4.1 Modules using Konect PakBus Router (private dynamic IP)10
4.1.1 Set up hardware10
4.1.2 Configure data logger10
4.1.3 Set up LoggerNet13
4.1.4 Test the connection15
4.2 Modules using a public static IP16
4.2.1 Set up hardware16
4.2.2 Configure data logger16
4.2.3 Set up LoggerNet18
4.2.4 Test the connection20
5. Specifications21
6. Installation23
6.1 Base station requirements23
6.2 Data logger site equipment23
6.3 Wiring and connections25
6.3.1 Module communications connections26
6.3.2 Module power connections28
6.3.3 Antenna connections29
6.4 CELL200 series and data logger configuration31
Table of contents - i
6.4.1 Integrated mode option31
6.4.2 Non-integrated mode option31
6.4.2.1 Configure CELL200 series32
6.4.2.2 Configure data logger32
6.4.2.3 Set up hardware32
6.4.2.4 Set up LoggerNet33
6.4.2.5 Test the connection35
6.4.3 Serial server mode option36
6.4.3.1 Configure CELL200 series36
6.4.3.2 Configure data logger39
6.4.3.3 Set up hardware39
6.4.3.4 Set up LoggerNet39
6.4.3.5 Test the connection41
6.4.4 Serial client mode option42
6.4.4.1 Configure CELL200 series43
6.4.4.2 Configure data logger (optional)45
6.4.4.3 Set up hardware46
6.4.4.4 Set up LoggerNet46
6.4.4.5 Test the connection47
6.4.5 Serial server/client mode option48
6.4.5.1 Configure CELL200 series49
6.4.5.2 Configure data logger52
6.4.5.3 Set up hardware53
6.4.5.4 Set up LoggerNet53
6.4.5.5 Test the connection54
7. Operation and maintenance55
7.1 Ports55
7.2 LED indicator lights56
7.3 Signal strength56
Appendix A. Controlling power to the CELL200 series58
Appendix B. Configuring settings and retrieving status information with the
CRBasic program60
B.1 Using the SetSetting() instruction60
Appendix C. Cellular module terminal functionality64
Table of contents - ii
C.1 Using cell modem terminal functionality65
C.2 Status commands72
C.3 Set commands77
C.4 Action commands79
Appendix D. Updating the operating system and firmware81
D.1 Using the web interface (cell.linktodevice.com)81
D.2 Using Device Configuration Utility83
Appendix E. Verizon Wireless and AT&T85
E.1 Verizon Wireless85
E.2 AT&T86
Appendix F. Cellular module regulatory information87
F.1 Important information for North American users87
F.2 RF exposure87
F.3 EU88
Table of contents - iii
1. Cellular communications
This manual provides information for interfacing CELL200 Series 4G LTE Cellular Modules to
Campbell Scientific data loggers.
Use of the CELL200 series requires a cellular line of service. The products compatible with
Verizon, AT&T, T-Mobile, Vodafone, and Telstra are shown in the following table.
Product
Cellular
protocol
4G LTE
CELL205
with
automatic
3G fallback
CELL2104G LTE CAT-1
4G LTE
with
CELL215
automatic
3G and
2G fallback
4G LTE
with
CELL220
automatic
3G fallback
MarketVerizonAT&TT-Mobile VodafoneTelstraOther
North
✔✔✔
America
United
✔
States
EMEA✔✔
Australia
and New
✔✔
Zealand
1
CELL2254G LTEJapan✔
1
More than 600 other providers are available worldwide through Campbell Scientific. See Establish cellular service
(p. 2) for more information.
Before using the CELL200 series, please review:
l Safety
l Pre-installation (p. 2)
l QuickStart (integrated mode) (p. 8)
CELL200-Series 4G LTE Cellular Module1
2. Pre-installation
TIP:
Check www.campbellsci.com to ensure you are using the latest data logger support software
and data logger operating system (OS).
Updating the OS during system setup and testing, or onsite is recommended. Sending an OS
to a remote data logger will interrupt the data logger program. If you have questions, contact
Campbell Scientific for assistance (https://www.campbellsci.com/support).
