled.
2. Use a second call of the instruction to tell the SDM-SIO4 to send out a
string to request data from a sensor and to tell it how to process the returned data.
3. At some point later in the program use a third call to collect the pre-
processed data from the SDM-SIO4.
Before examining the detail of the datalogger instruction it is necessary to understand the data output formatter and the input filters. These work in principle (and in certain details) like the formatting and filtering options used to write and read data from files in some high-level programming languages.
Before going on to discuss filters, you should understand how to enter special / control characters.
3-1
Section 3. Understanding How the SDM-SIO4 Handles Data
To enter a control character in the range of 0-255 decimal in a filter string, formatter string or a user string you must use the ‘&hh’ format, where ‘&’ defines the following two characters, ‘hh’, to be a hexadecimal number between 00 and FF. For example, ‘&de’ would be character 222 decimal. To use ‘&’ within the string you must type ‘&&’ (i.e. && = & when in a string).
NOTE

3.2 Input Filters

The hex. number must always be two ASCII characters.
Control characters can be entered for all commands in a similar way:
^M is carriage return, ^J line feed etc.
^^ means ^
"" means "
]] means ]
&& means &
&0d means line feed
&hex,hex used to enter 2-character hex. codes (0-9, A-F)
Input filters are used to convert received data into a form that is easy for the datalogger to process. Filters are generally used to strip out the required values from other, unnecessary, data transmitted from the sensor/device. The filters will also convert the required data into a form that the datalogger can use.
For example, the sensor may output the (unusual) complex str i ng ‘Sample data +12.3, 23.567,0xAB,12.4’. From this string you may only require to record the hexadecimal number 0xAB. A filter can be set up to strip out only this number, and then convert it to a 4-byte floating point number which the datalogger can use. The datalogger will then collect this value and place it into an input location –in this case as 171 decimal.
3-2
NOTE
You must always set up a filter if you want the datalogger to collect data from the SDM-SIO4.

3.2.1 Filter Types

Simple Filters
These filters can be set up by the datalogger program, i.e. command line set-up is not necessary. The four filters search for a specific data type to convert to Campbell Scientific floating point format. The SDM-SIO4 continues searching and reading data until it encounters a termination character (if this has been specified in Instruction 113) The filters are as follows:-
Search for an ASCII floating point number t o convert to Campbell
Scientific floating point format.*
Filter Strings
Section 3. Understanding How the SDM-SIO4 Handles Data
Search for an ASCII hex pair to convert to Campbell Scientific floating
point format.*
Search for an 8-bit binary number to convert to Campbell Scientific floating
point format.
Search for a 16-bit binary number to convert to Campbell Scientific floating
point format.
* Non-numeric characters are ignored.
See Section 5 – ‘Programming the Datalogger’.
These are used to define how to filter incoming data from a port into a format the datalogger can use. This is done by having a user-defined filter string pre­stored in the battery-backed memory of the SDM-SIO4. These strings have to be created via the command line (see Section 4), in a similar fashion to the format strings. The filter commands are as follows:
An Define a filter time-out. The range is from 0 to 255 in 50ms steps,
giving a range of 0 to 12.75 seconds. The accuracy is -50ms +0ms so an ‘n’value of 1 is not practical as the time-out could be between 0 and 50ms. This filter type can be put anywhere in the string. If a time-out occurs before the entire filter is complete, any data already processed is disregarded and the filter is restarted. When the filter string is finished the time-out is stopped and set to zero. If n=0 then this stops the time-out and the filter will operate with no time-out. While the time-out is active the SDM-SIO4 will not shut down into the low power state unless the filter is complete or the time-out has finished. Note it best to start the time-out after a trigger command.
B[n,n,n,...] Carry out a bit field to floating point conversion. The
SDM-SIO4 gets or waits for as many bytes as are required to fulfil the total number of bit fields. ‘n’ can be any number of bits from 0 to 255, but more than 23 bits is beyond the floating point range of the datalogger so the value returned to the datalogger will be invalid. There can be any number of bit fields, only limited by the command line buffer and the 255-byte limit for string storage. If there is part of a byte unconverted and there are no more bit fields remaining then those bits are discarded.
bn A binary number should be at this position. The SDM-SIO4 converts
‘n’ bytes (1, 2 or 3 bytes) to Campbell Scientific floating point.
C Discard one byte (character).
c Read one byte (not converted to Campbell Scientific floating point).
D A signed integer should be at this position. If it is found, the signed
integer is sent to the datalogger and removed from the buffer. If no signed integer is found, the SDM-SIO4 sends -99999 to the datalogger.
d Search for a si gned integer indefinitel y, ski pping non-numeric
characters.
3-3
Section 3. Understanding How the SDM-SIO4 Handles Data
e[ ] Scan until any ASCII character not entered between the brackets is
encountered. The maximum number of non-trigger characters is 255. Note that this filter does not remove the non-matching character from the buffer.
F A floating point number should be at this position. If it is found, the
signed floating point number is sent to the d atalogger and removed from the buffer. If no floating point number is found, the SDM-SIO4 sends -99999 to the datalogger.
f Search for a floating point number indefinitely, skipping a ny non-
numeric characters.
gn Error detection – start of signature calculation for received data – see
Section 6.
Gn Error detection – marks end of signature calculation for received data
– see Section 6.
i[ ] Scan until any ASCII characters entered between the brackets are
encountered. The maximum number of characters between the brackets is
255. Note that this filter does not remove the matched character from the buffer.
Jx:y ‘J’ deals with signed and unsi gned integers,
‘x’ is the number of characters or digits per integer (1 to 255) and y is the number of repetitions (1 to 255). Leading spaces and the signs ‘+’ and ‘-’ are allowed befo re the number but any integer which contains non-numeric characters (e.g. 23A5) will produce an error and return -99999.
nn Discard ‘n’ bytes. ‘n’ can be in the range of 0-255.
Nn Read ‘n’ bytes. ‘n’ can be in the range of 0-255 (not converted to
Campbell Scientific floating point).
pn Hexadecimal byte should be here, n=number of bytes to convert (n=1
to 3 hex pairs) to Campbell Scientific floating point.
Pn Converts hexadecimal value(s) to Campbell Scientific floating point
format. n=1,2,3 number of hex. pairs to convert into value LSByte first.
rn Send the byte received to port ‘n’ for re-transmission. ‘n’ can be
1-4. The byte is removed from the receive buffer.
s Stop the filter until commanded by the datalogger to restart.
t[ ] Search for an exact string match between the [ ]. All ASCII characters
up to and including the matching string are removed from the receive buffer before the next filter type starts.
T[ ] Search for an exact string match between the [ ]. All ASCII characters
up to the matching string are removed from the receive buffer before the next filter type starts. (Same as t[ ], except matching strings are not removed).
u[ ] Convert ASCII floating point into Campbell Scientific floating point
format until the termination character/string between [ ] is seen. The termination character is removed from the buffer.
3-4
Section 3. Understanding How the SDM-SIO4 Handles Data
vn[ ] Convert ‘n’ ASCII hex pairs into Campbell Scientific floating point
format until the termination character/string between [ ] is seen. ‘n’ can be 1-3. The termination character/string is removed from the buffer.
Vn Searches for hexadecimal value(s) and converts them to Campbell
Scientific floating point format. Terminates when a string between [ ] is seen. n=1,2, 3 number of hexadecimal pair s to convert into value LSB yte first.
wn[ ]Convert ‘n’-byte binary data into Campbell Scientific floating point
format until the termination character/string between [ ] is seen. ‘n’ can be 1-3. The termination character/string is removed from the buffer.
Wn Searches for binary value(s) and converts them to Campbell Scientific
floating point format. Terminates when a string between [ ] is seen. n=1,2,3 number of hexadecimal pairs to convert into value LSByte first.
x This marks the start of a data set. A data set is a set of converted data
for the datalogger to collect. When this filter type is used the data in the data set is only available to the datalogger when all parts of the data set have been converted – see ‘X’, below.
X This marks the end of a data set. This makes the data converted in the
data set available to the datalogger. This also means that data after this is available to the datalogger as soon as the SDM-SIO4 has converted each value. If the end of the data set is at the end of the filter string then this filter is not required as the end of the filter string is always the end of a data set.
Yn Converts binary value(s) to Campbell Scientific floating point format.
n=1,2,3 number of bytes to convert into value LSByte first.
z Flush the UART FIFO (serial port hardware buffer) and the Receive
buffer associated with the port that is using this filter type. This does not, however, clear the converted data buffer.
As an example, take the following sensor output string:
battery 12.65V,current 12mA
The filter string might be:
i[b]n8Fi[c]n8F
Output to the datalogger would be 12.65 and 12 as Campbell Scientific floating point numbers. This filter string works as follows:
1. i[b] waits for the trigger character ‘b’ of ‘battery’.
2. n8 discards everything up to 12.65V.
3. F converts the number to Campbell Scientific floating point. If a valid
number is not found -99999 is sent to the datalogger.
4. i[c] waits for the trigger character ‘c’ of ‘current’.
5. n8 discards everything up to 12mA.
6. F converts the number to Campbell Scientific floating point. If a number is
not found -99999 is sent to the datalogger.
This filter will repeat the above operations on all incoming values.
3-5
Section 3. Understanding How the SDM-SIO4 Handles Data
Predefined Filter Strings
A small number of fixed filter strings are pre-defined as follows:
Filter No. Filter String Used
256 r1 257 r2 258 r3 259 r4

3.3 Output Formatting

The output formatters are used to format data from the datalogger into English text messages, send strings/ commands to sensors and to outp ut t ext to a display.
For example, you may have a display on which you want to show air temperature and humidity. The datalogger would take the measurements from the sensors, and place two values into appropriate input locations. It would be impractical for the datalogger to store text labels in this way, and so you could use the SDM-SIO4 to send a label to the display along with the data from the datalogger.
The final result may be displayed as:
The temperature is 23.7C The humidity is 65.8%
The string generated would then be transmitted from the selected serial port. Because the formatter is programmable, almost any string can be output from the serial port, either by programming the datalogger or by using the command line.

