CAMBRIDGE M-SERIES Technical Manual

Page 1
M-SERIES
DRAW THRU
DIRECT GAS-FIRED
MAKE-UP AIR HEATERS
TECHNICAL MANUAL
mWARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property dam­age, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
FOR YOUR SAFETY
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
ASHRAE
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
Made in the USA
ASHRAE
90.1
COMPLIANT
COMPLIANT
®
®
M-TM1-0915
M110-M115 (3HP) REV. G
M115 (5HP) REV. H M118-M136 REV. C
M140 REV. A
Page 2
LIMITED WARRANTY
Cambridge Engineering, Inc. (“Manufacturer”) warrants its products (“the Products”) to be free from defects in material and workmanship. Manufacturer’s M-Series Products shall be warranted for a period of twenty-four (24) months from the date of shipment, except that burner assemblies are warranted for five (5) years from date of shipment.
Buyer’s sole and exclusive remedy for any nonconformity with this warranty shall be, at Manufacturer’s option, repair or replacement of nonconforming parts, provided that Buyer shall return to Manufacturer, shipping prepaid, said nonconforming part(s) bearing a durable tag indicating the Serial Number of the Product from which the part was taken. In addition, Manufacturer may opt not to repair or replace nonconforming Product or part(s), but instead may refund to Buyer the price thereof, in lieu of repair or replacement. In no event shall Manufacturer be liable for more than a refund of the purchase price or replacement value of the Product or part(s), whichever is less. This Warranty does not apply to field labor charges.
This Warranty does not apply and shall be void as to any Products that are misused or misapplied, that are installed, operated or maintained not in conformity with Manufacturer’s design, specifications, instruc­tions, or Technical Manual, or are installed, operated or maintained in violation of any applicable national or local codes or industry standards.
Manufacturer does not warrant Products if they are abused, improperly operated or maintained, subjected to abnormal wear and tear, damaged due to improper gas or electric service, damaged in transit, or that have been repaired or modified by others without Manufacturer’s written authorization.
Buyer shall have no right to enforce this Warranty unless it has complied with all of its obligations under the contract for purchase/lease of the Products, including without limitation being current on all payment terms.
THIS LIMITED WARRANTY IS MANUFACTURER’S ONLY WARRANTY WITH RESPECT TO THE PRODUCTS, AND IT IS IN LIEU OF AND SUPERSEDES ANY AND ALL OTHER WARRANTIES OF ANY KIND WHATSOEVER, WHETHER WRITTEN, ORAL OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THE REMEDIES AFFORDED BUYER BY THIS WARRANTY ARE THE ONLY REMEDIES AFFORDED BUYER FOR ANY NONCONFORMITY WITH THIS WARRANTY OR FOR ANY DEFECT IN PRODUCTS, SERVICES, OR REPRESENTATIONS PROVIDED BY MANUFACTURER IN CONNECTION WITH SUCH PRODUCTS. IN NO EVENT SHALL MANUFACTURER BEAR ANY LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION PERSONAL INJURY (INCLUDING DEATH), PROPERTY DAMAGE, LOST PROFITS OR OTHER ECONOMIC LOSS.
Buyer acknowledges that the foregoing warranty, limitations, and exclusions are a reasonable allocation of commercial risks by and among sophisticated business entities and are not subject to dispute as to their commercial reasonableness, fairness or ability to satisfy the essential purposes of the parties’ transaction.
Page 3
M-SERIES
TECHNICAL MANUAL
Contents
Hazard Summary .............................................................................................................. 2
Typical System Overview
Accessory Identication .................................................................................................. 4
Heater / Accessory Weights ............................................................................................5
Heater Operation ............................................................................................................. 6
Heater Conguration
Installation Instructions Uncrating Instructions Mounting Location
Horizontal Mount - Mounting Curb ................................................................................ 8
Horizontal Mount - Roof Top Conguration .................................................................. 9
Horizontal Mount - Outdoor Pad Mount Conguration ...............................................13
Horizontal Mount - Thru Wall Conguration ...............................................................16
Vertical Mount - Outdoor Conguration ....................................................................... 19
Vertical Mount - Indoor Conguration .........................................................................23
Gas Piping ..................................................................................................................... 26
Electrical .......................................................................................................................27
Start-Up Instructions ....................................................................................................... 28
Operating Instructions ..................................................................................................... 35
Operating Sequence ......................................................................................................35
Electronic Thermostat ................................................................................................... 36
TSS Controller ..............................................................................................................38
Maintenance Instructions ................................................................................................ 47
Reference ........................................................................................................................ 48
Heater Roof and Wall Openings ...................................................................................48
Heater Discharge Dimensions .......................................................................................48
Gas Train Drawings ......................................................................................................49
Electrical Control Enclosure Isometric Drawing ......................................................... 55
Electrical Wiring Diagrams ........................................................................................... 58
Connection Diagram ..................................................................................................... 64
Gas Control Systems ..................................................................................................... 65
Remote Control Station Components ........................................................................... 65
Individual Heater Component Descriptions .................................................................. 66
Damper Motor Replacement & Adjustment ................................................................. 70
Troubleshooting Guide..................................................................................................73
ANSI/ASHRAE/IESNA Standard 90.1 ..........................................................................79
Maintenance Log ............................................................................................................ 80
................................................................................................. 3
....................................................................................................... 6
..................................................................................................... 7
..........................................................................................................7
Copyright 2015 Cambridge Engineering, Inc. All Rights Reserved
Cambridge Engineering, Inc. 760 Long Road Crossing Dr.
Chesterfield, MO. 63005
Phone: (636) 532-2233, Fax: (636) 530-6133
www.cambridge-eng.com
Page 4
HAZARD SUMMARY
Hazard Identification
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
mWARNING: Indicates a potentially hazardous situation which could result in
death or serious injury.
mCAUTION: Indicates a potentially hazardous situation which may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION: Indicates a situation that may result in accidents with equipment or
property damage only.
The following safety precautions apply to the installa­tion, operation, and maintenance of the equipment described by this technical manual.
mWARNING:
Any unauthorized modification of this equipment shall void the warranty.
mWARNING:
Only qualified personnel should attempt instal­lation, service, and repair of this equipment. Use extreme caution and observe safety regulations at all times.
mWARNING:
Recirculation of room air is not permitted.
Adequate building relief shall be provided so as to not over-pressurize the building when the make-up air heat­ing system is operating at its rated capacity. It should be noted that this can be accomplished by taking into account, through standard engineering methods, the structure’s designed infiltration rate, by providing prop­erly sized relief openings, by interlocking a powered exhaust system, or by a combination of these methods.
when the heater is providing the make-up air to a boiler room), the heater is to be interlocked to open inlet air dampers or other such devices.
If the heater is installed such that an inlet duct is uti­lized, the duct system must be purged with at least four air changes prior to an ignition attempt.
IMPORTANT
Installation in Aircraft Hangars
Refer to the Standard for Aircraft Hangars, ANSI/ NFPA 409, for specific information on the installation requirements for these heaters in airplane hangars.
IMPORTANT
Installation in Parking Garages
Refer to the Standard for Parking Structures, ANSI/ NFPA 88A, or the Standard for Repair Garages, ANSI/ NFPA 88B, for specific information on the installation requirements for these heaters in public garages.
If in doubt regarding installation or application, contact Cambridge Engineering Customer Service Group at 800-473-4569 during the hours of 8:00 a.m. to 5:00 p.m. Central Time, Monday through Friday.
If the failure or malfunction of this heater creates a haz­ard to other fuel burning equipment in the building (e.g.
Cambridge Engineering, Inc. 2 M-Series Technical Manual
Page 5
TYPICAL SYSTEM OVERVIEW
CONTROL SYSTEMS: MAXITROL SERIES 14
The Maxitrol Series 14 electronic discharge temperature control system maintains a constant discharge tempera­ture. The standard control permits manual adjustment of discharge temperature (55° to 90°F) from inside the heater control enclosure. As an option, a Remote Heat Adjust control with override capability to 130°F can be provided to allow manual adjustment of discharge tem­perature (55° to 130°F) from either inside the heater con-
trol enclosure or in the Remote Control Station.
MAXITROL SERIES 14 WITH SPACE THERMOSTAT
The Maxitrol Series 14 modulation controls function as described above using the optional Remote Heat Adjust control in conjunction with an electronic space thermo­stat switch contact to increase discharge temperature. The discharge temperature will increase to a preset rise (0°F to 40°F) above the set point on the Remote Heat Adjust control face based on the setting of the override temperature dial, which is visible from the top of the control.
MAXITROL SERIES 44
The Maxitrol Series 44 modulation controls maintain a constant space temperature by increasing or decreas­ing the discharge temperature. The Space Temperature Selector is set to maintain the space temperature of the heated space by controlling the heater output between the MIN and MAX setting on the amplifier. The MIN dial setting determines the minimum discharge tempera­ture the heater will deliver (40°F to 80°F). The MAX dial setting determines the maximum discharge temperature the heater will deliver (80°F to 140°F).
MAXITROL SERIES 44 / TAMPER PROOF
The Maxitrol Series 44 / Tamper Proof temperature control system is similar to the Maxitrol Series 44 con­trols above except the adjustable Space Temperature Selector control is replaced by two other controls. The adjustable portion of the temperature selector is typically mounted in the Remote Control Station to prevent unwanted tampering of the temperature setting and the non-adjustable space sensor is mounted in the space being heated.
M-Series Technical Manual 3 Cambridge Engineering, Inc.
Page 6
TYPICAL SYSTEM OVERVIEW
FLOOR
ACCESSORY IDENTIFICATION
Horizontal Mount
Roof Top Configuration
Horizontal Mount
Thru Wall Configuration
(Not applicable to M140)
Horizontal Mount
Outdoor Pad Mount Configuration
Component Identification
DD Discharge Duct DE Discharge Elbow DP Discharge Plenum DRH Dual Rainhood w/ Inlet Screen & Filter Rack FS Filter Section V-Bank FSID V-Bank Filter Section/Inlet Damper Combo HBDD Horizontal Blast Discharge Diffuser IC Inlet Collar IE Inlet Elbow MC Mounting Curb MDD Motorized Discharge Damper MID Motorized Inlet Damper ML Mounting Legs SRH Single Rainhood w/ Inlet Screen
Vertical Mount
Outdoor Configuration
Cambridge Engineering, Inc. 4 M-Series Technical Manual
UNIT
FSID
Vertical Mount
Indoor Configuration
DP
IE
ML
IC
DRH
FLASHING & TRIM BY OTHERS
Page 7
HEATER / ACCESSORY WEIGHTS
Horizontal Mount (Weights Shown In Pounds)
Model M110 M112 M115
Base Heater
Rain Hood - Single
Rain Hood - Dual, Upper
Rain Hood - Dual, Lower
Filters for Rain Hood
Inlet Screen
Inlet Collar
Inlet Damper (internal)
V-Bank Filter Section
Discharge Duct - 20"
425 440 550 1125 1395 2045 2475 2845 5345*
45 45 70 135 175 275 325 375 N/A
N/A N/A N/A 95 145 240 270 325 480
N/A N/A N/A 75 105 170 205 280 410
10 10 15 20 30 45 60 80 90
5 5 10 10 15 25 35 40 45
40 40 50 85 110 170 200 230 335
25 25 35 55 65 125 155 210 290
70 70 100 215 235 285 400 500
M118 M120 M125 M130 M136 M140
**
Discharge Duct - 50"
Discharge Duct - 72"
Discharge Damper (internal)
Discharge Plenum 4-way
Discharge Plenum 3-way
Discharge Splash Pan
Curb 14"
Curb 24"
60 70 80 90 120 140 160 180 200
70 85 95 125 150 180 220 250 280
N/A N/A N/A 30 30 35 45 55 75
100 150 200 250 300 400 470 930 1480
80 130 175 220 260 360 430 500 795
40 40 40 60 60 60 80 80 80
60 70 80 100 120 180 210 230 270
100 120 140 170 200 270 310 340 445
*Due to shipping constraints the M140 consists of a of blower module (3625 lbs.) and burner module (1720 lbs.) **Consult Factory
Vertical Mount (Weights Shown In Pounds)
Model
Base Heater
Rain Hood - Single
Rain Hood - Dual, Upper
Rain Hood - Dual, Lower
Filters for Rain Hood
Inlet Collar
Inlet Elbow
Inlet Damper
V-Bank Filter Section
Filter Section/Inlet Damper Combo
Discharge Duct - 20"
Discharge Duct - 50"
Discharge Duct - 72"
Discharge Damper (internal)
Discharge Elbow
Discharge Plenum 3-way w/enclosure
Discharge Diffuser
Mounting Legs 3-foot, set of 4
Mounting Legs 5-foot, set of 4
M118 M120 M125 M130 M136
1800 2300 2900 3200 3600
105 165 285 395 485
80 120 210 290 345
55 90 150 210 275
20 30 45 60 80
80 110 170 200 230
450 500 780 1040 1175
305 345 400 475 490
280 380 420 555 715
470 600 670 860 920
90 120 140 160 180
125 150 180 220 250
35 35 40 60 75
95 120 170 230 340
280 320 420 510 580
210 230 280 310 350
250 250 250 250 250
400 400 400 400 400
M-Series Technical Manual 5 Cambridge Engineering, Inc.
Page 8
TYPICAL SYSTEM OVERVIEW
HEATER OPERATION
Cambridge M-Series Draw-Thru heaters provide fresh air ventilation to a facility, provide tempered air to replace the air that is mechanically exhausted, or address cold drafts from natural infiltration. Heater operation is typically electrically interlocked with mechanical exhaust fans, manually operated switches,
HEATER CONFIGURATION
programmable timers, or other process control sys­tems. The discharge temperature of heaters with fixed discharge temperature controls is typically set 10°F to 20°F above the desired space temperature. The enter­ing air thermostat acts as an economizer by deactivat­ing burner operation during mild weather.
Cambridge Engineering, Inc. 6 M-Series Technical Manual
Page 9
INSTALLATION INSTRUCTIONS UNCRATING INSTRUCTIONS
1. Verify the number of items on the Bill of Lading versus the number of items received.
IMPORTANT
Field constructed intake accessories should be de­signed to minimize the entry of snow and rain.
2. Check for shipping damage. If damage is found, immediately file a claim with carrier before proceeding further.
3. Check items received to make sure they agree with ordering information including verification of data on the make-up air heater nameplate.
IMPORTANT
Do not discard any components or accessories.
MOUNTING LOCATION
Verify feasibility of the installation location selected with respect to accessibility to the heater for service and maintenance functions. Ensure the positioning of the heater does not inhibit fork truck operation, stor­age rack access, or other operations within the facility. Ensure the heater inlet and outlet are not blocked or severely restricted, such that it would affect the rated airflow through the heater or affect the desired air dis­tribution pattern of the heater. If upon review of the proposed installation, a problem is discovered which may be considered detrimental to the performance of the heater, or restricts its serviceability, or deviates from the instructions or drawings which may be provided, it is the responsibility of the installer to communicate that information to the person or persons responsible for pro­viding the installation instructions or drawings prior to proceeding with the installation.
IMPORTANT
Minimum clearance from the face of the electrical con­trol enclosure to surrounding grounded surfaces for service activities is 42". Adequate clearance for burner removal is also required, which is based on 42" or the length of the burner + 12", whichever is greater. Access for service functions is also required on the op­posite side of the make-up air heater from the control enclosure for a distance of 24".
mWARNING:
Where the mounting height of the heater is required to be above 15 feet, work platforms or service lifts should be provided for accessibil­ity to the equipment for service and maintenance activities.
M-Series Technical Manual 7 Cambridge Engineering, Inc.
Page 10
INSTALLATION INSTRUCTIONS
HORIZONTAL MOUNT - MOUNTING CURB M110 - M136
(Shown for Roof Top Configuration - Downblast Application)
Cambridge Engineering, Inc. 8 M-Series Technical Manual
Model A B C
M110 M112 M115 M118 M120 M125 M130 M136
32.38" 27.12" 48"
32.38" 27.12" 48"
32.38" 40.31" 60"
32.38" 44.10" 60"
32.38" 50.26" 72"
37.88" 63.12" 84"
37.63" 84.81" 96"
37.88" 84.81" 96"
Page 11
INSTALLATION INSTRUCTIONS
HORIZONTAL MOUNT - ROOF TOP CONFIGURATION
mWARNING:
Due to the size and weight of this equipment, it is recommended that the heater support structure be reviewed and approved by a qualified structural engi­neer and the roof manufacturer before installing this equipment.
IMPORTANT
Before proceeding with the installation, verify the fea­sibility of the location selected with respect to acces­sibility to the equipment for service and maintenance functions.
