Camden EMF-2M, EMF-2 User Manual

5502 Timberlea Blvd., Mississauga, ON L4W 2T7 Telephone: 905-366-3377 Fax: 905-366-3378 Toll-Free: 1-877-226-3369 Web: www.camdencontrols.com
Section 1__________________ General Description
Camden model EMF-2 (EMF-2m or EMF-2ABM) is a microprocessor controlled multi-function relay. This all-in-one design replaces our previous models EMF-1, EMF-1m or EMF-1ABM.
The EMF-2 is designed for specialized applications such as ABM vestibules, one or two-door restrooms in shared-use facilities, 2 – 5 door airlocks, and secure man-traps.
Dip switches let you easily choose the mode, and the unit automatically programs the inputs, outputs and potentiometers accordingly.
Removable terminal strips simplify wiring chores, and all adjustments are conveniently located on one end of the case.
IMPORTANT: Do not apply power to the unit until you have read the instructions fully and made the required adjustments.
Section 2__________________ Installation
Mounting
The EMF-2 should be mounted in a clean dry location out of direct contact with the elements. Suitable locations include inside a metal box, operator header, or above a false ceiling. If placed on top of a header, ensure that unauthorized personnel cannot tamper with the unit.
If used in an Airlock or Mantrap application, the relay may be located at either door location, or, centrally to all doors. You must bring wiring from all door actuators to this unit (as well as the lock, operator, and door contact outputs as appropriate).
The EMF-2 is also available in an attractive lockable metal cabinet version (EMF-2m or EMF-2ABM), suitable for wall mounting.
EMF-2 / EMF-2m
Multi-Function Timer
Ver. A1-001
MADE IN CANADA PAGE 1 OF 19
Wiring
Wiring of this unit is dependant on the mode desired. Select your intended application, then proceed to the section indicated.
Note: Do not installed, wire your safety device directly to the operator control box.
IMPORTANT: Changes to the Mode and Out2 do not take effect until a power reset best to make these adjustments with the power
turned off!
NOTE: We highly recommend the use of a regulated power supply when powering equipment for barrier-free washroom applications where the strike power may be maintained from a few minutes to many hours. We offer a low-cost board-only regulated power supply - CX-PS13 V2, which in turn can be powered from a small 24VAC transformer, (or the auxiliary power on the door control) and will supply clean, filtered & regulated 24VDC power for the strike and EMF-2.
wire Safety devices to the EMF-2. If
APPLICATIONS & SET-UP INSTRUCTIONS:
ABM Vestibule Control (Mode 1) Proceed to section 3A on Page 3 1 Door Unsecured Restroom (Mode 2) Proceed to section 3B on Page 5 1 Door Secured Restroom (Mode 3) Proceed to section 3C on Page 7 2 Door Unsecured Restroom (Mode 4) Proceed to section 3D on Page 11 2 / 3 Door Airlock (w/ auto-crossing) (Mode 5) Proceed to section 3E on Page 13 2 - 5 Door Airlock (Mode 6) Proceed to section 3F on Page 15 2 Door Man-trap (Mode 7) Proceed to section 3G on Page 17 System Inspection Instructions Page 18 Technical Specifications, & Warranty Page 19
. It is therefore
Page 2
Connector Terminal Label Function
P1
1 Power Input
2 Power Input
1 Ground
2 Blue (or Brown)
3 N/C (or Yellow)
P2
4 CR Power +5V
5 Orange (output 1)
6 Output 2
7 Ground 2
1 Dry 1 Input
2 Dry 1 Input
3 Dry 2 Input
4 Dry 2 Input
5 Dry 3 Input
6 Dry 3 Input
P3
7 Dry 4 Input
8 Dry 4 Input
9 Dry 5 Input
10 Dry 5 Input
11 Dry 6 Input
12 Dry 6 Input
13 Dry 7 Input
14 Dry 7 Input
1 Relay 1 – NC
2 Relay 1 – COM
3 Relay 1 – NO
4 Relay 2 – NC
5 Relay 2 – COM
6 Relay 2 – NO
7 Relay 3 – NC
P4
8 Relay 3 – COM
9 Relay 3 – NO
10 Relay 4 – NC
11 Relay 4 – COM
12 Relay 4 – NO
13 Relay 5 – NC
14 Relay 5 – COM
15 Relay 5 – NO
NOTE: Pin 2 Connector. When connecting to Camden Card Reader in ABM Mode it is possible to read all cards by wiring the Blue wire to Pin 2, or only Cards beginning with a 4, 5, & 6 by wiring the Brown wire (Data) to Pin 2, and the yellow wire (Clock) to pin 3.
Dip4Dip
RELAY 5 CHART
To have Relay 5 shadow another
relay, set dipswitch
as s hown at right
OFF OFF
ON
OFF
ON ON
12/24 Volts AC/DC Non-polarized
Card-Reader Input (aka - Digital Connector)
Non-powered Input 1
Non-powered Input 2
Non-powered Input 3
Non-powered Input 4
Non-powered Input 5
Non-powered Input 6
Non-powered Input 7
Form C
Form C
Form C
Form C
Form C
=
5
1
OFF
2
ON
3
4
Power
Off / On
1
Mode
2
3 4
Rel 5
5
6
Opt
7 8
NC
1
Relay 1
C
2
NO
3
NC
4
Relay 2
C
5
NO
6
NC
7
Relay 3
C
P4
6 13/16" (160 mm)
P1
8
NO
9
NC
10
Relay 4
C
11
NO
12
NC
13
Relay 5
C
14
NO
15
1
12/24V Power
2
Top View
SCALE: NONE
DRAWN BY: DGW
EMF-2 Diagram 1, Electrical and Mechanical
DRAWING No: DRG -EMF-2_01
12V 5V
LED Output
Relay On Indicators
2345
1
Timer Settings
EMF-2
Digital
In/Out
terminal
strip
Inputs
Trouble
Output
Input
disables
Door #2
ON
14
7
13 12
6
11 10
5
9 8
4
3
2
1
P3
7 6 5 4 3 2 1
7 6
5 4
P2
3 2
1
6 7/8" (173 mm)
2 7/8" (72 mm)
Camden Door Controls
DATE: 03/24/10
FILENAME: EMF-2 Diagram 1.vsd
1" (25 mm)
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED:
06/08/10
Side View
Section 3A________________ Set-up Instructions
ABM Vestibule Controller (Mode 1)
The EMF-2 is a compact unit designed to interface an automatic door operator with a card reader and lock system such as those used on banks.