3.3.1 Simple Output Formatter

This can be set up by the datalogger and allows data to be transmitted out of the SDM-SIO4 in a number of simple formats. It is not necessary to use the command line mode to use these formats. Simple output formats are as follows:
Convert a location sent into ASCII floating point. If this option is selected
an extra ASCII character/delimiter can be added to the end of the ASCII number sent.
Convert a location sent into an ASCII hex pair. If this option is selected an
extra ASCII character/delimiter can be added to the end of the hex number sent.
Convert a location sent into an 8-bit binary byte. If this option is selected an
extra ASCII character/delimiter can be added to the end of the byte sent.
3-6
Convert a location sent into a 16-bit binary word. If this option is selected
an extra ASCII character/delimiter can be added to the end of the 16-bit word sent.
See Section 5 – ‘Programming the Datalogger’.
Section 3. Understanding How the SDM-SIO4 Handles Data

3.3.2 Output Format Strings

These allow either just long strings to be sent from the SDM-SIO4 or a combination of string data plus data from a datalogger input location. This type of format is normally set up from the ‘command line’. The user definable strings are referenced by a number in the range 0..255. The string is entered as a series of the following formatter commands:
<space> Send ASCII space.
bn Send a binary number received from the datalogger to the port. ‘n’ can
be 1, 2 or 3 bytes, i.e. 8-, 16- or 24-bit. If n=4 then it is direct Campbell
Scientific floating point format. If the formatter string asks for more values than the datalogger sends then the SDM-SIO4 sends ‘*’ characters.
fn:n Send a left-hand justified, formatted ASCII floating point number to
the port. The first ‘n’ is the field width in characters and the second ‘n’ is the number of decimal places to use within the field width. If the integer part of the ‘n’ number is bigger than the field width, the SDM-SIO4 still sends it even though it is longer tha n the set field width. If the formatter string asks for more values than the datalogger sends (because Instruction 113 specifies fewer values) then the SDM-SIO4 sends a number of ‘*’ characters to the port (e.g. for a fiel d width of 4 it sends ****). Minimum fi eld width 2 digits, maximum field width 15 characters, maximum number of decimal places 8.
gn Error detection – start of signature calculation for transmitted data –
see Section 6.
Gn Error d etection – marks end of signature calculation for transmitted
data – see Section 6.
hn Send an ASCII hex number to the port. ‘n’ can be 1, 2 or 3 bytes
converted, i.e. an 8-, 16- or 24-bit number. If the formatter string asks for more values than the datalogger sends then the SDM-SIO4 sends
‘*’ characters.
i[ ] Send the string between the brackets [ ] to the port. Up to 255 ASCII characters can be sent. (See Section 4.2 – Entering Commands).
J Send line feed.
M Send carriage return.
s Stop formatting.
zn Send a pre-stored string to the port. ‘n’ is the user-defined string
number 0-255 or a fixed string 256-511.
Table 3-1, below, shows all the defined Fixed Strings.
3-7
Section 3. Understanding How the SDM-SIO4 Handles Data
TABLE 3-1. Fixed Strings Currently Allocated
String number String (enclosed in quotes)
256 ‘+0000000000123.45670000000000CrLf’ 257 ‘Voltage’ 258 ‘Amps’ 259 ‘Watts’ 260 ‘Joules’ 261 ‘Temperature’ 262 ‘Pressure’ 263 ‘Speed’ 264 ‘Power’ 265 ‘Depth’ 266 ‘Length’ 267 ‘Height’ 268 ‘Enter’ 269 ‘Password’ 270 ‘Correct’ 271 ‘Incorrect’ 272 ‘Overrange’ 273 The ASCII characters: carriage return, linefeed.
If the datalogger sends more data than is defined in the SDM-SIO4’s formatter string, the SDM-SIO4 starts at the beginning again unle ss ‘s’ (stop formatting) is used, in which case any extra data within that transmission is ignored.
CR10X Program Example
This program example will output the battery voltage and panel temperature received from the datalogger input locations to port 2 on the SDM-SIO4, using the SDM-SIO4 Output Formatter.
The user defined format string, which is entered in the command line mode (see Section 4), is as follows:-
fmtst 123 "z261 f6:2 i[Battery ]z257 f6:1z273"
Typical example output from this formatter string is:-
Temperature 27.23 Battery Voltage 12.6
Here is a description of what each part of the formatter does:­fmtst 123 – This is the command word for storing the formatter string in area
123.
z261 – This outputs the fixed string ‘Temperature’. space – This outputs an ASCII space.
3-8
f6:2 – This takes the value from location 1 and outputs it in a field with a total width of 6 characters. There are 2 decimal places available within the field.
space – This outputs an ASCII space.
Section 3. Understanding How the SDM-SIO4 Handles Data
i[Battery ] – This outputs the word between the brackets [ ]. z257 – This outputs the fixed string ‘Voltage’. space – This outputs an ASCII space. f6:1 – This takes the value from location 2 and outputs it in a field with a total
width of 6 characters. There is 1 decimal place available within the field. z273 – This outputs the fixed string ‘CrLf (carriage return line feed)’.
*Table 1 Program
01: 2 Execution Interval (seconds)
;get battery voltage.
1: Batt Voltage (P10)
1: 2 Loc [ Batt_v ]
;get panel temperature.
2: Internal Temperature (P17)
1: 1 Loc [ Temp_C ]
;send battery voltage and temperature to port 2 on the SDM-SIO4.
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 2 Send/Receive Port 2 4: 2304 Command ;see Section 5 for explanation of 5: 9123 1st Parameters ;Command 2304 and its Parameters 6: 0 2nd Parameters ; 7: 2 Values per Rep 8: 1 Loc [ Temp_c ] 9: 1.0 Mult 10: 0.0 Offset
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
End Program
3-9
Section 3. Understanding How the SDM-SIO4 Handles Data
This is a blank page.
3-10

Section 4. Programming the SDM-SIO4

This section gives both the basic commands and advanced command line options which allow testing and advanced configuration of the SDM-SIO4.

4.1 Command Line Operation and Structure

To use the command line mode, connect a computer to port 1 of the SDM­SIO4. The computer should run a terminal emulation program (e.g. GraphTerm) which is set to 9600 baud, 8 data bits and 1 stop bit. If connecting to a PC you will need a null modem cable.
When the computer is connected, the command line can be made active by pressing the small momentary push-b ut ton switch, next to the Status LED. When this happens the SDM-SIO4 prompt ( At this prompt a number of commands can be typed and executed.
The command line buffer is 512 bytes long so no command with parameters
must be longer than this.
After ten minutes of inactivity (where no valid commands are executed) the
command line mode will time out and port 1 will return to its normal function.
SDMSIO4->) is sent out of port 1.
The command line mode can be activated while the datalogger is runni ng a
program which communicates with the SDM-SIO4. However, all
datalogger activity related to port 1 is ignored.
Complicated or long string definitions are best set up by editing a text file
which includes the string definition commands. This file can then be sent out to the SDM-SIO4 once it is configured in the command line mode. The SDM-SIO4 can accept multiple configuration strings sent within one file.
NOTE
By using (datalogger) Instruction P113 Command 321 it is possible to execute a command line command from a datalogger program. See Section 5 of this manual for further details.

4.2 Entering Commands

A command is executed when a carriage return (CR) is sent. This is normally sent by pressing the characters was discussed in Section 3.1, but is repeated here for convenience.
To enter a control character in the range of 0-255 decimal in a filter string, formatter string or a user string you must use the ‘&hh’ format, where ‘&’ defines the following two characters, ‘hh’, to be a hexadecimal number between 00 and FF. For example, ‘&de’ would be character 222 decimal. To use ‘&’ within the string you must type ‘&&’ (i.e. && = & when in a string).
ENTER key on a computer. The method of entering control
4-1
Section 4. Programming the SDM-SIO4
NOTE
The hex. number must always be two ASCII characters.
Control characters can be entered for all commands in a similar way:
^M is carriage return, ^J line feed etc.
^^ means ^
"" means "
]] means ]
&& means &
&0d means line feed
&hex,hex used to enter 2-character hex. codes (0-9, A-F)

4.3 Basic Commands

fltst [string number] ["filter defini tion"]

This command stores a filter definition to a string number 0..255. Example: fltst 22 "ccci[x]Fs" The above example stores the filter definition in filter string 22.
See Section 3 for filter types.

strst [string number] ["string definition"]

This command stores a user text string definition to a string number 0..255. Example: strst 22 """This is a string""^M^J" The above example stores the string definition "This is a string" This string will include the two quotation marks, as shown.

fmtst [string number] ["format definition"]

This command will store a formatter definition to a string number 0..255.
Example: fmtst 22 "i[volts=]f4:2" (result would be, for example,
volts=12.7)
The above example stores the formatter definition in string 22. See Section 3 for formatter types.

strdelete [string number]

This command deletes a stored filter, formatter or text string 0..255 from memory.
crlf in string 22.
4-2

strrd [string number]

This command outputs the stored string or definition 0..255 to the command line.
Section 4. Programming the SDM-SIO4
NOTE
1. When string definitions are stored, all control characters are
converted and so the string may not be identical to the one you typed in.
2. Formatter and filter strings cannot be read by this command
because they are compiled.

exit

This command exits the command line and returns port 1 of the SDM-SIO4 to normal operation.

4.4 Advanced Commands

version

This returns the internal EPROM part number, signature and the string signature if good or 0 if bad. This will give the same signature as Campbell Scientific’s SIG.COM PC program.
portset [port#] [baud#] [data length] [stop bits] [parity] [handshake
mode] [delay]
This sets up the port 1..4 to the communication format you require.
‘port #’ means the port number (1..4) to set up. For details of the other parameters (baud #...delay) see Appendix B.

reset

The SDM-SIO4 is set to a known default state. All strings, filters and formatters are erased, ports are set to 9600 baud, 1 stop bit, no parity and no handshake. All transmit and receive buffers are flushed. All error counts are zeroed.

ramtest

The system RAM is tested and the SDM-SIO4 is then reset. The string ‘Ram
test pass
of the memory failed.

changeport [port #]

This command changes the port for which the command line is available. This command line port setting will stay in effect for further sessions until a new
’ is returned if the RAM is OK or ‘Ram test fail’ if some part
4-3
Section 4. Programming the SDM-SIO4
port is chosen or power is removed and then re-applied, in which case the command line reverts to port 1.

status

This outputs the general status of the SDM-SIO4. The results are as follows:
BATT 0 or 1
If the value is 0 the battery needs replacing. If the value is 1 the battery is good.
ADDR 0 to 15
This is the current SDM-SIO4 hardware address.
WD n WDERR n WDADDR n
WD n is a count of the number of watchdog resets, WDERR is the number of the last task that crashed and WDADDR is the address at which the crash was found.
NC 0-9
This is the number of SDM commands the datalogger sent to the SDM-SIO4 that the SDM-SIO4 did not recognize. This counter may be incremented when the program is first compiled in the datalogger due to the auto speed detection of the datalogger.
PORT1-4
These four sets of values are the current port settings in the order as below:
Baud rate setting
Data length setting
Stop bit setting
Parity bit setting
Handshake mode
Delay time value
Parity error count
Framing error co unt
Overrun error count
Line break error count
DTR handshake line status, 0=low 1=high
RTS handshake line st atus, 0=low 1=high
CTS handshake line st atus, 0=low 1=high
DSR handshake line stat us, 0=low 1=high
DCD handshake line status, 0=low 1=high
4-4
You should refer to the appropriate section of this manual for further specific detail.

hexdump [start address] [number of bytes]

This is used by Campbell Scientific for test purposes and outputs a hex dump of the SDM-SIO4’s internal address space. The start address and number of bytes to dump must be in base 10, decimal integer.

lasterror

This command returns the last reported error to the command line. This command can be used, for instance, to get the return code from the ramtest command when in talk-through mode.

errorres

This resets all error counters.

bytewr [address] [byte]

This is used by Campbell Scientific for test purposes and writes a byte to the memor y of the SDM-SIO 4.
Section 4. Programming the SDM-SIO4

testio [test#]

The address and bytes to write must be in base 10, decimal integer. The address range is 0-65535 and the byte is from 0-255.
This is used by Campbell Scientific for test purposes.
Each test command is carried out for 2 seconds. Test# can be in the range 0­255; only five test numbers are currently valid, as shown below.
testio returns
test 0 DTR,RTS,IO=LOW test1 DTR=HIGH,RTS,IO=LOW test2 DTR=LOW,RTS=HIGH,IO=LOW test3 DTR,RTS=HIGH,IO=LOW test4 DTR,RTS=LOW,IO=HIGH
4-5
Section 4. Programming the SDM-SIO4
This is a blank page.
4-6

Section 5. Programming the Datalogger

The datalogger instruction specific to the SDM-SIO4 is P113 (CR7 and CR10/10X only). (Please check with Campbell Scientific to see if your version of the operating system supports this.) The instruction has the following format:
Parameter No. Description
01 Reps (number of adjacent addressed SDM-SIO4s) 02 Address of SDM-SIO4 (0..15) 03 Mode (0..5) 04 Command (0..9999). 05 First command option (0..9999) 06 Second command option (0..9999) 07 Values per rep 08 Starting input location 09 Multiplier 10 Offset

5.1 Instruction 113 Parameters

5.1.1 Parameter 1 — Reps

This specifies the number of times you wish this command to repeat for each SDM-SIO4 connected to the datalogger with sequential addresses. This will normally be set to one.