2.1 Establish cellular service
For better security, we recommend using Konect PakBus® Router with a private dynamic IP
address. This method allows only incoming PakBus communication. No other incoming
communication is supported. However, all forms of outbound communication from the data
logger are supported, including but not limited to PakBus, email, and ftp.
A public static IP address can also be used. This provides more incoming communication
functionality, but is less secure and more vulnerable to unsolicited traffic.
NOTE:
A public static IP account must be used when the module is set up in serial server mode.
Private dynamic IP accounts do not support the serial server mode.
2.1.1 Campbell Scientific cellular data service
Campbell Scientific can provide subscriptions to cellular service through Verizon, AT&T,
T-Mobile, Vodafone, Telstra, and over 600 other providers worldwide. When this cellular service
is purchased with the module, the module will come pre-provisioned with the required SIM card
and APN. If you have already purchased the CELL200 series, call Campbell Scientific to set up
service.
2.1.2 Other service providers
While using Campbell Scientific is the simplest way to obtain cellular data service for your
module, you can go directly to a provider. For more information on obtaining service directly
from Verizon and AT&T, see Verizon Wireless and AT&T (p. 85).
CELL200-Series 4G LTE Cellular Module2
TIP:
Prepaid cellular data plans may experience service slow downs when data limits are reached.
If file transfer from a cellular-connected data logger works initially, but later has problems,
check for data overage on the cellular plan.
This does not apply to Campbell Scientific cellular data services.
2.2 Install the SIM card
NOTE:
If you purchased cellular service from Campbell Scientific with the module, it will come with
the SIM (Subscriber Identity Module) card already installed. Proceed to Konect PakBus Router
setup (p. 4)
The CELL200 series requires a Micro-SIM (3FF) (6 position / contacts); a smartcard that securely
stores the key identifying a mobile subscriber. You should only need to install the SIM once in
the life of the module.
To install the SIM card:
1. Remove the SIM card cover.
2. Note the location of the notched corner for correct alignment. The gold contact points of
the SIM face down when inserting the SIM card as shown in the following figure. Gently
slide the card into the slot until it stops and locks into place. To eject the SIM card, press it
in slightly and release.
3. Replace the SIM card cover.
CELL200-Series 4G LTE Cellular Module3
FIGURE 2-1. SIM card installation
2.3 Konect PakBus Router setup
For better security, we recommend using Konect PakBus® Router with a private dynamic IP
address. This method allows only incoming PakBus communication. No other incoming
communication is supported. However, all forms of outbound communication from the data
logger are supported, including but not limited to PakBus, email, and ftp. Complete the steps in
the following two sections.
2.3.1 Get started
You will need the Konect PakBus Router redemption code that came on a card with the CELL200
series.
CELL200-Series 4G LTE Cellular Module4
Open a web browser and go to www.konectgds.com.
First-time users need to create a free account. After you submit your information, you will receive
two emails up to five minutes apart. One email will contain a Passport ID and the other your
Password. If emails are not received, check your email junk folder.
2.3.2 Set up Konect PakBus Router
1. Sign in to www.konectgds.com using your Passport ID and Password found in the two
received emails. Once logged in, you will be at the Welcome page.
CELL200-Series 4G LTE Cellular Module5
2.
Click devices and serviceson the command bar to the left and select Redeem PakBus
Router Code. Enter your complimentary Router Code found on the included card with your
cellular-enabled device and click Submit.
3. The next screen shows the assigned DNS address and Port for the router. Enter a TCP
Password and select a unique PakBus Address for your data logger.
TIP:
Make note of this information for use in later steps.
4. Click Submit.
CELL200-Series 4G LTE Cellular Module6
5.
To edit settings at a later date, click devices and serviceson the command bar and
select Manage PakBus Routers.
NOTE:
The DNS address and Port number, assigned when your account was setup, cannot be
edited.
3. Overview
The CELL200-series modules may be configured in one of five ways, depending on the data
logger, communications type, and needs of the user.
l Integrated: The module mimics the behavior of our integrated cell modems. No settings
are configured directly in the module. All settings are configured in the attached data
logger.
l Non-integrated: The module mimics the behavior of our older cellular modems. Settings
must be configured in both the module and the data logger.
l Serial Server: In this mode, the module receives IP communications over the cellular
network and converts those to serial communications to pass on to the data logger. From
the perspective of the data logger, this is no different than a serial cable connecting it to a
computer.