When in “Day Mode” the strike is retracted (manually, or electrically) and the card reader is out of the circuit. Pressing either exterior or interior wall switch will activate the door operator.
When the EMF-2 is switched to “Night Mode” the electric strike is energized (door is locked), and the exterior activator (ie - wall switch) is removed from the circuit. When a valid card is inserted, the strike unlocks immediately, and the exterior switch is put back into the circuit for an adjustable period, so that if pushed by the user, it will open the door automatically. The inside switch will unlock and open the door at all times.
A new feature of the EMF-2 is the ability to add an “Emergency - Push-to-Lock” switch near the ATM machine that when activated “locks out” the card reader input in order to afford the user extra security. Opening the door from the inside resets the system. (The system will also reset automatically after 10 minutes.)
Model EMF-2 ABM provides for a lockable cabinet to house the relay, c/w two lighted push-button switches – one to turn the relay power other to select DAY or NITE modes.
Step 1
Select switch as shown below:
See Diagram 1 for location of dipswitch, connectors, & potentiometers.
Step2 Dip switch Options
Push dipswitch #6 which is to be energized during “Day Mode”. If using an intermittent duty strike and/or the latch is to be mechanically retracted during “Day Mode”, then leave switch #6
Use of Relay 5 is optional, and set according to dipswitches #4 & 5. (See diagram 1 for location). Dipswitches # 7 & 8 have no effect in this mode.
MODE 1 via the first 3 positions of the dip
Off On 1 2 3
ON, for a continuous duty strike,
OFF.
IMPORTANT: Any changes Mode selector or Out2 settings must be made with power off!
ON or OFF, and the
Step 3 Connections
Refer to Diagram 2 (next page) for the following connections.
Wire all input connections to the (removable)
terminal strip
connector if removed. Next, make your wiring connections to the
Output strip
used in this application. Re-insert connector. If you are using this system with our Model #51T2B
card reader – then refer to the 7-pin and make wiring connections as per the respective card-reader wiring diagram.
If using our model #ECI-210, or another type of card reader, or dry contact - wire to terminals 1 & 2 of the
Digital I/O strip. (Re-insert connector firmly if
removed.) Finally, connect 12 or 24 Volt AC or DC supply to
terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots # 1 – 4. (Pot 5 has no effect.
Timer 1 Strike Delay-on-Release Timer 2 Operator Delay-on-activate Timer 3 Operator Delay-on-release Timer 4 Exterior Switch enable time
Apply power to door operator, EMF-2, and any applicable activating devices (ie – card-reader). Observe the lit. If not, re-confirm proper voltage connections.
(numbered 1 - 14). Firmly re-insert
(numbered 1 – 15). Note: Relay 4 is not
Digital I/O strip,
RED Power LED on the unit. It should be
Turn key switch (Input #3) to “Night Mode”. (Night mode via an open contact, Day mode via closed).
Activate interior switch. Door should unlock and open. Adjust potentiometers # 1, 2 & 3 for desired operating times.
Activate exterior switch. Door should remain closed and locked. Now activate the card reader input. The door should unlock. Adjust Timer 1 for sufficient time on the strike.
When the card reader is activated, the exterior switch is “put into the circuit” for a limited time. This time is adjustable from 1 – 30 seconds via pot # 4.
Re-activate the card reader, and within the time frame, press the exterior switch. The door should now open.
Page 3 of 19
Input
Relay
Page 4
Wire MOV
(supplied)
directly to strike
or magnet
MOV
RELAY 5 CHART
To have Relay 5 shadow another
relay, set dipswitch
as s hown at right
Electric Strike
(If Fail-Secure lock
Door
Operator
LOCKED
OUT
Optional and only if
Panic switch is utilized
Dip4Dip
5
OFF OFF
OFF
ON
ON
OFF
ON ON
Fail-Safe
Shown
is used, wire to
Terminals 1 & 2)
Power
for Strike
=
1 2 3 4
12 - 24 V
AC/DC Power
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
12V 5V
Relay On Indicators
2345
1
Timer Settings
Relay 1
Relay 2
Digital
In/Out
terminal
strip
Inputs
Yellow / N/C
Brown / Blue
Relay 3
Relay 4
Relay 5
Simple M icro-switch
SCALE: NONE
LED Output
Ground 2
Output 2
Output 1
Power +5V
Ground 1
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6 5
4 3 2
1
type Card reader
DRAWN BY: DGW
Mag-stripe style
or
Card reader
Camden Door Controls
DATE: 03/24/10
!
N.C.
DAY
NITE
PUSH
TO OPEN
PUSH
TO OPEN
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED:
Emergency
Panic Switch
(optional)
Magnetic
Contact Switch
(only required
if Panic switch
is utilised)
Day / Night
Toggle or
Key switch
Inside
Wall Switch
Outside
Wall Switch
(optional)
EMF- 2 D iagram 2, Typical ABM Vestib ul e Application
DRAWING No: DRG -EMF-2_02
FILENAME: EMF-2 Diagram 2.vsd
Turn the Key switch (or other type switch) to “Day Mode”. If the strike is to be dogged back mechanically, then do so. If it is to be powered all day long, then confirm that it is powered and released.
