Caltest CINERGIA Installation And Operation Manual

Page 1
DC Programmable Power Supply
(DCPS)
Installation and operation manual
Tel: +49(0)7842-99722-00
Fax: +49(0)7842-99722-29 www.caltest.de
Kohlmattstrasse 7
D-77876 KAPPELRODECK
info@caltest.de
Caltest Instruments GmbH
Page 2
Page2 / 55
INDEX
1. INTRODUCTION ..................................................................................................................... 5
1.1. Symbols used ................................................................................................................. 5
1.2. Safety notes ................................................................................................................... 5
1.3. Quality and regulations ................................................................................................. 5
2. PRESENTATION ...................................................................................................................... 7
2.1. Introduction .................................................................................................................. 7
2.2. Power supply features................................................................................................... 8
2.3. Operation and connection modes ................................................................................ 9
2.4. Limits ............................................................................................................................. 9
2.5. Configuration and control of the power supply .......................................................... 10
2.6. Functional diagram ...................................................................................................... 10
2.7. Principle of operation .................................................................................................. 11
3. INSTALLATION ..................................................................................................................... 13
3.1. Important safety instructions ...................................................................................... 13
3.2. Equipment views ......................................................................................................... 13
3.3. Equipment reception................................................................................................... 16
3.3.1. Unpacking and checking the content .................................................................. 16
3.3.2. Storage ................................................................................................................ 16
3.3.3. Transport to location ........................................................................................... 16
3.3.4. Location ............................................................................................................... 17
3.4. Connection .................................................................................................................. 19
3.4.1. Earth protection .................................................................................................. 19
3.4.2. Input connection, terminals (X1 to X5) ............................................................... 19
3.4.3. Output connection, terminals (X6 to X10) .......................................................... 19
3.4.4. Emergency Power Off terminals (X12) ................................................................ 19
3.4.5. Communications ................................................................................................. 20
3.4.6. Digital inputs and outputs ................................................................................... 20
3.4.7. Analog inputs and outputs .................................................................................. 21
4. OPERATION ......................................................................................................................... 22
4.1. Safety ........................................................................................................................... 22
4.2. State Machine ............................................................................................................. 22
4.2.1. Initialization ......................................................................................................... 23
4.2.2. Standby ................................................................................................................ 23
Page 3
4.2.3. Precharge ............................................................................................................ 23
4.2.4. Ready ................................................................................................................... 23
4.2.5. Run ...................................................................................................................... 23
4.2.6. Alarm ................................................................................................................... 24
4.3. Operation modes ........................................................................................................ 24
4.3.1. Current mode ...................................................................................................... 24
4.3.2. Voltage mode ...................................................................................................... 25
4.3.3. Power mode ........................................................................................................ 26
4.3.4. Programmable limits ........................................................................................... 27
4.4. Connection modes ...................................................................................................... 27
4.5. Working with the equipment ...................................................................................... 28
4.5.1. Start-up ................................................................................................................ 29
4.5.2. Stop ..................................................................................................................... 30
4.5.2.1. Full stop ........................................................................................................... 30
4.5.2.2. Standby stop .................................................................................................... 30
4.5.2.3. Ready ............................................................................................................... 30
4.5.3. Emergency stop ................................................................................................... 31
4.5.4. Accidental shut down .......................................................................................... 31
4.5.5. Alarms.................................................................................................................. 31
4.5.6. Alarms reset ........................................................................................................ 33
5. LOCAL TOUCHSCREEN CONTROL PANEL ............................................................................. 34
5.1. Basic functions............................................................................................................. 34
5.2. Menus and submenus ................................................................................................. 34
5.2.1. General ................................................................................................................ 34
5.2.2. Operational ......................................................................................................... 35
5.2.3. Configuration ....................................................................................................... 38
5.2.4. Alarms.................................................................................................................. 40
6. REMOTE COMMUNICATIONS .............................................................................................. 41
6.1. IQ MANAGEMENT ....................................................................................................... 49
7. HUMAN MACHINE INTERFACE ............................................................................................ 51
7.1. Operation tab .............................................................................................................. 51
7.2. Supervision tab ............................................................................................................ 52
7.3. Alarm tab ..................................................................................................................... 53
7.4. I, V, P configuration tab ............................................................................................... 53
Page 4
Page4 / 55
8. WARRANTY AND MAINTENANCE ........................................................................................ 54
8.1. Replacing the output fuses.......................................................................................... 54
8.2. Fans ............................................................................................................................. 54
8.3. DC bus capacitors ........................................................................................................ 54
8.4. Warranty ..................................................................................................................... 54
8.5. Claim procedure .......................................................................................................... 55
Page 5
5 / 55
1. INTRODUCTION
Dear customer, on behalf of CINERGIA team, thank you for the confidence placed in our company and for the purchase of this product. Please, read carefully this manual before using the equipment to get familiarized with it to obtain the maximum performance from it.
