• Remote LED - (located on TS-1)
Output for a remote Bi-color LED,
output follows LED on Face Plate.
• Door Status Relay - follows the Door
Contact Input, regardless of alarm or
bypass condition.
• Door Prop Alarm Relay - changes
state during a Door Prop
(Door Held) Alarm condition.
• Intrusion & Tamper Alarm Relay -
changes state during an Intrusion
or Tamper Alarm condition.
• Bypass/Key Switch Status Relay -
follows Bypass and Key inputs.
Output contacts change state when power
is lost.
DESCRIPTION
The CX-DA400 provides complete monitoring of access control points by
offering you prop/door held open and intrusion/door forced open detection.
These alarms are designed to complement card reader and access control
systems and will interface with electronic locks, produce audible warnings
and reduce nuisance alarms by encouraging user compliance with access
control procedures.
OTHER FEATURES
• Shunt Recycle - See Step 3. Pg. 4
• Door Supervision - See Step 1. Pg. 3
• Intrusion Detect - See Step 2. Pg. 3
• Loud Horn Volume - See Step 7. Pg. 5
• Extended Silent Time - See Step 4. Pg. 4
• Shunt Delay Timer - See Step 4 . Pg. 4
INPUTS
The inputs are located on Terminal Strip –1
and include:
• Dry Contact Shunt - a N/O or N/C Dry
Contact, selected using Shunt Contact
Mode Jumper 3. See Step 3. Pg. 4
• Voltage Sense - Monitors the power
wires on an electric lock (i.e.: Mag-lock or
Door Strike). Senses change in voltage
as valid user. See Step 3. Pg. 4
• Door Contact - a Closed Loop (N/C)
Dry Contact which opens when the
monitored door opens. See Step 1. Pg. 3
• Bypass - Connect to a N/O Dry Contact
from a remote location to bypass the
unit. See Step 7 Pg. 5
• Power - 12 to 24 VAC/DC @ 250 mA.
The terminals are not polarity sensitive.
See Step 5. Pg. 4
JUMPERCONFIGURES
1 Door Supervision (Part of Tamper circuit)TS1-7&8 Door Input
2 Voltage Sense Mode (Senses Lock Voltage as Valid User Input)TS1-3&4 Voltage Sense Input
3 Shunt Contact Mode (Senses Dry Contact as Valid User Input)TS1-1&2 Shunt Contact Input
4 Intrusion Detect Enable (Explained on reverse)Intrusion or Free Access selection
5 Shunt Recycle Enable (Explained on reverse)Shunt Recycle feature selection
6 RESERVED (Factory Diagnostic)Factory Use Only Leave Jumper OFF
7 & 8 Shunt Delay Timer (Set same as Lock Time)Access Time prior to opening door
9 Extended TimeSelect Ext. Silent Time 3-90 Min.
10 Horn VolumeSelect 96db or 103db
Page 1 of 6
CX-DA400 Door Prop Alarm Installation Instructions
TIMERS
• SilentTime - “Open Door” Time - 0-2.5 min. in standard mode,
3 - 90 min. in Extended mode (selected by Jumper 9).
• AlarmDelay - “Warning” Time - 0-5 min. and “Innite.” Local
Beeping Warning Audible sounds during this time.
• AutoReset - “Alarm” Time - 0-5 min. and Manual Reset.
Constant Alarm Audible sounds during this time.
• ShuntDelay - Valid Access Time prior to reset if Door is
unopened. 0, 5, 10, or 20 seconds (set with Jumpers 7 & 8).
TIMER SETTING TABLE
SIDE VIEW
SET
0
1
2
3
4
5
6
7
SILENT TIME
SELECT
(Extended Silent Time Jumper)
NORMAL
Jumper OFF
0 Sec3 Min0 Sec0 Sec
3 Sec3.5 Min3 Sec3 Sec
5 Sec4 Min5 Sec5 Sec
7 Sec4.5 Min7 Sec7 Sec
10 Sec5 Min10 Sec10 Sec
12 Sec6 Min12 Sec12 Sec
15 Sec7 Min15 Sec15 Sec
20 Sec8 Min20 Sec20 Sec
EXTENDED
Jumper ON
ALARM
DELAY
TIME
SELECT
AUTO
RESET
TIME
SELECT
TAMPER CIRCUIT- Alarm is not reset with key.