Now both the interior and exterior switches will open the door when activated. The card-reader has no effect on operation (it has been electronically de­activated).
A new option on the EMF-2 is the provision for an emergency “Lock Down” switch to be added. This momentary contact switch only functions in night mode. This test will take two persons – one to depress the switch inside, and another person outside to confirm the card-reader input has been disabled. Opening the door from the inside (either manually or automatically) will reset the system (a N/C magnetic door contact switch is required).
Once the desired operation is achieved, proceed to Section 4, for System Inspection Instructions.
Section 3B________________ Set-up Instructions
Unsecured Restroom (Mode 2)
This application is a shared-use single (normally unlocked) restroom door in facilities such as nursing homes, hospitals, shopping malls, etc. The relay provides control of the lock, operator, and switches, to provide the utmost in flexibility, safety for the occupants, yet still be easy to install and program.
The door is opened automatically by pressing the exterior wall switch. Once the door has closed, pressing the “Push to Lock” button inside then locks the door – the strike is energized, and the exterior switch is removed from the circuit. To exit the restroom, simply push the interior wall switch. The door unlocks, opens and resets the system. Should the door be opened manually, the magnetic contact switch will reset the system.
Unique to the EMF-2 is the emergency input, which allows a panic button to unlock, open the door (optional), and send an emergency signal for assistance. The output can be maintained or pulsed. As an added safety feature, the EMF-2 can be set to automatically reset (and unlock) after 15 minutes time.
Step 1 Select
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
MODE 2 via the first 3 positions of the
Off On 1 2 3
IMPORTANT: Any changes Mode selector or settings must be made with power off!
Step 2 Dip switch Options
Push dipswitch #6 button to unlock the door and also open it. Leave switch #6 the door only but not open it.
Push dipswitch #7 out (reset) feature. Leave in OFF position if you do not want an automatic reset.
Use of Relay 5 is optional, and set according to dipswitches #4 & 5. (See diagram 1 for location). A common use in this mode would be to have Relay 5 follow the the lock relay and light an occupied sign. By default, Relay #5 follows Relay #1. Dipswitch # 8 is not used in this mode.
Step 3 Connections
Refer to Diagram 3 (next page) for the following connections.
Wire all input connections to the (removable)
terminal strip
connector if removed. Next, make your connections to the
(numbered 1 – 15). (Relay 3 is not used in this application). Re-insert connector.
The 7-pin 5V DC on Terminals 6 & 7 for lighting an “Occupied” LED. This output is present whenever the door is locked. Select output voltage using jumper as shown below:
OFF to enable the panic button to unlock
(numbered 1 - 14). Firmly re-insert
Digital I/O strip provides either 12V DC or
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
ON when you want the panic
ON, to enable the 15 minute time-
Relay Output strip
12V 5V
LED Output
Page 5 of 19
Out2
Input
Page 6
Wire MOV
(supplied)
directly to strike
or magnet
MOV
Assistance
Door
Operator
Required !
Optional
Fail-Safe
Electric Strike
Shown
(If Fail-Secure lock
is used, wire to
Terminals 1 & 2)
Power
for Strike
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
Relay On Indicators
1
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
12V 5V
LED Output
2345
Timer Settings
Inputs
Occupied
Signal
(LED only)
Digital I/O
terminal
strip
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6 5
4 3 2
1
PUSH
TO
LOCK
N.C.
!
PUSH
TO OPEN
PUSH
TO OPEN
Inside
Push to Lock
Switch
Magnetic
Contact
Switch
Panic switch
(optional)
Inside
Wall Switch
Outside
Wall Switch
OCCUPIED
Optional
RELAY 5 CHART
To have Relay 5
shadow another
relay, set dipswitch
as shown at right
Dip4Dip
OFF OFF
OFF
ON
ON
OFF
ON ON
Occupied
LED
(optional)
12 - 24 V
AC/DC
=
5
1 2 3 4
Power
SCALE: NONE
EMF-2 Diagram 3, Single Door Restroom Application (unsecured)
DRAWING No: DRG -EMF-2_03
Camden Door Controls
DRAWN BY: DGW
DATE: 03/24/10
FILENAME: EMF-2 Diagram 3.vsd
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED: 06/08/10
Step 4 Adjustments
g
In this application, you will use pots 2 – 5. Pot #1 has no effect.
Timer 2 Operator Delay-on-activate Timer 3 Operator Delay-on-release Timer 4 Panic Relay (#4) ON time Timer 5 Panic Relay (#4) OFF time Note: If pot 5 is turned to zero, relay will be on steady
Apply power to door operator, EMF-2, and all connected equipment (ie – strike, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
Press the exterior wall switch. If the restroom is unoccupied the door will open automatically. Pot #2 adjusts the door hold-open time (up to 30 seconds). If the restroom is occupied and the lock button has been pressed, then the door will not open.
After entering the restroom, push the Lock button. The EMF-2 will energize the electric lock and remove the exterior Push switch from the circuit.
To exit the Restroom, two options are available:
1. To have the door unlock and open automatically, push the interior Wall switch. This will also reset the EMF-2 for the next person to use.
2. Manual Use. The door may also be used manually. To exit the restroom, turn the (lever) handle and pull (push) the door open. The magnet switch resets the unit into standby mode.
Emergency Panic Switch (optional) Should an emergency occur, and assistance from the
outside is required, the occupant can push a button or ribbon switch to signal the EMF-2. When activated, the EMF-2 will unlock the door (and optionally open the door). A maintaining type input is required to keep the door held open.
Further, Relay #4 is now activated, which can be used to signal for assistance, sound an alarm – whatever you choose. The installer can choose a continuous or pulsing output, depending on the settings of potentiometers # 4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is the ability to automatically reset to standby mode after a fixed lock time of 15 minutes. The door will unlock, so that personnel may enter the restroom. This feature is engaged by turning dipswitch # 7 to If not desired, simply leave dipswitch 7
ON position.