IMPORTANT
To minimize snow and rain ingestion, position the heat­er inlet opposite the prevailing wind.
mCAUTION:
To prevent contaminated air from being drawn into the heater, install the heater’s inlet at least 10 feet from any building exhaust, process exhaust, sewer stacks, or other sources that would allow contami­nants to be drawn into the heater. Consult local codes for applicable building code provisions for ventilation air.
IMPORTANT
For model M140 heaters, refer to the “Field Assembly Instructions” worksheets included with this manual for detailed heater assembly directions.
IMPORTANT
The roof curb or support structure should be in­stalled such that the heater will sit level. Cambridge Engineering recommends mounting the heater 24" off the roof surface in areas where snow accumulation could impact heater operation.
3. Lower the discharge duct through the roof opening.
4. Install the roof curb gasket.
5. Use a crane or comparable lifting device to raise and position the equipment. Block the heater where necessary. Use a spreader bar to prevent damage and connect slings to the lifting eyes.
6. Caulk all joints of the heater’s accessories installed in the field. Use a clear or gray latex based polyure­thane caulking to prevent water leaks.
7. Seal all roof penetrations to prevent roof leaks.
8. Install the discharge plenum, where used, by screw­ing the plenum to the discharge duct. Install 4 hang­ing rods from the ceiling supports to the plenum’s support brackets.
1. Prepare the roof for installation. (See pages 10-12 for roof opening dimensions for your specific heater.) The gas and electrical connections must not penetrate the unit base or mounting curb. Cambridge Engineering recommends using pitch pockets or decktite to seal the penetrations.
IMPORTANT
Accurate measurements are critical and will affect in­stallation process.
2. Assemble and secure the roof curb to the support structure per the recommendations of the structural engineer and roof manufacturer.
M-Series Technical Manual 9 Cambridge Engineering, Inc.
Page 12
TYPICAL INSTALLATION
HORIZONTAL MOUNT - ROOF TOP CONFIGURATION M110 - M115
Roof Opening
Model W L
M110
M112
M115
19.25" 19.25"
20.75" 20.75"
23.5" 23.75"
Cambridge Engineering, Inc. 10 M-Series Technical Manual
Typical Curb and Discharge Duct
Typical Curb and
Discharge Duct
Page 13
TYPICAL INSTALLATION
HORIZONTAL MOUNT - ROOF TOP CONFIGURATION M118 - M136
GAS CONTROL
ENCLOSURE
RAINHOOD
LIFTING EYES
MOUNTING
CURB
DISCHARGE
HANGING BRACKET
DUCT
DISCHARGE PLENUM
INCOMING POWER
CONTROL WIRING CONDUIT
7-9 WIRES REQ'D
(BY OTHERS)
HIGH PRESSURE SUPPLY TAP
HIGH PRESSURE REGULATOR (HPR)
SEDIMENT TRAP (BY OTHERS)
RCS
ELECTRICAL CONTROL ENCLOSURE
VENT PIPE
(BY OTHERS)
VENT w/ SCREEN (LOCATE MIN. 10 FT FROM INTAKE)
INLET GAS PIPE
HIGH PRESSURE SHUT-OFF VALVE
HPR
(OPTION)
Roof Opening
Model W L
M118
M120
M125
M130
M136
26.5" 26.5"
30.5" 30.5"
36" 36"
42" 42"
48" 48"
M-Series Technical Manual 11 Cambridge Engineering, Inc.
Typical Curb and
Discharge Duct
Page 14
TYPICAL ROOF TOP INSTALLATION
TYPICAL INSTALLATION
HORIZONTAL MOUNT - ROOF TOP CONFIGURATION M140
Lift Eyes
Rainhoods
Gas Control Enclosure
Vent Pipe (By Others)
Mounting Curb
Discharge Duct
Discharge Plenum
Hanger Bracket
Incoming Power
Control Wiring Conduit 7-9 Wires Req'd (By Others)
RCS
Typical Curb and
Typical Curb and
Discharge Duct
Discharge Duct
Vent w/ Screen (Locate Min 10 Ft from Intake)
Inlet Gas Pipe High Pressure Shut-off Valve High Pressure Supply Tap High Pressure Regulator (HPR)
Sediment Trap (By Others)
HPR (Option )
Roof Opening
Model W L
M140
55" 55"
Cambridge Engineering, Inc. 12 M-Series Technical Manual
Page 15
INSTALLATION INSTRUCTIONS
HORIZONTAL MOUNT - OUTDOOR PAD MOUNT CONFIGURATION
IMPORTANT
mWARNING:
Due to the size and weight of this equipment, it is recommended the heater support structure be reviewed and approved by a qualified structural engi­neer before installing this equipment.
IMPORTANT
Before proceeding with the installation, verify the fea­sibility of the location selected for accessibility to the equipment for service and maintenance functions.
IMPORTANT
To minimize snow and rain ingestion, position the
heater inlet opposite the prevailing wind.
mCAUTION:
To prevent contaminated air from being drawn into the heater, install the heater’s inlet at least 10 feet from any building exhaust, process exhaust, sewer stacks, or other sources that would allow contami­nants to be drawn into the heater. Consult local codes for applicable building code provisions for ventilation air.
Cambridge Engineering recommends mounting the heater a minimum of 24" off the mounting surface in areas where snow accumulation could impact heater operation.
4. Caulk all joints of the heater’s accessories installed in the field. Use a clear or gray latex based polyure­thane caulking to prevent water leaks.
5. Install the discharge duct through the wall opening.
6. Install fiberglass insulation in the gaps between the wall opening and discharge duct. Apply enough insulation material to accommodate the full thick­ness of the wall.
7. Install finish trim pieces (by others) to the top, sides and bottom of the discharge duct on both the inside and outside wall surfaces.
8. Apply a bead of latex based polyurethane caulk that best matches the color of the exterior wall surface of the facility and/or the color of the heater accessories at the joint between the top discharge duct and outside wall surface. Make certain this is a continuous bead and that it runs the entire width of the duct. Caulk all other exposed joints.
IMPORTANT
For model M140 heaters, refer to the “Field Assembly Instructions” worksheets included with this manual for detailed heater assembly directions.
1. Prepare the wall for installation. (See pages 14-15 for wall opening dimensions for your specific heater.)
IMPORTANT
Accurate measurements are critical and will affect in­stallation process.
2. Assemble and secure the support structure per the structural engineer’s recommendations.
IMPORTANT
The support structure should be installed such that the heater will sit level.
3. Use a crane or comparable lifting device to raise and position the equipment. Block the heater where necessary. Use a spreader bar to prevent damage and connect slings to the lifting brackets.
9. Install the discharge plenum, where used, by screw­ing the plenum to the discharge duct. Install hanging rods from the ceiling supports to the plenum’s sup­port brackets.
M-Series Technical Manual 13 Cambridge Engineering, Inc.
Page 16
TYPICAL INSTALLATION
HORIZONTAL MOUNT - OUTDOOR PAD MOUNT CONFIGURATION M118 - M136
Wall Opening
Model W L
M118
M120
M125
M130
M136
25.5" 25.5"
29.5" 29.5"
35" 35"
41" 41"
47" 47"
Typical Curb
Typical Duct Interface
Cambridge Engineering, Inc. 14 M-Series Technical Manual
Page 17
TYPICAL INSTALLATION
HORIZONTAL MOUNT - OUTDOOR PAD MOUNT CONFIGURATION M140
Wall Opening
Model W L
M140
54" 54"
TYPICAL CURB
M-Series Technical Manual 15 Cambridge Engineering, Inc.
Typical Duct Interface
Page 18
INSTALLATION INSTRUCTIONS
HORIZONTAL MOUNT - THRU WALL CONFIGURATION
mWARNING:
Due to the size and weight of this equipment, it is recommended that the heater support structure be reviewed and approved by a qualified structural engi­neer before installing this equipment.
IMPORTANT
Before proceeding with the installation, verify the fea­sibility of the location selected with respect to acces­sibility to the equipment for service and maintenance functions.
IMPORTANT
To minimize snow and rain ingestion, position the heat­er inlet opposite the prevailing wind.
mCAUTION:
To prevent contaminated air from being drawn into the heater, install the heater’s inlet at least 10 feet from any building exhaust, process exhaust, sewer stacks, or other sources that would allow contami­nants to be drawn into the heater. Consult local codes for applicable building code provisions for ventilation air.
4. Apply washers and double lock nuts to secure equip­ment on hanging rods. Note: The discharge end of
the heater should be raised slightly (1/8 to allow ingested moisture to drain from the heater.
5. Apply shims at the bottom of the rainhood to take up slack in the opening, leaving a small joint between the top of the heater and the wall.
6. Install fiberglass insulation in the gaps between the wall opening and the inlet collar. Apply enough material to accommodate the full thickness of the wall.
7. Install finish trim pieces (by others) to the top, sides and bottom of the inlet collar on both the inside and the outside wall surfaces.
8. Apply a bead of latex based polyurethane caulk that best matches the color of the exterior wall surface of the facility and/or the color of the heater accessories at the joint between the top inlet collar and outside wall surface. Make certain this is a continuous bead and that it runs the entire width of the collar. Caulk all other exposed joints.
" above level)
1. Prepare the wall for installation. (See pages 17-18 for wall opening dimensions for your specific heater.)
IMPORTANT
Accurate measurements are critical and will affect the installation process.
2. Install heater support rods per the structural engi­neer’s recommendations.
3. Use a crane or comparable lifting device to raise and position equipment. Block the heater where neces­sary. Use a spreader bar to prevent damage and con­nect slings to the lifting brackets.
IMPORTANT
Cambridge Engineering recommends mounting the heater’s rainhood a minimum of 24" off the ground or other surfaces.
9. Install the discharge plenum, where used, by screw­ing the plenum to the heater or to the discharge duct, as applicable. Install hanging rods from the ceiling supports to the plenum’s support brackets.
Cambridge Engineering, Inc. 16 M-Series Technical Manual
Page 19
TYPICAL INSTALLATION
HORIZONTAL MOUNT - THRU WALL CONFIGURATION M110 - M115
M-Series Technical Manual 17 Cambridge Engineering, Inc.
Wall Opening
Model W H
M110
M112
M115
32" 35.25"
32" 35.25"
46" 35.25"
Page 20
TYPICAL INSTALLATION
HORIZONTAL MOUNT - THRU WALL CONFIGURATION M118 - M136
Cambridge Engineering, Inc. 18 M-Series Technical Manual
Wall Opening
Model W H
M118
M120
M125
M130
M136
50" 55"
56" 55"
68" 71.75"
89.75" 71.75"
89.75 96.75"
Page 21
INSTALLATION INSTRUCTIONS
VERTICAL MOUNT - OUTDOOR CONFIGURATION
IMPORTANT
Before proceeding with the installation, verify the fea­sibility of the location selected with respect to acces­sibility to the equipment for service and maintenance functions.
IMPORTANT
To prevent contaminated air from being drawn into the heater, install the heater’s inlet at least 10 feet from any building exhaust, process exhaust, sewer stacks, or other sources that would allow contaminants to be drawn into the heater. Consult local codes for appli­cable building code provisions for ventilation air.
IMPORTANT
This heater should be mounted on a concrete pad with a minimum thickness of 4" and with length and width dimensions that exceed the dimensions of the heater by at least 5 feet (30" on each side). The pad should be poured at least two weeks before installation begins to permit proper curing. The pad should slope slightly away from the building (approximately 1/4" per foot) to avoid water collecting under the heater.
1. Prepare the wall for installation. (See pages 21-22 for opening dimensions for your specific heater.)
Accessory Identification drawings (see page 4) to identify the locations of these sections.
IMPORTANT
Cambridge Engineering recommends mounting the heater a minimum of 60" off the mounting surface in areas where snow accumulation could impact the heater operation.
4. Attach each mounting leg to the inlet accessory (fil­ter section, inlet damper, or filter section/inlet damp­er combo, as specified) using the 1/2"-13 x 1-1/2" bolts. The bolts install downward through a clear­ance hole in the accessory into a threaded insert in the mounting leg. Install all four legs on the acces­sory, then set this assembly in its intended position. If no inlet accessory is specified, install the legs directly to the heater. Level the assembly by placing shims under the appropriate legs.
5. Position the heater on the inlet accessory. Secure the heater using the 1/2"-13 x 1-1/2" bolts. The bolts install downward through a clearance hole in the heater into a threaded insert in the inlet accessory.
6. Attach discharge duct to heater.
IMPORTANT
Accurate measurements are critical and will affect the installation process.
2. Install the discharge duct through the wall opening.
3. Use a crane or comparable lifting device to raise and position the equipment. Block the heater where nec­essary. Use a spreader bar to prevent damage and connect slings to the lifting eyes.
The Vertical Mount heaters may be shipped in
sections due to shipping constraints. Review the
M-Series Technical Manual 19 Cambridge Engineering, Inc.
7. Caulk all joints of the heater’s accessories installed in the field. Use a clear or gray latex based polyure­thane caulking to prevent water leaks.
8. Install fiberglass insulation in the gaps around the
wall opening and discharge duct. Apply enough insulation material to accommodate the full thickness of the wall.
9. Install finish trim pieces (by others) to the top, sides
and bottom of the discharge duct on both the inside and outside wall surfaces.
Page 22
DETAIL A
DETAIL B
10. Apply a bead of latex based polyurethane caulk that best matches the color of the exterior wall surface of the facility and/or the color of the heater acces­sories at the joint between the top discharge duct and outside wall surface. Make certain this is a continu­ous bead and that it runs the entire width of the duct. Caulk all other exposed joints.
Cambridge Engineering, Inc. 20 M-Series Technical Manual
11. Install the discharge plenum by screwing the plenum to the discharge duct. Install hanging rods from ceil­ing supports to the plenum’s support brackets.
Page 23
TYPICAL INSTALLATION
HIGH PRESSURE REGULATOR (HPR)
VERTICAL MOUNT - OUTDOOR CONFIGURATION HORIZONTAL BLAST M118 - M136
LIFTING
BRACKETS
EXTERNAL WALL
WALL FLASHING
(BY OTHERS)
CONTROL WIRING CONDUIT
7-9 WIRES REQ'D
(BY OTHERS)
Wall Opening
Model W H
M118
M120
M125
M130
M136
RCS
INCOMING POWER
25.5" 25.5"
29.5" 29.5"
35" 35"
41" 41"
47" 47"
SEDIMENT TRAP (BY OTHERS)
VENT PIPE (BY OTHERS)
INLET GAS PIPE
HIGH PRESSURE SHUT-OFF VALVE
HIGH PRESSURE SUPPLY TAP
VENT w/ SCREEN (LOCATE MIN. 10 FT FROM INTAKE)
HPR
(OPTION)
M-Series Technical Manual 21 Cambridge Engineering, Inc.
Page 24
TYPICAL INSTALLATION
(OPTION)
VERTICAL MOUNT - OUTDOOR CONFIGURATION UP BLAST M118 - M136
DISCHARGE DUCT
DISCHARGE ELBOW W/ TURNING VANES
DISCHARGE DUCT
Model W H
M118
M120
M125
M130
M136
Wall Opening
25.5" 25.5"
29.5" 29.5"
35" 35"
41" 41"
47" 47"
WALL FLASHING
(BY OTHERS)
EXTERNAL WALL
RCS
CONTROL WIRING CONDUIT
7-9 WIRES REQ'D
(BY OTHERS)
INSULATION
DUCT OPENING COLLAR
TEK SCREW
OUTER PERIMETER
INCOMING POWER
SEDIMENT TRAP (BY OTHERS)
DISCHARGE DUCT
UNIT ROOF
LIFTING BRACKETS
VENT PIPE
(BY OTHERS)
VENT w/ SCREEN (LOCATE MIN. 10 FT
FROM INTAKE)
INLET GAS PIPE
HIGH PRESSURE SHUT-OFF VALVE
HIGH PRESSURE SUPPLY TAP
HIGH PRESSURE REGULATOR (HPR)
HPR
Cambridge Engineering, Inc. 22 M-Series Technical Manual
Page 25
INSTALLATION INSTRUCTIONS
VERTICAL MOUNT - INDOOR CONFIGURATION
IMPORTANT
Before proceeding with installation, verify the feasibil­ity of the location selected with respect to accessibility to the equipment for service and maintenance func­tions.
IMPORTANT
To prevent contaminated air from being drawn into the heater, install the heater’s inlet at least 10 feet from any building exhaust, process exhaust, sewer stacks, or other sources that would allow contaminants to be drawn into the heater. Consult local codes for appli­cable building code provisions for ventilation air.
1. Prepare the wall for installation. (See page 25 for opening dimensions for your specific heater.)
4. Attach each Mounting Leg to the inlet elbow using the 1/2"-13 x 1-1/2" bolts. The bolts install down­ward through a clearance hole in the accessory into a threaded insert in the Mounting Leg. Install all four legs on the accessory, and then attach the inlet collar to the inlet elbow using the 5/16"-18 x 1/2" bolts. Position this assembly with the inlet collar situated through the wall. Level the assembly by placing shims under the appropriate legs.