5.1.2 Parameter 2 — Address

This is the address of the SDM-SIO4 that the instruction applies to.
See Section 2 – ‘Installation and Hardware Set-Up’ for information on setting the SDM-SIO4 address

5.1.3 Parameter 3 — Mode

This defines which port the command applies to:
Code Port
1 Send/Receive port 1 2 Send/Receive port 2 3 Send/Receive port 3 4 Send/Receive port 4 5 Send to all four ports (global)
5-1
Section 5. Programming the Datalogger

5.1.4 Parameters 4, 5 and 6 — SDM-SIO4 Command

This command (with up to two options) defines exactly what the instruction will do. Where no options are needed, enter values of 0000 for parameters 5 and 6.

5.1.5 Parameter 7 — Values per Rep

This determines how many values to send or receive, starting from the specified input location (parameter 8). Data can be either 4-byte floating point values or single bytes, determined by the SDM-SIO4 command number.
Some commands require no input or output of values; for these commands this parameter would be set to zero.

5.1.6 Parameter 8 — Starting Input Location

This is the first input location that values will be sent from or written to consecutively until all values per rep (parameter 7) are done.
5.1.7 Parameters 9 and 10 — Multiplier and Offset
The multiplier and offset are applied to all incoming and outgoing data.
NOTE
The multiplier should normally be set to 1.000; if left at 0.000 then zero value data will be stored.

5.2 Commands and Options (Parameters 4, 5 and 6)

For many of the command options listed below, it is necessary to leave a small delay before calling another instance of the instruction which communicates with the SDM-SIO4. This is required to allow the SDM-SIO4 to process the instructions it has been given. Failure to allow these delays will probably cause the SDM-SIO4 to return invalid data. The delays are called ‘Minimum delay’ in the command descriptions.
Many of the delays vary with the parameters of the instruction, in which case a formula is quoted to enable you to calculate the delay. All delays are in milliseconds. The notation used in the formula is:
floats is number of locations to convert.
characters is the number of characters to each float value including decimal
point and sign.
5-2
ports is the number of ports the value or values are being transmitted from.
This is 1 if parameter 3 in P113 is 1..4 or 4 if parameter 3 is 5.
Section 5. Programming the Datalogger
NOTE
The delay required in the program can either be forced using Instruction P22, or by using the time to execute other measurement or processing instructions.

5.2.1 Understanding Parameter Options and Retur ned Val ues

NOTE
In the following examples, ‘x’ indicates a single digit from 0 to 9.
When the command requires or returns values, each digit, or combination of digits, can signify either a value, flag or setting.
Using Command 5 as an example:
Number of watch dog resets | | Number of invalid commands executed | | | Lithium battery level | | | |
x x x x
The first value returned by Command 5 indicates:
Actual number of watch dog resets (two digits 00 to 99) – a value.
Number of invalid commands executed (single digit 0 to 9) – a value.
Level (state) of the lithium battery (0=low, 1=good) – a flag.
If the value returned was, for example, 1281, then it would have the following meaning:
12 watch dog resets 8 invalid co mmands 1 battery level good
The second value returned shows whether or not data is available from a specific port. A non-zero digit indicates that data is available, whereas a zero signifies that no data is available.
Command 5 is explained in detail later.
NOTE
When a command parameter requires values to be entered (e.g. Command 1026), it is a good idea to always enter all four digits. Only trailing zeros are significant to the SDM-SIO4, and so entering 0001 or 1 would be identical. However, if the first parameter needs to be 1, you must enter 1000. The habit of always entering all four values helps to minimize input errors.

5.2.2 Command 1: Poll of Available Data

This command has no additional options after the command. The SDM-SIO4 returns one Campbell Scientific floating point number to indicate if data is available as below:
5-3
Section 5. Programming the Datalogger
Port 4 data available | Port 3 data available | | Port 2 data available | | | Port 1 data available | | | |
x x x x
If any of these four digits is greater than zero then data is available.
Values per repetition = 1

5.2.3 Command 2: Signatures

This command gets the SDM-SIO4 EPROM signature and the string memory area signature; the two values are written into consecutive input locations. If the signatures are zero then there could be corrupt data.
Values per repetition = 2

5.2.4 Command 3: Flush all Receive Buffers

Stored data in the SDM-SIO4 relevant to the port is also erased with this command.
Values per repetition = 0

5.2.5 Command 4: Send Data to Datalogger

This command requests the SDM-SIO4 to send the specified (values/reps) number of floating point values it has already received from the RS232 device (relevant to the port specified) into input locations. -99999 is stored if no value is available.
For example, this command could be used to get data conver ted using input filter strings of type d, D, f, F, pn, bn, u[ ], vn[ ], wn[ ] and B[n,n..] – see Section 3.

5.2.6 Command 5: Status

This command returns the SDM-SIO4 general status, lithium battery level, errors and data available flags. The data is supplied as two floating point values. First value:
Number of watch dog resets | | Number of invalid commands executed | | | Lithium battery level | | | |
x x x x
5-4
Number of watch dog resets: This is a count from 0 to 99. This indicates that there has been some hardware or software failure, or can be caused by the datalogger transmitting the correct address but not transmitting any commands.
Section 5. Programming the Datalogger
Number of invalid commands executed: This is a count from 0-9 and indicates that the command you have tried to execute is not a current SDM-SIO4 command. Because some dataloggers carry out auto speed detection for the SDM interface, this counter may be incremented when the program is first compiled.
Lithium battery level:
0 Lithium battery low and must be replaced.
1 Lithium battery good.
The second floating point value is the same as for Command 1:
Port 4 data available | Port 3 data available | | Port 2 data available | | | Port 1 data available | | | |
x x x x
If any of these four digits is greater than zero then data is available.
Values per repetition = 2

5.2.7 Command 6: Flush Transmit Buffer

This command flushes the SDM-SIO4 transmit buffer of data it is waiting to send.
Values per repetition = 0

5.2.8 Command 7: Activate Command Line

This command simulates pressing the push button on the SDM-SIO4 which activates the command line mode on the port determined by the mode. If the mode parameter of P113 is 0, the command line will be on the currently defined port. If the parameter is 1-4, then the command line will be on the port number specified.
Values per repetition = 0

5.2.9 Command 8: Poll Tx Buffers for Data

This command polls the Tx buffers to see if they have data.
This command has no additional options after the command. The SDM-SIO4 returns one Campbell Scientific floating point number to indicate if it has data as below:
Port 4 has data | Port 3 has data | | Port 2 has data | | | Port 1 has data | | | |
x x x x
5-5
Section 5. Programming the Datalogger
If any of these four digits is greater than zero then the buffer has data.
Values per repetition = 1

5.2.10 Command 9: Flush Converted Data Buffer

This command flushes the converted data buffer of data that is available for the datalogger to collect.
Values per repetition = 0

5.2.11 Command 66: Send Single-Byte Data to Datalogger

This command requests the SDM-SIO4 to send single-byte binary data, which is written one byte per location for all values/rep. If no data is available then the digit 255 is stored in the input location. This command could be used, for example, to get data from filter strings of type c (read any byte) and Nn (read ‘n’ bytes) – see Section 3.

5.2.12 Command 67: Get Return Code

This command gets the return error code and places it into a specified location. Command 67 is used in conjunction with command 321 and provides a single return code value which indicates if the command was successful or not. See Section 5.6 for the return codes.
Values per repetition = 1

5.2.13 Command 320: Send Byte Data to SDM-SIO4

This command transmits bytes of data (one per input location) to the SDM­SIO4 for retransmission. The values in the input location should be in the range
0..255.

5.2.14 Command 321: Execute Command Line Command

By using P113 command 321 it is possible to execute a command line command from the datalogger program. This is done by loading the datalogger’s input locations with exactly the same string of characters that you would use to execute a real command line command, except you would have to enter the character codes in sequential locations. The P113 command 321 would then load the string into the SDM-SIO4 and execute the command. The 321 command is useful for reconfiguring a remote SDM-SIO4 as changes can be made by downloading programs (using the 321 command) which can change the SDM-SIO4 setup.
5-6
The datalogger can send other commands to the SDM-SIO4 while the command line command is executing.
Any command line command executed from the datalogger can only return a single return code value to indicate if it was successful or not, and any other output which that command would normally produce is lost. This means that
Section 5. Programming the Datalogger
there would be no point executing some commands, for example STATUS, from the datalogger, as there would be no status output to be seen. To get the return code you can use the P113 Command 67 which will put the return code into a storage location. The return codes are listed at the end of this section.
This command requires a 4ms delay before any other SDM-SIO4 instruction from the datalogger is executed
NOTE
Do not attempt to run a program with command 321 while accessing the command line via one of the SDM-SIO4 ports.
Program Example for P113 Command 321
An example of executing a command line command to store the following filter string as shown below:
The filter string is fltst 25 “ffCc”
;test flag one. If clear then set-up the SDM-SIO4.
P91
1: 21 2: 30
;load command line string into consecutive locations.
P65 Bulk load
1: 102 f 2: 108 l 3: 116 t 4: 115 s 5: 116 t 6: 32 ascii space 7: 50 2 8:5 3 5 9: 1 First location to store the first lot of 8 characters.
P65 Bulk load
1: 32 ascii space 2: 34 “ 3: 102 f 4: 102 f 5:6 7 C 6: 99 c 7: 34 “ 8: 0 9: 9 First location to store second lot of characters.
;execute the command line string.
5-7
Section 5. Programming the Datalogger
P113
1: 1 2: 0 3: 1 4: 21 Command to execute command line command. 5: 0 6: 0 7:1 5 Length of command line string. ;no. of datalogger input locations 8: 1 9: 1 10: 0
;delay large enough (10ms) to allow SDM-SIO4 instruction 321 to finish.
P22
1: 1 2: 0 3: 1 4: 0
;get the command line return code. In this case the returned code would be 22 as the SDM-SIO4 would still be executing the command line command. This P113 instruction in most cases would not be required and would generally be used in development of the datalogger program.
P113
1: 1 2: 0 3: 1 4: 67 Command to get return error codes. 5: 0 6: 0 7: 1 8: 20 Location to store return code. 9: 1 10: 0
;set flag one so that set-up will only be done once.
P86
11
;end of set-up.
P95
NOTE
If you use the RAMTEST command you will have to wait a minimum of 6 seconds for it to complete before you try to execute another P113.
5-8
Some Dataloggers do not support P65 Bulk Load. In that case you would have to use a P30 Instruction for each ASCII character.
Section 5. Programming the Datalogger

