For a red enclosure, add an “R” suffix to the part # e.g. AL300ULMR
Rev. 111103
Overview:
T
hese multi-output access control power supply/chargers are specifically designed for use with access control systems and
a
ccessories. These units convert a 115VA C / 60Hz input into five (5) individuall y protected 12VDC or 24VDC outputs (see
s
pecifications). Each output will route power to a variety of access control hardw are de vices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled
trigger input is achieved through normally open [NO] or normally closed [NC] supervised input or the polarity reversal
from an FACP (Fire Alarm Control Panel). A form “C” dr y output relay enables HVAC Shutdown, Elevator Recall or may
be used to trigger auxiliary devices.
M Series Power Supply Configuration Reference Chart:
Model Number
Altronix
Current (amp)
12VDC Total Output
24VDC Total Output
Current (amp)
Outputs
Power Limited
Class 2 Rated
115VAC 60Hz Input
AL300ULM2.52.55Yes1.45
AL400ULM435Yes1.9
AL600ULM665Yes2.5
AL1024ULM-105Yes4.4
AL1012ULM10
-5Yes1.9
(current draw/amp)
Input Fuse Rating
Power Supply Board
3.5 amp
250VAC
3.5 amp
250VAC
3.5 amp
250VAC
10 amp
250VAC
3.5 amp
250VAC
Agency Listings
NYC Dept.
of Buildings
California
State
Fire Marshal
File Numbers
UL Listings and
UL File # S4707
UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL Listed Access Control System Unit.
UL Listed for Burglar Alarms Systems.
UL Listed Hospital Signaling and Nurse Call Equipment.
“Signal Equipment” Evaluated to CSA 22.2
UL Listed for Power Supplies for
Fire Protective Signaling Systems
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
UL Listed Access Control System Unit.
“Signal Equipment” Evaluated to CSA 22.2
UL 1481
UL 294
UL 603
UL 1069
N205-M1983
UL File # S4707
UL 1481
UL 294
N205-M1983
UL File # BP617
UL 294
N205-M1983
Specifications:
Input:
• Power input 115VAC 60Hz (see reference chart above).
• Fire Alarm Panel or Access Control System trigger
inputs. [NO] or [NC] supervised trigger input and
polarity reversal trigger input (4mA draw from FACP).
Output:
• Five (5) individual power limited class 2 outputs.
• Current limit is 2 amp @ 12VDC or 24VDC
per output (12VDC only for AL1012ULM and
24VDC only for AL1024ULM).
• Filtered and electronically regulated outputs.
• Thermal and short circuit protection with auto reset.
erload protection.
Ov
•
Output relay energizes when unit is triggered
•
m “C” contact rated 1 amp @ 28VDC).
(for
- 2 -Mseries
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• AL300ULXB, AL400ULXB, AL600ULXB and
AL1012ULXB (P
rent .7 amp.
ge cur
char
AL1024ULXB (P
current 3.6 amp).
• Zero voltage drop when switching over to
battery backup.
• AL300ULM, AL400ULM and AL600ULM enclosures
accommodate up to two (2) 12VDC/7AH batteries.
• AL1012ULM should be fitted with
one (1) 12VDC/12AH batter
AL1024ULM enclosure accommodates
• Power supply is complete with enclosure, cam lock,
transformer and battery leads.
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws
Secure enclosure to earth ground. It is recommended to first review the following tables for screw
terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up.
2. Set output v
AL300ULM, AL400ULM and AL600ULM set desired DC output voltage by setting switch SW1 to the appropriate
position on the power supply board (
is 24VDC only.
3. Secure green lead to earth g round. Connect AC power (115VAC 60Hz to terminals marked [L, G, N] on
power supply board
Use 18 AWG or lar
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
4. Measure output voltage before connecting devices. This helps avoid potential damage.
Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires).