5. Position the next inlet accessory, if specified, on the inlet elbow, and then secure them to each other using the 1/2"-13 x 1-1/2" bolts. The bolts install downward through a clearance hole in the upper accessory into a threaded insert in the inlet elbow.
IMPORTANT
Accurate measurements are critical and will affect the installation process.
2. Install heater support rods per the structural engi­neer’s recommendations.
3. Use a crane or comparable lifting device to raise and position the equipment. Block the heater where nec­essary. Use a spreader bar to prevent damage and connect slings to the lifting eyes.
The Vertical Mount heaters may be shipped in
sections due to shipping constraints. Review the Accessory Identification drawings (see page 4) to identify the locations of these sections.
IMPORTANT
Cambridge Engineering recommends mounting the heater’s rain hood a minimum of 60" off the ground or other surfaces in areas where snow accumulation could impact operation.
6. Position the heater on the last inlet accessory. Secure the heater using the 1/2"-13 x 1-1/2" bolts. The bolts install downward through a clearance hole in the heater into a threaded insert in the inlet acces­sory.
7. Attach the rain hoods to the inlet collar using the 5/16"-18 x 1/2" bolts.
8. Install fiberglass insulation in the gaps around the wall opening and inlet collar. Apply enough insula­tion material to accommodate the full thickness of the wall.
9. Install finish trim pieces (by others) to the top, sides and bottom of the inlet collar on both the inside and outside wall surfaces.
M-Series Technical Manual 23 Cambridge Engineering, Inc.
Page 26
DETAIL A
DETAIL B
10. Apply a bead of latex based polyurethane caulk that best matches the color of the exterior wall surface of the facility and/or the color of the heater accessories at the joint between the top inlet collar and outside wall surface. Make certain this is a continuous bead and that it runs the entire width of the collar. Caulk all other exposed joints.
Cambridge Engineering, Inc. 24 M-Series Technical Manual
11. Install the discharge plenum by screwing the plenum to the heater. Install hanging rods from the ceiling supports to the plenum’s support brackets.
Page 27
TYPICAL INSTALLATION
CONTROL WIRING CONDUIT
VERTICAL MOUNT - INDOOR CONFIGURATION HORIZONTAL BLAST M118 - M136
LIFTING
BRACKETS
SEDIMENT TRAP (BY OTHERS)
Wall Opening
Model W H
M118
M120
M125
M130
M136
69" 57.5"
75" 57.5"
81" 81.5"
101.5" 81.5"
107" 81.5"
VENT PIPE
(BY OTHERS)
INLET GAS PIPE
HIGH PRESSURE SHUT-OFF VALVE
HIGH PRESSURE SUPPLY TAP
HIGH PRESSURE REGULATOR (HPR)
INCOMING POWER
7-10 WIRES (TYP)
(BY OTHERS)
RCS
VENT w/ SCREEN (LOCATE MIN.
10 FT FROM INTAKE)
HPR
(OPTION)
M-Series Technical Manual 25 Cambridge Engineering, Inc.
Page 28
INSTALLATION INSTRUCTIONS
GAS PIPING
IMPORTANT Refer to the heater rating plate for determining the minimum gas supply pressure for obtaining the maximum gas capacity for which this heater is specified.
1. Check with the local utility or gas supplier for the
facility gas supply pressure.
mCAUTION:
If the gas supply pressure is in excess of the maxi­mum pressure indicated on the heater nameplate, a separate positive shut-off high pressure regula­tor must be added upstream of the heater’s indi­vidual manual shut-off valve. This regulator must be vented to the outside of the building at least 10 feet from any intake opening or 4 feet above the heater. The vent pipe should be designed to prevent the entry of water, snow, insects or other foreign material that could cause blockage. There must be no reduction in the size of the vent pip­ing. Depending on the length and the configuration of the vent piping the pipe size may need to be increased. Refer to the applicable codes for proper sizing.
mWARNING:
For roof mounting, the gas and electrical connec­tions must not penetrate the unit base or mounting curb. Cambridge Engineering recommends using
pitch pockets or decktite to seal the penetrations.
IMPORTANT A 1/8" NPT tap is supplied with the heater for measuring the gas supply pressure. If the gas supply pressure exceeds that indicated on the nameplate, the installer must install a 1/8" NPT tap and high pressure manual shut-off valve upstream of the high gas pressure regulator.
IMPORTANT An adequate sediment trap must be installed prior to all gas controls for the heater and as close to the gas inlet connection of the heater as practical. Many gas train components are equipped with listed Vent Limiters as atmo­spheric bleeds, however, local codes may require that these vents and bleeds be vented to the outdoors. If so, the vent piping should be designed to prevent the entry of water, snow, insects or other foreign materials that could cause blockage.
6. Check for leaks in the supply piping system. Use
liquid gas leak detector. Do NOT use flame.
mCAUTION:
If the test pressure is in excess of 1/2 PSIG (3.5 KPA), the heater and its manual shut-off valve must be disconnected from the gas supply system during pressure testing. Failure to comply will void the warranty.
If the test pressure is less than or equal to 1/2 PSIG (3.5 KPA), the heater must be isolated from the gas supply piping by closing its manual shut-off valve during pressure testing.
2. Properly size the gas supply piping for the rated capacity, per local codes, and/or the National Fuel Gas Code, ANSI Standard Z223.1 or the CAN/CGA B149 Installation Codes.
3. Make sure the supply piping is free of foreign matter and purged.
4. Verify that the gas piping, when installed, will not restrict or block the access door from fully opening.
5. Install gas piping to the make-up air heater in accordance with local codes or, in their absence, in accordance with the National Fuel Gas Code, ANSI Standard Z223.1, or the CAN/CGA B149 Installation Codes.
Cambridge Engineering, Inc. 26 M-Series Technical Manual
mCAUTION:
Do not attempt to start the
make-up air heater at this time.
Premature start-up can result in damage to the
equipment and components.
Page 29
INSTALLATION INSTRUCTIONS
ELECTRICAL
IMPORTANT
Before attempting electrical installation, review the following instructions and wiring and connection dia­grams to make sure you have a thorough understand­ing of what is required.
mWARNING:
High voltage electrical input to this equipment is required. EXTREME caution should be exercised. This equipment must be electrically grounded in accordance with local codes or in accordance with National Electrical Code ANSI/NFPA No. 70.
1. Check the heater nameplate to determine the voltage and amperage requirements.
mCAUTION:
If the supply voltage does not agree with the nameplate voltage, notify your local agent or Cambridge Engineering’s Customer Service Group at 800-473-4569.
mWARNING:
For roof mounting, the gas and electrical connec­tions must not penetrate the unit base or mounting curb. Cambridge Engineering recommends using
pitch pockets or decktite to seal the penetrations.
2. Wire the supply wiring and adequate Branch Circuit Protection in accordance with the National Electric Code ANSI/NFPA 70.
3. Mount the Remote Control Station in a location inside of the building and convenient to the operator without
being susceptible to damage.
4. Space temperature sensors are normally located along a perimeter wall and out of the direct path of the discharge air or air infiltration. Consult the design drawing or your local Cambridge Engineering Representative for placement assistance. Do not locate the remote mounted temperature sensors immediately adjacent to overhead doors because the infiltration air can affect the sensor when the door is closed and may not adequately sense the tempera­ture when the door is open. In dock areas, the sensor should be located on the first column in from the outside wall.
IMPORTANT Observe the special notes and instructions on the wiring diagrams including the following: The wiring for the space temperature sen-
sors must be “shielded, twisted-pair” wiring and must run separate from the other “AC” wiring. This also applies to other remote mounted controls utilized in the Maxitrol Series 14 and 44 control systems. Shielded wire which is routed to the electrical con­trol enclosure on the heater should extend beyond the high voltage section of the enclosure before the shielding is terminated and the wiring is distributed to its ultimate destination. Shielding must be grounded on one end only.
IMPORTANT Conduit connections for power and control wir­ing must be caulked to ensure a tight seal and prevent moisture accumulation.
5. Wire the Remote Control Station and other tem-
perature control options using Class II wiring per Cambridge Engineering wiring diagram and National Electrical Code Article 725 or local codes.
6. Run conduit and primary wiring to the disconnect
switch inside of the control enclosure on the heater per N.E.C., Article 430, ANSI/NFPA 70.
7. If applicable on vertical mount, feed the cable
marked “inlet damper” through the bottom of the heater into the inlet damper housing. Connect wir­ing to the damper motor junction box per the wiring diagram.
8. Return the wiring diagram to the manual holder.
Replace and fasten all access covers.
mCAUTION:
Do not attempt to start the make-up air heater at this
time.
Premature start-up can result in damage to the
equipment and components.
M-Series Technical Manual 27 Cambridge Engineering, Inc.
Page 30
START-UP INSTRUCTIONS
1. Visual Inspection Of Equipment (page 28)
2. Electrical Supply Voltage Verification (page 28)
3. Gas Supply Pressure Verification (page 29)
4. Blower Rotation Check (page 29)
5. Burner Profile Damper Pressure Drop Check (page 29)
6. Motor Amp Draw Check (page 30)
7. Calculating and Adjusting Burner Manifold Pressure
(page 30)
8. Gas Valve Leak Check
(page 31)
9. Gas Train Leak Check
(page 32)
IMPORTANT Read the following instructions carefully. Any unauthorized modifications to, or deviations from these instructions may void the warranty.
1. VISUAL INSPECTION OF EQUIPMENT
a. Check for any physical damage from ship-
ping or installation that could render the heater inoperable.
b. Verify all heater accessories and filters (if
applicable) have been properly installed.
c. Check for loose components (belts, plugs, ter-
minal screws, etc.).
d. Verify the access doors and controls enclosure
are free from obstructions, such that they can be fully opened.
e. Verify the field wiring, both primary and
control, has been installed according to the Cambridge Engineering wiring diagram and the National Electrical Code.
10. Minimum Fire Setting (page 32)
11. Low Fire Start Adjustment (page 33)
12. Preliminary Remote Control Station Operational Check
(page 33)
13. Final Heater Preparation
(page 34)
14. Final Remote Control Station Check
(page 34)
After start-up, please complete and fax the M-Series Start Up Checklist to the Cambridge Customer Service Group. Receipt of a completed checklist will extend the start date for your warranty period to the date of the start-up but not to exceed six months from date of ship­ment.
f. Verify that a sediment trap has been provided
upstream of other gas train components.
g. Verify the high pressure regulator and/or vent
valve, if applicable, have been vented to the outside of the building at least 10 feet from any intake opening or 4 feet above the heater.
h. Verify the factory supplied manual gas shut-
off cock is installed external to the heater and downstream of the high pressure regulator, if applicable.
i. Verify that the gas piping unions are tight.
j. Verify that the burner union is tight.
2. ELECTRICAL SUPPLY VOLTAGE VERIFICATION
For model M110 - M115 heaters, remove electri-
cal enclosure access door and check the electrical supply voltage at the terminal block provided off
Cambridge Engineering, Inc. 28 M-Series Technical Manual
Page 31
of the disconnect switch. For model M118 - M140 heaters, check the electrical supply voltage at the disconnect switch.
mCAUTION:
Do not proceed with start-up unless the supply voltage agrees with the nameplate voltage. If the supply voltage does not agree with the name­plate voltage, check with your local Cambridge Engineering representative or Cambridge Engineering’s Customer Service Group at 800­473-4569 to determine what changes are required.
3. GAS SUPPLY PRESSURE VERIFICATION
Verify that the gas supply pressure complies with the heater nameplate.
b. Turn the blower service switch to the “LOCAL”
position. The blower motor will start after the motorized inlet damper opens. Then turn the
blower service switch to the
“OFF” position and
verify the blower is rotating in the proper direction. (See the directional arrow on the blower housing.)
IMPORTANT
On a three phase system, the rotation direction of the blower may be reversed by switching any two wires lo­cated on the downstream side of the service disconnect. The electrical supply to the heater must be turned off prior to switching the wiring.
IMPORTANT
Indications of loose belts include barking or squeal­ing when the blower starts. If these symptoms occur, please refer to the BELT TENSIONING section of the MAINTENANCE INSTRUCTIONS (see page 59). Periodic belt adjustments may be required.
mCAUTION:
Do not proceed with start-up unless the gas sup­ply pressure agrees with the nameplate pressure requirements. If the gas supply pressure is in excess of the maximum pressure indicated, a sepa­rate positive shut-off high pressure regulator must be added upstream of the heater’s individual low pressure manual shut-off valve. If a high pressure regulator is needed and has not been installed, check with your local Cambridge Engineering rep­resentative or Cambridge Engineering’s Customer Service Group at 800-473-4569 to determine the size and capacity requirements that are required.
4. BLOWER ROTATION CHECK
a. Open the access door on the electrical control enclosure
side and turn the disconnect switch on.
mWARNING:
When the disconnect switch is activated with the enclosure open, live power is present. Only experi­enced technicians with knowledge and respect for live power should proceed beyond this point.
5. BURNER PROFILE DAMPER PRESSURE DROP CHECK
IMPORTANT
The blower access doors must be in place when adjust­ing the profile plate.
IMPORTANT
Verify that the inclined manometer, if applicable, is level and zeroed for proper readings to be obtained.
a. Turn the blower service switch to the “LOCAL”
position. (Note: The burner service switch must remain in the “OFF” position)
b. Check the pressure drop across the burner prole
plate to ensure that it complies with the table below:
Profile Plate Pressure Drop -
Blower Only (inches WC)
Gas
Type
Nat­ural
LP
Models Filters
M110-M140 No 0.68
M140 Yes 0.75
M110-M140 No 0.90
M110-M136 Yes 0.94
M140 Yes 0.97
Manual
Adjust
Automatic
Adjust
Min. Max.
0.62 0.72M110-M136 Yes 0.72
0.84 0.94
M-Series Technical Manual 29 Cambridge Engineering, Inc.
Page 32
c1. To change the prole plate pressure drop on
model M110 - M115 heaters with a Manual Prole Adjust mechanism, locate the adjust­ing mechanism in the electrical control enclo­sure, loosen the lock-down bolt, and rotate the adjuster to increase or decrease the pressure as required. Retighten the lock-down bolt to secure the mechanism.
IMPORTANT
Call the Cambridge Engineering Customer Service Group at 800-473-4569 if unable to obtain the required pressure drop across the burner profile plate.
o 6. MOTOR AMP DRAW CHECK
IMPORTANT
The heater access doors must be closed for this test.
a. Check the motor current at the overload relay
on all three legs.
b. Turn the blower service switch to the “OFF”
position.
c2. To change the prole plate pressure drop on
model M118 - M140 heaters with a Manual
Prole Adjust mechanism, locate the adjusting
mechanism in the gas train enclosure, loosen the jam nut, and rotate the adjusting nut to increase or decrease the pressure drops, as re­quired. Hold the adjusting nut and retighten the jam nut to secure the mechanism.
c3. For make-up air heaters with an Automatic
Prole Adjust system, check the Differential
Pressure Switch/Gauge and verify that the left orange needle is set to the Minimum setting and the right orange needle is set to the Maximum setting from the table above.
IMPORTANT
The average amps must not exceed the motor nameplate FLA. High amperage may indicate excessive blower RPM. Call the Cambridge Engineering Customer Service Group at 800-473-4569 if unable to obtain ac-
ceptable amperage readings.
7. CALCULATING AND ADJUSTING BURNER
o
MANIFOLD PRESSURE
Cambridge Engineering, Inc. 30 M-Series Technical Manual
a. Turn the disconnect switch off.
b. Disconnect #3 wire from the amplifier to drive the
modulating valve to full open.
c. If the ambient temperature is at or above the
Entering Air Thermostat (EAT) setpoint on the multi-functional PC board, then note the setpoint position and set the EAT to its highest
Page 33
setting. If the ambient temperature exceeds its highest setting, remove the set point jumper
and rotate 90˚ for the bypass mode.
d. Remove the 1/8" NPT plug from the manual
shut-off valve located just prior to the burner and connect a manometer for the purpose of mea-
e. Refer to the heater nameplate for the Manifold
suring the manifold pressure.
Differential Pressure (MDP) (inch WC) for which the heater was specified.
below 0.51 inches WC for natural gas heaters without filters or 0.55 inches WC for natural gas heaters with a filter section or filters in the rainhood. The pressure drop must not fall below 0.75 inches WC for LP gas heaters without filters or 0.79 inches WC for LP gas heaters with a filter section or filters in the rainhood. If the pressure drop is below these values, it is an indica­tion of low airflow or burner overfiring. To correct this condition, either adjust the manifold pressure regulator to reduce the manifold pressure or increase the blower speed, provided the motor full load amps are not ex­ceeded.