5.2.15 Command 1024: Send String to Device

This command requests the SDM-SIO4 to transmit a user-defined text string (entered in the command line mode) number 0..255 or a fixed string 256..511. The string number is defined in parameter 5. The string is transmitted from the specified port to the RS232 device. If the specified string has not been allocated
string not allocated’ is transmitted.
then ‘
Values per repetition = 0
NOTE
Minimum delay = characters*0.26*ports in milliseconds

5.2.16 Command 1025: Transmit a Byte

This command transmits a byte (defined in parameter 5) from the SDM-SIO4 to the RS232 device. The byte must be in the range of 0..255 for binary code.
Values per repetition = 0

5.2.17 Command 1026: Serial Port Status

This command requests the SDM-SIO4 to send the current output level of status lines, number of framing errors, number of parity errors and number of overruns. This is sent to the datalogger as four Campbell Scientific floating point numbers to consecutive input locations.
Values per repetition = 4
First Value Returned
Parity errors (count from 0..99) | | DTR status (0=DTR low, 1=DTR high) | | | RTS status (0=RTS low, 1=RTS high) | | | |
x x x x
Second Value Returned
CTS status (0=CTS low, 1=CTS high) | DSR status (0=DSR low, 1=DSR high) | | RI status (see below) | | | DCD status (0=DCD low, 1=DCD high) | | | |
x x x x
For the RI (Ring Indicator): 0 = no trailing edge seen since last read 1 = trailing edge seen since last read
5-9
Section 5. Programming the Datalogger
Third Value Returned
Framing errors | | Overrun errors | | | |
x x x x
Framing errors is a count from 0-99. This count shows how many times there has been a receive error, caused by a character corruption or incorrect set-up.
Overrun errors is a count from 0-99. This count shows how many times characters have been lost due to data being sent too quickly for the SDM-SIO4 to process the data.
Fourth Value Returned
NOT USED - SET TO ZERO | | Line break errors | | | |
x x x x
Line break er rors is a count from 0-99. This count shows how many times the line has been broken or disconnected.
First Command Option — Reset Error Counters
When command 1026 is specified in parameter 4 of Instruction 113, this additional option can be used (parameter 5 of Instruction 113) to force the error counters to be reset to zero.
This means that command 1026 requests data from the SDM-SIO4 and can also be used to send these reset commands to the SDM-SIO4.
NOTE
The command to reset the error counters has no effect on a port if the command line is active.
Break reset | Framing reset | | Overrun reset | | | Parity reset | | | |
x x x x
Break reset: 0 Do nothing 1 Reset line break count to zero
Framing reset: 0 Do nothing 1 Reset framing error count to zero
5-10
Overrun reset: 0 Do nothing 1 Reset overrun error count to zero
Section 5. Programming the Datalogger
Parity reset: 0 Do nothing 1 Reset parity error count to zero

5.2.18 Command 1027: ‘Manual’ Handshake Mode

In this mode, the datalogger can set DTR, RTS and XON/XOFF as required.
Not used - set to zero. | XON/XOFF | | RTS | | | DTR | | | |
x x x x
XON/XOFF: 0 Leave as set previously 1 XOFF data (stop data transmission from SDM-SIO4) 2 XON data (restart data transmission from SDM-SIO4)
RTS: 0 Leave as set previously 1 Clear RTS to low 2 Set RTS to high
DTR: 0 Leave as set previously 1 Clear DTR to low 2 Set DTR t o high
Values per repetition = 0
NOTE
A 2ms delay is required after this command before the next SDM-SIO4 command is started.

5.2.19 Command 2049: Set Communications Parameters

This command sets the baud rate, data length, stop bits, parity and handshake mode as follows (please refer to Appendix B for a more detailed explanation):
Values per repetition = 0
First Command Option (Parameter 5)
Handshake mode | Stop bits + parity | | Data length | | | Baud rate | | | |
x x x x
5-11
Section 5. Programming the Datalogger
Handshake Mode: 0 Leave as set previously 1 DTR always set, set RTS when data is available to transmit, only
2 DTR always set, RTS always set, only transmit if CTS is set 3 DTR and RTS always set, ignore CTS 4 XON/XOFF data flow control 9 No automatic handshake (leaves lines in previous state)
Stop Bits and Parity: 0 Leave as set previously. 1 1 stop bit no parity. 2 1 stop bit even parity. 3 1 stop bit odd parity. 4 1.5/2 stop bits no parity. 5 1.5/2 stop bits even parity. 6 1.5/2 stop bits odd parity.
Data Length: 0 Leave as set previously 1 5 data bits 2 6 data bits 3 7 data bits 4 8 data bits
transmit if CTS is set
Baud Rate: 0 Leave as set previously 1 300 baud 2 600 baud 3 1200 baud 4 2400 baud 5 4800 baud 6 9600 baud 7 19200 baud 8 32400 baud 9 76800 baud
Second Command Option (Parameter 6)
This option is used to set the handshaking delay in units of 50ms. The accuracy is -50ms, +0ms. The range is 0-254, with 255 reserved for XON /XOFF mode. XOFF will force the SDM-SIO4 to wait indefinitely for an XON.
NOTE
NOTE
When the SDM-SIO4 is reset from the ‘command line’, the ports are set to 9600 baud, 8 data bits, 1 stop bit, no parity and no handshake as the default.
A 1ms delay is required after Command 2049 before the next SDM­SIO4 command is initiated.
5-12
Section 5. Programming the Datalogger

5.2.20 Command 2054: Set Up Receive Filter

This command clears all buffers relevant to the mode number and restarts the filter.
Values per repetition = 0
NOTE
With the string filter type the SDM-SIO4 buffers are not cleared.
First Command Option (Parameter 5)
Input mode | String number or character code | | | |
x x x x
Input Mode: 0 No filter 1 Convert any ASCII numbers to Campbell Scientific floating point up to the
termination character if set
2 Convert any ASCII hex pair to Campbell Scientific floating point up to the
termination character if set
3 Convert 8-bit binary number to Campbell Scientific floating point up to the
termination character if set
4 Convert 16-bit binary number to Campbell Scientific floating point up to the
termination character if set. 8 Transmit a user-defined string 0-255 or fixed string 256-511 9 String filter type. See Filter Strings in Section 2.3.
String Number or Character Code: If input mode 9 is chosen, this is the user-defined filter string number 0..255 or
fixed filter string 256..511 used for the filter; if the string is not allocated the filter will not operate. If input mode 8 is chosen, this number is the defined string 0-255 or fixed string 256-511. If input modes 1 to 4 are chosen, this is the termination character as an ASCII code 0..255; 999 means character not enabled.
NOTE
Minimum delay = 4 +(characters to Tx)*0.26*ports, in milliseconds.

5.2.21 Command 2304: Transmit String and/or Data to Device (Formatter/Filter)

This command transmits a string and/or floating point data and optionally sets up a filter ready for returned data.
Values per repetition for Command 2304 are: if transmitting a string = 0 if transmitting data from input locations = number of locations
5-13
Section 5. Programming the Datalogger
First Command Option (Parameter 5)
Output mode | String number or termination character | | | |
x x x x
Output Mode: 0 No output format string 1 Convert location to ASCII floating point. Add character/delimiter between
values if enabled. The last value will not have a delimiter after it.
2 Convert location to ASCII hex pair. Add character/delimiter between values
if enabled. The last value will not have a delimiter after it.
3 Convert location to 8-bit binary. Add character/delimiter between values if
enabled. The last value will not have a delimiter after it.
4 Convert location to 16-bit binary. Add character/delimiter between values if
enabled. The last value will not have a delimiter after it. 8 Transmit a user-defined string 0-255 or fixed string 256-511. 9 String type formatter; this is used where input; location data is to be
transmitted in a complex format. See Output Formats in Section 3. String Number or Delimiter Character:
If output mode 9 is chosen this is the string number 0..255. If the string is not allocated then the formatter will not operate. If mode 8 is chosen, then this is the user defined string 0-255 or fixed string 256-511. If output modes 1 to 4 are chosen, then this specifies the delimiter character as an ASCII code 0..255. 999 means character not enabled.
Second Command Option (Parameter 6)
This is used for filter set-up if data is expected back after output.
Input mode | String number or character/delimiter code | | | |
x x x x
Input Mode: 0 No filter 1 Convert any ASCII numbers to Campbell Scientific floating point up to the
termination character if set 2 Convert any ASCII hex pair to Campbell Scientific floating point up to the
termination character if set 3 Convert 8-bit binary number to Campbell Scientific floating point up to the
termination character if set 4 Convert 16-bit binary number to Campbell Scientific floating point up to the
termination character if set. 8 Transmit a user-defined string 0-255 or fixed string 256-511 9 String filter type. See Filter Strings in section 3.
String Number or Character Code
If input mode 9 is chosen, this is the user-defined filter string number 0..255 or fixed filter string 256..511 used for the filter; if the string is not allocated the filter will not operate. If input mode 8 is chosen, this number is the defined string 0-255 or fixed string 256-511. If input modes 1 to 4 are chosen, this is
5-14
Section 5. Programming the Datalogger
the termination character as an ASCII code 0..255; 999 means character not enabled.
NOTE
Min. delay for floating point data = floats*3*(characters*0.26*ports). Min. delay for strings = characters*0.26*ports.

5.2.22 Command 2305: Transmit Byte(s)

By using P113 command 2305 it is possible to transmit either one or two bytes from the command options. If any command option is set to 999 then the byte will not be sent. The number range for each command option is 0-255 and 999. An example of its use is below:
1: SDM-SIO4 (P113)
1: 1 Reps. 2: 0 SDM address. 3: 1 Mode, send bytes to port 1. 4: 2305 Command. 5: 13 Decimal number that represents Carriage Ret. 6: 10 Decimal number that represents Line Feed 7: 0000 Values/Rep. 8: 0000 Start location. 9: 1 Mult. 10: 0.0 Offset.
The example will transmit the bytes ‘carriage return line feed’ (CrLf) to port one.
Values per repetition = 0

5.3 SDM-SIO4 Configuration Examples

Although the serial port configurations can be set up using the ‘command line’, many users may prefer to set up the ports from their program. This would normally be done once when the program is first compiled. The instruction can be placed within a logical block which only runs when a specified datalogger flag is reset. The program should be written so that the flag can then be set to prevent the instr uction running after the first e xecution; this also enable s you t o force reconfiguration by toggling the flag low.