This document is intended for appropriately qualified personnel. Only personnel with the appropriate skills are allowed to perform the electrical connection and commissioning of the equipment.
The information in this documentation is not binding. CINERGIA reserves the right to make changes in part on in the whole at any time and without prior notice due to technical advance or product improvement.
1.1. Symbols used
DANGER: Indicates a hazardous situation which can result in death or serious injury and can cause important damage or destruction of the equipment or the property
WARNING: Indicates important information that must be taken into account to operate the equipment. Take the appropriate prevention measures.
INFORMATION: Information that is important but is not safety-relevant
1.2. Safety notes
Improper use of this equipment can cause both important personal injury and physical damage to the electrical power grid and the loads connected to it. Read this document carefully and follow all safety precautions at all times.
1.3. Quality and regulations
The equipment is based on a hardware designed, manufactured and commercialized in accordance with the standard EN ISO 9001 of Quality Management Systems. The marking shows the conformity to the EEC Directive by means of application of the following standards
• 2006/95/EC Low voltage directive.
• 2004/108/EC Electromagnetic Compatibility directive (EMC)
In accordance with the specifications of the harmonized standards:
Page 6
6 / 55
• EN-IEC 62040-1. Uninterruptible power supply (UPS). Part 1-1: General and safety requirements for UPS’s used in accessible areas by end users.
• EN-IEC 60950-1. IT equipments. Safety. Part 1: General requirements.
• EN-IEC 62040-2. Uninterruptible power supply (UPS). Part 2: Prescriptions for
Electromagnetic compatibility (EMC).
• EN-IEC 62040-3. Uninterruptible power supply (UPS). Part 3: Methods of operation specification and test requirements.
The manufacturer responsibility is excluded in the event of any modification or intervention in the product by the customer’s side.
Page 7
7 / 55
2. PRESENTATION
2.1. Introduction
The DCPS is a DC Programmable Power Supply, a power electronics equipment with the following main functionalities:
- It converts the AC input, of the main grid, in a controlled DC output by using an IGBT-
based switching topology and DSP-based state-of-the-art digital control.
- It can be operated as:
o Constant voltage output o Constant current output o Constant power output
- It is a bidirectional power source: energy can flow from the grid to the load or
viceversa (it allows saving energy during the working period by returning the energy to the mains)
- The AC current consumed from the grid is sinusoidal (THD < 2%)
- The user can define the reactive power to be injected by the power supply and also
choose between capacitive or inductive
The power range covered by the DCPS power supplies goes from 6.75 to 160kW at the output. The parallelization of power supplies is possible to increase output power.