Nameplate Manifold Differential Pressure
f. Turn the disconnect switch on.
g. Turn the blower service switch to the
“LOCAL” position. The blower motor will
start. Monitor the pressure reading on the manom­eter. Record the Manifold Static Pressure (Blower Only).
h. Using the formula below, calculate the required
manifold pressure:
Nameplate Manifold Differential Pressure ___________inch WC
+ Manifold Static Pressure (Blower Only) ___________inch WC
= Calculated Manifold Pressure ___________inch WC
IMPORTANT
The high limit may trip on warm or mild temperature days. A jumper may be necessary to complete the mani­fold pressure adjustment.
i. Turn the burner service switch to the
“LOCAL” position. After a delay for pre-
purge and igniter warm-up, the burner will light.
j. Observe the manometer reading and compare
to the Calculated Manifold Pressure above. If the manifold pressure reading does not equal this value, adjust the manifold pressure regulator until the proper manifold pressure is obtained.
k. Turn the blower and burner service
switches to the “OFF” position, remove the manometer from the manual shut-off valve, re-install the 1/8" NPT plug and remove the jumper (if used).
o 8. GAS VALVE LEAK CHECK
All heaters should be evaluated for the gas tight-
ness of the gas valve seat. Heaters with separate redundant valves are equipped with a leak test facil­ity to assist in checking this seal. A momentary switch and a gas port for measuring pressure between valves are provided as the leak test hardware. Refer to the Individual Component Description Section for more information regarding the leak test switch. The procedures for the gas valve leak check are as follows:
a. Connect a 0 to 10 inches water column
(
inch WC) manometer to the 1/8" NPT
tapped fitting on the manual shut-off valve located just prior to the burner for the purpose of monitoring an increase in pressure. Verify that the manometer is properly zeroed.
b.1. On single redundant valve applications
(heaters rated less than 400,000 Btu/hr), close the manual burner shut-off valve and wait 30 seconds to read the manom-
eter. If the reading is greater than 0
inch
WC, replace the gas valve and retest. If the reading is 0 inch WC, remove the manom­eter and reinstall the pipe plug.
IMPORTANT
The pressure drop across the burner profile damper that was adjusted in Step 5 (page 30) must not fall
M-Series Technical Manual 31 Cambridge Engineering, Inc.
b.2. On heaters with separate redundant
valves, close the manual burner shut­off valve, hold the momentary leak test
Page 34
switch in the closed position, and wait 30 seconds to read the manometer. If the
reading is greater than 0 to the Maintenance Instruction Section for information on Gas Valve Cleaning for cleaning the second gas valve and retest.
If the reading is 0 manometer and reinstall the pipe plug.
c. To check the gas tightness of the first
valve in the gas train on heaters with separate redundant valves, connect the manometer to the leak test port between the valves and verify that the manom­eter is properly zeroed. Wait 30 seconds to read the manometer. If the reading
is greater than 0 Maintenance Instruction Section for infor­mation on Gas Valve Cleaning for the first gas valve and retest. If the reading is
0
inch WC, remove the manometer and
reinstall the pipe plug.
inch WC, refer to the
inch WC, refer
inch WC, remove the
from the amplifier.
b. Connect a meter set to read DC micro-
amps (mA) in order to verify the minimum fire flame signal during the adjustment process. Connect the meter by removing the red wire from terminal FP of the flame
safe
guard relay (FSR) and attaching the
positive lead of the meter to terminal FP and the negative lead to the red wire.
c. Turn the blower and burner switches to
the “LOCAL” position.
d. After the burner has ignited remove #8
wire from the amplifier to drive the modu­lating valve to minimum fire.
e. Look through the burner porthole in the
front of the heater to verify that the burner flame is a very small ribbon (approxi-
mately 1-1/2" to 2 spread across the burner (without gaps).
" long) that is evenly
9. GAS TRAIN LEAK CHECK
o
a. Turn the blower and burner service
switches to the “LOCAL” position.
b. With the burner operating, spray the com-
plete gas train with leak detector solution, checking all pipe connections and plugs.
c. Turn the blower and burner service
switches to the “OFF” position.
mWARNING:
Do not use flame to leak check piping.
mWARNING:
Any gas leak detected must be repaired before the make-up air heater is placed into service.
10. MINIMUM FIRE SETTING
f. Verify that the minimum fire flame signal
is steady and above 2.0 microamps (mA).
IMPORTANT
If any of the conditions in steps 10.e and 10. f are not met, an adjustment is required.
g. Minimum Fire Adjustment
i. To adjust the minimum fire, remove
cap (A) exposing the mini­mum fire adjusting screw. On the MR212 modulating/ regulating valve, remove the housing cover, then cap (A), and then loosen lock screw (C). Turn the adjusting screw (B) to obtain the desired mini­mum fire setting. Repeat steps 10.e and 10.f.
IMPORTANT
All access doors must be closed during this procedure.
a. Reinstall the #3 wire previously removed
Cambridge Engineering, Inc. 32 M-Series Technical Manual
Page 35
. ii. Replace the cap (A). Tighten the lock
screw (C) on the MR212 valve prior to reinstalling the cap and housing cover.
iii. Turn the blower and burner service
switches to the “OFF” position.
iv. Reconnect wire #8 to the amplifier.
v. Remove the meter and reattach the red
wire to terminal FP on the FSR board.
11. LOW FIRE START ADJUSTMENT
The Low Fire Start control setting is preset at the
factory to provide a fixed, repetitive, initial firing rate that equates to the following for most burner applications:
• 20˚F to 30˚F temperature rise
• 0.10 to 0.30 inches WC manifold differential
pressure (above blower pressure)
• Voltage to the modulating valve of 9 to 11 Volts
DC for the Maxitrol M511 or M611 valve and 10 to 13 Volts DC for the Maxitrol MR212 valve.
• Flame length of 3" to 5"
The Low Fire Start function lasts for 15 seconds
before returning to the control of the temperature control system. It is important that the flame travels across the burner length fast enough (within 2 sec­onds) to establish the flame signal during the trial for ignition period. If adjustment is required, proceed as follows:
a. Connect a meter in the flame sense circuit
as in step 10.b (see page 33).
b. Connect a manometer to the burner static
pressure port. Turn the blower service switch to the “LOCAL” position and the burner service switch to the “OFF” posi­tion and measure the burner static pres­sure.
c. Connect a DC voltmeter to terminals “MV
OUT” on the multi-functional PC board.
d. Turn the burner service switch to the
“LOCAL” position and monitor the modu-
lating valve voltage, flame length, manifold differential pressure, and the time required to establish flame signal after the gas valves are energized. (This may need to be repeated several times to note all of the above information)
e. If adjustment is required, the Low Fire
Start adjustment screw is located on the multi-functional PC board as shown in the drawing. Only minor adjustments are normally required to obtain the proper set­ting.
12. PRELIMINARY REMOTE CONTROL
STATION OPERATIONAL CHECK
a. Turn the blower and burner service switches
to the “REMOTE” position and, if applica­ble, turn the Remote Control Station mode selector switch to the “HEATING” posi­tion.
b. Identify the type of Remote Control Station,
if applicable, that is utilized on this appli­cation. Refer to Individual Component Description Section for additional infor­mation.
c.1. If the Remote Control Station utilizes
a thermostat, refer to the Operating Instructions for the Electronic Thermostat (see page 65) or the TSS Controller (see page 67) to set the thermostat at its high­est setting.
c.2. If another device in the Remote Control
Station controls the operation of the heater, activate this device.
M-Series Technical Manual 33 Cambridge Engineering, Inc.
Page 36
c.3. If the make-up air heater is not equipped
with a Remote Control Station, activate that part of the control system which will initiate the blower and burner operation.
d. After a short delay for damper operation,
the blower should operate, followed by burner ignition after a delay for prepurge and igniter warm-up.
14. FINAL REMOTE CONTROL STATION CHECK
a. To ensure the heater’s disconnect and service
switches have been left in the correct posi­tion, turn the mode selection switch to the “SUMMER VENTILATION” position and verify the blower operates.
e. Adjust the applicable temperature control
and verify the heater output changes.
f. Reset the thermostat, if applicable, and the
temperature control to the desired tempera­ture.
g. Turn the mode selector switch to the
“SUMMER VENTILATION” position. Verify the blower operates.
13. FINAL HEATER PREPARATION
a. Turn the disconnect switch off.
b. Set the Entering Air Thermostat (EAT) to
the specified temperature setting. Refer to the Individual Component Description Section for additional information.
c. Remove the jumper wire from the high
limit, if one was used. Reset the high limit.
SHUT-DOWN INSTRUCTIONS
1. Turn the mode selector switch of the
Remote Control Station to the “OFF” position.
2. Turn the service disconnect switch off.
3. Turn the blower and burner service
switches to the “OFF” position.
4. Close the supply gas cock.
5. Turn off the electric supply to the heater.
IMPORTANT
If you need technical assistance, call the Cambridge Engineering Customer Service Group at 800-473-4569 during the hours of 8:00 a.m. to 5:00 p.m. Central Time, Monday through Friday.
d. For the Maxitrol Series 44 control system,
set the “MIN” and “MAX” setting of the amplifier to the application specifications.
e. Verify the blower and burner service
switches are in the “REMOTE” position.
f. Return the Technical Manual and Wiring
Diagram to the manual holder.
g. Perform a visual inspection of all wiring and
gas valve plugs to ensure they have been properly replaced.
h. Replace and fasten all covers and panels.
Turn the disconnect switch on.
Cambridge Engineering, Inc. 34 M-Series Technical Manual
Page 37
OPERATING INSTRUCTIONS
OPERATING SEQUENCE
POWER ON
1. Control transformer energized.
2. Operator must select “SUMMER VENTILATION” or “HEATING” mode.
SUMMER VENTILATION MODE
1. Mode switch in “SUMMER VENTILATION” position.
2. Optional TSS Controller schedule calls for ventila­tion.
3. Optional motorized inlet or discharge damper opens.
4. Blower motor starts.
5. Unit continues to run until turned off.
HEATING MODE
1. Mode switch in “HEATING” position.
2. Thermostat or interlock calls for heat.
3. Optional motorized inlet or discharge damper opens.
4. Blower motor starts.
5. Low airflow switch closes.
6. Entering air thermostat closes when inlet tempera­ture is below setpoint after the prepurge delay.
7. Igniter warm up timing.
8. Gas valve opens.
9. Burner lights.
10. Igniter is de-energized.
11. Low Fire Start is de-energized after 15 seconds.
12. Unit runs and modulates until operating thermostat and/or interlock opens (heater shuts off).
13. Steps (2) through (12) repeat themselves automati­cally as necessary.
M-Series Technical Manual 35 Cambridge Engineering, Inc.
Page 38
OPERATING INSTRUCTIONS
ELECTRONIC THERMOSTAT
The Cambridge Engineering Operating Electronic Thermostat (OET) controls the heater’s ON/OFF operation in a space heating mode. It includes the following features:
• Digital LED display of current temperature and temperature settings.
• LED indication of status of output relay.
• Separate settings for HEAT ON and HEAT OFF settings.
• Temperature Calibration for accurate temperature control.
• EEPROM storage maintains temperature settings indefinitely in case of power loss.
The thermistor enclosure (SH-1) is packed inside the Remote Control Station for shipment. It can be mounted on the exterior sides or bottom of the Remote Control Station or a remote location within 500 feet of the Remote Control Station using 18 gauge stranded, twisted-pair, shielded cable. The thermistor is hard wired to the temperature sensor terminal block.
Cambridge Engineering, Inc. 36 M-Series Technical Manual
Page 39
SETTING TEMPERATURES
TEMPERATURE CALIBRATION
The Electronic Thermostat requires two temperature set­tings. When the temperature drops below the HEAT ON setting, the heater will turn on. When the heater raises the space temperature above the HEAT OFF setting, the heater will turn off. This difference provides an adjust­able range of operation for the heater which minimizes temperature swings.
The minimum run time and off time for the heater regardless of temperature are both set at 2 minutes. The allowable temperature range is 40°F to 99°F. The HEAT OFF temperature can not be set lower than the HEAT ON temperature.
1. Press and hold the HEAT ON button while pressing the UP or the DOWN button until the desired tempera­ture for the heater to turn ON is displayed.
To compensate for lead wire resistance, it may be neces­sary to make an adjustment to the displayed temperature to correct it to the temperature measured at the thermis­tor sensor. The calibration feature allows the displayed temperature to be offset either above or below the actual sensed temperature. Be sure to use an accurate tempera­ture meter for making this correction.
1. Press and hold the HEAT ON and HEAT OFF buttons while pressing the UP or the DOWN button until the
correct temperature is displayed. ( A period [.] after the temperature will indicate the Calibration Mode).
2. Press and hold the HEAT OFF button while pressing the UP or the DOWN button until the desired tempera­ture for the heater to turn OFF is displayed.
2. Pressing the UP or the DOWN button will display the current calibration difference above or below (-) the measured temperature.
M-Series Technical Manual 37 Cambridge Engineering, Inc.
Page 40
OPERATING INSTRUCTIONS
TSS CONTROLLER
The Cambridge Engineering TSS Controller provides several features to tailor the operation of the Cambridge heating system to particular applications.
• Seven day programmable clock.
• Separate temperature settings for Heating and Setback operation.
• Separate schedules for Summer Ventilation and Heating modes.
• Setback Override for temporary heating operation.
• Real-Time Clock with automatic adjustment for Daylight Saving Time.
• Nine Holiday Setback Periods for temporary setback operation.
• Temperature Calibration for accurate temperature control.
• Capacitor backup maintains current time and day of week for power loss of up to 96 hours.
• EEPROM storage maintains schedules and temperature settings indefinitely.
The thermistor enclosure (SH-1) is packed inside the Remote Control Station for shipment. It can be mounted on the exterior sides or bottom of the Remote Control Station or a remote location within 500 feet of the Remote Control Station using 18 gauge stranded, twisted-pair, shielded cable. The thermistor is hard wired to the tempera­ture sensor terminal block.
Cambridge Engineering, Inc. 38 M-Series Technical Manual
Page 41
SETTING CURRENT DAY OF WEEK, TIME, MONTH/DAY, AND YEAR
For proper operation of the scheduler, the TSS Controller clock must be set to the correct day of week, time, month/day and year. In the event of power loss of more than 96 hours, these settings must be updated.
During normal operation, the TSS Controller display will alternate between the current space temperature and the current time and day of the week.
1. Press and hold the DAY OF WEEK button while pressing the UP or the DOWN button until the light for the current day is illuminated.
3. Press and hold the MONTH/DAY button while press­ing the UP or the DOWN button until the current date is displayed.
4. Press and hold the YEAR button while pressing the
UP or the DOWN button until the current year is dis-
played.
2. Press and hold the TIME button while pressing the
UP or the DOWN button until the current time is dis-
played.
SETTING AUTOMATIC ADJUSTMENT FOR DAYLIGHT SAVING TIME
The TSS Controller has the ability to automatically detect and adjust for daylight saving time. The default setting on the controller is to recognize daylight saving time.
M-Series Technical Manual 39 Cambridge Engineering, Inc.
Page 42
SETTING TEMPERATURES
1. Press the SETBACK SCHEDULE/EXIT button to enter the scheduling program at the first ON cycle.
2. Press the UP button once to enter the daylight saving time setting ("d-SA" is displayed).
The TSS Controller has two temperature control modes with the keyswitch on the front of the enclosure in the HEATING position. The HEATING mode controls the heater when the ON time schedule is in effect. The SETBACK mode controls the heater when the OFF time schedule is in effect. (See SETTING SCHEDULES for instructions on setting the ON and OFF schedules). With the keyswitch in the SUMMER VENTILATION posi­tion the heater fan will run based on the time schedule with no temperature control.
HEATING MODE (ON Time Schedule)
The HEATING mode requires two temperature settings. When the temperature drops below the HEAT ON set­ting the heater will turn on. When the heater raises the space temperature above the HEAT OFF setting, the heater will turn off. This difference provides an adjust­able range of operation for the heater, which minimizes temperature swings. The minimum on time and off time for the heater regardless of temperature is 2 minutes. The allowable temperature range is 41°F to 99°F.
3. Press and hold the YEAR button while pressing the
UP or the DOWN button to scroll to "YES" if daylight
saving time should be recognized or "NO" if daylight saving time is not recognized.
The HEAT OFF temperature cannot be set lower than the HEAT ON temperature.
1. Press and hold the HEAT ON button while pressing the UP or the DOWN button until the desired tempera­ture for the heater to turn ON is displayed.
4. Press the SETBACK SCHEDULE/EXIT button to exit the scheduling program.
Cambridge Engineering, Inc. 40 M-Series Technical Manual
Page 43
2. Press and bold the HEAT OFF button while pressing the UP or the DOWN button until the desired tempera­ture for the heater to turn OFF is displayed.