OFF.
Section 3C________________ Set-up Instructions
Secured Restroom (Mode 3)
This application is a shared-use single (normally locked) restroom door in facilities such as nursing homes, hospitals, shopping malls, etc. The relay provides control of the lock, operator, and switches, to provide the utmost in facility security, safety for the occupants, yet still be easy to install and program.
In this application the door is normally locked whether occupied or not. It may be unlocked by Key-switch, keypad, or another credential. The EMF-2 can be configured to activate the door operator immediately, or after pressing the wall-switch within the (adjustable) time period. Once the door has closed, pressing the “Push to Lock” button removes the exterior keypad / key-switch from the circuit. The electric lock will pulse twice to let the user know that the door is secure, and an output is available to light an Occupied LED (s).
To exit the restroom, simply push the interior wall switch. The door unlocks, opens and resets the system. Should the door be opened manually, the magnetic contact switch will reset the system.
Unique to the EMF-2 is the emergency input, which allows a panic button to unlock, open the door (optional), and send an emergency signal for assistance. The output can be maintained or pulsed. As an added safety feature, the EMF-2 can be set to automatically reset (and unlock) after 15 minutes time.
Step 1 Select
switch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
MODE 3 via the first 3 positions of the dip
Off On 1 2 3
IMPORTANT: Any changes Mode selector or settings must be made with power off!
e 7 of 19
Pa
Out2
Page 8
Wire MOV
(supplied)
directly to strike
or magnet
MOV
Assistance
Door
Operator
Required !
Optional
OCCUPIED
Fail-Safe
Electric Strike
Shown
(If Fail-Secure lock
is used, wire to
Terminals 1 & 2)
Power
for Strike
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
Relay On Indicators
1
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Digital
In/Out
terminal
strip
12V 5V
LED Output
2345
Timer Settings
Inputs
Occupied
Signal
(LED only)
Output
Power +5V
Ground
7
6
5
4
3
2
1
N/C
Input
ON
14 13 12 11 10
9 8 7 6 5 4 3 2 1
7 6 5
4 3 2
1
Keypad, or
Card-reader
123 456 789
C
PUSH
TO
LOCK
N.C.
!
PUSH
TO OPEN
PUSH
TO OPEN
Inside
Push to Lock
Switch
Magnetic
Contact
Switch
Panic switch
(optional)
Inside
Wall Switch
Outside
Wall Switch
(optional)
Occupied
LED
(optional)
Optional
RELAY 5 CHART
To have Relay 5
shadow another
relay, set dipswitch
as shown at right
Dip4Dip
OFF OFF
OFF
ON
ON
OFF
ON ON
12 - 24 V
AC/DC
=
5
1 2 3 4
Power
SCALE: NONE
EMF-2 Diagram 4, Single Door Restroom Application (secured)
DRAWING No: DRG -EMF-2_04
Camden Door Controls
DRAWN BY: DGW
DATE: 03/24/10
FILENAME: EMF-2 Diagram 4.vsd
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED: 06/08/10
Step 2 Dip switch Options
Use of Relay 5 is optional, and set according to dipswitches #4 & 5.
Push dipswitch #6 button to unlock the door and also open it. Leave switch #6 the door only but not open it.
Push dipswitch #7 out (reset) feature. Leave in not want an automatic reset.
Dip switch # 8 can have the keypad unlock and open the door (
ON, then an exterior wall-switch is required to open
the door automatically.
Step 3 Connections
Refer to Diagram 4 (previous page) for the following connections.
Wire all input connections to the (removable)
terminal strip (numbered 1 - 14). Firmly re-insert
connector if removed. Next, make your connections to the r
(numbered 1 – 15). (Relay 3 is not used in this application). Re-insert connector.
The 7-pin 5V DC on Terminals 6 & 7 for lighting an “Occupied” LED. This output is present whenever the “Push-to­Lock” switch has been pressed. Select output voltage using jumper as shown below:
Wire the keypad, key-switch or other secure device to terminals 1 & 2 of this terminal strip.
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots 1 – 5. Timer 1 Strike Delay-on-release
Timer 2 Operator Delay-on-activate Timer 3 Operator Delay-on-release Timer 4 Panic Relay (#4) ON time Timer 5 Panic Relay (#4) OFF time Note: If pot 5 is turned to zero, relay will be on steady
Apply power to door operator, EMF-2, and all connected equipment (ie – strike, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or
OFF to enable the Panic button to unlock
OFF) or just unlock the door (ON). If set to
Digital I/O strip provides either 12V DC or
ON when you want the panic
ON, to enable the 15 minute time-
OFF position if you do
Input
elay output strip
12V 5V
LED Output
terminal strip connection. Enter keypad, key-switch or other credential to
activate EMF-2. Depending on dipswitch #8, the door will unlock and open or just unlock. If required press the exterior wall switch. Pot #1 adjusts the lock hold time. Pot #2 adjusts the door hold-open time (up to 30 seconds). (If the restroom is occupied and the Lock button has been pressed, then the door will not unlock or open).
After entering the restroom, push the Lock button. The EMF-2 will (de)energize the electric lock momentarily to let the occupant know the door is secure, and remove the exterior inputs from the circuit.
To exit the Restroom, two options are available:
1. To have the door unlock and open automatically, push the interior Wall switch. This will also reset the EMF-2 for the next person to use.
2. Manual Use. The door may also be used manually. To exit the restroom, turn the (lever) handle and pull (push) the door open. The magnet switch resets the unit into standby mode.
Emergency Panic Switch (optional) Should an emergency occur, and assistance from the
outside is required, the occupant can push a button or ribbon switch to signal the EMF-2. When activated, the EMF-2 will unlock the door (and optionally open the door). A maintaining type input is required to keep the door held open.