NOTE:
A public static IP account must be used when the module is set up in serial server
mode. Private dynamic IP accounts do not support the serial server mode.
CELL200-Series 4G LTE Cellular Module7
l Serial Client:Use this mode when the module is behind a cellular provider firewall and it
has a privatedynamic IP address. In serial client mode the module will connect to the
cellular network and initiate a TCP client socket connection.
l Serial Server/Client:In serial server/client mode the module connects to the cellular
network and opens a listening port. When a client connects to the listening port, the
CELL200 series will be in "Serial Server" mode, as described earlier. When no client is
connected to the listening port, the CELL200 series will be in "Serial Client" mode, as
described earlier, and all data on the active port will be sent and received through the
initiated TCP client socket connection.
Data loggers compatible with each mode are shown in the following table.
Integrated
PPP
Non-
integrated
PPP
Serial
server
Serial
2
client
3
Serial
server/
client
CR6 series/CR1000X/
CR300series
1
✔✔✔✔✔
CR1000/CR3000/CR800series✔✔✔✔
CR200(X) series✔✔✔
Array-based
✔✔✔
(Edlog)dataloggers
1
Integrated PPP mode requires operating system 03.00 or later for the CR1000X, 09.00 or greater for the CR6
series, and 08.00 or later for the CR300 series.
2
Serial server mode requires a public static IP account.
3
Requires CELL200 series OS 2.00 or later.
3
4. QuickStart (integrated mode)
NOTE:
This QuickStart describes configuring the CELL200 series in integrated mode (mimicking our
internal cell modems) with its default settings. It can also be configured in non integrated or
serial server mode.
This QuickStart section does not apply to CR3000, CR1000 and CR800-series users. See
Overview (p. 7) for more information on the different modes. See CELL200 series and data
CELL200-Series 4G LTE Cellular Module8
logger configuration (p. 31) for more information on configuring the module in the different
modes.
The Provisioning Report received with your Cellular Data Service shows whether the module was
configured with a private dynamic or public static IP address. See FIGURE 4-1 (p. 9) for an
example of a Campbell Scientific Provisioning Report. Other cellular providers should provide
similar information.
FIGURE 4-1. Static IP provisioning report
Additionally, Campbell Scientific cellular modules configured with a public static IP address will
have two stickers on the module, as shown in FIGURE 4-2 (p. 9). One sticker will show the
module phone number and data plan. The second sticker will show the static IP address.
Campbell Scientific cellular modules configured with a private dynamic IP address will have one
sticker on the module. It will show the module phone number and data plan.
FIGURE 4-2. Module with public static IP address
CELL200-Series 4G LTE Cellular Module9
4.1 Modules using Konect PakBus Router
(private dynamic IP)
4.1.1 Set up hardware
1. Connect the Cellular antenna.
2. Connect your data logger to the CELL200-series module RS-232 or CS I/O port. See Wiring
and connections (p. 25).
3. If not connecting through CS I/O, provide power to the CELL200 series.
4.1.2 Configure data logger
1. Connect to your data logger by using Device Configuration Utility.
2. On the Network Services tab in the PakBus/TCP Client field, enter the DNS address and
Port number noted during the Konect PakBus Router setup.
3. On the PPP tab, set Config/Port Used to CS I/O SDC8 or RS-232, depending on how you
are connected to the data logger.
4. (Optional) On the PPP tab, set User Name and Password if required by your cellular carrier
(usually outside of the United Sates).
5. Verify the Modem Dial String setting is blank.
6. If connecting through RS-232, on the Comport Settings tab, set RS232 BaudRate to
115200Fixed.
7. Shut down Device Configuration Utility and start it again. This will activate the Cellular tab
needed for the next step.
CELL200-Series 4G LTE Cellular Module10
8. On the Cellular tab, enter the APN provided by your cellular provider.
9. On the Datalogger tab enter the PakBus/TCP Password twice. This setting specifies a
password that will make the data logger authenticate any incoming or outgoing
PakBus/TCP connection. It must match the value entered in the Konect PakBus Router
setup.