SETBACK MODE (OFF Time Schedule)
The SETBACK mode requires setting only the ON tem­perature. The OFF temperature will be automatically set based on the temperature difference between HEAT ON and HEAT OFF programmed above for the HEAT mode.
1. Press and hold the SETBACK TEMP. button while pressing the UP or the DOWN button until the desired temperature for the heater to turn ON is displayed.
SETTING SCHEDULES
The TSS Controller has separate programmable daily schedules for the HEATING and the SUMMER VENTILATION modes. The schedule currently in effect is determined by the position of the keyswitch in the door of the enclosure. With the keyswitch in the HEATING or OFF position, the schedule for the Heating Mode is accessible. With the keyswitch in the SUMMER VENTILATION position, the schedule for the Ventilation Mode is accessible. (This will be indi­cated by the VENT MODE light on the TSS Controller being illuminated). Before attempting to program the schedule, determine the planned time periods for HEAT (ON) and SETBACK (OFF) for the HEATING mode and the planned ON and OFF time periods for the Ventilation mode. The time that it takes to recover from the SETBACK temperature to the HEAT temperature must also be taken into consideration for the ON time in the HEATING mode. The following charts can be filled in for a reference during the programming of the schedule. There are fifteen available ON and OFF program cycles for both HEATING and SUMMER VENTILATION. The first ON and OFF cycles are fixed for Monday through Friday and should only be used when the schedules for those days are identical. The fourteen additional numbered cycles can be programmed for any one day or successive days.
SETBACK OVERRIDE
In instances where temporary heat is desired when the scheduler is in the SETBACK mode, the OVERRIDE timer can be used. Setting this timer, located on the front of the TSS panel, will override the SETBACK tempera­ture setting and increase the space temperature to the HEAT ON and HEAT OFF temperature settings for the
amount of time set on the OVERRIDE timer.
NOTE: Do not program the TSS controller with over­lapping schedules, as operational errors will occur. Whenever the heater is operating during a scheduled ON cycle and a subsequent overlapping program is encoun­tered, that program will be ignored.
A Holiday Setback Schedule is available for temporary operation in the Setback Mode of up to nine different holiday periods without affecting the current schedules. (See HOLIDAY SETBACK SCHEDULE section for instructions on using this feature).
All unused program cycles should not contain any set­tings. Check all cycles after programming to assure that the display for unused cycles shows "--:--". If undesired settings have been entered, scroll the time display until "--:--" is displayed (between 11.59PM and 12.00AM for time settings; between 12.31 and 1.01 for date settings).
M-Series Technical Manual 41 Cambridge Engineering, Inc.
Page 44
HEATING SCHEDULE
Cycle Time AM/PM Day
On
Off
On 1
Off 1
On 2
Off 2
On 3
Off 3
On 4
Off 4
On 5
Off 5
On 6
Off 6
On 7
Off 7
On 8
Off 8
On 9
Off 9
On 10
Off 10
On 11
Off 11
On 12
Off 12
On 13
Off 13
On 14
Off 14
M-F
M-F
SUMMER VENTILATION SCHEDULE
Cycle Time AM/PM Day
On
Off
On 1
Off 1
On 2
Off 2
On 3
Off 3
On 4
Off 4
On 5
Off 5
On 6
Off 6
On 7
Off 7
On 8
Off 8
On 9
Off 9
On 10
Off 10
On 11
Off 11
On 12
Off 12
On 13
Off 13
On 14
Off 14
M-F
M-F
Cambridge Engineering, Inc. 42 M-Series Technical Manual
Page 45
1. Switch the keyswitch on the front of the enclosure to the desired operating mode. Allow ten seconds before proceeding.
2. Press the SETBACK SCHEDULE/EXIT button to enter the scheduling program at the first ON cycle.
3. Press and bold the TIME button while pressing the UP or the DOWN button to scroll to the desired ON time for Monday through Friday.
5. Press and bold the TIME button while pressing the UP or the DOWN button to scroll to the desired OFF time for Monday through Friday.
6. If Monday through Friday is the only schedule required, proceed to Step 14. If any additional pro­gramming is required, proceed with the following steps. Remember that subsequent program cycles must not overlap with the ON and OFF times set above.
7. Press the UP button once to step to the next ON cycle.
4. Press the UP button once to step to the first OFF cycle.
M-Series Technical Manual 43 Cambridge Engineering, Inc.
8. Press and bold the TIME button while pressing the UP or the DOWN button to scroll to the desired ON time.
9. Press and bold the DAY OF WEEK button while pressing the UP or the DOWN button until the light for the desired day is illuminated.
Page 46
10. Press the UP button once to step to the next OFF cycle.
11. Press and hold. the TIME button while pressing the
UP or the DOWN button to scroll to the desired OFF
time.
12. Press and hold the DAY OF WEEK button while
pressing the UP or the DOWN button until the light for the desired day is illuminated.
13. Repeat steps 7-12 until all required program cycles have been entered.
14. Press the SETBACK SCHEDULE/EXIT button to exit the scheduling program.
15. Verify that the correct current time and light for day of the week are still displayed.
HOLIDAY SETBACK SCHEDULE
The Holiday Setback Schedule overrides the normal schedule and holds the space at the SETBACK tempera­ture. The TSS Controller allows up to nine holiday peri­ods (Holiday Start Date [HSD] and Holiday End Date [HED]) to be scheduled.
HOLIDAY SETBACK SCHEDULE
Cycle Date
HSD 1
HED 1
HSD 2
HED 2
HSD 3
HED 3
HED 4
HED 4
HSD 5
HED 5
HSD 6
HED 6
HSD 7
HED 7
HSD 8
HED 8
HSD 9
HED 9
Cambridge Engineering, Inc. 44 M-Series Technical Manual
Page 47
1. Press the SETBACK SCHEDULE/EXIT button to enter the scheduling program at the first ON cycle.
4. Press the UP button once to step to the first holiday end date cycle (HEd1).
2. Press the UP button repeatedly to step to the first holi­day start date (HSd1).
3. Press and hold. the MONTH/DAY button while press­ing the UP or the DOWN button to scroll to the desired holiday start date.
5. Press and hold the MONTH/DAY button while pressing the UP or the DOWN button to scroll to the desired holiday end date. (NOTE: Holiday end date must be at least one day after holiday start date).
6. Repeat steps 2-5 until all required holiday cycles have been entered.
7. Press the SETBACK SCHEDULE/EXIT button to exit the scheduling program.
M-Series Technical Manual 45 Cambridge Engineering, Inc.
Page 48
TEMPERATURE CALIBRATION
To compensate for lead wire resistance, it may be neces­sary to make an adjustment to the displayed temperature to correct it to the temperature measured at the thermis­tor sensor. The calibration feature allows the displayed temperature to be offset either above or below the actual sensed temperature. Be sure to use an accurate tempera­ture meter for making this correction.
1. Press and hold the HEAT ON and HEAT OFF buttons
while pressing the UP or the DOWN button until the correct temperature is displayed. (A period [.] after the F will indicate the Calibration Mode).
2. Pressing the UP or the DOWN button will display the current calibration difference above or below (-) the measured temperature.
Cambridge Engineering, Inc. 46 M-Series Technical Manual
Page 49
MAINTENANCE INSTRUCTIONS
mWARNING:
Turn the disconnect switch off when performing
service or maintenance functions.
BLOWER BEARING LUBRICATION
Heaters with 3 HP or smaller motors have permanently lubricated, double shielded, and double sealed ball bear­ings which do not require additional lubrication. Heaters with 5 HP or larger motors require lubrication on inter­vals of 3 to 6 months. Use Shell Alvania #2, Exxon Unirox N2, Mobil Mobilith SHC100, Mobil 532, Mobil Mobilux #2, Texaco Multifak #2 and Texaco Premium RB lubricants.
MOTOR BEARING LUBRICATION
Motors are pre-greased normally with Shell Dolium R. Equivalent greases which are compatible with the motor furnished grease are Chevron SRI No. 2 and Texaco
Premium RB
Annual Motor Op-
Intermittent Operation
- >5000 hours
Continuous Operation
- Standard Service Seasonal Service
(Motor is idle for 6
months or more)
Continuous Operation
- Severe Service
(High ambient, dirty
or moist location, high
.
eration
vibration)
Recommended Lubrica-
tion Interval
NEMA 215T
Frame or
smaller
5 years 3 years
2 years 1 year
1 year 1 year
6 months 6 months
NEMA 254
Frame or
larger
BELT TENSIONING
Using a Browning Belt Tension Checker and a straight edge, verify proper belt tension exists according to the following table. Periodic belt adjustments may be required. Indications of loose belts include barking or squealing when blower starts.
Center
Span
Deec-
tion
5VX 9/16" 9-11 8-10
Force (lbs)
New
Belts
6½ -
8½
6½ -
8½
6½ -
8½
6½ -
8½
6½ -
8½
6½ -
8½
8½ ­10½
Used Belts
6 - 7½
6 - 7½
6 - 7½
6 - 7½
6 - 7½
6 - 7½
4½ -
6½
8-10
Model
M110-
M112
M110-
M115
M112-
M118 M115
M118-
M120
M118-
M120
M120
M120 M125
M125-
M130
M125-
M130
M125-
M130
M130-
M136
M130-
M136
M130-
M136
M130-
M136
M136-
M140
M136-
M140 M140
M140
M140
M140
Belt(s)
Motor
HP
7½ 2 BX 7/16" 6 - 8 5½ - 7
7½ 2 BX 9/16" 6 - 8 5½ - 7
50-60 6 BX 9/16" 7-9 6-8
50-60
Qty Type
1 1 A 1/4" 2 - 3 1 - 2
2 1 A 1/4" 2½ - 4 1½ - 3
3 1 BX 1/4" 4½ - 6 4 - 5½
5 2 BX 1/4" 3 - 5 2½ - 4
5 2 BX 7/16" 5 - 7
10 2 BX 7/16"
15 2 BX 7/16" 7 - 9 6 - 8
10 2 BX 9/16"
15 2 BX 9/16" 7 - 9 6 - 8
20 3 BX 9/16"
25 3 BX 9/16" 7 - 9 6 - 8
25 4 BX 9/16"
30 4 BX 9/16"
30 3 5VX 9/16" 7 - 9 6 - 8
40 5 BX 9/16"
40 3-4 5VX 9/16" 8 - 10 7 - 9½
4 or
5
75 5 5VX 9/16" 10-12 9-11
75 6 5VX 9/16"
M-Series Technical Manual 47 Cambridge Engineering, Inc.
Page 50
REFERENCE
HEATER ROOF AND WALL OPENINGS
Horizontal Mount
Wall Opening
Discharge Inlet
Model W H W H W L
M110
M112
M115
M118
M120
M125
M130
M136
M140
18.25" 18.25" 32" 35.25" 19.25" 19.25"
19.75" 19.75" 32" 35.25" 20.75" 20.75"
22.75" 22.75" 46" 35.25" 23.5" 23.75"
25.5" 25.5" 50" 55" 26.5" 26.5"
29.5" 29.5" 56" 55" 30.5" 30.5"
35" 35" 68" 71.75" 36" 36"
41" 41" 89.75" 71.75" 42" 42"
47" 47" 89.75 96.75" 48" 48"
54" 54" 119.5" 101" 55" 55"
Vertical Mount
Wall Opening
Discharge Inlet
Model W H W H
M118
M120
M125
M130
M136
1
Based on 2" added to both the length and width of the discharge duct
2
Based on 3" added to both the length and width of the discharge duct
25.5" 25.5" 69" 57.5"
29.5" 29.5" 75" 57.5"
35" 35" 81" 81.5"
41" 41" 101.5" 81.5"
47" 47" 107" 81.5"
1
Roof
Opening
1
2
HEATER DISCHARGE DIMENSIONS
Discharge Opening Discharge Duct Size
Model W L W L
M110
M112
M115
M118*
M120*
M125*
M130*
M136*
M140
*Applies to both horizontal and vertical mount
Cambridge Engineering, Inc. 48 M-Series Technical Manual
12.7" 13.6" 16.25" 16.25"
12.9" 15.9" 17.75" 17.75"
18.6" 15.9" 20.75" 20.75"
21.9" 18.7" 23.5" 23.5"
24.5" 24.7" 27.5" 27.5"
31.2" 31.2" 33" 33"
36.6" 36.6" 39" 39"
42.5" 42.8" 45" 45"
50" 50" 52" 52"
Page 51
REFERENCE
GAS TRAIN DRAWINGS
Horizontal Mount < 400 MBH CSA Certified
Vertical Mount > 400 MBH Low Pressure CSA Certified
Horizontal Mount > 400 MBH High Pressure CSA Certified
M-Series Technical Manual 49 Cambridge Engineering, Inc.
Page 52
BLOWER CLEANING
The blower wheel should be examined for accumulation of dust on the blades. These surfaces must be kept clean. Dirt accumulation will result in significant air flow reduction and/or possible imbalance of the blower wheel. Prolonged imbalance CAN result in catastrophic failure of the blower wheel and other related components.
BURNER CLEANING
The Cambridge Engineering burner is for the most part self-cleaning. However, if the application is extremely dirty or dusty, it may become necessary to periodically clean the burner. Remove and clean the burner in accor­dance with the following recommended procedures.
to the coil is correct, sluggish valve operation, excessive noise, or leakage will indicate that cleaning is required. Refer to step 8, Gas Valve Leak Check, of the Start-up Procedures (see page 32).
mWARNING:
In the extreme case, faulty valve operation will occur and the valve may fail to open or fully close.
IMPORTANT
It is not necessary to remove the valve from the gas train for cleaning.
1. Turn the heater disconnect switch off. Close the man­ual gas supply shut-off valve.
2. Loosen the union in the gas train.
CAUTION:
The igniter is made of silicon carbide material and should be handled with care to avoid breakage.
3. Disconnect the ignition cable from the burner and then remove the flame rod and the igniter.
4. Examine the flame rod ceramic for cracks and replace if necessary. Clean the flame rod element with emery cloth to remove oxidation.
5. Remove the fasteners that secure the burner to the
housing. The burner will then be free to slide out.
mCAUTION:
Be sure to take necessary safety precautions (such as wearing eye protection, etc.) before attempting this step.
mWARNING:
To prevent the possibility of severe personal inju­ry or property damage, turn off electrical power, close the upstream manual gas valve, depres­surize the valve, extinguish all open flames and avoid any type of sparking or ignition. Vent haz­ardous or combustible fumes to a safe area before servicing the valve.
6. Clean the burner by back-flushing using high pressure air (40-80 PSI). Continue back-flushing until dust par­ticles are completely expelled from the burner.
7. Re-install the burner using the above steps in reverse
order.
GAS VALVE CLEANING
All solenoid valves should be cleaned periodically. The time between cleanings will vary depending on the medium and service conditions. In general, if the voltage
Cambridge Engineering, Inc. 50 M-Series Technical Manual
Page 53
ASCO GAS VALVES: SERIES 8214
Disassemble the valve (See page 62) and clean all parts as follows:
IMPORTANT
If parts are worn or damaged, install a complete ASCO Rebuild Kit.
mWARNING:
To prevent the possibility of severe personal injury or property damage, check the valve for proper operation before returning to service. Also perform a gas valve leak check and gas train leak check in accordance with steps 8 and 9 of the Start-up Procedures (see page 32).
1. Remove the solenoid enclosure.
2. Remove the bonnet screws, valve bonnet, bonnet gas­ket, core/diaphragm sub-assembly and body gasket.
3. All parts are now accessible to clean or replace.
4. Lubricate the bonnet gasket and body gasket with a light coat of Dow Corning equivalent high-grade silicone fluid.
5. Apply a light coat of RemGrit TFL 50® Dry Lubricant to: the valve seat; the valve body surface where dia­phragm assembly contacts the valve body and body gasket; and internal surface of the valve bonnet where the diaphragm assembly contacts the bonnet when the valve is in the energized (open) position.
IMPORTANT:
If the valve has been disassembled for inspection and cleaning only and a Rebuild Kit is not being installed, lubricate the following with RemGrit TFL 50® Dry Lubricant:
®
200 Fluid lubricant or an
ORDERING INFORMATION FOR ASCO REBUILD KITS
Parts marked with an asterisk (*) in the exploded views are supplied in Rebuild Kits.
When ordering Rebuild Kits for ASCO valves, order the Rebuild Kit number stamped on the valve nameplate. If the number of the kit is not visible, order by indicating the number of kits required, and the Catalog Number and Serial Number of the valve(s) for which they are intended.
GAS TRAIN LEAK CHECK
Periodically check the gas control assembly, internal and external piping for leaks. Refer to step 9, Gas Train Leak Check, of the Start-up Procedures (see page 32). All relief vents on the gas controls should be checked for blockage (gas pressure regulators and pressure switches).