Example CR10X Program

This program is an example of how you could set up the SDM-SIO4 serial mode and filter type once on program compilation or if flag 1 was reset. This works on port 1 of the SDM-SIO4.
The program will convert ASCII floating point input values into Campbell Scientific floating point format. The datalogger will store two values in locations 1 and 2.
5-15
Section 5. Programming the Datalogger
*Table 1 Program
01: 2 Execution Interval (seconds)
;if flag one is not set then set up the serial mode and filter.
1: If Flag/Port (P91)
1: 21 Do if Flag 1 is Low 2: 30 Then Do
;set serial mode to DTR, RTS always set, ignore CTS, 1 stop bit no parity, ;8 bit data length, 9600 baud and no handshake delay.
2: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2049 Command 5: 3146 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1.0 Mult 10: 0.0 Offset
;set up a simple filter 1999 search for floating point number.
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 1999 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1.0 Mult 10: 0.0 Offset
;the set up filter command requires a delay of 4ms, the nearest we can get ;is 10ms with P22.
4: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;set flag one high so the above will only be done once.
5-16
5: Do (P86)
1: 11 Set Flag 1 High
;end of serial and filter setup.
6: End (P95)
;get two floating point numbers into locations 1 and 2.
7: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ Number ] 9: 1.0 Mult 10: 0.0 Offset
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
Section 5. Programming the Datalogger
End Program
The normal configuration would include setting the speed and serial data format by calling the datalogger instruction with command 2049 and the relevant parameters.
For the majority of sensor applications where data is returned in only one type of format to the SDM-SIO4, the receive data format filters can also be defined once only by using command 2054. Similarly, some sensors may also require set-up strings to be sent once; these actions can also be placed in the same configuration block.
There are two general methods of obtaining data from an intelligent RS232 device, depending on the sensor type, as indicated below:

5.3.1 Sensors Where the Datalogger Can Request Data by Sending a Prompt or Using a Handshaking Line

For these sensors the measurement would consist of three phases:
1. For software-controlled sensors, use the datalogger instruction to send out a
command string (to request data), using commands 0320, 1024, 1025 or
2304. (Command 2304 also allows you to set up the receive filter to match the expected data; this instruction is useful when several different types of data are being requested from the sensor, i.e. a one-off set-up of the receive filter with command 2054, is not appropriate.) For hardware-controlled sensors, use command 1027 to change the state of the handshaking lines.
2. The data logger waits for a period long enough for the SDM-SIO4 to process
the set-up data (minimum delay), plus time for the data to be transmitted out of the serial port, plus the time for the sensor to respond and the data string to be transmitted back to the SDM-SIO4. The delay can either be instigated
5-17
Section 5. Programming the Datalogger
by using Instruction 22, or a delay loop, or more efficiently by running some of the other measurement tasks required of the datalogger. After the minimum delay, these tasks could also include further communications with the SDM-SIO4 to deal with one of the other sensors connected to another port.
3. Finally the SDM-SIO4 instruction is used to read the collected data back
from the SDM-SIO4. Commands 4 or 66 are used for this function.
Example CR10X Program Using Instruction P113 Command 4
This program is written so that, on every execution interval, the datalogger will send a string out of port 1 to command the sensor to transmit its measurements back to the SDM-SIO4, which has a filter set up ready to receive the data.
The output formatter is set up to transmit a string as follows:
strst 101 "Send Data^J^M"
Here is how the above string works:
strst 101 – this is the command to store a sting in area 101. Send Data – this is the command string the sensor will execute. ^J^M – this is a way of entering control characters for carriage return/linefeed
into a string
The following program example works as follows:
1. The first P113 sets up a simple filter to search for floating point numbers.
2. The first parameter of this command is used to transmit a string which will
prompt the sensor into taking measurements and then transmitting the numbers to the SDM-SIO4.
3. A delay is required by the set up formatter command and is calculated as
follows: delay=chars*0.26*ports. This works out as the following: 11*0.26*1 = 2.86ms. Also you will have to
wait long enough for the sensor to respond which must include the time to receive and transmit the data. This example is using a 9600 baud rate, and so 11 characters could take 12ms for the sensor command and another 20 characters (21ms) for output data from the sensor. The total time before the datalogger can get the data would therefore be 2.86+12+21 = 35.86ms. This time does not allow for any delay that the sensor may have in executing and taking any measurements. This example gives the sensor 4.24ms for measurements by giving P22 a 40ms delay.
4. By doing the above, the datalogger can get the two floating point values
returned from the sensor into locations 1 and 2.
5-18
*Table 1 Program
01: 2 Execution Interval (seconds)
;set up the filter and then send string 101.
1: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 8101 1st Parameters 6: 1999 2nd Parameters 7: 0 Values per Rep 8: 0 Loc [ ] 9: 1.0 Mult 10: 0.0 Offset
;wait long enough for sensor to send data.
2: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 4 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
Section 5. Programming the Datalogger
;get data from SDM-SIO4 and put into locations 1 and 2.
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ number ] 9: 1.0 Mult 10: 0.0 Offset
;At zero minutes into a 10 minute interval set the output ;so that the data from the sensor will be stored into ;final storage.
4: If time is (P92)
1: 0 Minutes (Seconds --) into a 2: 10 Interval (same units as above) 3: 10 Set Output Fl ag High (Flag 0)
;Time stamp.
5: Real Time (P77)
1: 1110 Year,Day,Hour/Minute
5-19
Section 5. Programming the Datalogger
;Instantaneous sample form the sensor.
6: Sample (P70)
1: 2 Reps 2: 1 Loc [ number ]
;Average over the 10 minute interval.
7: Average (P71)
1: 2 Reps 2: 1 Loc [ number ]
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
End Program

5.3.2 Sensors Which Send Data Out Without Prompting

It can be very difficult to acquire data from this type of sensor because of the lack of synchronization with the datalogger program.
For sensors which output data relatively slowly data can be collected by using special features of the input filters which tell the SDM-SIO4 only to recognize the start and end of data (using the x and X options – see Section 3). These options only allow the datalogger to collect data once a complete data set has been received by the SDM-SIO4 (avoiding problems of collection in mid­transmission). Thus, by polling the SDM-SIO4 using command 1, it is possible to see if data has been received and if so use a second call of the datalogger SDM-SIO4 instruction to collect the available data.
Example CR10X Program without Polling or Interrupts
This simple program is an example for sensors that send data at random intervals. If no data was available when the datalogger asked for it then -99999 will be put into locations 1 and 2. An IF THEN structure could be used in the datalogger program to store only values that are not -99999.
A typical filter that could be used is:
fltst 200 "t[data]A5xff"
This filter works as follows: t[data] – this filter waits for an exact string match before it starts the next filter.
In this case it is waiting for the sensor to send the string ‘data’.
5-20
A5 – this filter sets up a 250ms filter time-out. This time-out should be long enough for the senso r to transmit all of its data .
x – this filter marks the start of the data set. In this case the data set is two floating poi nt numbers.
f – this filter searches for the first ASCII floating point number to convert. f – this filter searches for the second ASCII floating point number to convert.
*Table 1 Program
01: 2 Execution Interval (seconds)
;test flag one to see if set up is required.
1: If Flag/Port (P91)
1: 21 Do if Flag 1 is Low 2: 30 Then Do
;set the filter up.
2: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 9200 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1.0 Mult 10: 0.0 Offset
Section 5. Programming the Datalogger
;filter set up requires a delay.
3: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;set flag one so setup only happens once.
4: Do (P86)
1: 11 Set Flag 1 High
;end of set up.
5: End (P95)
;get the two floating point values from the SDM-SIO4.
5-21
Section 5. Programming the Datalogger
6: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ Voltage ] 9: 1.0 Mult 10: 0.0 Offset
;Only set the output flag when the voltage is ;greater than or equal to -99998.
7: IF (X<=>F) (P89)
1: 1 X Loc [ Voltage ] 2: 3 >= 3: -99998 F 4: 10 Set Output Fl ag High (Flag 0)
;Time stamp.
8: Real Time (P77)
1: 1111 Year,Day,Hour/Minute,Seconds
;Instantaneous values stored to final storage.
9: Sample (P70)
1: 2 Reps 2: 1 Loc [ Voltage ]
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
End Program
Example CR10X Program using the Polling Method
This program will deal with sensors that send data at random intervals. The program polls the SDM-SIO4 to see if data is available and only stores the data then.
A typical filter that could be used is as follows:
5-22
fltst 200 "t[data]A5xff"
This filter works as follows: t[data] – this filter waits for an exact string match before it starts the next filter.
In this case it is waiting for the sensor to send the string ‘data’.
A5 – this filter sets up a 250ms filter time-out; this time-out should be long enough for the senso r to transmit all of its data .
x – this filter marks the start of the data set. In this case the data set is two floating poi nt numbers.
f – this filter searches for the first ASCII floating point number to convert. f – this filter searches for the second ASCII floating point number to convert.
*Table 1 Program
01: 2 Execution Interval (seconds)
;do filter set-up only if flag one is clea r.
1: If Flag/Port (P91)
1: 21 Do if Flag 1 is Low 2: 30 Then Do
;set up string filter.
2: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 9200 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0 Loc [ _________ ] 9: 1.0 Mult
10: 0.0 Offset
Section 5. Programming the Datalogger
;delay required by filter set-up command.
3: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;set flag one high so the filter set-up is only done once.
4: Do (P86)
1: 11 Set Flag 1 High
;end of IF.
5: End (P95)
;poll SDM-SIO4 to see if data is available.
5-23
Section 5. Programming the Datalogger
6: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 1 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 1 Values per Rep 8: 2 Loc [ poll ] 9: 1.0 Mult 10: 0.0 Offset
;if value returned from poll is >=1 then data must be available.
7: IF (X<=>F) (P89)
1: 2 X Loc [ poll ] 2: 3 >= 3: 1 F 4: 30 Then Do
;get voltages into locations 3 and 4 if poll was true.
8: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 3 Loc [ voltage1 ] 9: 1.0 Mult 10: 0.0 Offset
;set the output flag so the data can be store to final storage.
9: Do (P86)
1: 10 Set Output Fl ag High (Flag 0)
;time stamp.
10: Real Time (P77)
1: 1111 Year,Day,Hour/Minute,Seconds
;Instantaneous value stored into final storage.
11: Sample (P70)
1: 2 Reps 2: 3 Loc [ voltage1 ]
5-24
;end of IF.
12: End (P95)
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
End Program
Example CR10X Program using Interrupts
Sensors with fast data output or where very close time stamping is required would need to be read using the hardware interrupt output from the SDM-SIO4 in combination with an interrupt-driven subroutine in the datalogger (only the CR10/10X currently support this mode). This output on the SDM-SIO4 pulses high when there is data available from one of the serial ports.
This program will deal with sensors that send data at random intervals. It uses the IO line to cause an interrupt to the datalogger program if data is available. The IO line is always automatically pulsed by the SDM-SIO4 when data is available – see ‘SDM Port’ in Section 1 for details. This should be connected to control port 8 for this example.
Section 5. Programming the Datalogger
A typical filter that could be used is as follows:
fltst 200 "t[data]A5xff"
This filter works as follows: t[data] – this filter waits for an exact string match before it starts the next filter.
In this case it is waiting for the sensor to send the string ‘data’. A5 – this filter sets up a 250ms filter time out. This time out should be long
enough for the senso r to transmit all of its data . x – this filter marks the start of the data set. In this case the data set is two
floating poi nt numbers.
f – this filter searches for the first ASCII floating point number to convert. f – this filter searches for the second ASCII floating point number to convert.
*Table 1 Program
01: 2 Execution Interval (seconds)
;set control port 8 to i/p so it can be used as an interrupt
1: Set Port(s) (P20)
1: 8999 C8..C5 = input/nc/nc/nc 2: 9999 C4..C1 = nc/nc/nc/nc
;do filter setup only if flag one is clea r
2: If Flag/Port (P91)
1: 21 Do if Flag 1 is Low 2: 30 Then Do
5-25
Section 5. Programming the Datalogger
;set up string filter
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 9200 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0 Loc [ _________ ] 9: 1.0 Mult 10: 0.0 Offset
;delay required by filter setup comman d
4: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;set flag one high so the filter set-up is only done once
5: Do (P86)
1: 11 Set Flag 1 High
;end of IF
6: End (P95)
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
;interrupt routine for control port 8
1: Beginning of Subroutine (P85)
1: 98Subroutine 98
;get voltages into locations 3 and 4
5-26
2: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 3 Loc [ voltage1 ] 9: 1.0 Mult 10: 0.0 Offset
;set the output flag so that readings can be stored into ;final storage.
3: Do (P86)
1: 10 Set Output Fl ag High (Flag 0)
;time stamp.
4: Real Time (P77)
1: 1111 Year,Day,Hour/Minute,Seconds
Section 5. Programming the Datalogger
;instantaneous readings stored into final storage.
5: Sample (P70)
1: 2 Reps 2: 3 Loc [ voltage1 ]
;end of interrupt routine.
6: End (P95)
End Program
NOTE
Where multiple ports are being used, the first instruction would have to be command 1 to see which port has data, followed by a second call, or calls, to collect the data.