CELL200-Series 4G LTE Cellular Module11
10. (Optional) By default, the CELL200 series will accept incoming communications from any IP
address. This can be a security risk. You may specify up to four IP addresses, with wild cards,
to limit connections to only those trusted sources. Use an asterisk (*) as a wild card. For
example, a setting of 166.22.*.* would allow connections from devices that have IP
addresses starting with 166.22. Both IPv4 and IPv6 addresses are supported.
CAUTION:
Only set a Trusted IP address if you are familiar with their use. Consult your IT
department or Campbell Scientific for assistance.
NOTE:
This setting does not affect outbound connections, only incoming connections.
In the Device Configuration Utility go to the Settings Editor then Network Services. Next to
the Trusted Hosts field, click Edit and Add your trusted IP addresses, one at a time.
11. Click Apply to save the changes.
CELL200-Series 4G LTE Cellular Module12
4.1.3 Set up LoggerNet
The LoggerNet Network Map is configured from the LoggerNet Setup screen.
NOTE:
Setup has two options, EZ (simplified) and Standard. Click on the View menu at the top of
the Setup screen, and select Standard view.
From the LoggerNet toolbar, click Main > Setup and configure the Network Map as described in
the following steps:
1. Select Add Root > IPPort.
2. Select PakBusPort and pbRouter for PakBus data loggers such as the CR1000X or CR300.
3. Add a data logger to the pbRouter.
4. Select the IPPort in the Network Map. Enter the Konect PakBus Router DNS address and
port number as noted in the Konect PakBus Router setup. The DNS address and port
number are input in the Internet IP Address field separated by a colon. For example,
axanar.konectgds.com:pppp where pppp is the port number.
CELL200-Series 4G LTE Cellular Module13
5. For PakBus data loggers, leave the default settings for the PakBusPort. PakBus Port Always
Open should not be checked. Enter the TCP Password; this must match the value entered
in the Konect PakBus Router setup and LoggerNet setup.
6. For PakBus data loggers, select the pbRouter in the Network Map and set the PakBus
Address to 4070.
CELL200-Series 4G LTE Cellular Module14
7. For PakBus data loggers, select the data logger in the Network Map and set the PakBus
Address to match that of the data logger (default address in the data logger is 1). If a
PakBus Encryption Key was entered during data logger setup, also enter it here. Click Apply
to save the changes.
4.1.4 Test the connection
After the Network Map has been configured, test the cellular connection by using the Connect
screen as shown in the following image. Click on the appropriate station and click Connect to
initiate a call to the data logger.
TIP:
The connection time is subject to many external factors. It is often less than 30 seconds but
could be up to fifteen minutes. Be patient.
CELL200-Series 4G LTE Cellular Module15
If the call is successful, the connectors at the bottom of the screen will come together and clock
information from the data logger will be displayed in the Station Date/Time field. If the
connection fails, a Communications Failure message will be displayed.
4.2 Modules using a public static IP
4.2.1 Set up hardware
1. Connect the Cellular antenna.
2. Connect your data logger to the CELL200-series module RS-232 or CS I/O port. See Wiring
and connections (p. 25).
3. If not connecting through CS I/O, provide power to the CELL200 series.
4.2.2 Configure data logger
1. Connect to your data logger by using Device Configuration Utility.
2. On the PPP tab, set Config/Port Used to CS I/O SDC8 or RS-232, depending on how you
are connected to the data logger.
3. Verify the Modem Dial String setting is blank.
4. If connecting through RS-232, on the Comport Settings tab, set RS232 BaudRate to 115200
Fixed.
CELL200-Series 4G LTE Cellular Module16
5. On the Cellular tab, enter the APN provided by your cellular provider.
6. (Optional) By default, the CELL200 series will accept incoming communications from any IP
address. This can be a security risk. You may specify up to four IP addresses, with wild cards,
to limit connections to only those trusted sources. Use an asterisk (*) as a wild card. For
example, a setting of 166.22.*.* would allow connections from devices that have IP
addresses starting with 166.22. Both IPv4 and IPv6 addresses are supported.