• Diaphragm assembly on both sides
• Main disc at base of core/diaphragm sub-assembly
• Pilot disc at base of core assembly
mCAUTION:
Do not distort the hanger spring between the core assembly and the diaphragm assembly when lubricating the pilot disc.
6. Replace the body gasket and the core/diaphragm sub­assembly with the closing spring attached. Locate the bleed hole in the core/diaphragm sub-assembly
approximately 30˚ CCW from the valve inlet.
7. Replace the valve bonnet and the bonnet screws (6). Torque the screws in a crisscross manner to 100 ± 10 in-lbs. Replace the solenoid and make the electrical hookup.
M-Series Technical Manual 51 Cambridge Engineering, Inc.
Page 54
Indicates parts supplied
in ASCO Rebuild Kit.
SOLENOID BASE SUBASSEMBLY
BONNET SCREW
BLEED HOLE
Locate bleed hole in
core/diaphragm sub---
assembly approximately
30° from valve inlet
BONNET GASKET
VALVE BONNET
CORE/DIAPHRAGM SUBASSEMBLY
BODY GASKET
CAUTION
Do not damage
valve seat
VALVE BODY
Disassembled View of ASCO Valve
Cambridge Engineering, Inc. 52 M-Series Technical Manual
Page 55
FILTERS
Filters may be installed in the V-bank filter section or in the intake of the rainhoods. These may be of the dispos­able or permanent type. Filters are removed and replaced from the V-bank filter section by opening the filter access door. Filters are removed from the rainhood by removing the retainer from the end of the rainhood. To remove the retainer, remove the shipping screws from the ends of the retainer, then pull the retainer back and downward from the rainhood.
Permanent Filters are 2" thick washable, metal mesh filters that may be installed in the rainhoods or in the V-bank filter section.
Disposable Filters may be one of two types:
1. Pleated panel filters are 2" thick filters which slide into tracks provided in the V-Bank filter section only. (Do not use this type of filter in the rainhoods because of moisture exposure.)
2. Continuous filters are constructed of a two-stage media. The white side faces into the airstream and the orange side faces the exiting air. Internal frames ensure rigidity, while the continuous media eliminates gaps between filters and effectively seals against the filter tracks. These filters are unaffected by moisture and may be installed in the rainhoods or in the V-bank filter section.
Disposable pleated panel filters are replaced when they become dirty. Replace the filter with the same size of filter which is removed from the filter section. Note the airflow markings on the filter.
Disposable continuous filters are replaced when they become dirty. Continuous filters are manufactured one panel wide by 24 panels long. (eg., 16" x 600" filters consists of 24-16" x 25" panels and 25" x 384" filters consist of 24-25" x 16" panels.) Cut these filters between panels to select the continuous length required for the fil­ter track. If four 16" x 25" panels are required for a filter track, simply cut a four-panel length. Install the filters with the white side toward the air inlet.
CLEANING AND REPLACEMENT
Shut down the heater and turn off the blower before ser­vicing the filters. Remove the filters from the rainhood or filter section. Handle carefully to prevent debris from being dislodged from the filter into the heater.
Permanent filters can be cleaned using a stream of water or soap and water. Back flush the filters until the water comes out clean. If soap is used, ensure that all soap is rinsed out of the filter. Visually inspect the filter to ensure that it is clean. Allow to dry before returning to service.
M-Series Technical Manual 53 Cambridge Engineering, Inc.
Page 56
Filters for Horizontal Mount
Filter Type
Size (inches) 16x20 16x25 20x20 20x25 16x480 16x600 20x384 20x480 20x600 25x384 25x480
M110 M112 M115
M118
M120
M125
Rainhood
M130
M136
M140
Single 3 3 (1x3)
Single 3 3 (1x3)
Single 4 2 4 (2x2) 2 (1x2)
Upper 2 2 2 (1x2) 2 (1x2) Lower 2 2 2 (1x2) 2 (1x2) Upper 6 3 6 (2x3) 3 (1x3) Lower 4 2 4 (2x2) 2 (1x2) Upper 12 12 (4x3) Lower 8 8 (4x2) Upper 12 4 12 (3x4) 4 (1x4)
Lower 9 3 9 (3x3) 3 (1x3)
Upper 15 5 15 (3x5) 5 (1x5) Lower 12 4 12 (3x4) 4 (1x4) Upper 5 25 5 (1x5) 25 (5x5) Lower 4 20 4 (1x4) 20 (5x4)
M110 M112
M115
M118 M120 M125
Filter Section
M130 M136 M140
Permanent or
Disposable Panel
3 3 (3x1)
3 3 (3x1)
6 6 (3x2)
8 8 (4x2)
10 10 (5x2)
20 20 (5x4)
24 24 (6x4)
28 28 (7x4)
56 56 (8x7)
Continuous*
Filters for Vertical Mount
Filter Type
Size (inches) 16x20 16x25 20x20 20x25 16x480 16x600 20x384 20x480 20x600 25x384 25x480
M118
M120
M125
Rainhood
M130
M136
Upper 8 8 (4x2) Lower 4 4 (4x1) Upper 2 4 2 (1x2) 4 (2x2) Lower 2 4 2 (1x2) 4 (2x2) Upper 9 9 (3x3) Lower 6 6 (3x2) Upper 3 9 3 (1x3) 9 (3x3) Lower 3 9 3 (1x3) 9 (3x3) Upper 15 15 (5x3) Lower 15 15 (5x3)
M118 M120 M125 M130
Filter Section
M136
* Continuous filters are manufactured in lengths of 24 panels. Cut filter panels like chain links. For example, 6 (2x3) means cut
2 rows x 3 panels long for total of 6 panels of this type. Cut only between filter panels.
Permanent or
Disposable Panel
9 9 (3x3)
16 16 (4x4)
15 15 (5x3)
36 36 (6x6)
30 30 (6x5)
Continuous*
Cambridge Engineering, Inc. 54 M-Series Technical Manual
Page 57
REFERENCE
ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING M110 - M115
M-Series Technical Manual 55 Cambridge Engineering, Inc.
Page 58
REFERENCE
ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING M118 - M136
Cambridge Engineering, Inc. 56 M-Series Technical Manual
Page 59
ELECTRICAL CONTROL ENCLOSURE ISOMETRIC DRAWING
M140
M-Series Technical Manual 57 Cambridge Engineering, Inc.
Page 60
REFERENCE
ELECTRICAL WIRING DIAGRAMS
Series 14
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX1 Auxiliary Contact AX Auxiliary Contact CR1 Control Relay D & D1 Damper Motor & End Switch DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat EFI Exhaust Fan Interlock FR Flame Rod FSR Flame Safeguard Relay (HSI)
Cambridge Engineering, Inc. 58 M-Series Technical Manual
SYMBOL DESCRIPTION
FU1 Fuse 24 Volt Control FU2 Fuse 120 Volt Control HGP High Gas Pressure Switch HL High Limit IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve
SYMBOL DESCRIPTION
OL Overload Relay PT Purge Timer RA Remote Adjust R1A&R1B Relay Gas Valve SOV Shut-Off Valve - Gas SSV Safety Shut-Off Valve - Gas SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Fan/Off/Heat SW4 Switch - SOV Leak Test T1 Multi-Tap Transformer (24&120 Volt) T2 Class 2 Transformer (24 Volt) TS Temperature Sensor
Page 61
Series 14
Kitchen Ventilation System
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX Auxiliary Contact AX1 Auxiliary Contact AX2 Auxiliary Contact CR1 Control Relay DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat FPI Fire Protection Interlock FR Flame Rod FSR Flame Safeguard Relay (HSI)
M-Series Technical Manual 59 Cambridge Engineering, Inc.
SYMBOL DESCRIPTION
FU1 Fuse 24 Volt Control FU2 Fuse 120 Volt Control HL High Limit IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LTC Low Temperature Cutout M Motor - Supply Fan MS1 Motor Starter - Supply Fan MS2 Motor Starter - Exhaust Fan MV Modulating Valve
SYMBOL DESCRIPTION
OL1 Overload Relay - Supply Fan OL2 Overload Relay - Exhaust Fan PT Purge Timer RA Remote Heat Adjust R1A&R1B Relay-Gas Valve SOV Shut-Off Valve - Gas SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Off/On T1 Multi-Tap Transformer (24&120 Volt) T2 Class 2 Transformer (24 Volt) TS Temperature Sensor
Page 62
Series 44
M140
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX1 Auxiliary Contact AX Auxiliary Contact CR1 Control Relay D & D1 Damper Motor & End Switch DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat FR Flame Rod FSR Flame Safeguard Relay (HSI) FU1 Fuse 24 Volt Control
Cambridge Engineering, Inc. 60 M-Series Technical Manual
SYMBOL DESCRIPTION
FU2 Fuse - 120 Volt Control HGP High Gas Pressure Switch HL High Limit IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve OL Overload Relay
SYMBOL DESCRIPTION
PT Purge Timer R1A&R1B Relay Gas Valve RC Resistor - Calibration SOV Shut-Off Valve - Gas SSV Safety Shut-Off Valve - Gas STS Space Temperature Selector SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Fan/Off/Heat SW4 Switch - SOV Leak Test T1 Multi-Tap Transformer (24&120 Volt) T2 Class 2 Transformer (24 Volt) TS Temperature Sensor
Page 63
Series 44
Tamperproof Controls
Operating Thermostat
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX1 Auxiliary Contact AX Auxiliary Contact CR1 Control Relay D & D1 Damper Motor & End Switch DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat EFI Exhaust Fan Interlock FR Flame Rod FSR Flame Safeguard Relay (HSI)
FU1 Fuse 24 Volt Control FU2 Fuse 120 Volt Control
M-Series Technical Manual 61 Cambridge Engineering, Inc.
SYMBOL DESCRIPTION
HL High Limit IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve OET Operating Electronic Thermostat OL Overload Relay
PT Purge Timer R1A&R1B Relay Gas Valve R2 Relay - Intermittent/Continuous
SYMBOL DESCRIPTION
RC Resistor - Calibration RTS Remote Temperature Sensor SOV Shut-Off Valve - Gas SSV Safety Shut-Off Valve - Gas STS Space Temperature Selector SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Fan/Off/Heat SW4 Switch - SOV Leak Test T1 Multi-Tap Transformer (24&120 Volt) T2 Class 2 Transformer (24 Volt) TPS Tamper Proof Space Sensor TS Temperature Sensor
Page 64
Series 44
Temperature Setback System
Temperature Averaging System
Tamperproof Controls
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX1 Auxiliary Contact AX Auxiliary Contact CR1 Control Relay D & D1 Damper Motor & End Switch DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat FR Flame Rod FSR Flame Safeguard Relay (HSI) FU1 Fuse 24 Volt Control FU2 Fuse 120 Volt Control
Cambridge Engineering, Inc. 62 M-Series Technical Manual
SYMBOL DESCRIPTION
HL High Limit IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LTC Low Temperature Cutout M Motor MS Motor Starter MV Modulating Valve OTS Override Timer Switch OL Overload Relay PT Purge Timer R1A&R1B Relay - Gas Valve
SYMBOL DESCRIPTION
R2 Relay - Intermittent/Continuous RC Resistor - Calibration RTS Remote Temperature Sensor SOV Shut-Off Valve - Gas SSV Safety Shut-Off Valve - Gas STS Space Temperature Selector SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Fan/Off/Heat SW4 Switch - SOV Leak Test T1 Multi-Tap Transformer (24&120 Volt) T2 Class 2 Transformer (24 Volt) TPS Tamper Proof Space Sensor TS Temperature Sensor TSS Temperature Setback System
Page 65
Series 44
Tamperproof Controls
Variable Frequency Drive
Room Pressure Controller
SYMBOL DESCRIPTION
AFL Air Flow Switch - Low AFH Air Flow Switch - High AMP Amplifier Solid State AX1 Auxiliary Contact AX Auxiliary Contact BR Relay - Blower CR1 Control Relay D & D1 Damper Motor & End Switch DISC Service Disconnect Non - Fused DTS Discharge Temperature Sensor EAT Entering Air Thermostat FR Flame Rod FSR Flame Safeguard Relay (HSI)
FU1 Fuse 24 Volt Control FU2 Fuse 120 Volt Control HGP High Gas Pressure Switch
M-Series Technical Manual 63 Cambridge Engineering, Inc.
SYMBOL DESCRIPTION
HL High Limit HPR Relay - High Pressure IG Ignitor L1 Light - Alarm L2 Light - Fan L3 Light - Heat LFS Low Fire Start LPR Relay - Low Pressure LSK Low Speed Kit LSR Relay - Low Speed LTC Low Temperature Cutout M Motor MV Modulating Valve PDA Profile Damper Adjustment PDM Profile Damper Motor
PT Purge Timer
SYMBOL DESCRIPTION
PXR Pressure Transducer R1A&R1B Relay Gas Valve SOV Shut-Off Valve - Gas SSV Safety Shut-Off Valve - Gas STS Space Temperature Selector SW1 Service Switch - Fan SW2 Service Switch - Heat SW3 Switch - Fan/Off/Heat SW4 Switch - SOV Leak Test SW5 Service Switch - Run/Test T1 Multi-Tap Transformer (24&120 Volt) T3 Class 2 Transformer (24 Volt) TPS Tamper Proof Space Sensor TS Temperature Sensor VFD Variable Frequency Drive
Page 66
CONNECTION DIAGRAM
(Typical)
PROVIDED ON MAXITROL SERIES 44 SYSTEMS AND SERIES 14 SYSTEMS WITH OPTIONAL RHA CONTROL
FOR MAXITROL SERIES 44 SYSTEMS AND SERIES 14 SYSTEMS WITH RHA CONTROL USE 2 WIRE SHIELDED TWISTED-PAIR 18 AWG MINIMUM RUN SEPARATE FROM ALL OTHER AC WIRING GROUND SHIELD AT REMOTE CONTROL STATION ONLY
Cambridge Engineering, Inc. 64 M-Series Technical Manual
Page 67
GAS CONTROL SYSTEMS
Maxitrol Series 14
The Maxitrol Series 14 controls electronically modulate the burner input to maintain a selected dis­charge temperature. The discharge temperature is set on the amplifier (AD1014) between 55°F and 90°F with the standard controls. As an
option, the discharge temperature can be set on a Remote Heat Adjust (TD114) control between 55°F and 130°F. The Remote Heat Adjust con­trol can be mounted in the heater control enclosure or in the Remote Control Station.
Maxitrol Series 44
The Maxitrol Series 44 controls electronically modulate the burner input to maintain a constant space temperature by increasing or decreasing the discharge tempera­ture. The Space Temperature Selector (T244A) is set to main-
tain the space temperature of the heated space by controlling the heater output between the MIN and MAX setting on the amplifier. The MIN dial setting determines the minimum discharge temperature the heater will deliver (40°F to 80°F). The MAX dial set­ting determines the maximum discharge temperature the heater will deliver (80°F to 140°F)
Intermittent/Continuous Control
The Intermittent/Continuous Control allows the burner input to be modulated to be operated continuously at modulating discharge temperature for make-up air (see Maxitrol 44 above) or operated intermittently based on a thermostat at maximum discharge temperature for space heating.
Requires Maxitrol 44 controls and a signal to switch between modes (Exhaust Fan Interlock, Temperature Setback System, Manual Make-Up Air Switch, etc.)
REMOTE CONTROL STATION COM­PONENTS
Remote Control Station
The Remote Control Station is a lockable NEMA 1 enclosure (9" wide x 14" high x 5" deep) equipped with a three position key lock selector switch (Summer Ventilation – Off – Heating) and indicat­ing lights for blower operation (green),
burner operation (red), and reset (amber). An auxiliary contact wired between terminals Z1 and Z2 is required to control heater operation in the heat­ing mode. This can be accomplished by an Exhaust Fan Interlock, a Manual Make-up Air Switch, an Operating Electronic Thermostat, etc.
IMPORTANT
A number of the components listed below can be combined to yield a custom Remote Control Station to address a wide variety of applications.
Maxitrol Series 14 Remote Heat Adjustment Dial
The adjustment dial on the remote heat adjust (TD114) is either mount­ed on the exterior of the door of the Remote Control Station or mounted inside the
Remote Control Station for tamperproof applications. The remote heat adjust­ment control permits manual adjustment of the dis­charge temperature from 55˚F to 90˚F. The override tem­perature selector dial, visible from the top of the remote heat adjustment control, increases the discharge tem­perature above the setting on the dial face by the incre­ment selected (10˚F to 40°F) when a jumper or switch contact is provided across terminals 20 and 22.
Maxitrol 14 Space Temperature Override
The Maxitrol Series 14 with Space Thermostat control system uses the Maxitrol Series 14 controls described above along with an electronic space thermostat switch contact to automatically increase the discharge tem­perature.