Further, Relay #4 is now activated, which can be used to signal for assistance, sound an alarm – whatever you choose. The installer can choose a continuous or pulsing output, depending on the settings of potentiometers # 4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is the ability to automatically reset to standby mode after a fixed lock time of 15 minutes. The door will unlock, so that personnel may enter the restroom. This feature is engaged by turning dipswitch # 7 to If not desired, simply leave dipswitch 7
ON position.
OFF.
Page 9 of 19
Page 10
Door #1 Lock
Fail-Safe
Electric Strikes
Shown
(If Fail-Secure locks
are used, wire to Terminals 1 & 2)
Door #1
Operator
Door #2
Operator
Assistance
Required !
Optional
Door #2 Lock
Power for Locks
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
Relay On Indicators
1
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Digital
In/Out
terminal
12V 5V
LED Output
2345
Timer Settings
Inputs
Occupied
Signal
(LED only)
strip
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6 5
4 3 2
1
Magnetic Contact Switch
on both doors. Wire in series.
N.C.
PUSH
TO
LOCK
PUSH
TO OPEN
PUSH
TO OPEN
!
PUSH
TO OPEN
Inside
Push to Lock
Switch
If 2 are used
then wire
in parallel
Inside
Wall Switch
Door #2
Outside
Wall Switch
Door #2
Panic sw itch
(optional)
Inside
Wall Switch
Door #1
RELAY 5 CHART
To have Relay 5
shadow another
relay, set dipswitch
as shown at right
Dip4Dip
OFF OFF
OFF
ON
ON
OFF
ON ON
Occupied
LED’s
(optional)
12 - 24 V
AC/DC
=
5
1 2 3 4
Power
SCALE: NONE
EMF-2 Diagram 5, 2 Door (shared) Restroom Application
DRAWING No: DRG -EMF-2_05
Camden Door Controls
DRAWN BY: DGW
DATE: 03/24/10
FILENAME: EMF-2 Diagram 5.vsd
PUSH
TO OPEN
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED: 06/08/10
Outside
Wall Switch
Door #1
Section 3D________________ Set-up Instructions
2-Door Restroom (Mode 4)
This application is a shared-use (normally unlocked) restroom between two suites (and therefore utilizing two doors), in facilities such as nursing homes & hospitals, etc. The relay provides control of both locks, operators, and all switches, to provide the utmost in flexibility, safety for the occupants, yet still be easy to install and program.
Either door is opened automatically by pressing the respective exterior wall switch. Once the door has closed, pressing either “Push to Lock” button inside then locks both doors – the strike is energized, and exterior switches are removed from the circuit. To exit the restroom, simply push either interior wall switch. The respective door unlocks, opens and resets the system. Should either door be opened manually, the magnetic contact switch will reset the system.
Unique to the EMF-2 is the emergency input, which allows a panic button to unlock, open (one or both) door(s), (optional), and send an emergency signal for assistance. The output can be maintained or pulsed. As an added safety feature, the EMF-2 can be set to automatically reset (and unlock) after 15 minutes time.
It is strongly encouraged to utilize the dry contact output (Relay #5) or the LED output to indicate “Occupied” on the exterior of both doors to let others know the restroom is in use.
Step 1 Select
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
Step 2 Dip switch Options
Leave switch #6 unlock the door only, but not open it. Put dipswitch #6 door and also open it. Furthermore, if dipswitch #6 is set to
MODE 4 via the first 3 positions of the
Off On 1 2 3
IMPORTANT: Any changes Mode selector or settings must be made with power off!
OFF to enable the panic button to
ON when you want the panic button to unlock the
ON, and dipswitch # 8 is set to OFF, then only
Out2
the last door used will open. Setting dipswitch #8 ON, will open both doors simultaneously.
Push dipswitch #7 out (reset) feature. Leave in not want an automatic reset.
Use of Relay 5 is optional, and set according to dipswitches #4 & 5. (See diagram 1 for location). A common use in this mode would be to have Relay 5 follow the lock relay and light an occupied sign. It could also be utilized for the second door lock, rather than connecting both door locks to Relay #1 output. By default, Relay #5 follows Relay #1.
Step 3 Connections
Refer to Diagram 5 (page 10) for the following connections.
Wire all input connections to the (removable)
terminal strip (numbered 1 - 14). Firmly re-insert
connector if removed. Next, make your connections to the
(numbered 1 – 15). Both door locks may be connected to relay #1 or, wire one lock to Relay #1 and the other to Relay #5. Re-insert connector.
ON, to enable the 15 minute Time-
OFF position if you do
Input
relay output strip
The 7-pin 5V DC on Terminals 6 & 7 for lighting “Occupied” LED’s. This output is present whenever the door is locked. Select output voltage using jumper as shown below:
Digital I/O strip provides either 12V DC or
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots 2 – 5. Pot #1 has no effect.
Timer 2 Operator Delay-on-activate Timer 3 Operator Delay-on-release Timer 4 Panic Relay (#4) ON time Timer 5 Panic Relay (#4) OFF time Note: If pot 5 is turned to zero, relay will be on steady
Apply power to door operators, EMF-2, and all connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
12V 5V
LED Output
Page 11 of 19
Page 12
Door A
Operator
Operator
Operator
RELAY 5 CHART
To have Relay 5 shadow another
relay, set dipswitch
as shown at right
Door B
Door C
Dip4Dip
OFF OFF
ON
OFF
ON
OFF
ON ON
Power
Off / On
1
Mode
2
3 4
Rel 5
5
6
Opt
7 8
NC
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
1
=
5
1
2 3
4
2
EMF-2
C NO NC
C NO NC
C NO NC
C NO NC
C NO
12/24V Power
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
12V 5V
LED Output
Relay On Indicators
2345
1
Timer Settings
Inputs
Digital
In/Out
terminal
strip
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6 5
4 3 2
1
Input 7 will cause
all doors to lock
immediately
LOCK
OFF
Trouble
Trouble output after 5
minutes of door ajar.