Minim
5. Connect Fail-Secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to terminals
ed [1 through 5 POS (+) DC OUTPUT (ALARM)] on MOM5 board and the negative leads to terminals marked
mark
[NEG 1 through NEG 5] on MOM5 board
6. Connect Fail-Safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to terminals
marked [6 through 10 POS (+) DC OUTPUT (STAND-BY)] on MOM5 board and negative leads to terminals
marked [NEG 1 through NEG 5] on MOM5 board
7. To trigger the unit from a FACP connect signaling circuit of FACP to terminals marked [- INPUT +] on MOM5
board
ire alar
f
Note: A 2.2K EOL must be installed across terminals marked [TRIGGER] on MOM5 board or the unit will remain
in an alarm condition.
8. To trigger the unit using a supervised dr y contact connect the 2.2K resistor in series for a NC trigger input
and in parallel for [NO] trigger input (Fig. 5, pg. 11).
9. Connect auxiliary devices triggered by the unit to the terminals marked [DRY OUTPUT NO & C] on MOM5 board
for nor
output
Note: This relay will energize when the unit is triggered.
Access Control applications batteries are optional.
or
10.F
of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery to terminals
marked [+ BAT--] on power supply board for 12VDC operation
Fig. 4, pg. 8)
oltage:
Fig. 1B, pg. 5; Fig. 2B, pg. 6). AL1012ULM is 12VDC only and AL1024ULM
(Output Voltage and Stand-by Specification Charts below, pg. 4).
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating (see marking on the board). Replace fuse cover before energizing.
Do not expose to rain or moisture.
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Power Limited
NC C NO NC C NO
A
C FAIL
BAT FAIL
Battery & AC
Supervision Circuit
(power limited)
Switch Detail
--- DC
+
L G N
PTC3
NC C NO NC C NO
+ BAT ---
DC
AC
24V - OPEN
12V - CLOSED
AC FAIL
RL2
BAT FAIL
RL1
RL3
SW1
OPEN SWITCH
CLOSED SWITCH
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
Green
Lead
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Output Voltage and Stand-by Specification Charts, pg. 4).
Battery Test: Under normal load conditions check that the batter y is fully charged, check specified voltage at
the battery terminals and at the board terminals marked [+ BAT-- ] to insure that there is no break in the batter y
connection wires.
Note: AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge
current is .7 amp.
AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp.
Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.
Fig. 1
AL300ULM
AL400ULM
Fig. 1A
Fig. 1B
Mseries- 5 -
Fig. 2
Green
Lead
Battery connection (non power limited)
Wire
Strap
(from
Enclosure
to Door)
1
15VAC
power mains
non-power
l
imited
Class 1
Divider
NC C NO
DRY OUTPUT
TRIGGER
LED
6 7 8 9 10
POS (+) DC OUTPUT (STANDBY)
NC C NO
POWER FAIL
T
RIGGER
1 2 3 4 5
POS (+) DC OUTPUT (ALARM)
NEG1 NEG2 NEG3 NEG4 NEG5
-- DC INPUT +
NEG (-) INPUT POS (+)
DC Outputs to devices
(power limited)
Fire Alarm
Interface
non-power limited
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating (see marking on the board). Replace fuse cover before energizing.
D
o not expose to rain or moisture.
Power Limited
NC C NO NC C NO
AC FAIL
BAT FAIL
Battery & AC
Supervision Circuit
(power limited)
+
DC ---
BAT FAIL
NC C NO NC C NO
+ BAT ---
DC
2
4V - OPEN
1
2V - CLOSED
SW1
AC FAIL
L G N
AC
A
C Delay
Switch Detail
OPEN SWITCH
CLOSED SWITCH
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Green
Lead
A
L600ULM
F
ig. 2A
Fig. 2B
- 6 -Mseries
Fig. 3
Green Lead
Battery connection (non power limited)
Door
Wire Strap
(from
Enclosure
to Door)
115VAC
p
ower mains
non-power limited
Divider
Battery and AC
S
upervision Circuit
(power limited).
Power
Limited
Class 1
DC Outputs
t
o devices
(power limited)
NC C NO NC C NO
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating (see marking on the board). Replace fuse cover before energizing.
