Camden Door Controls CX-PS30UL, CX-PS60UL Installation Instructions

M Series
Multi-Output Access Control Power Supply Chargers
Installation Guide
Models Include:
AL300ULM AL400ULM
- 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC
or 4 amp @ 24VDC.
- 6 amp @ 12VDC or 24VDC. - 10 amp @ 12VDC.
AL1024ULM
- 10 amp @ 24VDC.
For a red enclosure, add an “R” suffix to the part # e.g. AL300ULMR
Rev. 111103
Overview:
T
hese multi-output access control power supply/chargers are specifically designed for use with access control systems and
a
ccessories. These units convert a 115VA C / 60Hz input into five (5) individuall y protected 12VDC or 24VDC outputs (see
s
pecifications). Each output will route power to a variety of access control hardw are de vices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open [NO] or normally closed [NC] supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form “C” dr y output relay enables HVAC Shutdown, Elevator Recall or may be used to trigger auxiliary devices.
M Series Power Supply Configuration Reference Chart:
Model Number
Altronix
Current (amp)
12VDC Total Output
24VDC Total Output
Current (amp)
Outputs
Power Limited
Class 2 Rated
115VAC 60Hz Input
AL300ULM 2.5 2.5 5 Yes 1.45
AL400ULM 4 3 5 Yes 1.9
AL600ULM 6 6 5 Yes 2.5
AL1024ULM - 10 5 Yes 4.4
AL1012ULM 10
- 5 Yes 1.9
(current draw/amp)
Input Fuse Rating
Power Supply Board
3.5 amp
250VAC
3.5 amp
250VAC
3.5 amp
250VAC
10 amp
250VAC
3.5 amp
250VAC
Agency Listings
NYC Dept. of Buildings
California State Fire Marshal
File Numbers
UL Listings and
UL File # S4707
UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL Listed Access Control System Unit.
UL Listed for Burglar Alarms Systems.
UL Listed Hospital Signaling and Nurse Call Equipment.
“Signal Equipment” Evaluated to CSA 22.2
UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
UL 1481
UL 294
UL 603
UL 1069
N205-M1983
UL File # S4707
UL 1481
UL 294
N205-M1983
UL File # BP617
UL 294
N205-M1983
Specifications:
Input:
• Power input 115VAC 60Hz (see reference chart above).
• Fire Alarm Panel or Access Control System trigger
inputs. [NO] or [NC] supervised trigger input and polarity reversal trigger input (4mA draw from FACP).
Output:
• Five (5) individual power limited class 2 outputs.
• Current limit is 2 amp @ 12VDC or 24VDC
per output (12VDC only for AL1012ULM and 24VDC only for AL1024ULM).
• Filtered and electronically regulated outputs.
• Thermal and short circuit protection with auto reset.
erload protection.
Ov
Output relay energizes when unit is triggered
m “C” contact rated 1 amp @ 28VDC).
(for
- 2 - Mseries
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (P
rent .7 amp.
ge cur
char AL1024ULXB (P current 3.6 amp).
• Zero voltage drop when switching over to battery backup.
• AL300ULM, AL400ULM and AL600ULM enclosures accommodate up to two (2) 12VDC/7AH batteries.
• AL1012ULM should be fitted with one (1) 12VDC/12AH batter AL1024ULM enclosure accommodates
• up to tw
o (2) 12VDC/12AH batteries.
ower Supply Board) maximum
er Suppl
w
o
y Board) maximum charge
.
y
Specifications (cont’d):
Visual Indicators:
• DC output LED indicator.
• LEDs indicate condition of power outputs.
• Power & input trigger LED’s.
Supervision:
• AC fail supervision (form "C" contact).
• Low battery supervision (form "C" contact).
Supervision (cont’d):
• Battery presence supervision (form “C” contact).
• Power fail supervision relay (form “C” contact rated 1 amp @ 28VDC).
• Power supply is complete with enclosure, cam lock, transformer and battery leads.
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws Secure enclosure to earth ground. It is recommended to first review the following tables for screw terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up.
Carefully review: Output Voltage & Stand-by Specifications (pg. 4) Terminal Identification Table (pg. 10) LED Diagnostics (pg. 9) Typical Application Diagrams (pgs. 11 & 12)
2. Set output v AL300ULM, AL400ULM and AL600ULM set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board ( is 24VDC only.