Select 5V or 12V output
with jumper
PUSH
TO OPEN
PUSH
TO OPEN
PUSH
TO OPEN
N.C.
N.C.
N.C.
Contact
C
Door
Contact
B
Door
Contact
A
Door C
Switch
Door B Switch
Door A Switch
12 - 24 V
Door
AC/DC Power
Camden Door Controls
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
SCALE: NONE
DRAWN BY: DGW
EMF-2 Diagram 6, 2 - 3 Door Airlock Application
DRAWING No: DRG -EMF-2_06
DATE: 03/24/10
REVISED:
FILENAME: EMF-2 Diagram 6.vsd
Press the exterior wall switch at door #1. If the restroom is unoccupied the door will open automatically. Pot #2 adjusts the door hold-open time (up to 30 seconds). If the restroom is occupied and the Lock button has been pressed, then the door will not open. (An Occupied light would be lit.)
After entering the restroom, push the nearest Lock button. The EMF-2 will energize both electric locks and remove both exterior Push switches from the circuit.
To exit the Restroom, two options are available:
1. To have the door unlock and open automatically, push the respective interior Wall switch. This will also reset the EMF-2 for the next person to use.
2. Manual Use. The door may also be used manually. To exit the restroom, turn the (lever) handle and pull (push) the door open. The magnet switch resets the unit into standby mode. The Occupied lights / LED’s will extinguish.
Repeat the above procedure door #2. It should function exactly as above.
Emergency Panic Switch (optional) Should an emergency occur, and assistance from the
outside is required, the occupant can push a button or ribbon switch to signal the EMF-2 (input #3). When activated, the EMF-2 will unlock the door (and optionally open the door). A maintaining type input is required to keep the door held open.
Based on the settings of Dipswitch #’s 6 & 8 either the doors will unlock only, or the last door used will open, or, both doors will unlock and open simultaneously.
Further, Relay #4 is now activated, which can be used to signal for assistance, sound an alarm – whatever you choose. The installer can choose a continuous or pulsing output, depending on the settings of potentiometers # 4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is the ability to automatically reset to standby mode after a fixed lock time of 15 minutes. The door will unlock, so that personnel may enter the restroom. This feature is engaged by turning dipswitch # 7 to If not desired, simply leave dipswitch 7 OFF.
ON position.
Section 3E________________ Set-up Instructions
2 / 3 door Airlock (Mode 5)
This function is designed to control up to 3 sets of sliding, or swinging doors. The relay will allow only 1 door to be open at a time.
It accomplishes this by a Door Sense input, such as a magnetic contact switch, located at each door. If the Door Sense determines that a door is open, then it will not allow a second door to open, but remembers the request to open and allows it once the first door has closed.
For 2-door airlocks, the installer can set up “Auto­crossing” whereby after triggering one door, the second door will activate after the first door closes. (This is also known as bi-directional door sequencing).
Should a door become stuck open, a Trouble signal is output after 5 minutes. The EMF-2 also includes a “Lock-down” input that resets the system and/or disables all “Open” requests.
Step 1 Select
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
Step 2 Dip Switch Options
Use of Relay 5 is optional, and set according to dipswitches #4 & 5.
Push switch #6 sequencing). In this Mode when input A is activated, first door A opens, then when closed again, door B opens in sequence. Conversely, when input B is activated, first door B opens, then when it is closed again, door A opens sequentially. A third door cannot be used in “Auto-Mode”. Selecting this mode disables door C input and contact input.
Set dipswitch #7 only, or set to effect in this mode.
MODE 5 via the first 3 positions of the
Off On 1 2 3
ON for “Auto Mode” (door
ON for airlocks containing 2 doors
OFF for 3 doors. Dipswitch #8 has no
Page 13 of 19
Page 14
Door 1 Contact
Door 2 Contact Door 3 Contact
Power
for Strike
Power
for Strike
Power
for Strike
Power
for Strike
Power
for Strike
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
Relay On Indicators
1
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
12V 5V
LED Output
2345
Timer Settings
Inputs
Digital
In/Out
terminal
strip
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6
5 4
3 2
1
Clear Trouble
Switch
Trouble
N.C.
Door 4 Contact Door 5 Contact
N.C.
N.C.
PUSH
TO UNLOCK
PUSH
TO UNLOCK
PUSH
TO UNLOCK
PUSH
TO UNLOCK
N.C.
N.C.
Door 5 Switch
Door 4 Switch
Door 3
Switch
Door 2
Switch
12 - 24 V
AC/DC Power
SCALE: NONE
DRAWN BY: DGW
EMF-2 Diagram 7, 2 - 5 Door Airlock Application
DRAWING No: DRG -EMF-2_07
Trouble output after 5
minutes of door ajar.
Select 5V or 12V output
with jumper
Camden Door Controls
DATE: 03/24/10
FILENAME: EMF-2 Diagram 7.vsd
PUSH
TO UNLOCK
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED:
Door 1
Switch
j
IMPORTANT: Any changes to Dip switches,
umpers, and Mode selector settings must be made
with power off!
Step 3 Connections
Refer to Diagram 6 (page 12) for the following connections.
Wire all input connections to the (removable)
terminal strip
connector if removed.
NOTE: Concerning Magnetic contact switches.
This system wants to see a Normally Closed connection when the door is closed. The contact will then open when the door opens. Any other configuration will cause the relay to malfunction. We suggest standard door contacts (ie - Camden Model # CX-MDC)
Next, make your connections to the (numbered 1 – 15).
The 7-pin pins 6 & 7 after 5 minutes of door ajar.
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots 1 – 3 & 5. Pot 4 is not used in this mode.