5.4 Outputting Datalogger Data

The SDM-SIO4 can be used to drive displays, printout devices and other output-only systems. In this case after the initial configuration (as above) either simple data can be sent using commands 0320, 1025 or just data strings using 1024 or strings plus formatted data sent using command 2304.
This program example will output the battery voltage and panel temperature from the datalogger locations using the SDM-SIO4 Output Formatter.
5-27
Section 5. Programming the Datalogger
The user-defined formatter used is:
fmtst 123 "z261 f6:2 i[Battery ]z257 f6:1z273"
An example of typical output from this formatter string might be: Temperature 27.23 Battery Voltage 12.6 Here is a description of what each part of the formatter does: fmtst 123 – This is the command word for storing the formatter sting in area
123.
z261 – This outputs the fixed string ‘Temperature’. space –This outputs an ASCII space. f6:2 – This takes the value from location 1 and outputs it. The output field has a
total width of 6 characters; 2 decimal places are available within the field.
space – This outputs an ASCII space. i[Battery ] –This outputs the word between the brackets [ ]. z257 – This outputs the fixed string ‘Voltage’. space – This outputs an ASCII space. f6:1 – This takes the value from location 2 and outputs it. The output field has a
total width of 6 characters; 1 decimal place is available within the field. z273 – This outputs the fixed string ‘CrLf (carriage return line feed)’.
*Table 1 Program
01: 2 Execution Interval (seconds)
1: Batt Voltage (P10)
1: 2 Loc [ Batt_v ]
2: Internal Temperature (P17)
1: 1 Loc [ Temp_C ]
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 2 Send/Receive Port 2 4: 2304 Command 5: 9123 1st Parameters 6: 0 2nd Parameters 7: 2 Values per Rep 8: 1 Loc [ Temp_c ] 9: 1.0 Mult 10: 0.0 Offset
5-28
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
Section 5. Programming the Datalogger
*Table 3 Subroutines
End Program

5.5 Flushing the Input and Output Buffers

One important aspect of the SDM-SIO4 is that it will continue to collect data and store it i n its buffers even if the datal ogger program stops r unni ng. Care must be taken to ensure that data does not build up in the buffers and as a result either a buffer overflows, or data is collected which relates to a different time than anticipated.
To prevent this, the instruction set includes instructions which either allow the buffers to be erased or special filter options which allow buffers to be flushed and data collection to be stopped and started. Please refer to these instructions for more details.
Unless the filters used specifically flush the input buffer it is advisable to include instructions to flush the buffers within the configuration section of the program.

5.6 Return Error Codes

These return error codes are used by the command line and by the datalogger comma nd 67.
0= No error. 1= String not enclosed in double quotes 2= String > 255 characters long 3= Out of string memory 4= Unknown error 5= String not allocated 6= String pointer corrupt 7= Command not recognized 8= Command index error 9= Bad parameters 10= String > 255 characters long or Out of string memory 11= Filter definition error 12= Filter definition error - number too big 13= Formatter definition error 14= Formatter definition error - number too big 15= No ‘:’ separator between numbers 16= COMMAND LINE is now on port number 1 17= COMMAND LINE is now on port number 2 18= COMMAND LINE is now on port number 3 19= COMMAND LINE is now on port number 4 20= System RAM failure 21= System RAM good 22= SDM-SIO4 busy 23= Command successful
5-29
Section 5. Programming the Datalogger
This is a blank page.
5-30

Section 6. Data Error Detection

Error detection by checksum, CRC or signatures is a way of detecting errors in data, either transmitted or received. This section gives details on how to use filter strings together with datalogger program examples to implement error detection methods.

6.1 Error Detection with the SDM-SIO4

Error detection is carried out to provide confidence that critical data is received/transmitted correctly.
For example, some data may be transmitted through a noisy environment, which could introduce errors into the data. Thus the received data could be corrupted in some way – for instance a number might possibly be changed from ‘1000’ to ‘2000’. This change would not be detected if the numbers were both in the valid number ra nge unless some error detection system was used.
Error detection usually takes the form of the transmitting device calculating a Checksum, CRC (cyclic redundancy checksum) or Signatur e for the data it is transmitting. This Checksum, CRC or Signature result is transmitted at the end of the data in some form. The receiving device is configured to calculate exactly the same Checksum, CRC or Signature on the data it receives (except for the checksum bytes). The two sep arate Checksums, CRCs or Signatures are then compared, and if the two match exactly then the data received should be error free.

6.2 Received Data

NOTE
No checksum will detect 100% of all errors. The more sophisticated the algorithm the better the error detection.
The signature that the sensor returns can be in many different data types – for example ASCII decimal, binary or hexadecimal. Additionally, each of the data types can have differences; for example with binary you can have 8 bit, 16 bit, and 32 bit and also the most significant byte could be transmitted first or the least significant byte could be transmitted first. Because of the above the SDM­SIO4 has two error detection filters ‘gn’ and ‘Gn’. The first, ‘gn’, the signature type you want to use and ‘Gn’ is used to set the data type of the signature expected from the sensor/device. A full description of how these filters operate is shown below.
gn
This filter type can be put into the filter string to mark the start of a signature generation. When this happens the signature type determined by ‘n’ will be initialized ready to start signature calculation for all characters until filter Gn is encountered, which marks the end of the string (see below). The value of ‘n’ for filter gn can be in the range of 0-255. The signature types supported are below:
is used to set
6-1
Section 6. Data Error Detection
0 No Signature t ype used. 1 CRC16 standard. Polynomial x 2 CRC16-CCITT standard. Polynomial x
16+x15+x2
16+x12+x5
+1.
+1. 3 CRC16-CCITT-IBM (Tag Receiver). 4 CRC32 standard.
Polynomial
32+x26+x23+x22+x16+x12+x11+x10+x8+x7+x5+x4+x2
x
+x+1. 5 CSI Signature (see Appendix C of the CR10X Manual). 6 Checksum using modulo 256. 7 Checksum using modulo 8192 (See Section 5 of the CR10X Manual).
8 Checksum which performs exclusive OR on the first byte and then
each succeeding byte until all bytes are read. The result is the checksum ‘g8’.
9-255 For future use.
Gn
This filter type can be added to the filter string to mark the end of the string and the point where the sensor signature should be. It also sets the data type to use. When this filter is done, the signature returned from the sensor will be converted into a standard data type, so the SDM-SIO4 can compare the original signature it calculated to the one the sensor returned. If the two signatures match, then the data is ready for the datalogger to collect, but if they do not match, the data will be removed, as it will be considered to be corrupt data (if no other data is ready for the datalogger to collect then -99999 for floating point or 255 for single-byte characters will be stored into the datalogger input location).
6-2
From the programmer's point of view, the datalogger could be set up to do one of the following:
1. Poll the SDM-SIO4 to see if data is available.
2. Read the corrupt values as -99999 or 255 into locations and just store them
as normal.
3. Read the values, check to see if they are -99999 or 255, and if so then ask
the device connected to the SDM-SIO4 to re-send the data. Note that the removal of corrupt data in this way will only work if the Data Set filters are used. Since Gn is always at the end of a data set, the data will always remain available for collection by the datalogger unless you define another data set with the ‘x’ filter.
n can be in the range of 0-255 which is the data type to use.
The data types that the SDM-SIO4 can deal with are as follows: 0 No data type or check 1 8-bit binary. Expects 1 byte 2 16-bit binary least significant byte first. Expects 2 bytes
Section 6. Data Error Detection
3 16-bit binary most significant byte first. Expects 2 bytes 4 32-bit binary least significant byte first. Expects 4 bytes 5 32-bit binary most significant byte first. Expects 4 bytes 6 ASCII decimal. Waits until non ASCII 0-9 received 7 8-bit ASCII hex. Expects 2 ASCII bytes, if not 0-9,a-f,A-F then fail 8 16-bit ASCII hex. Expects 4 ASCII bytes, if not 0-9,a-f,A-F then fail 9 32-bit ASCII hex. Expects 8 ASCII bytes, if not 0-9,a-f,A-F then fail 10-255 for future use.