3. Secure green lead to earth g round. Connect AC power (115VAC 60Hz to terminals marked [L, G, N] on power supply board Use 18 AWG or lar Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires). Minim
5. Connect Fail-Secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to terminals
ed [1 through 5 POS (+) DC OUTPUT (ALARM)] on MOM5 board and the negative leads to terminals marked
mark [NEG 1 through NEG 5] on MOM5 board
6. Connect Fail-Safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to terminals marked [6 through 10 POS (+) DC OUTPUT (STAND-BY)] on MOM5 board and negative leads to terminals marked [NEG 1 through NEG 5] on MOM5 board
7. To trigger the unit from a FACP connect signaling circuit of FACP to terminals marked [- INPUT +] on MOM5 board
ire alar
f Note: A 2.2K EOL must be installed across terminals marked [TRIGGER] on MOM5 board or the unit will remain in an alarm condition.
8. To trigger the unit using a supervised dr y contact connect the 2.2K resistor in series for a NC trigger input and in parallel for [NO] trigger input (Fig. 5, pg. 11).
9. Connect auxiliary devices triggered by the unit to the terminals marked [DRY OUTPUT NO & C] on MOM5 board for nor output Note: This relay will energize when the unit is triggered.
Access Control applications batteries are optional.
or
10.F of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery to terminals marked [+ BAT--] on power supply board for 12VDC operation
Fig. 4, pg. 8)
oltage:
Fig. 1B, pg. 5; Fig. 2B, pg. 6). AL1012ULM is 12VDC only and AL1024ULM
(Output Voltage and Stand-by Specification Charts below, pg. 4).
(Fig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7; Fig. 4, pg. 8).
ger for all power connections (Batter
um .25” spacing m
ig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7; Fig. 4, pg. 8).Polarity is shown in alarm condition. For latching
(F
m interf
mall
(Fig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7; Fig. 4, pg. 8).
ace
(F
y open output or ter
. Use two (2) 12VDC batteries connected in series for 24VDC operation. (Battery leads included).
ust be provided.
igs. 8, 9, 10, pg
minals mark
(Fig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7; Fig. 4, pg. 8).
. 12).
DR
ed [
y, DC output, AC input).
(Fig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7; Fig. 4, pg. 8).
Y OUTPUT
When batteries are not used a loss of AC will result in the loss
NC & C] on MOM5 board for normally closed
(Fig. 1, pg. 5; Fig. 2, pg. 6; Fig. 3, pg. 7;
(Enclosure Dimensions, pg. 13,14).
Mseries - 3 -
11.Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] and [Power Fail] s
upervisory relay outputs marked [NO, C, NC] on power supply board
F
ig. 4A, pg. 8).
N
ote:When used in fire alar m, burglar alar m or access control applications, “AC Fail” relay must be used to provide
a visual indication of AC power on.
12. Please insure that the cover is secured with the provided Key Lock.
U
se 22 AWG to 18 AWG for AC Fail & Low Battery reporting.
