Camden Door Controls CM-30EE Installation Instructions

Installation Instructions
Exit Switch & Integrated Time r
CM-30EE & CM30EE/LED
Section 1 __________________ General Description
Camden models CM-3 0 EE/ LED ar e i lluminated Exit switches incorporating a 30 second timer. The stainless steel faceplate is designed to mount into a 2 ½” deep single gang electrical box, includ ed.
The large 2” translucent but ton is easy to push. CM­30EE model is supplied with a 12V AC/DC incandescent light bulb, which is accessed through the front or rear of the switch. CM-30EE/LED model is supplied with a 12V DC long-life LED. If the unit is
powered 24VDC, the supplied in-line resistor must not be removed.
This switch has been designed specifically to release a magnetic lock from the inside, as per the BOCA code. When the button is pushed and released, the lock will release for 30 seconds. Re-trigger is possible at any time.
The “double break” circuitry has been designed so that even if the timer fails, depressing the switch will interrupt power to the magnetic lock.
Section 2__________________ Installation
Mounting
The unit is completely pre-wired for easy installation. Connect the appropriate wired to your devices as per the enclosed wiring diagram. Tuck wiring into box (retrofit box included), and fasten switch plate using standard or tamper screws provided.
Wiring
Six color coded leads are provided. This unit will operate on 12 or 24 VDC, with no jumper change required. For convenience it may be powered by the same power that supplies the magnetic lock. The two pairs of Red & Black wires connect to 12 or 24 VDC. One pair supplies power to the timer, and the other pair powers the light.
The internal timer and the push button are connected in series with the Green & White wires. This is how the “double break” feature works. Therefore, the unit must

be wired as shown

The Green wire goes to the positive input wire of the magnetic lock, and the White wire goes to a source of + Voltage. Please refer to the enclosed wiring diagram for typical hook-up.
Important
CM-30EE models have a connected lead wire wit h black-colored heat shrink (over an in-line resistor). CM-30EE/LED models have a connected lead wire with blue-colored heat shrink (over an in-line resistor).
If powered 24V; Do not remove in-line resi stor If powered 12V; Cut (remove) in-line resistor
Section 3 _________________ Technical Data
Lens Color Green lens Legend Push to Exit Size 4.5”h x 2.75”w x 2.5”d
114.3mm x 69.8mm x 63.5mm Mounting 2 x #6-32 machine or tamper
screws, supplied Operating voltage 12 / 24 Volts DC Time Delay 30 seconds Contact Rating 4 amps @ 30 VDC Incandescent Bulb Life 15,000hrs. @ rated capacity
Section 4_________________
Limited Warranty
Camden Door Controls Inc. warrants this product to be free from defects for 3 years from date of manufacturing. Visit our web site at www.camdencontrols.com to see our complete warranty polic y, including limitations and the procedures for product returns.
Questions?

Call us toll-free at 1-877-226-3369

(Ver. 2)
Optional Motio n Detector shown. If not used, wire White to Positive Terminal of power supply.
12 / 24
VDC
Power
+
Power In Relay Out
Motion Detector
Wire White to "+" 12 / 24 VDC,
through Relay of Motion Detector
or,
(optional)
Rear View of CM-30EE switch and Faceplate
White
Green
"+"
"-"
Red
(Light) (Light)
Black
Magnetic Lock
Red
Note: A lead with blue-colored heat shrink (over in-line resistor) is supplied on LED model. A lead with black colored heat shrink (over in-line resistor) is supplied on incandescent bulb model.
Leave resistor for 24 Volts, Cut off resistor for 12 Volts.
Black
-
NOTES:
The light bulb (incandescent or LED), can be accessed from the front, by using a small slot (flat) screwdriver to remove the plastic lens cover or from the back. To access from the back, detach the contact block from the light fixture assembly, held in place by two plastic retaining pins. Squeeze the retaining pins and gently pull the contact block to remove the light fixture assembly.
The contact block can be reassembled into the light assembly by simply pressing it in place.
Camden Door Controls
SCALE: NONE
CM-30EE Egress Switch Wiring Diagram (Ver 2.0)
DRAWING No: DRG-CM30EE-022803
DRAWN BY: DGW
5502 Timberlea Blvd. Mississauga, Ontario L4W 2Z3
DATE: 02/28/03
REVISED: 03 /22/12
FILENAME: CM-30EE Diagram.vsd
Loading...