CAUTION:
Only set a Trusted IP address if you are familiar with their use. Consult your IT
department or Campbell Scientific for assistance.
NOTE:
This setting does not affect outbound connections, only incoming connections.
CELL200-Series 4G LTE Cellular Module17
In the Device Configuration Utility go to the Settings Editor then Network Services. Next to
the Trusted Hosts field, click Edit and Add your trusted IP addresses, one at a time.
7. Click Apply to save the changes.
4.2.3 Set up LoggerNet
The LoggerNet Network Map is configured from the LoggerNet Setup screen.
NOTE:
Setup has two options, EZ (simplified) and Standard. Click on the View menu at the top of
the Setup screen, and select Standard view.
From the LoggerNet toolbar, click Main > Setup and configure the Network Map as described in
the following steps:
1. Select Add Root > IPPort.
2. Select PakBusPort
3. Add a data logger to the PakBusPort.
CELL200-Series 4G LTE Cellular Module18
4. Select the IPPort in the Network Map. Enter the CELL200 series IP address and port number.
The IP address and port number are input in the Internet IP Address field separated by a
colon. Preceding zeros are not entered in the Internet IP Address (for example,
070.218.074.247 is entered as 70.218.74.247). The default port number is 6785.
5. For PakBus data loggers, leave the default settings for the PakBusPort. PakBus Port Always
Open should not be checked. If used, enter the TCP Password.
CELL200-Series 4G LTE Cellular Module19
6. For PakBus data loggers, select the data logger in the Network Map and set the PakBus
Address to match that of the data logger (default address in the data logger is 1). If a
PakBus Encryption Key was entered during data logger setup, also enter it here. Click Apply
to save the changes.
4.2.4 Test the connection
After the Network Map has been configured, test the cellular connection by using the Connect
screen as shown in the following image. Click on the appropriate station and click Connect to
initiate a call to the data logger.
TIP:
The connection time is subject to many external factors. It is often less than 30 seconds but
could be up to fifteen minutes. Be patient.
CELL200-Series 4G LTE Cellular Module20
If the call is successful, the connectors at the bottom of the screen will come together and clock
information from the data logger will be displayed in the Station Date/Time field. If the
connection fails, a Communications Failure message will be displayed.
5. Specifications
Data Logger Compatibility
The CELL200 series is compatible with the CR1000X, CR300 series, CR6 series, CR1000, CR3000,
CR800 series, CR200(X) series, CR5000, CR10X, CR10X-PB, CR510, CR510-PB, CR23X, and
CR23X-PB. See Module communications connections (p. 26) for information on communication
options with each data logger model.
Cellular WAN
See
https://s.campbellsci.com/documents/us/miscellaneous/Cellular%20Modem%20Frequency%20B
ands.pdf for a complete list of supported frequency bands.
Host Interfaces
l CS I/O communications port, DB9 male
l RS-232 serial port, DB9 female
l USB version 2.0 with micro-B connector
CELL200-Series 4G LTE Cellular Module21
RF Connectors
l 2 SMA antenna connectors (primary and diversity)
Power
l Operating Voltage: 10 to 30 VDC
l Low Power Mode:300 μA
l Typical Idle: 14 mA @ 12 VDC
l Typical Active: 39 mA @ 12 VDC (CELL205, CELL215, CELL220, CELL225)
25 mA @ 12 VDC (CELL210)
Size
l Dimensions: 13.46 X 8.1 X 2.86 cm (5.3 X 3.19 X 1.13 in)
l Weight: 215.5 g (7.6 oz)
Environmental
l Operating Temperature Range: –40 to 80 °C
l Storage Temperature: –45 to 80 °C
l Humidity: 10 to 90%
Industry Certifications
l Environmental: RoHS
SIM (Subscriber Identity Module) card interface
l Micro-SIM (3FF) (6 position / contacts)
l Supports SIMs that require 1.8 or 3 VDC
Data Speeds
l LTE: Max 10 Mbps (download) / Max 5 Mbps (upload)
l WCDMA: Max 384 Kbps (download) / Max 384 Kbps (upload)
l GSM
o
EDGE: Max 296 Kbps (download) / Max 236.8 Kbps (upload)
o
GPRS: Max 107 Kbps (download) / Max 85.6 Kbps (upload)
6.4 CELL200 series and data logger configuration31
6.4.1 Integrated mode option31
6.4.2 Non-integrated mode option31
6.4.3 Serial server mode option36
6.4.4 Serial client mode option42
6.4.5 Serial server/client mode option48
6.1 Base station requirements
A computer running Campbell Scientific LoggerNet software with access to the Internet is
needed.