(
Fig. 1A, pg. 5; Fig. 2A, pg. 6; Fig. 3A, pg. 7;
Output Voltage and Stand-by Specification Charts:
AL300ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm
12VDC / 40 AH Battery
24VDC / 12 AH Battery
24VDC / 40 AH Battery
Closed
Open
Open
Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp
Stand-by = 200mA
Alarm = 2.5 amp
Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp
AL400ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm
12VDC / 40 AH Battery
24VDC / 12
AH Battery
Closed
Open
Stand-by = 4.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 4.0 amp Alarm = 4.0 amp Alarm = 4.0 amp
Stand-b
y = 200mA
Alarm = 3.0 amp
24VDC / 40 AH Battery
Open
Stand-by = 3.0 amp Stand-by = 1.0 amp Stand-by = 300mA
Alarm = 3.0 amp
Alarm = 3.0 amp Alar
m = 3.0 amp
AL600ULM
Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by &
5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm Stand-by = 6.0 amp Stand-by = 1.0 amp Stand-by = 300mA
m = 6.0 amp Alarm = 6.0 amp Alarm = 6.0 amp
Alar
Stand-by = 200mA
m = 6.0 amp
Alar
Stand-b
y = 6.0 amp
Alarm = 6.0 amp Alar m = 6.0 amp Alarm = 6.0 amp
Stand-b
y = 1.0 amp
Stand-by = 300mA
12VDC / 40 AH Battery
24VDC / 12 AH Battery
24VDC / 40
AH Batter
y
Position
Closed
Open
Open
AL1012ULM
Output
12VDC / 12 AH Battery
15 Minutes of Stand-b
y @ 10 amp
AL1024ULM
Output 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by /
5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm
24VDC / 12 AH Battery 7.7 amp / 9.7 amp 1 . 2 a mp / 9.7 a m p ------------------------- ------------------------­24VDC / 65 AH Battery ------------------------- 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp 200mA / 9.7 amp
- 4 - Mseries
Maintenance:
Green
Lead
Battery connection (non power limited)
W
ire
S
trap
(
from
E
nclosure
to Door)
115VA C
power mains
non-power
limited Class 1
Divider
NC C NO
DRY OUTPUT
TRIGGER
LED
6 7 8 9 10
POS (+) DC OUTPUT (STANDBY)
NC C NO
POWER FAIL
TRIGGER
1 2 3 4 5
POS (+) DC OUTPUT (ALARM)
NEG1 NEG2 NEG3 NEG4 NEG5
-- DC INPUT +
NEG (-) INPUT POS (+)
DC Outputs to devices
(power limited)
Fire Alarm
Interface
non-power limited
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Replace fuse cover before energizing. Do not expose to rain or moisture.
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Power Limited
NC C NO NC C NO
A
C FAIL
BAT FAIL
Battery & AC
Supervision Circuit
(power limited)
Switch Detail
--- DC
+
L G N
PTC3
NC C NO NC C NO
+ BAT ---
DC
AC
24V - OPEN
12V - CLOSED
AC FAIL
RL2
BAT FAIL
RL1
RL3
SW1
OPEN SWITCH
CLOSED SWITCH
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
Green
Lead
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Output Voltage and Stand-by Specification Charts, pg. 4).
Battery Test: Under normal load conditions check that the batter y is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT-- ] to insure that there is no break in the batter y connection wires. Note: AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge
current is .7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
Fig. 1 AL300ULM AL400ULM
Fig. 1A
Fig. 1B
Mseries - 5 -
Fig. 2
Green
Lead
Battery connection (non power limited)
Wire Strap (from Enclosure to Door)
1
15VAC
power mains
non-power
l
imited
Class 1
Divider
NC C NO
DRY OUTPUT
TRIGGER
LED
6 7 8 9 10
POS (+) DC OUTPUT (STANDBY)
NC C NO
POWER FAIL
T
RIGGER
1 2 3 4 5
POS (+) DC OUTPUT (ALARM)
NEG1 NEG2 NEG3 NEG4 NEG5
-- DC INPUT +
NEG (-) INPUT POS (+)
DC Outputs to devices
(power limited)
Fire Alarm
Interface
non-power limited
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Replace fuse cover before energizing. D
o not expose to rain or moisture.
Power Limited
NC C NO NC C NO
AC FAIL
BAT FAIL
Battery & AC
Supervision Circuit
(power limited)
+
DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
DC
2
4V - OPEN
1
2V - CLOSED
SW1
AC FAIL
L G N
AC
A
C Delay
Switch Detail
OPEN SWITCH
CLOSED SWITCH
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Green
Lead
A
L600ULM
F
ig. 2A
Fig. 2B
- 6 - Mseries
Fig. 3
Green Lead
Battery connection (non power limited)
Door
Wire Strap (from Enclosure to Door)
115VAC
p
ower mains
non-power limited
Divider
Battery and AC
S
upervision Circuit
(power limited).
Power
Limited
Class 1
DC Outputs
t
o devices
(power limited)
NC C NO NC C NO
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Replace fuse cover before energizing. Do not expose to rain or moisture.
12VDC Rechargeable Battery
(optional)
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Fuse
Cover
A
L1012ULM
Fig. 3A
Mseries - 7 -
Fig. 4
Green Lead
Battery connection (non power limited)
Door
Wire Strap (from E
nclosure
to Door)
1
15VAC
p
ower mains
non-power limited
D
ivider
Battery and AC Supervision Circuit
(power limited).
