Camden Door Controls CX-ED1579L Installation Instructions

CX-ED1579L
‘All-in-One’ Fire Electric Strike
Installation Instructions
This Package Includes:
1 - 4 PIN power connector
1 -3 PIN door status connector
1 -EMP1, EMP2, EMP3, EMP4 and EMP5 faceplates
4 - Wire nuts
5 - M5 x 12 mm screws
2 - #10 x 1 1/4” wood screws
2 -#10-32 x 1/2” screws
2 - Mounting brackets
2 -Spacers
1. Description
Camden CX-ED1579L grade 1 electric strike for mortise and cylindrical locksets offer the very best strike quality and features, with the added value of built-in latch monitoring, four stainless steel faceplates and ‘Universal’ performance,
operation.
2. Specifications
Voltage
Current Draw
12/24V AC/DC
260mA@12V AC/DC 150mA@24V AC/DC
3. Dimensions
UL 1034 UL 294
UL 294 Performance Levels
- Line Security = Level I
- Attack Level = Level I
- Endurance Level = Level IV
- Standby Power = Level I
1 1/4"
(32mm)
UL10C/ CAN4-S104, 3hr. Fire rating
Static Strength
Dynamic Strength
Endurance
Fire Rating
Mode
Operation
Duty
Latch Bolt Monitor
Dimensions (Body)
1,500 Lbs.
70 Ft-Lbs.
1,500,000 Cycles (Factory Tested)
250,000 Cycles (UL Verified)
UL 10C/CAN4-S104 3 hrs. (Fail Secure Only)
Field Selectable Fail Safe/Fail Secure
AC-Buzz DC-Silent
Continuous
SPDT, 100mA @ 24V DC
3 3/8” H x 1 5/8” W x 1 13/4” D (86mm x 41mm x 44mm)
4 7/8"
(124mm)
3/16"
(5mm)
4 1/8"
(105mm)
3 3/8"
(86mm)
3 1/8"
(80mm)
5/8"
(16mm)
1 5/8"
(41mm)
1 3/4"
(45mm)
Page 1 of 3
4. Installation
DRILL & COUNTERSINK FOR M5 FLAT-HEAD SCREW(2PCS) PRESSED METAL NUT
1. Prepare the door jamb as per the appropriate drawing.
2. Install mounting brackets to jamb using M5x12 screws and pressed metal nuts. Do not tighten.
3. Spacers are used to assure ush nal assembly of
faceplate into jamb. Add one or more spacers between jamb and mounting bracket when face plate extends beyond the jamb. When the faceplate sits inside the jamb, spacers must be added between the mounting bracket & the lip bracket. Make sure the clearance hole in the spacer aligns with the hole in mounting bracket.
4. Connect wires coming from the low voltage side of the transformer to wires from strike.
5. Install electric strike jamb by attaching with # 10-32 screws and lockwashers.
6. Tighten secure M5x12 screws holding mounting brackets to jamb.
Note: The products are intended to be installed in accordance with the installation wiring diagram, mechanical assembly drawings provided with each product, the local authority having jurisdiction (AHJ) and the National Electric Code, NFPA
70. When installed in fail secure mode, the local authority shall be consulted with regard to the use of possible panic hardware to allow emergency exit from the secure area.
The electric door strike shall be installed in such a way and in such a location so as to not impair the operation of an emergency exit device or panic hardware mounted on the door.
CX-ED1579L ‘All-in-One’ Fire Electric Strike
MOUNTING
BRACKET
JAMB
M5x12 FLAT-HEAD SCREW(2PCS)
M5x12 SCREW
JAMB
Frame Install
"
3
[43mm]
1
4
3
" [86mm]
3
8
HORIZONTAL CENTERLINE
7
4
" [124mm]
8
1
6
8
"
[155mm]
Latch Bolt Monitor and
Bracket Installation
DEAD BOLT BRACKET
LATCH BOLT MONITOR PLATE
Keeper Shim
Installation
Note: Figures show typical installation. The dead bolt bracket, monitor plate and keeper shims can be mounted in alternate locations depending on RH or LH installation.
KEEPER SHIM
Figure 2 Figure 1
Page 2 of 3
CX-ED1579L ‘All-in-One’ Fire Electric Strike
Blue
5. Connections
POWER 12V AC/DC
Red/Black: +12V Blue/Green: Ground
24V AC/DC
Red: +24V Black/Blue: ­Green: Ground
A varistor is provided to protect/prevent strike from spikes.
Connect varistor between input wires.
Note: For UL 294 / UL 1034 compliance the door strikes are to be powered via a UL 294/ UL 603 class 2 power limited output from a control panel and or power supply. Furthermore, when powered by AC/DC the units shall use a UL regulated UL 294/ UL 603 power limited class 2 output rated 12/24V with AC on indicator.
6. Installation
Power
12V
Door Status Sensor (Closed position)
Purple = N/O
(+12V) Varistor
( - )
(+24V)
Varistor
( - )
24V
Red Black
Blue Green
Red
Black
Blue Green
Brown = N/C
Yellow = COM
Grey White Orange
Black Red
8. Faceplates
7. Operation
How to modify fail-safe to fail-secure or vice versa.
(1). Loosen the screw as per the product diagram below.
(2). Rotate the set plate 180° and slide the plate until it is properly seated.
(3). Tighten the screw.
Fail Safe Changing
Fail Secure
Note: UL re rating is only valid while in Fail Secure Mode.
7
"
[22mm]
8
3
1
8
"
[34mm]
1
"
1
[31mm]
4
"
5
[16mm]
8
4
[105mm]
[123mm]
"
1 8
"
1
1
[28mm]
8
"
7
4
8
"
1
1
[37mm]
2
1
"
1
[31mm]
4
"
5
[16mm]
8
1
4
8
[105mm]
[123mm]
"
1
"
1
[31mm]
4
"
5
[16mm]
8
"
3
1
[43mm]
4
"
7
4
8
"
1
1
[37mm]
2
1
4
8
[105mm]
[123mm]
"
"
7
[22mm]
8
"
7
4
8
"
1
3
[79mm]
8
1
"
1
[31mm]
4
"
5
[16mm]
8
1
4
8
[105mm]
7
4
8
[123mm]
"
"
1
1
8
[28mm]
1
3
8
[79mm]
1
"
1
[31mm]
4
"
5
[16mm]
"
[31mm]
"
[37mm]
8
"
1
1
4
"
1
4
8
"
1
[105mm]
3
2
EMP1 EMP2 EMP3 EMP4 EMP5
Push Buttons Keypads Strikes Magnetic Locks Key Switches Relays & Timers Access Control
5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7
www.camdencontrols.com Toll Free: 1.877.226.3369
Page 3 of 3
File: CX-ED1579L Designer Installation Instructions.indd R3 Revision:20/04/2018 Part No.: 40-82B202
7
4
8
[123mm]
"
Loading...