Do not expose to rain or moisture.
12VDC Rechargeable Battery
(optional)
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Fuse
Cover
A
L1012ULM
Fig. 3A
Mseries- 7 -
Fig. 4
Green Lead
Battery connection (non power limited)
Door
Wire Strap
(from
E
nclosure
to Door)
1
15VAC
p
ower mains
non-power limited
D
ivider
Battery and AC Supervision Circuit
(power limited).
Power
Limited
Class 1
D
C Outputs
to devices
(power limited)
NO C NC NO C NC
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating (see marking on the board). Replace fuse cover before energizing.
D
o not expose to rain or moisture.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
Fuse
Cover
A
L1024ULM
Fig. 4A
- 8 -Mseries
LED Diagnostics:
Power Supply Board
L
ED
R
ed (DC)Green (AC)Power Supply Status
ONONNormal operating condition.
ONOFFLoss of AC, Stand-by battery supplying power.
OFFONNo DC output. Short circuit or thermal overload condition.
OFFOFFNo DC output. Loss of AC. Discharged battery.
MOM5 - Output Module
LEDONOFF
Power (Green)Normal operation.Power failure.
Trigger (Green)Input is triggered (alarm condition).No input trigger (non-alarm condition).
Outputs (Red)Output tripped due to a Normal operation.
short circuit or overload condition.
Mseries- 9 -
Terminal Identification Tables:
Power Supply Board
T
erminalFunction/Description
L
egend
L, G, NConnect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC +AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power limited).
AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power limited).
AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (non-power limited).
AL1012ULM - 12VDC @ 10 amp to MOM5 board (non-power limited).
AL1024ULM - 24VDC @ 10 amp to MOM5 board (non-power limited).
AC FAILIndicates loss of AC power, e.g. connect to audible device or alarm panel. Relay
NO, C, NCnormally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to
6 hrs., cut “AC delay” jumper and reset power to unit.
BAT FAILIndicates low battery condition, e.g. connect to alarm panel. Relay normally
NO, C, NCenergized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported
within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULM),
24VDC output threshold set @ approximately 21VDC.
+ BAT -Stand-by battery connections. AL300ULXB, AL400ULXB and AL600ULXB (Power Supply
Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board)
maximum charge current is 3.6 amp.
MOM5 - Output Module
Ter minal LegendFunction/Description
---DC INPUT +12VDC or 24VDC from power supply.
TRIGGERDr
y normally open [NO] or nor
input trigger. A shor t or open circuit will transfer power from terminals marked
[POS. (+) DC OUTPUT (ST
[POS (+) DC OUTPUT (ALARM)]
--- INPUT + Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown
will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to
terminals marked [POS (+) DC OUTPUT (ALARM)] (e.g. fire alar m control panel
indications circuit).
NEG 1 THRU NEG 5Supplies constant negative (-) voltage.
POS (+) DC OUTPUTSupplies positive (+) voltage when dry trigger input or f ire
(ALARM) 1-5alarm wet trigger input is applied.
e (+) voltage in normal condition.
POS (+) DC OUTPUT
Supplies positi
v
(STAND-BY) 6-10Power is removed when dry trigger input or f ire alar m wet trigger input is applied.
NC, C, NO
When the MOM5 is triggered the terminals marked [C and NO] will open and the
DRY OUTPUTterminals marked [C and NC] will close. This output is used to trigger auxiliary devices.