M-Series Technical Manual 65 Cambridge Engineering, Inc.
Page 68
Maxitrol Series 44 / Tamperproof
The Maxitrol Series 44 / Tamperproof controls function identically to the Maxitrol Series 44 con­trols (see gas control system) except the space temperature selector (T244A) is replaced with two devices. The adjustable portion, the space temperature selector (TD244A), is mounted inside the Remote Control Station, and the non-adjust-
able (tamperproof) space sensor (TS244A) is mounted in the space being heated.
Maxitrol Series 44 / Hazardous Area
The Maxitrol Series 44 / Hazardous Area is the same as the Maxitrol Series 44 / Tamperproof, except the space sensor (TS244A) is replaced by a space sensor with epoxy coated circuitry (ES225A). The standard Remote Control Station is not suitable for hazardous areas and would need to be mounted outside of the hazardous area.
Operating Electronic Thermostat
The operating electronic thermostat is wired between terminals Z1 and Z2 to control heater ON/OFF operation in the heating mode (see pages 65).
Non-Adjustable Thermostat
The non-adjustable thermostat is a fixed temperature, solid state, epoxy sealed thermostat with a specified temperature setpoint, either: 41°F, 50°F, 55°F, 60°F, or 65°F. It is wired between terminals Z1 and Z2.
Temperature Setback System
The temperature setback system is a com­bination seven-day programmable timer with independent programs for summer ventila­tion/heating modes and integral electronic thermostat with separate selectable day/ night setback temperatures (see page 67). The thermostat contact is wired between
Z1 and Z2.
Manual Make-Up Air Switch
A manual make-up air toggle switch is used to manu­ally turn the heater on and off. It is either mounted on the exterior of the door of the Remote Control Station or mounted inside the Remote Control Station for tamper­proof applications.
Exhaust Fan Interlock
An exhaust fan interlock is used to interlock the make­up air heater as a slave to an exhaust fan. Terminals are provided in the Remote Control Station for wiring of dry contacts (by others).
INDIVIDUAL HEATER COMPONENT DESCRIPTIONS
AIR FLOW SWITCH (High and Low)
The air flow switches sense the pres­sure drop across the burner profile plate. They are factory set and not adjustable. They are designed to pre­vent burner operation if the pressure drop across the burner drops below
0.40
inch WC or increases above
0.85
inch WC for natural gas applications or below
0.60
inch WC or above 1.12 inches WC for LP gas
applications.
AMPLIFIER
The amplifier creates a voltage output to drive an electronic proportioning gas valve to maintain the selected discharge temperature (Maxitrol Series 14) or space temperature (Maxitrol Series 44). On Maxitrol Series 14 control systems, the discharge temperature is set either
on the amplifier (AD1014) or the Remote Heat Adjust (TD114). On Maxitrol Series 44 control systems, the range of the discharge temperature is set on the amplifier (A1044), but the space tempera­ture selector controls when more or less heat is required.
Clogged Filter Light
The clogged filter light is an alarm light mounted in the Remote Control Station to indicate a clogged filter con­dition. Includes an adjustable pressure switch mounted in the make-up air heater control enclosure to monitor the pressure drop across the filters.
Cambridge Engineering, Inc. 66 M-Series Technical Manual
CONVENIENCE OUTLET
A convenient 115 volt GFI duplex receptacle is provided inside the heater’s electrical enclosure. The electrical supply source for this device can be either the heater’s control power transformer (5 amps max.) or a separate outside source (15 amps max.).
Page 69
DAMPER MOTOR
The damper motor operates on 24 Volts AC and transmits power to the motor starter when the damp­er blades are fully open by the closure of the damper end switch. The damper end switch is an
adjustable internal auxiliary switch which has been factory set to operate when the damper is fully open. The damper motor will power closed when the heater cycles off. The damper motor will not close unless the blower service switch is in the
“REMOTE” position. Refer to detailed instructions
regarding the replacement and adjustment of the damper motor (see page 53).
DISCHARGE TEMPERATURE SENSOR
The discharge temperature sensor is
mounted on the fan housing and is a component of the Maxitrol Series 14 and Series 44 temperature control sys­tems. It senses the average fan dis­charge temperature and transmits a resistance signal back to the ampli­fier that corresponds to the dis-
charge temperature. The Maxitrol Series 44 and Maxitrol Series 44/Tamperproof tempera­ture control systems use the Maxitrol Series 44 sensor (TS144). The Maxitrol Series 14 control systems use the Maxitrol Series 14 sensor (TS114).
DISCONNECT SWITCH
The non-fused disconnect switch is provided on all heaters and includes a lockable operating knob. The disconnect must be off before accessing the electrical con­trol enclosure. Once the control enclo-
sure is open, experienced service technicians may activate the electrical circuit to assist in trou­bleshooting.
EXHAUST FAN CONTACT
The exhaust fan contact is an auxiliary dry contact that is mechanically interlocked to operation of the heater’s motor starter and is provided with terminals located in heater’s electrical enclosure. The dry contact is typically wired into an exhaust fan control circuit to activate the exhaust fan as a slave to the make-up air heater.
FLAME SAFEGUARD RELAY
The flame safeguard relay supplies 24 Volts AC to the igniter for 4 seconds prior to the gas valve being energized. If the burner does not light (flame is not estab­lished within 7 seconds), this control
will lock out. If flame signal is lost during burner operation, the control will allow one retry for ignition.
FLAME ROD
The flame rod senses the pres­ence of flame, and signals the flame safeguard relay. The pres­ence of flame is detected by the flame rectification of the AC sig-
nal that is supplied to the flame rod, thus creating the DC response. The resulting current flow produced can be measured with a DC microamme­ter. The reading should be steady and between 2.0 and
6.0 microamps (mA).
FUSE BLOCK
The fuse block provides line fusing for
branch circuit protection. It is wired in conjunction with the non-fused discon­nect switch.
HIGH GAS PRESSURE SWITCH
The high gas pressure switch is a manual reset safety device to lock out the burner operation should large gas pressure fluctuations occur. The high gas pressure switch should be set at 25% above manifold gas pressure. The adjustment screw is located
under the top plate.
HIGH PRESSURE REGULATOR
The high pressure regulator is required when the gas supply pressure exceeds the nameplate rating for the heater. The high pressure regulator assembly is also furnished with a high gas pres-
sure manual shut-off valve and a tap for measuring the upstream gas pressure. The high pressure regulator is a positive lock-up type regulator which must be vented to the outdoors. It is sized according to the gas supply pressure and the capacity requirements of the heater.
M-Series Technical Manual 67 Cambridge Engineering, Inc.
Page 70
HIGH TEMPERATURE LIMIT
The high temperature limit opens when the discharge air temperature exceeds
150˚F. This limit must be manually reset.
INCLINED MANOMETER
An inclined manometer with a range of
-0.1 to 1.0 inch WC is provided on each heater with manual profile damper adjustment to indicate the pressure drop across the burner profile plate. The pressure drop should be set without the burner operating (blower only) at 0.68
inch WC for natural gas applications and 0.90 inch WC for LP applications. If the heater is sup­plied with a filter section or filters in the rainhood, increase the manometer reading to 0.72 inch WC for natural gas and to 0.94 inch WC for LP gas heaters.
DIFFERENTIAL PRESSURE SWITCH/GAUGE
A differential pressure switch/gauge is available as part of the Automatic
Prole Adjust system to control the pressure drop across the burner prole
plate. The differential pressure switch
drives a Prole Damper Adjust Motor
to maintain approximately 0.68 inch WC for natural gas applications, or approximately 0.90 inch WC for LP applications.
IGNITER
The hot surface igniter is the ignition source for lighting the gas in the burn­er. It is made of silicon carbide which is very fragile. Care should be used in handling. It operates on 24 Volts and
the current ranges from 1.3 to 1.7 amps. It will reach
temperatures in excess of 2400˚F during the ignition
trial. It is furnished with a sleeve for shock mounting and sealing the igniter in the mounting tube.
heater’s electrical enclosure. Furnished with safety guards. 100 watts maximum, each. A separate electrical supply source is required.
LEAK TEST FACILITY
The leak test facility is provided on all heaters over 400,000 Btu/hr and consists of a momentary switch for the first safety shut-off valve in the gas train and a gauge port between the first and second safety shut-off valve. By holding the gas valve momentary switch closed, the first
gas valve is energized which allows gas pressure to build on the seat of the second gas valve. The gauge port between valves is used to determine if the first gas valve seat is properly sealed.
MODULATING VALVE
The modulating valve responds to a 4 to 24 Volt DC signal from the amplifier to modulate the flow of gas to the burner. On the Maxitrol M511 or M611 valve, the minimum fire adjusting
screw is located on the far side of the valve under the dust cover. On the Maxitrol MR212 valve, the minimum fire adjusting screw is located under the large dust cover. The MR212 modulating valve also serves as the manifold pressure regulator to control the burner manifold pressure. The MR212 is rated for 5 PSIG.
COMBINATION VALVE
The combination valve serves as a mani­fold pressure regulator and redundant gas shut-off valve. This control is typically used for gas capacities below 400,000 Btu/hr. The valve operates on 24 Volts AC power. The combination valve is rated for a maxi-
mum gas supply pressure of 14 inches WC.
INTERIOR LIGHT(S)
Available for the heater cabinet, electrical control enclosure, and/or gas train enclo­sure. Light switches are located inside the
Cambridge Engineering, Inc. 68 M-Series Technical Manual
MANIFOLD PRESSURE REGULATOR
The manifold pressure regulator con­trols the burner manifold pressure. When the MR212 valve is used, this
Page 71
modulating valve also serves as the pressure regulator. The maximum gas supply pressure rating is normally determined by the exposed pressure rating of the regulat­ing device. The RV61 and RV81 are rated at 1 PSIG; and the MR212 is rated at 5 PSIG. (For make-up air heaters rated at 400,000 Btu/hr or below, see the combi­nation valve above.)
MOTOR STARTER, OVERLOAD, & AUXILIARY CONTACT
The motor starter assembly consists of a motor starter, overload relay and auxiliary contact. The overload relay protects the motor from excessive current or single phas­ing. If the overload relay trips, it must be reset manually. The auxiliary contacts are used in the gas valve safety circuit as
an indication the blower is operating, and as an optional exhaust fan contact for interlocking other equipment with the operation of the heater.
MULTI-FUNCTIONAL PC BOARD
The multi-functional PC board provides five (5) separate functions for heaters with the Maxitrol Series 14 or Series 44 controls. The functions are as follows:
1) Blower Relay (CR1) which is ener­gized on a “call for blower” from the Remote Control Station.
2) The LTC (Low Temperature Cutout) circuit func­tions to turn off the blower in approximately 3 1/2 minutes if any of the following occurs: (a) The inlet temperature drops below the selectable LTC setpoint (40˚F, 45˚F, 50˚F, or 55˚F) in the ventila­tion mode; (b) the gas valve fails to remain ener­gized during a heating cycle or (c) the high airflow switch contacts indicate the burner profile plate pressure drop is too high.
3) The EAT (Entering Air Thermostat) circuit func­tions automatically to turn off the burner when the outdoor temperature reaches the selectable EAT
setpoint (45˚F, 50˚F, 55˚F, 57.5˚F, 60˚F, 62˚F, 64˚F, 66˚F, 68˚F or 70˚F).
4) The PT (Purge Timer) circuit function is preset at the factory to provide four air changes within the heater cabinet prior to an ignition attempt (normally set at 4 or 8 seconds). If inlet ducting is attached to the heater, the delay time can be increased to 8, 16, or 32 seconds, as applicable.
5) The patented LFS (Low Fire Start) circuit func-
tion limits the initial heater firing for the first 15 sec­onds of a heating cycle to obtain proper ignition. The voltage to the modulating valve is adjusted between 9 and 13 Volts DC by an adjustable potentiometer on the multi-functional PC board.
SERVICE SWITCH
The service switches are mounted in the electrical control enclosure. In the “LOCAL” or “OFF” position, the service techni­cian has local control of the heater. These
switches must be placed in the “REMOTE” position for normal control from the Remote Control Station.
SPACE TEMPERATURE SELECTOR
The space temperature selector is part of the Maxitrol Series 44 control system. The space temperature selector senses the space temperature. A 3˚F drift above the set temperature will cause the heater to modulate to the MIN setting on the
amplifier and a 3˚F drift below the set temperature will cause the heater to modulate to the MAX setting.
TRANSFORMER
Heaters are furnished with a dual voltage transformer unless the pri­mary voltage is 115 Volts. The transformer furnished depends on the primary voltage (208, 230, 460 or 575 Volts). This transformer pro­vides secondary control voltages of
24 and 115 Volts. Heaters supplied for 115 Volts are furnished with a 24 Volt secondary transformer only. Secondary fusing is provided in all Class I transformer circuits to protect the downstream components from short circuit. Fuse sizing is as follows: FNM-6.25 for 150 va 24 Volt and FNM-1.6 for 150 va 115 Volt. Consult the heater wiring diagram to identify the proper fusing for the heater in question. Do not increase the fuse rating over that which is specified.
M-Series Technical Manual 69 Cambridge Engineering, Inc.
Page 72
DAMPER MOTOR REPLACEMENT & ADJUSTMENT
1. Before re-installing the damper motor into the heater assembly, remove the black plastic weather cover from the damper motor by removing the screw that secures the cover to the damper assembly using either a flat tip screw driver or a 1/4" nut driver. It may be necessary to twist the cover slightly to disengage it from its mounting to the end of the motor after the screw is removed.
2. Verify the damper motor is in the closed position (Drive tube is retracted with a minimum of 1/4" gap between drive tube and body of the damper assem­bly).
3. Verify the inner cam has fully engaged the lower limit switch plunger and the lower limit switch (next to the body of the damper motor) shows continuity between the common (C) terminal and the normally open (NO) terminal.
CAUTION:
If the lower limit switch does not indicate continuity, the damper motor must be driven to the fully closed position before connecting the damper linkage to the drive tube of the damper assembly.
a deep well 1/2" hex socket or nut driver to manu­ally rotate the cam counterclockwise a few clicks, as required, to obtain the correct starting position (see Figure 1).
Figure 1
5. Verify the heater disconnect switch is turned off and the Service Switches are in the “OFF” position.
6. Connect wires to terminals as shown in Figure 2 and re-install the weather cover.
CAUTION:
If the drive tube bottoms out against the damper motor housing, damage to the PC board or trip­ping of the onboard fuse may result. If the fuse trips, place the blower service switch in the “OFF” position for 15 seconds to allow the fuse to reset. Proceed with steps 4 through 10 BEFORE connect­ing the damper motor to the linkage arm.
4. Verify the cam location on the upper cam is set just short of the four o’clock position with respect to the switch plunger being the twelve o’clock reference position. If it is beyond the four o’clock position, use
7. Remove the push-in plug (located in the weather cover) to have access to the upper cam adjusting nut.
8. Connect the motor pivot to the damper motor support bracket using the 3/8" diameter clevis pin. Do not connect the damper linkage at this time.
Cambridge Engineering, Inc. 70 M-Series Technical Manual
Figure 2
Page 73
9. Remove the wire from the “G” terminal of the termi­nal block. (This is to avoid a “Call-for-Fan” signal from the Remote Control Station during the next two steps).
10. Let the damper assembly hang down (suspended
by the damper motor support bracket) and turn the heater disconnect on and momentarily turn the blower service switch to the “LOCAL” position (for approximately 5 seconds). Do not restrain the drive tube from turning freely. Then, turn the blower service switch to the “REMOTE” position until the damper motor drive tube stops turning. (Drive tube is now fully retracted).
11. Turn the heater disconnect switch off and manually
trip the motor starter overload. The manual trip lever is located on the overload between the overload and the motor starter.
12. Connect the damper linkage to the drive tube by
manually rotating the drive tube in 1/2 turn incre­ments until the 3/8" diameter bolt can seat into the nut on the damper linkage. Maintain the damper blades in the tightly-held, fully closed position dur­ing this adjustment.
15. Turn the blower service switch to the “REMOTE” position and, after the damper motor closes, turn the heater disconnect off.
16. Re-install the weather cover push-in plug.
17. Re-connect the wire removed in step 9 to terminal
“G” and reset the motor starter overload.
18. Verify both service switches are in the “REMOTE” position, close the electrical enclosure door and turn the heater disconnect switch on.
13. Turn the heater disconnect switch on and place the blower service switch to the “LOCAL” position. Damper will open to the point the upper cam engag­es the upper limit switch.
14. Using the deep-well, 1/2" hex socket or nut driver, turn the upper cam hex nut in a clockwise direction in one click increments until the damper blades fully open.
CAUTION:
Do not over-drive the damper motor as damage to the PC board or tripping of the onboard fuse may result. If the fuse trips, place the blower service switch in the “OFF” position for 15 seconds to allow fuse to reset.