(CX-DA401 only)
• TAMPER SWITCH - Switch is located on stand-off under spring steel
actuator. (Cut cable tie to Enable switch)
• DOOR SUPERVISION - Enable with Jumper 1. Requires resistors on
Door Switch. (Schematic on Step 1 Pg.3)
OPERATION
VALID ACCESS / PROPPED DOOR OPERATION
ARMED STATE - Red LED (Green if Intrusion Detect is Off)
VALID USER INPUT - Shunt or Voltage Sense Input
LED - Changes to Green
DOOR - Opened by user, Silent Timer begins
DOOR - Closed by user, Returns to Armed State, or
- SILENT TIME TIMER - expires, then
AUDIBLE WARNING - Beeps to alert user locally
LED - Flashes Green
DOOR - Closed by user, returns to Armed State, or*
- SHUNT RECYCLE - 2nd Valid User Input (*if enabled)
SILENT TIME RESET - Silent Timer begins again
DOOR HELD/PROPPED - Alarm Delay Times out
LED - Flashes Red
AUDIBLE - Constant tone, Auto Reset (AR) Timer begins
OUTPUT - Door Prop Alarm relay toggles
DOOR CLOSED - After Door Prop Alarm exists
AUDIBLE - On until Auto Reset (AR) Time expires
LED - Flashes Red for AR Time
OUTPUT - Relay held for duration of AR Time
INTRUSION OPERATION
ARMED STATE - Red LED
DOOR Opened by invalid entry
LED - Flashes Red
AUDIBLE - Constant tone, Auto Reset (AR) Timer begins
OUTPUT - Intrusion/Tamper Alarm relay toggles
- DOOR CLOSED
LED - Flashes for duration of AR Time
AUDIBLE - Continues for duration of AR Time
OUTPUT - Changed for duration of AR Time
- REARM - After AR time expires OR by Manual reset
LED - Red (Armed State)
8
9
A
B
C
D
E
F
25 Sec9 Min30 Sec30 Sec
30 Sec10 Min45 Sec45 Sec
35 Sec20 Min1 Min1 Min
45 Sec30 Min2 Min2 Min
1 Min40 Min3 Min3 Min
1.5 Min50 Min4 Min4 Min
2 Min60 Min5 Min5 Min
2.5 Min90 MinINFINITEMANUAL
TAMPER OPERATION (CX-DA401 only)
ARMED STATE - Red LED (Door Supervision Enabled)
- TAMPER (Door circuit open/shorted, or if unit is
removed from wall)
LED - Flashing Red
AUDIBLE - Constant tone
OUTPUT - Intrusion/Tamper Alarm relay toggles
- RESET - Door normal, and Tamper switch closed
LED - Red (Armed State)
Page 2 of 6
CM-324 Active Infrared “Hands-Free” Switch Installation Instructions
CX-DA400 Door Prop Alarm Installation Instructions
STEP BY STEP INSTRUCTIONS
FOR EASY CONFIGURATION
THE DEFAULT SETUP IS FOR ACCESS CONTROLLED,
AND EMERGENCY EXIT APPLICATIONS.
• This unit may be connected to power and a closed-loop
Door Input and be ready to work immediately for the
Default application.
• A Voltage Sense input used with a Mag-Lock, and/or a N/C Dry
Contact Shunt input will require additional jumper conguration
(J2 and/or J3 respectively) and is covered in Step 3 Pg. 4.
• The unit is easily congured for a stand-alone Door Prop
application by removing the Intrusion Detection jumper.
(LED will always be Green when Intrusion Detection is disabled.)
TIMER SETTING DEFAULTS: (Step 4 Pg.4)
• Silent Time 5 seconds;
• Alarm Delay Time 5 seconds
• Auto Reset Time 5 seconds
• Shunt Delay 20 seconds
See text for Feature Description and Setup info.
TERMS USED IN THIS INSTRUCTION
N/C DOOR CONTACT - is a “closed-loop” circuit which goes open
when the door is opened.
SHUNT INPUT - is a dry contact Valid User Input provided by an
Access Control System or a PIR / REX device.
DMA - Door Management Alarm (i.e.: CX-DA400)
Normally Energized - in reference to a Mag-Lock or other locking
device where power is removed to unlock.
Normally De-energized - in reference to a Door Strike or other
locking device where power is applied to unlock.
CX-DA400
Figure 1
• Tamper Alarm (cannot be reset or bypassed)
A) To Enable feature cut cable tie on Tamper Switch located on
standoff (Component Location on reverse. (CX-DA401 only)
INTRUSION DETECTION
2
A) Jumper 4 is ON for Access Control and Emergency Exit Only
applications.
B) Jumper 4 is OFF for Door Prop/Held applications without Access
Control.
NOTE: If OFF, LED is Green
except during a Door Prop Alarm.
If OFF, Go to Step 4-Timer Settings. (Skip Step 3)
1
DOOR SUPERVISION, AND TAMPER
• Connect N/C Door Contact to TS1 7&8.
• If resistors are installed for Door Supervision:
A) place Jumper 1 ON and put resistors at door switch as shown in
Figure 1.
B) If unused, leave Jumper OFF and use a closed-loop Door Switch
circuit.
ACCESS CONTROL
3
• VOLTAGE SENSE monitors Lock Power as “Valid User” input on
TS1 (3&4)
A) If unused, Jumper 2 must be OFF.