Timer 1 Door A delay-on-release Timer 2 Door B delay-on-release Timer 3 Door C delay-on-release Timer 4 Not used Timer 5 Timer for clearing “walk-aways”
Apply power to door operators, EMF-2, and all connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
Activate an input device to one of the doors. Observe the respective output LED, which should light immediately. The door should unlock and/or open.
If a request to open comes in from another door while the first is still open, it will retain the call in memory until the Door Sense switch indicates the first has closed. If there is a succeeding request on the first door (or the door that is already opened) it will keep that door opened.
(numbered 1 - 14). Firmly re-insert
relay output strip
Digital I/O strip provides a trouble output on
Input
If automatic sequential operation between doors A and B is desired, then put dipswitch #6 into ON position. Otherwise, for normal operation, leave this dipswitch off.
Potentiometer #5 is useful if the application utilizes locks only, and not automatic door operators. Should a person approach a door and request the door to unlock, but then change his/her mind and “walk­away”, pot #5 can be set to ignore that request after an adjustable time. Typically this time would be set at or close to minimum. For automatic door applications it could be set higher (10 – 15 seconds.)
Switch closure on Input #7 will cause all doors to lock immediately, regardless of pending “open” requests.
Once the desired operation is achieved, proceed to Section 4, System Inspection Instructions.
Section 3F________________ Set-up Instructions
2 - 5 door Airlock (Mode 6)
This function is designed to control up to 5 sets of sliding, or swinging doors. The relay will allow only 1 door to be open at a time.
It accomplishes this by a Door Sense input, such as a magnetic contact switch, located at each door. If the Door Sense determines that a door is open, then it will not allow a second door to open, but remembers the request to open and allows it once the first door has closed.
Should a door become stuck open, a Trouble signal is output after 5 minutes, and may be reset with Input #7.
Step 1 Select
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
Step 2 Dip Switch Options
There are no dip switch options with this mode. Since all door contacts are wired in series and
connected to Input #6, the unit does not care if less than 5 doors are used.
MODE 6 via the first 3 positions of the
Off On 1 2 3
Page 15 of 19
Page 16
Lock Down switch disables both door Inputs
Magnetic Contact Switch
Door #2
N.C.
PUSH
TO OPEN
Wall Switch
Door #2
Card Reader
Door #2
N.C.
PUSH
TO OPEN
Wall Switch
Door #1
Inside
Magnetic
Contact
Switch
Door #1
Inside
Fail-Secure
Electric Strikes
Shown
(If Fail-Safe locks are used,
wire to Terminals 1 & 2, and 7 & 8)
Door #1
Operator
Door #2 Lock
Door #2
Operator
Door #1 Lock
Power for Lock
Power for Lock
Mode
Rel 5
Opt
Power
Off / On
1 2
3 4
5
6 7 8
NC
1
C
2
NO
3
NC
4
C
5
NO
6
NC
7
C
8
NO
9
NC
10
C
11
NO
12
NC
13
C
14
NO
15
1
12/24V Power
2
EMF-2
Relay On Indicators
1
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
Digital
In/Out
terminal
12V 5V
LED Output
2345
Timer Settings
Inputs
Trouble
Output
strip
Input disables Door #2
ON
14
7
13 12
6
11 10
5
9 8
4
7 6
3
5 4
2
3 2
1
1
7 6 5
4 3 2
1
DOWN
Trouble output after 5
minutes of door ajar.
Select 5V or 12V
output with jumper
LOCK
RELAY 5 CHART
To have Relay 5
shadow another
relay, set dipswitch
as shown at right
Dip4Dip
OFF OFF
OFF
ON
ON
OFF
ON ON
Normally Open input
will disable Door #2
Common device is a
specially constructed
electric switch mat.
=
5
1 2
3
4
12 - 24 V
AC/DC Power
SCALE: NONE
DRAWN BY: DGW
STEP
HERE
ONLY
Trouble
Camden Door Controls
DATE: 03/24/10
Card Reader
Door #1
5502 Timberlea Blvd Mississauga, Ontario L4W 2T7
REVISED: 05/04/11
EMF-2 Diagram 8, 2 Door Mantrap Appl ication
DRAWING No: DRG -EMF-2_08
FILENAME: EMF-2 Diagram 8.vsd
IMPORTANT: Any changes Mode selector or settings must be made with power off!
Step 3 Connections
Refer to Diagram 7 (page 14) for the following connections.
Wire all input connections to the (removable)
terminal strip
connector if removed.
NOTE: Concerning Magnetic contact switches.
This system wants to see a Normally Closed connection when the door is closed. The contact will then open when the door opens. Any other configuration will cause the relay to malfunction. We suggest standard door contacts (ie - Camden Model # CX-MDC). Wire all contacts in series as shown in the diagram.
Next, make your connections to the (numbered 1 – 15).
The 7-pin pins 6 & 7 after 5 minutes of door ajar.
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots 1 & 5. Pots 2 - 4 are not used in this mode.
Timer 1 All Doors delay-on-release Timer 2 Not used Timer 3 Not used Timer 4 Not used Timer 5 Timer for clearing “walk-aways”
Apply power to door operators, EMF-2, and all connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
Activate an input device to one of the doors. Observe the respective output LED, which should light immediately. The door should unlock and/or open.
If a request to open comes in from another door while the first is still open, it will retain the call in memory until the Door Sense switch indicates the first has closed. If there is a succeeding request on the first door (or the door that is already opened) it will keep that door opened.
(numbered 1 - 14). Firmly re-insert
relay output strip
Digital I/O strip provides a trouble output on
Out2
Input
Potentiometer #5 is useful if the application utilizes locks only, and not automatic door operators. Should a person approach a door and request the door to unlock, but then change his/her mind and “walk­away”, pot #5 can be set to ignore that request after an adjustable time. Typically this time would be set at or close to minimum. For automatic door applications it could be set higher (10 – 15 seconds.)
Once the desired operation is achieved, proceed to Section 4, System Inspection Instructions.