6.2.1 Example of Using Received Data Filters

If a sensor transmitted the following string:
Frequency=12.34567HzBB3DCrLf
then a user defined filter string would have to be used. The BB3D part of the string is the CRC sent in hex. from the sensor. To produce a filter string to deal with the sensor output you could type in the following command:
FLTST 100 “T[Frequency=]xg2n10fCCG8” FLTST is the command to store a user defined filter from the command line. 100 is the string number you want to store it under this can be 0-255. is the start of the filter string. T[Frequency=] is a filter which looks for an exact string match for
“Frequency=”. The next filter will only start if this string matches what is sent from the sensor. “Frequency=” is not removed from the receive buffer.
x this filter marks the start of a data set; in other words the data will only be available for the datalogger to collect when the complete string is received correctly.
g2 this is the filter that tells the SDM-SIO4 to use the CRC16-CCITT algorithm. It initializes the CRC16-CCITT algo rithm to start calculation on any characters from this point.
n10 This filter discards the 10 ASCII characters that make the word “Frequency=”. Note: The word is discarded after filter g2. This is to ensure that the discarded word will be included in the CRC calculations.
f this filter gets the numeric value from the sensor and converts it into a format the datalogger can use. Because filter “x” was used this converted value will not be available for the datalogger to collect until the CRC16-CCITT signature check is done. In this case the value converted is “12.34567”.
C this filter removes the char “H”. C this filter removes the char “z”. G8 this filter tells the SDM-SIO4 that the next ASCII hex is the start of the
checksum from the sensor. It also defines the data type to be ASCII hex 16 bit. This filter will wait until enough characters have been received to make the hex number up, in this case four bytes of ASCII hex. When the characters have been received, the SDM-SIO4 will compare it with the check sum it calculated
6-3
Section 6. Data Error Detection

6.2.2 CR10X Program Example

*Table 1 Program
01: 1.0 Execution Interval (seconds)
on the received data. If they match then the value converted with the “f” filter is made available for the datalogger to get. If the checksums do not match then the value is discarded as soon as any error is detected.
marks the end of the filter string.
The above example is just one way of using a filter to achieve the required result.
A typical CR10X datalogger program to work with the above filter is shown below.
Assume the SDM-SIO4 is set to address 0, the sensor is connected to port 1 of the SDM-SIO4 and the port settings, baud rate, etc. have been set. The sensor outputs its string every second. Only the parameter values to be entered into the appropriate instructions are shown.
;test flag 1 – if not set tell the SDM-SIO4 to use filter string 100
1: If Flag/Port (P91)
1: 21 Do if Flag 1 is Low 2: 30 Then Do
;tell the SDM-SIO4 to use filter string 100
2: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2054 Command 5: 9100 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 0 Mult 10: 0 Offset
;a minimum delay of 4ms is required by the above P113
3: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
6-4
;set flag 1 to instruct the SDM-SIO4 to use the filter once only
Section 6. Data Error Detection
4: Do (P86)
1: 11 Set Flag 1 High
;end of filter setup
5: End (P95)
;poll SDM-SIO4 to see if data is available for the datalogger to collect ;the value from the poll is read into location 1
6: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 1 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 1 Values per Rep 8: 1 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
;if the value in location 1 is greater than zero then there must be data ;this assumes only one sensor is connected to the SDM-SIO4
7: IF (X<=>F) (P89)
1: 1 X Loc [ _________ ] 2: 3 >= 3: 1 F 4: 30 Then Do
;if data is available then get the value and put into location 2
8: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 4 Command 5: 0 1st Parameters 6: 0 2nd Parameters 7: 1 Values per Rep 8: 2 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
;end of get data.
8: End (P95)
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
6-5
Section 6. Data Error Detection
*Table 3 Subroutines
End Program
The program shown above will only put data into the storage locations if any data was available. Data being available is detected by polling the SDM-SIO4 to see if any data is waiting. If you decided not to poll the SDM-SIO4 then you would get -99999 in the locations if data was not available to collect.
When the Checksum, CRC or Signature calculation is used it will reduce the speed at which the filters can deal with the data from the receive buffers. How much slower the filters will be depends on which algorithm is used. The timings for the algorithms are given below. These timings are in addition to the normal filter processing times:
a
Time to set up an algorithm using filter “g” is 0.0656ms.
b
The time using the different checksum algorithms is shown below. Note that this is the time that is needed for each character the filter has to deal with, and this time would be multiplied by the number of characters you expect to receive while the algorithm is being calculated. This factor would generally constitute the most significant delay.
1,2 CRC16 and CRC16-CCITT 0.159ms/char. 3 CRC16-CCITT-IBM 0.159ms/char. 4 CRC32 0.369ms/char. 5 CSI Signature 0.077ms/char. 6 Checksum using modulo 256 0.066ms/char. 7 Checksum using modulo 8192 0.071ms/char.
c
The time for the different data types is shown below. Note that this is the time needed to convert the received signature into a known format and is done at the end of the signature calculation before the compare. The ASCII decimal conversion timing is for a number with ten or more digits. If the number is less than this, the 1.125ms figure shown would reduce by 0.1ms per digit.
1 8 bit binary 0.155ms 2,3 16 bit binary 0.216ms 4,5 32 bit binary 0.334ms 6 ASCII decimal 1.125+(0.075*characters)ms 7 8 bit ASCII hex 0.226ms 8 16 bit ASCII hex 0.355ms 9 32 bit ASCII hex 0.613ms
d
When using CRC32 and CRC16-CITT there is a extra 0.19ms for an additional calculation. This is required as part of the CRC algorithm.
6-6
The total extra processing time over and above the SDM-SIO4’s normal delay is calculated by the following:
The extra time, in milliseconds, you must wait before trying to get the data from the SDM-SIO4 = a+(one from b)+(one from c)+(d if applicable)

6.3 Transmitted Data

The SDM-SIO4 can also do transmission signature generation with the calculated signature appended to the end of the string. This is done by the formatter types ‘g’ and ‘G’. Formatter type ‘g’ is used to mark where signature calculation should start and the type of signatur e /CRC to use. Formatter type ‘G’ is used to mark the end of signature generation, the position in the string where the calculated signature will be transmitted and the transmitted signature data format. The formatter types are described in detail below:
gn
This formatter type can be put into the formatter string to mark the start of a signature generation. When this happens the signature type determined by ‘n’ will be initialized ready to start signature calculation for all characters until formatter Gn is encountered. ‘n’ can be in the range of 0-255. The signature types supported are shown below:
Section 6. Data Error Detection
0 No Signature t ype used. 1 CRC16 standard. Polynomial x
16+x15+x2
2 CRC16-CCITT standard. Polynomial x
+1.
16+x12+x5
+1. 3 CRC16-CCITT-IBM (Tag Receiver). 4 CRC32 standard.
Polynomial
32+x26+x23+x22+x16+x12+x11+x10+x8+x7+x5+x4+x2
x
+x+1. 5 CSI Signature ( CR10X user manual section C-4). 6 Check sum using modulo 256. 7 Check sum using modulo 8192 (CR10X user manual section 5-2). 8-255 reserved for future use.
Gn
This formatter type can be put into the formatter string to mark the end of the string and the point at which the signature should be transmitted. It also sets the data type to use. ‘n’ can be in the range of 0-255 which indicates the data type to use. The data types that the SDM-SIO4 can deal with are as follows:
0 No data type or check. 1 8 bit binary. Expects 1 byte. 2 16 bit binary least significant byte first. Expects 2 bytes. 3 16 bit binary most significant byte first. Expects 2 bytes. 4 32 bit binary least significant byte first. Expects 4 bytes. 5 32 bit binary most significant byte first. Expects 4 bytes. 6 ASCII decimal. Waits until non ASCII 0-9 received.
6-7
Section 6. Data Error Detection

6.3.1 Example of Using Transmitted Data Filters

7 8 bit ASCII hex. Expects 2 ASCII bytes, if not 0-9,a-f,A-F then fail. 8 16 bit ASCII hex. Expects 4 ASCII bytes, if not 0-9,a-f,A-F then fail. 9 32 bit ASCII hex. Expects 8 ASCII bytes, if not 0-9,a-f,A-F then fail. 10-255 reserved for future use.
A sensor requires the string ‘123456789’ but also requires a CRC16 appended to the end in 16 bit ASCII Hex which, in this case, would be ‘123456789BB3D’. The BB3D is the CRC16 calculated for the ‘123456789’ string.
You would need to define a formatter string to do this. One way would be by using the command line. You would need to make a formatter string transmit the required string and CRC as follows:
FMTST 100 “g1i[123456789]G8” FMTST is the command to store a user defined formatter from the command
line.
100 is the string number you want to store it under; this can be 0-255. is the start of the format string. g1 is the formatter that instructs the SDM-SIO4 to use the CRC16 algorithm.
It initializes the CRC16 to start calculation from here on any characters. i[123456789] is the formatter that will transmit the string ‘123456789’ to
whichever port Instruction P113 requires. While this string is being processed by the SDM-SIO4 the CRC16 will be calculated on it.
G8 is the filter which tells the SDM-SIO4 that this is the position where it should append the CRC16 to the string. Also the number 8 define s the CRC16 output format which in this case is 16 bit ASCII hex.
is the end of the string.

6.3.2 CR10X Program Example

A typical CR10X datalogger program to work with the above formatter is shown below.
The program assumes that the SDM-SIO4 is set to address 0, the sensor is connected to port 1 of the SDM-SIO4 and the port settings, baud rate etc have been set. The output from the SDM-SIO4 is every second:
*Table 1 Program
01: 1.0 Execution Interval (seconds)
6-8
;Transmit formatter string 100, which includes the calculated CRC16 to port 1
1: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9100 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
*Table 2 Program
02: 0.0000 Execution Interval (seconds)
*Table 3 Subroutines
End Program
The program shown above will output to port 1 the string ‘123456789BB3D’.
Section 6. Data Error Detection

6.3.3 Alternative CR10X Program

The earlier formatter e xa mple assumes the signature/CRC is calculated and completed in one formatter string, which also means it will all be done within one P113 datalogger instruction. This is not the only way to do it. It is possible to calculate a CRC/signature ac ross a number of formatter strings and therefore a number of P113 Datalogger instructions. This could be done by using command line commands and a datalogger program as shown below.
Formatter strings sto red by using the command line.
FMTST 100 “g1” FMTST 101 “i[some data]” FMTST 102 “f6:2 G8”
*Table 1 Program
01: 1.0 Execution Interval (seconds)
;use formatter string 100 to set up the CRC16 on port 1
1: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9100 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
6-9
Section 6. Data Error Detection
;A minimum delay of 1ms is required after this command
2: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;use formatter string 101 to transmit the string ‘get data’ to port 1
3: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9101 1st Parameters 6: 0 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
;a minimum delay of 3.8ms is required after this command
4: Excitation with Delay (P22)
1: 1 Ex Channel 2: 0 Delay W/Ex (units = 0.01 sec) 3: 1 Delay After Ex (units = 0.01 sec) 4: 0 mV Excitation
;send the ASCII characters ‘Y’ and ‘Z’ to port 1
5: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2305 Command 5: 89 1st Parameters 6: 98 2nd Parameters 7: 0 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
;use formatter string 102 and output datalogger location 1 as ASCII floating point ;to port 1 and then output the calculated ASCII hex CRC16
6-10
6: SDM-SIO4 (P113)
1: 1 Reps 2: 0 Address 3: 1 Send/Receive Port 1 4: 2304 Command 5: 9102 1st Parameters 6: 0 2nd Parameters 7: 1 Values per Rep 8: 0000 Loc [ _________ ] 9: 1 Mult 10: 0 Offset
*Table 2 Program
02: 0.0 Execution Interval (seconds)
*Table 3 Subroutines
End Program
The string transmitted from port one might be ‘some dataYZ+234.34FFFF’. where FFFF would be the hex CRC16 for the string ‘some dataYZ+234.34’.
Section 6. Data Error Detection
NOTE
FFFF is not the actual signature for the above string it is only an example.
When the Checksum, CRC or Signature calculation is used it will increase any delay required after initiating one P113 and before initiating the next. How much extra time required will be dependent on which algorithm is used. The timings for the algorithms are shown below. These timings are in addition to the normal formatter delay times:
a
Time to set up an algorithm using formatter ‘g’ is No. of Ports*0.0656ms.
b
The time using the different algorithms is shown below. Note that this is the time that is needed for each character that the formatter has to deal with, and so this time would be multiplied by the total number of characters you expect to transmit multiplied by the number of ports you are sending it to.
1,2 CRC16 and CRC16-CCITT 0.159ms/char. 3 CRC16-CCITT-IBM 0.159ms/char. 4 CRC32 0.369ms/char. 5 CSI Signature 0.077ms/char. 6 Checksum using modulo 256 0.066ms/char. 7 Checksum using modulo 8192 0.071ms/char.
c
The different data types are shown below. Note that this is the time needed to convert the calculated signature into the correct format and must be multiplied by the number of ports it is being sent to. The ASCII decimal conversion timing
6-11
Section 6. Data Error Detection
is for a number with ten digits – if the number is less than this the 1.125ms figure would reduce by 0.1ms per digit.
1 8 bit binary 0.155ms 2,3 16 bit binary 0.216ms 4,5 32 bit binary 0.334ms 6 ASCII decimal 1.125ms 7 8 bit ASCII hex 0.226ms 8 16 bit ASCII hex 0.355ms 9 32 bit ASCII hex 0.613ms
The above timings are preliminary.
d
With the CRC32 and CRC16-CCITT there is a extra 0.19ms for an additional calculation. This is required as part of the CRC algorithm.
The total extra processing time above the SDM-SIO4’s normal delays is calculated by the following:
Total time in µsec needed before the next P113 is started =
a+(one from b)+(one from c)+(d if applicable)+any other delays required by the format command
6-12