Power
Limited
Class 1
D
C Outputs
to devices
(power limited)
NO C NC NO C NC
CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Replace fuse cover before energizing. D
o not expose to rain or moisture.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Fuse
Cover
A
L1024ULM
Fig. 4A
- 8 - Mseries
LED Diagnostics:
Power Supply Board
L
ED
R
ed (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery.
MOM5 - Output Module
LED ON OFF Power (Green) Normal operation. Power failure. Trigger (Green) Input is triggered (alarm condition). No input trigger (non-alarm condition). Outputs (Red) Output tripped due to a Normal operation.
short circuit or overload condition.
Mseries - 9 -
Terminal Identification Tables:
Power Supply Board
T
erminal Function/Description
L
egend L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC + AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power limited).
AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power limited). AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (non-power limited). AL1012ULM - 12VDC @ 10 amp to MOM5 board (non-power limited). AL1024ULM - 24VDC @ 10 amp to MOM5 board (non-power limited).
AC FAIL Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay NO, C, NC normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAIL Indicates low battery condition, e.g. connect to alarm panel. Relay normally NO, C, NC energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULM), 24VDC output threshold set @ approximately 21VDC.
+ BAT - Stand-by battery connections. AL300ULXB, AL400ULXB and AL600ULXB (Power Supply
Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
MOM5 - Output Module
Ter minal Legend Function/Description
---DC INPUT + 12VDC or 24VDC from power supply. TRIGGER Dr
y normally open [NO] or nor input trigger. A shor t or open circuit will transfer power from terminals marked [POS. (+) DC OUTPUT (ST [POS (+) DC OUTPUT (ALARM)]
--- INPUT + Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to terminals marked [POS (+) DC OUTPUT (ALARM)] (e.g. fire alar m control panel indications circuit).
NEG 1 THRU NEG 5 Supplies constant negative (-) voltage. POS (+) DC OUTPUT Supplies positive (+) voltage when dry trigger input or f ire
(ALARM) 1-5 alarm wet trigger input is applied.
e (+) voltage in normal condition.
POS (+) DC OUTPUT
Supplies positi
v
(STAND-BY) 6-10 Power is removed when dry trigger input or f ire alar m wet trigger input is applied. NC, C, NO
When the MOM5 is triggered the terminals marked [C and NO] will open and the
DRY OUTPUT terminals marked [C and NC] will close. This output is used to trigger auxiliary devices.
(e.g. HVAC Shutdown, Elevator Recall etc.) Conta ct ratin g 1 am p @ 28 VDC.
m “C” contacts used for repor
or
NC, C, NO
F
POWER FAIL terminals. Under normal conditions, terminals marked [NO and C] are open, [NC and C]
are closed. A loss of power causes terminals marked [NO and C] to close and [NC and C] to open. Contact rating 1 amp @ 28VDC.
mally closed [NC] supervised (2.2K EOL resistor)
AND-BY)]
to terminals marked
.