Reference
Rated Power
(Load side)
Rated Current
(Load side)
Rated Voltage
(Load side)
Dimensions
(mm)
kW
DC
(per channel)
DC
(total)
DC
DxWxH
DCPS7.5
6.75
10A
30A
0-750V
700x450x1100
DCPS10
9
15A
45A
0-750V
700x450x1100
DCPS15
13.5
20A
60A
0-750V
700x450x1100
DCPS20
18
25A
75A
0-750V
700x450x1100
DCPS30
27
40A
120A
0-750V
805x590x1320
DCPS40
36
50A
150A
0-750V
805x590x1320
DCPS50
45
65A
195A
0-750V
805x590x1320
DCPS60
54
80A
240A
0-750V
805x590x1320
DCPS80
72
105A
315A
0-750V
805x590x1320
DCPS100
90
130A
390A
0-750V
805x590x1320
DCPS120
108
155A
465A
0-750V
805x590x1320
DCPS160
128
185A
555A
0-750V
850x900x2000
DCPS200
160
230A
690A
0-750V
850x900x2000
Page 8
8 / 55
2.2. Power supply features
Magnitude Value
Power 6.75kW-160kW
Input AC Voltage
Rated
3x400V+Neutral+Earth
Voltage range
+15% / -20 %
AC Current
2Arms -290Arms
Frequency
50/60Hz
Power Factor
Controllable
-1/1 (capacitive/inductive)
Efficiency
at full load
>92%
Overload
125% for 10 min / 150% for 60 s
DC Outputs
DC Current
3 independent channels
0-230A (per channel)
DC Current
1 parallelized channel
0-690A
DC Voltage 0-750V
Minimum voltage
at rated power
220V
Modes of operation
Range
Resolution
Ripple
Constant Current (CC)
0-100%
<±0.1%
<1%
Constant Voltage (CV)
0-100%
<±0.1%
<1%
Constant Power (CP)
0-100%
<±0.1%
<1%
Response time
In all operation modes
<2ms Rise/Fall time 10%-90%
GENERAL
Measurements
Input Voltage (Vrms) and Current (Irms)
Active and Reactive Input Power (P,Q)
Output Voltages (Vdc) and Currents (Idc)
Output Power
Temperatures
User interface
3.2” Touchscreen
Control port: 3 analog inputs, 3 analog outputs, 5 digital inputs, 3 relay
Communication Protocols: Modbus/TCP
Communication Ports: Ethernet, RS485 (optional)
Customized communications for IEC61850, ERP or MATLAB® (optional)
Humidity
10-90% (Absolute maximum, without condensation)
Temperature
5-40°C (Absolute maximum)
Refrigeration
Forced air
Protections
Over Current, Over
Shortcircuit
Over Temperature
Galvanic Isolation (optional)
Standards
Safety
EN-62040-1-2, EN-60950-1
EMC
EMC: EN-62040-2
Please note that items marked as optional shall be requested specifically at additional cost.
Page 9
9 / 55
2.3. Operation and connection modes
The output of the power supply is formed by three channels referenced to a common negative channel. The power supply can be used in two different connection modes:
- Independent channel: each channel (U,V,W) is controlled independently. The setpoint
and also the operation mode can be different for each channel.
- Parallel channels: the three channels are controlled by the control software as a
unique channel to multiply the output current by 3. The setpoint and the operation mode are the same for all three channels. It is mandatory to shortcircuit by hardware the three output channels. All operation modes are available in this connection mode.
However, three operation modes are allowed:
- Constant Voltage (CV): the output voltage is controlled to the setpoint value.
- Constant Current (CC): the output current is controlled to the setpoint value.
- Constant Power (CP): the output power is controlled to the setpoint value.
2.4. Limits
The DCPS output limits are defined by:
- Maximum voltage: 750V
- Maximum current: defined in the datasheet as Rated Current DC (per channel) or
Rated Current DC (total)
- Maximum power: defined in the datasheet as Rated Power (kW)
For example, below the limits of a DCPS160 power supply (with 750 V as maximum voltage) are shown:
0
100
200
300
400
500
600
700
800
0
25
50
75
100
125
150
170
195
220
245
270
295
320
345
370
395
420
445
470
495
520
545
555
Output voltage (V)
Output current, 3ch (A)
Page 10
10 / 55
2.5. Configuration and control of the power supply
The power supply can be interfaced by three means:
- Local touchscreen: a 3.2” colour local touchscreen panel can be used to configure,
monitor and operate the power supply. See section Local Touchscreen Control Panel for further information.