Appendix A. ASCII Table

American Standard Code for Information Interchange
Decimal Values and Characters
(X3.4-1968)
Dec. Char. Dec. Char. Dec. Char. Dec. Char.
0 CONTROL @ 32 SPACE 64 @ 96 ` 1 CONTROL A 33 ! 65 A 97 a 2 CONTROL B 34 " 66 B 98 b 3 CONTROL C 35 # 67 C 99 c 4 CONTROL D 36 $ 68 D 100 d 5 CONTROL E 37 % 69 E 101 e 6 CONTROL F 38 & 70 F 102 f 7 CONTROL G 39 ' 71 G 103 g 8 CONTROL H 40 ( 72 H 104 h 9 CONTROL I 41 ) 73 I 105 i 10 CONTROL J 42 * 74 J 106 j 11 CONTROL K 43 + 75 K 107 k 12 CONTROL L 44 , 76 L 108 l 13 CONTROL M 45 - 77 M 109 m 14 CONTROL N 46 . 78 N 110 n 15 CONTROL O 47 / 79 O 111 o 16 CONTROL P 48 0 80 P 112 p 17 CONTROL Q 49 1 81 Q 113 q 18 CONTROL R 50 2 82 R 114 r 19 CONTROL S 51 3 83 S 115 s 20 CONTROL T 52 4 84 T 116 t 21 CONTROL U 53 5 85 U 117 u 22 CONTROL V 54 6 86 V 118 v 23 CONTROL W 55 7 87 W 119 w 24 CONTROL X 56 8 88 X 120 x 25 CONTROL Y 57 9 89 Y 121 y 26 CONTROL Z 58 : 90 Z 122 z 27 CONTROL [ 59 ; 91 [ 123 { 28 CONTROL \ 60 < 92 \ 124 | 29 CONTROL ] 61 = 93 ] 125 } 30 CONTROL ^ 62 > 94 ^ 126 ~ 31 CONTROL _ 63 ? 95 _ 127 DEL
A-1
This is a blank page.

Appendix B. Serial Port Data Transfer Modes

This appendix describes the serial port set-up in some detail. Please note that the numerical option codes vary between the command line set-up and the datalogger command set-up. The ones listed below are those for the command line mode.

B.1 Baud rates

The SDM-SIO4 ports can support 16 baud rates if set up from the command line but only 9 are available from datalogger set-up using SDM commands. An asterisk indicates not available in SDM command mode:-
0. 57600 baud *
1. 115200 baud *
2. 25 baud *
3. 50 baud *
4. 75 baud *
5. 110 baud *
6. 150 baud *
7. 300 baud
8. 600 baud
9. 1200 baud
10. 2400 baud
11. 4800 baud
12. 9600 baud
13. 19200 baud
14. 38400 baud
15. 76800 baud
NOTE

B.2 Stop Bits

B.3 Data Length

If the baud rate is higher than 9600 on two or more ports the SDM-SIO4 may not be able to reliably collect data when there is a lot of simultaneous input activity of more than 16 bytes without delays. This limitation can normally be overcome by careful planning of when data is requested from the RS232 devices, by keeping data to less than 16-byte blocks at full speed, or by using delays between characters. Please contact Campbell Scientific for further advice.
The number of stop bits can be set to 1, 1.5 and 2.
0. 1 stop bit
1. 1.5 stop bits if 5-bit data length or 2 stop bits for all other data lengths.
The data length can be set from 5 to 8 bits.
B-1
Appendix B. Serial Port Data Transfer Modes
0. 5 data bits
1. 6 data bits
2. 7 data bits
3. 8 data bits

B.4 Parity Bits

Parity can be enabled and set to either odd or even.
0. No parity set
1. Odd parity set
2. Even parity set

B.5 Serial Handshake Modes

You can select different kinds of handshaki ng from none at all, hardware (DTR, CTS etc.) and XON/XOFF. On modes 0 and 1 there is a user-set delay (0..254 x 50ms) between CTS being set and data being sent; this allows time for sensors to power up.
0. Leave as previously set.
NOTE
1. DTR is always set as the SDM-SIO4 is always ready for data. RTS is set
when data is ready to transmit. Data is transmitted following a delay (n x 50ms) after CTS is set; transmission stops if CTS falls.
2. DTR and RTS are always set. Data is transmitted following a delay (n x
50ms) after CTS is set; transmission stops if CTS falls.
3. DTR and RTS are always set; ignore CTS.
4. XON/XOFF software handshake. The SDM-SIO4 will XON again if no
more XOFFs are sent after a time-out of n x 50ms. This mode is only functional for data transmissions from the SDM-SIO4. If an RS232 device sends large amounts of data and it can only be controlled by XON/XOFF techniques it must be implemented from within the datalogger program (by using datalogger instructions to send the stop and start characters).
9. No automatic handshaking. The datalogger can read, set or clear RTS and DTR under datalogger program control; this is effectively ‘manual’ handshake control.
Delay – this is the delay referred to above. It is entered in 50ms steps. Values in the range 0..254 are acceptable. The accuracy is -50ms, +0ms.With XOFF/XON, 255 is a special case as indicated below.
If the delay is set to 255, then the SDM-SIO4 will stay in the XOFF state indefinitely, until an XON is received.
B-2
Appendix C. Limitations of the Talk­Through Mode
When using talk-through mode, other aspects of the SDM-SIO4 can be affected or limited. This Appendix lists these limitations.

C.1 Limitations

The talk-through mode is entered by issuing a command of the form T x:y, where x is the SDM-SIO4 address and y is the port number (0 for the command line mode). See the datalogger manual for further details.
When talking through to any of the four serial ports, the baud ra te, word length, parity and handshake mode are as set previously by the PORTSET command or by the datalogger program.
Once in this mode, any characters typed, or sent from the PC, are transmitted via the SDM-SIO4 to the relevant port. The datalogger polls the SDM-SIO4 at a frequency of approximately 10Hz to pick up any characters received on the relevant port and transmits them back to the PC. This mode of operation is slower than a direct serial connection, but is fast enough for most purp oses.
If you talk-through to a serial port, that port will not be available for use by the datalogger progr am currently running. No characters will be sent out, nor received, from that port under program control. This will usually result in out of range values being stored if data is being read from that port by the program.
The talk-through mode is terminated by a 40 second time-out. The timeout is reset by characters being sent from the PC to the SDM-SIO4 via the datalogger. If no characters are received after 40 seconds the talk through mode will be cancelled and all ports returned to normal operation.
When using talk-through in command line mode the follo wing limita tions apply:
1. if the datalogger is running a program that includes P113 instructions that
require a lot of processing of data or reconfiguration of the SDM-SIO4, then the speed of response and data transfer to and from the serial port in question will slow down. In some cases, characters sent from the PC may not be received by the SDM-SIO4, as it gives the highest priority to other tasks. Therefore you either need to check the commands sent are received correctly, or even stop the datalogger program if this appears to be a problem with your talk-through sessions.
2. the commands RAMTEST and RESET will cause talk-through mode to
exit. This is because these commands ‘take over’ the SDM-SIO4 for a time, which makes it unresponsive to communication attempts by the datalogger. The commands still function, but to get the result from the RAMTEST command you will have to wait long enough for the command
C-1
Appendix C. Limitations of the Talk-Through Mode
to complete and then start a new talk-through session and use the command LASTERROR to get the result code – see Section 4.4.
C-2
This is a bla nk page.
Campbell Scientific Companies
Campbell Scientific, Inc. (CSI)
815 West 1800 North
Logan, Utah 84321
UNITED STATES www.campbellsci.com info@campbellsci.com
Campbell Scientific Africa Pty. Ltd. (CSAf)
PO Box 2450
Somerset West 7129
SOUTH AFRICA
www.csafrica.co.za
sales@csafrica.co.za
Campbell Scientific Australia Pty. Ltd. (CSA)
PO Box 444
Thuringo wa Cent ra l QLD 4812 AUSTRALIA www.campbellsci.com.au
info@campbellsci.com.au
Campbell Scientific do Brazil Ltda . (CSB)
Rua Luisa Crapsi Orsi, 15 Butantã
CEP: 005543-000 São Paulo SP BRAZIL
www.campbellsci.com.br
suporte@campbellsci.com.br
Campbell Scientific Canada Corp. (CSC)
11564 - 149th Street NW
Edmonton, Alberta T5M 1W7
CANADA
www.campbellsci.ca
dataloggers@campbellsci.ca
Campbell Scientific Ltd. (CSL)
Campbell Park
80 Hathern Road
Shepshed, Loughborough LE12 9GX
UNITED KINGDOM
www.campbellsci.co.uk
sales@campbellsci.co.uk
Campbell Scientific Ltd. (France)
Miniparc du Verger - Bat. H
1, rue de Terre Neuve - Les Ulis
91967 COURTABOEUF CEDEX
FRANCE
www.campbellsci.fr
campbell.scientific@wanadoo.fr
Campbell Scientific Spain, S. L.
Psg. Font 14, local 8
08013 Barcelona
SPAIN www.campbellsci.es info@campbellsci.es
Please visit www.campbellsci.com to obtain contact information for your local US or International representative.
Loading...