ting no v
oltage is present at [-- DC input +]
- 10 - Mseries
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER ON LED
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER ON LED
EOL 2.2K
EOL 2.2K
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
N.O. INPUT FROM FACP OR ACCESS CONTROL DEVICE
DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE
(+)
(--)
TO TRIGGER INPUT OF NEXT MOM5
NC C NO
DRY OUTP UT
NC C NO
POWER FA IL
NC C NO
DRY OUTP UT
NC C NO
POWER FA IL
Typical Application Diagrams:
TRIGGER
NEG (-) INPUT POS (+)
E
OL 2.2K
(
+)
(
-
)
D
C VOLTAGE INPUT
F
ROM FACP
S
IGNALING
O
UTPUT OR ACCESS
C
ONTROL DEVICE
N
.C. INPUT FROM
F
ACP OR ACCESS
C
ONTROL DEVICE
TRIGGER
NEG (-) INPUT POS (+)
EOL 2.2K
(
+
)
(
-
)
D
C VOLTAGE INPUT
F
ROM FACP
S
IGNALING
O
UTPUT OR ACCESS
C
ONTROL DEVICE
N
.O. INPUT FROM
F
ACP OR ACCESS
C
ONTROL DEVICE
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER ON LED
T
RIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
P
OWER
ON LED
EOL 2.2K
E
OL 2.2K
N.C. INPUT FROM FACP OR ACCESS CONTROL DEVICE
DC VOLTAGE INPUT F
ROM FACP
S
IGNALING
O
UTPUT OR ACCESS
C
ONTROL DEVICE
(+)
(
--)
TO TRIGGER INPUT OF NEXT MOM5
NC C NO
DRY OUTPUT
NC C NO
POWER F AIL
NC C NO
D
RY OUTPU T
NC C NO
P
OWER F AIL
Fig. 5
MOM5 module shown with wet and/or dry nor­mally closed trigger inputs
MOM5 module shown with wet and/or dry nor mally open trigger inputs (Non-Latching):
(Non-Latching):
Fig. 6- Two (2) or more MOM5 modules shown with wet and/or dry normally closed trigger inputs (Non-Latching):
F
. 7
ig
o (2) or more
w
- T
Mseries - 11 -
MOM5 modules shown with wet and/or dry normally open trigger inputs
(Non-Latching):
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER O
N LED
TRIGGER
LED
TRIGGER
-
DC INPUT+
NEG (-) INPUT POS (+)
POWER O
N LED
N.O. RESET
EOL 2.2K
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT FROM FACP S
IGNALING OUTPUT OR ACCESS CONTROL DEVICE
N.C. INPUT FROM FACP
N
C C NO
DRY OUTPUT
NC C NO
POWER FAIL
NC C NO
D
RY OUTPU T
N
C C NO
POWER FAIL
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER ON LED
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER ON LED
EOL 2.2K
(+)
(-)
(+)
(-)
N.C. RESET
EOL 2.2K
DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE
N.O. INPUT FROM FACP
NC C NO
DRY OUTP UT
NC C NO
POWER FAIL
NC C NO
DRY OUTP UT
NC C NO
POWER FAIL
T
RIGGER
LED
TRIGGER
NEG (-) INPUT POS (+)
POWER
O
N LED
N
.C.
RESET
EOL 2.2K
(
+)
(
-
)
DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT
N.O. INPUT FROM FACP SIGNALING OUTPUT
N
C C NO
D
RY OUTP UT
N
C C NO
POWER FA IL
TRIGGER
L
ED
TRIGGER
NEG (-) INPUT POS (+)
P
OWER
ON LED
N.O. RESET
E
OL 2.2K
(
+)
(
-
)
DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT
N
.C. INPUT
F
ROM FACP
S
IGNALING
O
UTPUT
N
C C NO
D
RY OUTPUT
NC C NO
P
OWER FA IL
Typical Application Diagrams (cont’d.):
F
ig. 8
OM5 module shown with with wet and/or dry
M
ormally open fire alar m trigger inputs (Latching
n
with Manual Reset)
:
OM5 module shown with with wet and/or dry
M
ormally closed fire alar m trigger inputs
n (Latching with Manual Reset):
Fig. 9 - Two (2) MOM5 modules shown with wet and/or dry normally closed fire alar m trigger inputs
(Latching with Manual Reset):
Fig. 10 - Two (2) MOM5 modules shown with wet and/or dry normally open fire alar m trigger inputs
(Latching with Man
- 12 - Mseries
ual Reset)
:
5
.10"
6.5625"
3.25"3.25"
5.10"
5
.10"
3.25"
1.00"10.50"1.00"
1.00"
1.00"
1.40"
1
.20"
1
.40"
1
.20"
0.75
"0.75" 11.00"
12.50"
3.25"
0.9375"
0.9375"
1
.40" 4.85" 4.85" 1.40"
1
.20"
Bottom
Top
RightLeft
• AL300ULM
AL400ULM
• AL600ULM
13.5”H x 13”W x 3.25”D
Enclosure Dimensions:
Mseries - 13 -
1.285
1.285
• AL1012ULM
AL1024ULM
1
5.5”H x 12”W x 4.5”D
Enclosure Dimensions:
- 14 - Mseries
Notes:
Mseries - 15 -
Notes:
Altronix is not responsible for any typographical errors.
Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIMseries G11G
- 16 - Mseries
MEMBER
Loading...