Section 3G________________ Set-up Instructions
2 door Mantrap (Mode 7)
This function is designed to control a 2-door mantrap with or without automatic door operators. The relay will allow only 1 door to be open at a time.
It accomplishes this by a Door Sense input, such as a magnetic contact switch, located at each door. If the Door Sense determines that a door is open, then it will not allow a second door to open, but remembers the request to open and allows it once the first door has closed. (The memory feature may be disabled)
An input is available for a contact mat on the floor to ensure that only one person is within the mantrap at any time.
Should a door become stuck open, a Trouble signal is output after 5 minutes,
Finally, a “Lock-down” input is available which immediately locks all doors and disables further egress/ingress.
Step 1 Select
dipswitch as shown below:
See diagram 1 for location of dipswitch, connectors, & potentiometers.
MODE 7 via the first 3 positions of the
Off On 1 2 3
Step 2 Dip Switch Options
Use of Relay 5 is optional, and set according to dipswitches #4 & 5.
Push switch #6 left
OFF, then the EMF-2 will remember a request to
open and open that door when the other door has re­closed and locked.
ON to disable the memory feature. If
Page 17 of 19
Dipswitches #7 & 8 are not used in this mode.
j
IMPORTANT: Any changes to Dip switches,
umpers, and Mode selector settings must be made
with power off!
Step 3 Connections
Refer to Diagram 8 (page 16) for the following connections.
Wire all input connections to the (removable)
terminal strip
connector if removed.
NOTE: Concerning Magnetic contact switches.
This system wants to see a Normally Closed connection when the door is closed. The contact will then open when the door opens. Any other configuration will cause the relay to malfunction. We suggest standard door contacts (ie - Camden Model # CX-MDC).
Next, make your connections to the (numbered 1 – 15).
The 7-pin pins 6 & 7 after 5 minutes of door ajar. If utilizing an electric floor mat, wire to pins 1 & 2. (This input should be normally open).
Finally, connect 12 or 24 Volt AC or DC supply to terminals 1 & 2 of the 2-pin Power Connector. (The terminals are not polarity sensitive).
Step 4 Adjustments
In this application, you will use pots 1 - 3 & 5. Pot 4 is not used in this mode.
Timer 1 Door lock delay-on-release Timer 2 Operator delay-on-activate Timer 3 Operator delay-on-release Timer 4 Not used Timer 5 Timer for clearing “walk-aways”
Apply power to door operators, EMF-2, and all connected equipment (ie – strikes, lights, etc). Observe the red Power LED on the unit, which should light. If not, re-confirm proper voltage and/or terminal strip connection.
Activate an input device to one of the doors. Observe the respective output LED, which should light immediately. The door should unlock and/or open.
If a request to open comes in from another door while the first is still open, it will retain the call in memory until the Door Sense switch indicates the first has
(numbered 1 - 14). Firmly re-insert
relay output strip
Digital I/O strip provides a trouble output on
Input
closed. If there is a succeeding request on the first door (or the door that is already opened) it will keep that door opened. This memory feature can be disabled by setting dipswitch #6
Potentiometer #5 is useful if the man-trap utilizes locks only, and not automatic door operators. Should a person approach a door and request the door to unlock, but then change his/her mind and “walk­away”, pot #5 can be set to ignore that request after an adjustable time. Typically this time would be set at or close to minimum. For automatic door applications it could be set higher (5 – 10 seconds.)
Once the desired operation is achieved, proceed to Section 4, System Inspection Instructions.
ON
Section 4 _________________ System Inspection Instructions
After the Installation and operational check of the system:
1. Place warning label on the door (as per ANSI A156.10 or A156.19 guidelines). This will advise the person entering the swing side zone that the door will move.
2. Instruct the owner on door system operation and how to test it. This should be checked on a daily basis.
3. Instruct the owner on what to do if the door or any of its components become damaged.
4. Strongly recommend to the owner that the complete entry be inspected twice a year as part of the service agreement.
Page 18 of 19
Section 5_________________ Technical Data
Models EMF-2 / EMF-2m / EMF-2ABM Size EMF-2 7” x 3” x 7/8”
EMF-2m & EMF-1ABM 12” x 7.5” x 3.75”
Mounting EMF-2 Double sided foam tape
or two #6 screws EMF-2m & EMF-2ABM 4 x Metal screws & anchors (provided)
Enclosure EMF-2 - Formed Plastic housing EMF-2m & EMF-2ABM
- Beige Metal Cabinet Firmware Version A1-001 Operating voltage 12 / 24 Volts, AC / DC Current Draw 150 mA nominal
500 mA maximum Response time 0.3 seconds Mode Selector Via 3 dip-switches Inputs 7 “dry” contacts,
1 Digital input Outputs 5 SPDT relays
1 Digital output Relay contact rating 3 amps @ 20 VDC Time Delays 5 pots, adjustable from
1 to 30 seconds (depending
on mode selected) Electrical Life 100,000 operations @ rated,
or 500,000 operations @ ½
rated capacity In addition to above, Model EMF-2 ABM includes a
lockable metal cabinet to house the relay. The cabinet is equipped with two lighted push-switches – on to turn the relay power on or off, and the other to control the
DAY / NITE function.
Section 6_________________ Warranty
Camden Door Controls guarantees the EMF-2 (or EMF-2m / EMF-2ABM) to be free from manufacturing defects for 3 years from date of sale. If during the first 3 years the CX-EMF-2 / EMF-2ABM) fails to perform correctly, it may be returned to our factory where it will be repaired or replaced (at our discretion) without charge. Except as stated herein, Camden extends no warranties expressed or implied regarding function, performance or service.
Call us toll-free at 1-877-226-3369
Questions?
Filename: CX-EMF-2 Instructions.doc Revision: 6/28/2012 4:02 PM
Page 19 of 19
Loading...