6.2 Data logger site equipment
l CELL200-series module with power cable (included with module)
l Data logger — CR1000X series, CR300 series, CR6 series, CR1000, CR3000, CR800 series,
CR5000, and GRANITE 6/9/10
l Module Interface, see Module communications connections (p. 26)
l Environmental Enclosure — ENC10/12, ENC12/14, or ENC16/18
CR800 series, CR5000, and GRANITE 6/9/10 data loggers ) — connects the module to
current data logger with a CS I/O port. See CS I/O connection (p. 27)
SC105 Interface — connects the module to any data logger with a CS I/O port. It must
be configured using Device Configuration Utility. Settings should be:
l CS I/O Mode: SDC Address 8
l CS I/O ME Baud Rate: 115.2k
l RS-232 Mode: Modem (default)
l Baud Rate:
l 115.2k fixed for CR1000X series, CR300 series, CR6 series, CR1000, CR3000,
CR800 series, CR5000, and GRANITE 6/9/10 data loggers
l 9600 for CR10X, CR10X-PB, CR510, CR510-PB, CR23X, CR23X-PB, and CR200
(X) series data loggers
l 8 data bits, 1 stop bit, no parity
If connecting to RS-232 port:
Null Modem Cable (9 pin, male-to-male) — connects the module to the CR1000X series,
CR300 series, CR1000, CR3000, CR800 series, and CR200(X) series RS-232 port.
CPI/RS-232 RJ45 to DB9 Cable — connects the module to the CR6 series or CR1000X
series CPI/RS-232 port.
l Antenna — the following antennas are available from Campbell Scientific. Contact
Campbell Scientific for help in determining the best antennas for your application.
o
2 dBd 4G/3G Omnidirectional Antenna: An omnidirectional antenna with mounting
bracket that is ideally suited for use with 4G and 3G cellular gateways. The mounting
bracket attaches to a mast or crossarm, and it serves as the antenna ground plane.
The antenna has an N type (female) threaded permanent stud for easy mounting to
the included bracket or through an enclosure wall. A coaxial cable, sold separately, is
required to connect this antenna to the inline surge suppression or module antenna
jack. The antenna includes a mount/U-bolt assembly for attaching the antenna to a
mast, post, or crossarm up to 3.8 cm (1.5 in) in diameter.
CELL200-Series 4G LTE Cellular Module24
o
8 dBd Yagi Wideband Antenna: A higher gain antenna that should be “aimed” at the
service provider antenna. It covers both the 800-MHz band and the 1.9-GHz band.
The antenna comes with bracket/U-bolt assembly for attaching the antenna to a
mast or post. A coaxial cable, sold separately, is required to connect this antenna to
the inline surge suppression or module antenna jack. This antenna is recommended
for areas that require a higher gain antenna.
o
4G/3G Cellular Whip Antenna with SMA Connector: A wideband termination
antenna with SMA connector and articulating base. This antenna is intended for
short-term testing use only. It is not intended for long-term use. Campbell Scientific
recommends that customers use external antennas for the best reception and
transmission of cellular signals.
NOTE:
When antennas are located away from the CELL200 series, keep the cables as short as
possible to prevent the loss of antenna gain. Route the cables to protect them from damage
and so they will not be snagged or pulled on. Avoid binding or sharp corners in the cable
routing. Bundle and tie off excess cable. Make sure the cables are secured so their weight will
not loosen the connector from the CELL200 series over time.
TIP:
Cellular phone apps, such as OpenSignal (https://opensignal.com/), show the direction to
point an antenna to get the best signal strength.
6.3 Wiring and connections
This section explains how to connect the module for different communications methods. It also
describes how to power the module and connect an antenna.
CELL200-Series 4G LTE Cellular Module25
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.