(e.g. HVAC Shutdown, Elevator Recall etc.) Conta ct ratin g 1 am p @ 28 VDC.
m “C” contacts used for repor
or
NC, C, NO
F
POWER FAILterminals. Under normal conditions, terminals marked [NO and C] are open, [NC and C]
are closed. A loss of power causes terminals marked [NO and C] to close and [NC and C]
to open. Contact rating 1 amp @ 28VDC.
mally closed [NC] supervised (2.2K EOL resistor)
AND-BY)]
to terminals marked
.
ting no v
oltage is present at [-- DC input +]
- 10 -Mseries
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
EOL 2.2K
EOL 2.2K
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
MOM5_S
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
N.O. INPUT FROM
FACP OR ACCESS
CONTROL DEVICE
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
MOM5 module shown with wet and/or dry nor mally open trigger
inputs (Non-Latching):
(Non-Latching):
Fig. 6- Two (2) or more MOM5 modules shown with wet and/or dry normally closed trigger inputs (Non-Latching):
F
. 7
ig
o (2) or more
w
- T
Mseries- 11 -
MOM5 modules shown with wet and/or dry normally open trigger inputs
(Non-Latching):
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
O
N LED
TRIGGER
LED
TRIGGER
-
DC INPUT+
NEG (-) INPUT POS (+)
POWER
O
N LED
N.O. RESET
EOL 2.2K
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP
S
IGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.C. INPUT
FROM FACP
N
C C NO
DRY OUTPUT
NC C NO
POWER FAIL
NC C NO
D
RY OUTPU T
N
C C NO
POWER FAIL
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG(-) INPUT POS (+)
POWER
ON LED
TRIGGER
LED
TRIGGER
- DC INPUT+
NEG (-) INPUT POS (+)
POWER
ON LED
EOL 2.2K
(+)
(-)
(+)
(-)
N.C. RESET
EOL 2.2K
DC VOLTAGE INPUT
FROM FACP
SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
N.O. INPUT
FROM FACP
NC C NO
DRY OUTP UT
NC C NO
POWER FAIL
NC C NO
DRY OUTP UT
NC C NO
POWER FAIL
T
RIGGER
LED
TRIGGER
NEG (-) INPUT POS (+)
POWER
O
N LED
N
.C.
RESET
EOL 2.2K
(
+)
(
-
)
DC VOLTAGE INPUT
FROM FACP
SIGNALING OUTPUT
N.O. INPUT
FROM FACP
SIGNALING
OUTPUT
N
C C NO
D
RY OUTP UT
N
C C NO
POWER FA IL
TRIGGER
L
ED
TRIGGER
NEG (-) INPUT POS (+)
P
OWER
ON LED
N.O. RESET
E
OL 2.2K
(
+)
(
-
)
DC VOLTAGE INPUT
FROM FACP
SIGNALING OUTPUT
N
.C. INPUT
F
ROM FACP
S
IGNALING
O
UTPUT
N
C C NO
D
RY OUTPUT
NC C NO
P
OWER FA IL
Typical Application Diagrams (cont’d.):
F
ig. 8
OM5 module shown with with wet and/or dry
M
ormally open fire alar m trigger inputs (Latching
n
with Manual Reset)
:
OM5 module shown with with wet and/or dry
M
ormally closed fire alar m trigger inputs
n
(Latching with Manual Reset):
Fig. 9 - Two (2) MOM5 modules shown with wet and/or dry normally closed fire alar m trigger inputs
(Latching with Manual Reset):
Fig. 10 - Two (2) MOM5 modules shown with wet and/or dry normally open fire alar m trigger inputs
(Latching with Man
- 12 -Mseries
ual Reset)
:
5
.10"
6.5625"
3.25"3.25"
5.10"
5
.10"
3.25"
1.00"10.50"1.00"
1.00"
1.00"
1.40"
1
.20"
1
.40"
1
.20"
0.75
"0.75"11.00"
12.50"
3.25"
0.9375"
0.9375"
1
.40"4.85"4.85"1.40"
1
.20"
Bottom
Top
RightLeft
• AL300ULM
•
AL400ULM
• AL600ULM
13.5”H x 13”W x 3.25”D
Enclosure Dimensions:
Mseries- 13 -
1.285
1.285
• AL1012ULM
•
AL1024ULM
1
5.5”H x 12”W x 4.5”D
Enclosure Dimensions:
- 14 -Mseries
Notes:
Mseries- 15 -
Notes:
Altronix is not responsible for any typographical errors.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIMseriesG11G
- 16 -Mseries
MEMBER
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.