M-Series Technical Manual 71 Cambridge Engineering, Inc.
Page 74
GAS TRAIN DRAWINGS (FM & IRI)
Vertical Mount > 2500 MBH Factory Mutual (FM) Compliant CSA Certified
Horizontal Mount > 400 MBH Industrial Risk Insurers (IRI) Compliant CSA Certified
Cambridge Engineering, Inc. 72 M-Series Technical Manual
Page 75
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
1. Make-up air heater in Reset
I. No Blower Operation
a) Outside temperature below LTC setpoin­tin Vent Mode b) Gas Valve not energized during call for heat cycle c) Pressure drop across burner too high d) Sustained excessive winds present e) High Air Flow Switch defective
2. Heater Disconnect
a) Disconnect in OFF position
3. Mode Selector Switch on RCS
a) Switch in OFF position a) Place switch in proper mode.
4. Operating Thermostat
a) Thermostat satisfied b) Open in thermistor circuit c) Defective thermostat
5. Blower Service Switch
a) Switch in OFF position b) Defective switch
6. Control Transformer
a) No input voltage b) Blown control fuse C) Defective transformer
7. Class II Transformer
a) No output voltage b) Defective transformer
8. Multi-Functional PC Board
a) No input voltage on Terminal G (RCS) b) Improper wiring c) Defective board
9. Damper Motor
a) Damper End Switch not made b) Damper motor not operating
c) Defective damper motor
10. Motor Protection
a) Overload relay tripped
b) Overload relay defective
11. Motor Starter
a) Coil open (Defective) b) Contacts welded closed (Defective)
12. Motor
a) No input voltage b) Improper voltage c) Defective motor
13. Blower Damage
a) Defective or locked bearings b) Physical damage
14. Belts
a) Belt Slipping b) Belt broken or missing
a) Turn heater “OFF” momentarily and turn heater “ON.” b) See Problem III.
c) Adjust Profile Plate Damper. d) Wait until winds abate and reset. e) Replace High Air Flow Switch.
a) Turn disconnect ON.
a) Adjust thermostat, if applicable. b) Check wiring or replace thermistor. c) Replace thermostat.
a) Place switch in REMOTE position. b) Replace switch.
a) Check disconnect and supply fusing. b) Replace control fuse. c) Replace transformer.
a) Check supply voltage. b) Replace transformer.
a) Check voltage in RCS. b) Check wiring. c) Replace multi-functional PC board.
a) Check end switch/cam interface. b) Check end switch/cam interface b1) Check damper fuse. b2) Check diodes on switch assy c) Replace damper motor
a1) Check primary power source a2) Reset overload relay and check motor
amps/overload setting.
b) Replace overload relay
a) Replace starter. b) Replace starter.
a) Check primary power source. b) Consult factory. c) Replace motor.
a) Replace bearings. b) Replace or repair blower
a) Tighten belts. b) Replace belts
M-Series Technical Manual 73 Cambridge Engineering, Inc.
Page 76
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
II. BLOWER RUNS;
NO HEAT;
FLAME SAFETY RELAY DOESN’T LOCK OUT
III. BLOWER RUNS;
NO HEAT;
FLAME SAFETY RELAY LOCKS OUT
1. Mode Selector Switch
a) Switch in VENT position a) Place switch in HEAT position.
2. Burner Service Switch
a) Switch in OFF position a) Place switch in REMOTE position.
3. Multi-Functional PC Board
a) No input voltage on Terminal W (RCS) b) Thermostat satisfied c) Improper wiring
d) Defective board
4. Airflow Switch
a) Blower running backwards b) Belts slipping c) Blocked intake or discharge d) Clogged airflow tubing or pickup ports e) Defective switch
5. Flame Safeguard Relay (FSR)
a) No input voltage b) Defective FSR
6. Entering Air Thermostat (EAT)
a) EAT set too low
1. Igniter
a) No current (open igniter) b) No voltage
2. High Limit
a) High limit tripped a) See Problem Number VI
3. High or Low Gas Pressure Switches
a) Low gas pressure switch tripped
b) High gas pressure switch tripped
c) Defective gas pressure switch
4. Gas Valve
a) No input voltage
b) Gas valve does not open
c) Defective solenoid
5. Modulating Valve
a) Minimum fire set too low a) Adjust minimum fire on modulating valve
6. Multi-Functional PC Board
a) Low fire start set too low
b) Thermistor open or not connected
a) Check voltage in RCS. b) Adjust thermostat. c) Check wiring to multi-functional PC
board.
d) Replace multi-functional PC board.
a) Reverse motor direction. b) Tighten and/or replace belts. c) Find and remove obstruction. d) Clean or replace tubing or pickup ports. e) Replace switch.
a) Check wiring. b) Replace FSR
a) Increase EAT setting During trial for ignition:
a) Check igniter current b) Check FSR output to igniter.
a) Check gas supply for low gas pressure or
no gas
b1) Check manifold gas pressure for high
pressure reading and reset pressure regu­lator
b2) Check gas supply pressure against name
plate
b3) Verify the high pressure regulator is a
lock-up type
c) Replace gas pressure switch
a1) Check FSR output to R1 relay
during ignition trial a2) Check gas valve circuit and wiring b1) Compare supply voltage to nameplate
voltage b2) Clean and/or replace gas valve parts. c) Replace solenoid or valve assembly.
a) Adjust modulating valve voltage between
10 and 13 Volts DC
b) Properly install or replace thermistor
Cambridge Engineering, Inc. 74 M-Series Technical Manual
Page 77
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
III. BLOWER RUNS; NO HEAT; FLAME SAFETY RELAY LOCKS OUT (Continued)
IV. BLOWER RUNS;
BURNER FIRES;
FLAME SAFETY RELAY LOCKS OUT
V. BLOWER RUNS;
UNIT HEATS;
SHORT CYCLES
WITHOUT RESETTING
7. Regulator
a) Clogged vent orifice b) No supply pressure c) Improper manifold pressure d) Defective regulator
8. Burner
a) Defective burner a) Replace burner.
1. Low Flame Current
a) Dirt build-up on insulator
b) Minimum fire set too low c) Defective burner
2. Multi-Functional PC Board
a) Low fire start set too low
3. No Flame Current
a) Ground connection open
b) Wire termination oxidized
4. Fluctuating Flame Current
a) Unit overfiring b) Minimum fire set too low c) Intermittent ground connection d) Defective burner
5. Flame Safeguard Relay
a) Defective FSR a) Replace FSR
6. High Limit
a) High limit contact intermittent a) Replace high limit.
1. Air Flow Switch
a) Blower running backwards b) Belts slipping c) Blocked intake or discharge d) Air delivery below minimum require­ments e) Clogged airflow tubing or pick-up ports
f) Defective switch
2. Flame Safeguard Relay
a) Defective FSR a) Replace FSR.
3. Operating Thermostat
a) Differential temperature setting too tight a) Increase differential temperature setting
4. Damper Motor End Switch
a) End switch making intermittent contact a) Replace end switch assembly.
a) Clean or replace orifice
b) Check all gas cocks and piping
c) Adjust regulator.
d) Replace regulator.
a) Clean dirt deposit from insulator
surface and install protective boot. b) Adjust minimum fire on modulating valve c) Replace burner.
a) Adjust modulating valve voltage between
9 and 13 Volts DC
a1) Reference transformer to ground. a2) Secure FSR grounded.
a3) Tighten loose ground screws b) Clean terminal and reinsert
a) Check manifold pressure. b) Adjust minimum fire on modulating valve. c) Tighten all ground points d) e) Replace burner.
a) Reverse motor direction b) Tighten and/or replace belts c) Find and remove obstruction. d) Increase fan RPM for air delivery require-
ments. e) Clean or replace airflow tubing or pick-up
ports f) Replace switch.
M-Series Technical Manual 75 Cambridge Engineering, Inc.
Page 78
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
VI. HIGH LIMIT TRIPPED
1. High Limit
a) High limit will not reset a) Replace high limit.
VII. BLOWER RUNS;
UNIT HEATS;
WILL NOT CYCLE OFF
VIII. MODULATING
VALVE DOES NOT MODULATE;
CONTINUOUS HIGH FIRE
2. Burner Overfiring
a) Manifold pressure too high
3. Discharge Damper
a) Damper blades partially closed b) Defective damper motor
4. Low Airflow
a) Blower running backwards b) Belts slipping c) Blocked intake or discharge
5. Temperature Control System
a) Temperature control system does not
modulate
1. Operating Thermostat
a) Short in thermistor circuit
b) Thermostat located improperly
c) Thermostat differential setting too wide d) Defective thermostat
2. Burner Service Switch
a) Switch in LOCAL position a) Place switch in REMOTE position.
3. Auxiliary Control
a) Auxiliary contacts closed
4. Misunderstood Control System Operation
a) Control system doesn’t function as
expected
1. Amplifier (A1014 or A1044)
a) Wire not connected to amplifier terminal
3 or 4.
b) Jumper not installed between terminals 2
and 3 of A1014 amplifier only.
c) Defective amplifier
2. Discharge Temperature Sensor
(TS114 or TS144)
a) Open in sensor circuit
b) Sensor cross-wired to amplifier
3. Space Temperature Selector (Series 44 only) (T244 or TS244/TD244)
a) Open in sensor circuit
b) Induced voltage in field wiring c) Space sensor located improperly
a) Adjust manifold pressure regulator to
obtain temperature rise specified on heater nameplate.
a) Adjust damper stroke length. b) Replace damper motor.
a) Reverse motor direction. b) Tighten or replace belts. c) Find and remove obstruction
a) See problem VIII for Electronic Discharge Control systems.
a) Check thermistor wiring and/or replace
thermistor. b1) Thermostat in cold draft-relocate. b2) Thermostat not satisfied-turn down c) Reduce differential setting. d) Replace thermostat.
a) Check auxiliary circuit wiring and
contacts
a) Review control system operational charac-
teristics.
a) Reinstall wire.
b) Reinstall jumper.
c) Replace amplifier.
a) Replace the sensor if the resistance mea-
sured at terminals 1 and 2 on TS114 sen-
sor exceeds 11,000 Ω; terminals 1 and 3
or 2 and 3 onTS144 exceeds 6,000Ω.
c) Correct wiring terminations.
a) Replace the sensor if the resistance mea-
sured is more than: 7,000 Ω for the T244;
5,500 Ω for the TS244; or 2,250 Ω for the
TD244. b) Utilize shielded, twisted pair wiring c) Sensor in cold draft - relocate
Cambridge Engineering, Inc. 76 M-Series Technical Manual
Page 79
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
VIII. MODULATING
VALVE DOES NOT MODULATE;
CONTINUOUS HIGH FIRE
(Continued)
IX. MODULATING VALVE
DOES NOT MODULATE;
CONTINUOUS LOW FIRE
4. Space thermostat (Series 14 only)
a) Thermostat out of calibration b) Thermostat located improperly c) Thermostat differential setting too wide d) Thermostat defective
5. Remote Heat Adjust (TD114)
a) Short in Remote Heat Adjust circuit
b) Induced voltage in field wiring
6. Modulating Valve (M511, M611 or MR212)
a) Foreign material holding valve open
b) Modulating valve misassembled
1. Class II Transformer
a) No voltage output to amplifier a1) Check for short in modulating valve coil.
2. Modulating Valve
a) Valve coil is open or shorted
b) Plunger jammed c) Ruptured main or balancing diaphragm
3. Amplifier
a) No output voltage to valve
4. Discharge Temperature Sensor (TS114 or TS144)
a) Short in sensor circuit
b) Temperature control system out of cali-
bration
a) Recalibrate thermostat or replace. b) Thermostat in cold draft - relocate. c) Reduce differential setting. d) Replace thermostat.
a) Replace Remote Heat Adjust if resistance
measure between terminals 1 and 3 of
Remote Heat Adjust is less than 6,000 Ω.
b) Utilize shielded, twisted pair wiring.
a) Disassemble valve and remove foreign
material.
b) Disassemble valve and assemble correctly
a2) Replace transformer.
a) Replace valve coil if its resistance is less
than 40 Ω or greater than 85 Ω.
b) Clean or replace plunger. c) Check diaphragm condition and replace if
defective.
a) With the wire removed from terminal 3
of amplifier, replace amplifier if the valve voltage does not exceed 18 Volts DC.
a) Replace the sensor if the resistance mea-
sured at: terminals 1 and 2 on TS114 is
less than 8,000 Ω; terminals 1 and 3 or 2 and 3 on TS144 is less than 2,900 Ω.
b) Perform temperature control system cali-
bration.
M-Series Technical Manual 77 Cambridge Engineering, Inc.
Page 80
TROUBLESHOOTING GUIDE
Problem Possible Cause Corrective Action
IX. MODULATING
VALVE DOES NOT MODULATE;
CONTINUOUS LOW FIRE
(Continued)
5. Space Temperature Selector (T244A or TS244A/TD244A)
a) Short in sensor circuit a) Replace the sensor if the resistance mea-
6. Remote Heat Adjust (TD114)
a) Open in the Remote Heat Adjust control
circuit
sure is less than 5,000 Ω for the T244A or 3,500 Ω for the TS244A and 1,950 Ω for
the TS244A.
a) Replace the control if the resistance
measured at terminals 1 and 3 exceeds
12,000 Ω.
X. ERRATIC OR
PULSATING FLAME
7. High Airflow Switch
a) Pressure drop across burner too high b) Defective Airflow Switch
8. Multi-Functional PC Board
a) Temp sensor wires not seated properly in terminal block. b) Defective board
1. High Pressure Regulator
a) Vent undersized
b) Defective regulator
2. Amplifier
a) Hunting
b) Temperature control system out of cali-
bration
c) Defective amplifier
3. Space Temperature Selector (T244A or TS244A/TD244A)
a) Induced voltage in field wiring a) Utilize shielded, twisted pair wiring.
4. Remote Heat Adjust (TD114)
a) Induced voltage in field wiring
a) Measure pressure drop and adjust profile damper. b) Replace Airflow Switch.
a) Reinstall sensor wires. b) Replace board.
a) Enlarge vent piping size or reduce vent
piping length.
b) Replace regulator.
a) Adjust sensitivity control dial counter-
clockwise.
b) Perform temperature control system
calibration.
c) Replace amplifier.
a) Utilize shielded, twisted pair wiring.
Cambridge Engineering, Inc. 78 M-Series Technical Manual
Page 81
ANSI/ASHRAE/IESNA STANDARD 90.1
Overview
Energy efficient, Genuine Cambridge gas-fired heating equipment can comply with the requirements of ANSI/ASHRAE/IESNA Standard
90.1. Compliance is shown on the Cambridge heater nameplate.
Purpose of ASHRAE Standard 90.1
ASHRAE Standard 90.1 provides minimum require­ments for the energy efficient design and construc­tion of new commercial buildings in the United States. The standard covers the entire building, setting minimum equipment efficiency levels for components that may be used, rather than setting standards for component manufacturing.The provi­sions of this standard do not apply to single family houses, low rise residential buildings and buildings (or portions of buildings) that use energy primarily for industrial, manufacturing or commercial pro­cesses.
®
direct
• Damper (Section 6.4.3.4.3)
A damper is required on each heater. The
Cambridge Engineering Motorized Discharge Damper (MDD) will meet the standard.
• Labeling (Section 6.4.1.5.1)
The heater must be labeled to indicate that it
complies with the requirements of the standard. The nameplate of Cambridge heaters includes the required labeling.
• Efficiency (Section 6.4.1.3)
Direct gas-fired heating equipment has no
minimum efficiency requirement. However Cambridge Engineering certifies that its equip­ment has a 100% combustion efficiency (Ec) and a 92% thermal efficiency (Et).
Compliance Requirements:
The following are required for Cambridge heaters to comply with Standard 90.1:
• Controls (Section 6.4.3)
Total airflow of all heaters less than 10,000
cfm - The Cambridge Engineering Temperature
Setback System (TSS) will meet the standard. A properly configured building DDC system with the necessary programming for zone control, automatic shutdown and setback can also meet the standard.
Total airflow of all heaters exceeds 10,000 cfm - The Cambridge Engineering Temperature
Setback System (TSS) with optimum start con­trol will meet the standard. A properly config­ured building DDC system with the necessary programming for zone control, automatic shut­down, setback and optimum start can also meet the standard.
Heaters intended to operate continuously - No special controls are required to meet the standard.
M-Series Technical Manual 79 Cambridge Engineering, Inc.
Page 82
MAINTENANCE LOG
MODEL NO. SERIAL NO.
Date
Activity Technician
Cambridge Engineering, Inc. 80 M-Series Technical Manual
Page 83
Cambridge Engineering, Inc. reserves the right to change specifications, modify the design and/or
substitute equivalent materials without notice as the result of code requirements, product enhancements,
ongoing research/development and vendor changes beyond our control.