B) If used, select: Normally Energized (Jumper 2 ON); or, Normally
De-Energized (Jumper 2 OFF)
VOLTAGE SENSE
EXPLAINED - This
input samples the
voltage to a Mag
Lock (J2 ON) or a
Door Strike* (J2
OFF) and accepts a
change in voltage
as a valid user
input. *Normally
de-energized.
• SHUNT INPUT detects a Dry Contact input for each valid access.
TS1 (1&2)
A) If unused, Jumper 3 must be ON
B) If used, Select:
Jumper 3 ON for N/O input; or Jumper 3 OFF for N/C input
Page 3 of 6
• SHUNT RECYCLE (see description below)
A) Jumper 5 is ON
B) Jumper 5 is OFF
SHUNT INPUT
EXPLAINED - This
input from a PIR
or Access Control
system provides
user validation.
CX-DA400 Door Prop Alarm Installation Instructions
• SILENT TIME SELECT begins when the door is opened
by a valid user. (see Timer Setting Table on reverse)
A) Timer has two ranges selected with Jumper 9;
• Normal - 0 seconds to 2.5 minutes (Jumper OFF)
• Extended - 3 minutes to 90 minutes (Jumper ON)
B) After selecting appropriate range, turn dial to SET #
for the Silent Time period desired for your application.
• ALARM DELAY SELECT begins on the expiration of the
Silent Timer. Warning Alarm sounds locally to alert user.
A) Turn dial to SET # on table (see reverse) for the time
you want the Warning (beeping) alarm to sound (prior to triggering
the Door Prop Alarm Horn and Relay).
• AUTO RESET TIME SELECT is the minimum time the
Horn, LED and Relays are on following an alarm condition.
NOTE: Alarm will continue for as long as the door is open
A) Turn the dial to SET Timer (0 seconds to 5 minutes,
or Manual).
POWER
5
• POWER - Connect 12-24 VAC/DC to TS1 11&12.
Not polarity sensitive.
SHUNT RECYCLE EXPLAINED -
• When Shunt Recycle is Enabled (ON), a Shunt Contact or Voltage Sense Input
during the Alarm Delay warning period (beeping) will reset the Silent Time
Timer. Shunt Recycle gives the User the ability to Hold the door indenitely by
repeating a valid input during each Alarm Delay warning.
• When disabled, only a Key or Bypass input will reset the DMA.
TIMER SETTINGS SEE TABLE ON REVERSE
4
• The SHUNT DELAY TIMER begins after a Valid User input (prior to
door being opened) and if door is not opened the DMA will reset
when timer expires. Cancels upon door opening.
A) Shunt Delay works only with Intrusion Detection enabled.
B) See table on Back Plate for Jumper 7&8 setting detail.
OUTPUTS (FORM-C)
6
• DOOR STATUS RELAY
TS2-22,23,24 changes state when the
Door Input changes. Used to monitor
changes in Door Contact status.
• DOOR PROP ALARM RELAY
TS2-19,20,21 changes state when a
door is held open beyond the Silent and
Alarm Delay time, combined.
• FORCED DOOR/TAMPER ALARM
RELAY
TS2-16,17,18 changes state when a
door is forced or a tamper condition
exists (Door Supervision/Tamper
Switch).
• BYPASS/KEY SWITCH
STATUS RELAY
TS2-13,14,15 changes state during Bypass (TS1 9&10) and Key
Switch Inputs. Used to monitor for changes in Bypass status.
Page 4 of 6
ADDITIONAL OUTPUT INFORMATION
• Each of the Output functions offers the availability
of monitoring a Normally Open or a Normally
Closed Dry contact.
• Each contact’s state will change to follow the status
of the monitored function.
• To combine multiple outputs, connect N/O contacts
in parallel, or N/C contacts in series.
See diagrams at right. The use of any/all Outputs
is optional.
• If power is removed from the CX-DA400, each contact in it’s normal
state (powered), will change state. Example: Door Status will appear as
if the door
has been opened; Alarm and Bypass contacts will appear as if an alarm
or bypass condition exists.
ADDITIONAL FEATURES
7
SEE COMPONENT LOCATION DIAGRAM ON PAGE 2
BYPASS TS1
(9&10) input, to
N/O contact to
remotely Bypass or
Reset the unit.
CX-DA400 Door Prop Alarm Installation Instructions
REMOTE LED
to TS1 (5&6).
HORN VOLUME -
Jumper 10 is used
to set the volume of
the sounder.
ON = 103db
OFF = 96db
TROUBLE SHOOTING TIPS
• Horn won’t Reset - Verify Tamper Switch is closed; Verify
Door Supervision Jumper is correct for application; Check
Door Contact Resistors are installed as per Step 1 if Door
Supervision is enabled.
• LED always Green - Normal condition when Jumper 4 is OFF;
Verify Shunt Contact & Voltage Sense jumpers are correct for
your application; Verify Key Switch is Vertical and Bypass Input
is open.
• Alarm when Door Opens - Verify that SO&S1 Jumpers and
Silent Time are set greater than 0 sec.; Verify Intrusion Jumper
is set correctly for application.