- Analog and digital inputs / outputs: the power supply owns:
o 5 optocoupled digital inputs o 3 relay outputs o 3 isolated analog inputs o 3 isolated analog outputs
- Remote interface: an Ethernet communication interface with protocol MODBUS/TCP
can be used to configure, monitor and operate the power supply. By using HMI software application provided by CINERGIA, downloading of excel files is also possible.
2.6. Functional diagram
The diagram below is the conceptual functions blocks diagram of the power supply:
AC
ACTIVE RECTIFIER
GRID
DC DC
DC
LOAD
DC/DC
Input LCL
filter
Input EMI
filter
Protections Protections
Output EMI
filter
Output LCL
filter
OPTIONAL
DC PROGAMMABLE POWER SUPPLY
The main components of the diagram are the following (from grid side to load side):
- Isolation transformer: a 50/60Hz isolation transformer can be provided optionally in
order to isolate the output channels. In this case, an isolation monitor can be integrated in the power supply to detect isolation faults too. This isolation transformer is mandatory if the power supply is to be used as a 4 quadrants equipment (by connecting the load between two output channels).
- Input protections: these protections include a thermal-magnetic circuit breaker and
fuses. The connection of the power supply input with the grid is done by screw terminals. Please follow safety instructions in Installation section to connect the DCPS.
- Input EMI filter: an electromagnetic filter is integrated to fulfil electromagnetic
compatibility regulations. The structure of the filter in question is the same as the one of the output EMI filter.
- Input LCL filter: the purpose of this filter is to reduce the current distortion at
frequencies equal to or higher than switching frequency and thus reduce THD.
- Active Rectifier: a three-branch IGBT active front end is integrated in the equipment to
consume/inject a sinusoidal current from/to the grid.
The DC link voltage is set to 430V providing a regulation margin for fast transients at the output of the DCPS.
Page 11
11 / 55
The active rectifier has bidirectional power flow capability and the injected reactive power (grid side) can be defined by the customer.
- DC/DC output converter: a three-branch IGBT converter allows three buck-boost DC-
DC conversions from the DC bus to each of the output channels. Each channel can be controlled independently or, by software, the three channels will share the same operation mode and setpoints.
- Output LCL filter: this filter reduces voltage distortion (caused by switching) at the
output of the power supply.
- Output EMI filter: a high frequency common mode LC filter is used to reduce
electromagnetic disturbances at the output of the DCPS.
- Output protections: the DC outputs are protected by fuses. A disconnector is provided
to isolate the output from the load. Screw terminals are also integrated to connect the load. Please, follow safety instructions in Installation section to connect the power supply.
2.7. Principle of operation
Below, a technical diagram of the power supply is shown:
Drivers x6 Drivers x6
Current
sensor x3
Voltage
sensor x2
Voltage
sensor x3
Current
sensor x3
Voltage
sensor x3
PE
-U
-U
PE
PE
EMC filter
EMC filter
DC output
1/3 channels
PE
DCPS
U
DSP
board
DSP
board
CAN/
Ethernet
board
CAN
MODBUS/TCP
ETHERNET
V W N
PE
R S T
N
PE
(Please note that earth protection cable is only connected to the cabinet chassis).
Page 12
12 / 55
State-of-the art digital control is used in all CINERGIA products. In the DCPS case, the control system algorithms are computed in a dual core DSP-based hardware, designed by CINERGIA, allowing a multitask execution of the regulation systems for the Active Rectifier and the DC/DC output. This produces a fast transient response and high performance against load changes. A 12 bits analog to digital conversion, with digital processing, allows a high resolution output up to 0.1% with high stability too.
Resonant control
Control algorithms based on Resonant Control are used in the AC side. The regulation is structured in blocks resonating at a given frequency. Within the resonant frequency each block allows the suppression of gain and phase errors of the controlled magnitude: voltage, current, …etc. Thanks to this, each harmonic can be controlled independently and thus it can be generated or suppressed, as needed.
PID control
The DC side control algorithm is based on a traditional PID controller which will be explained later.
Page 13
13 / 55
3. INSTALLATION
3.1. Important safety instructions
As a device with class l protection against electric shocks, it is essential to install a protective
earth wire (connect earth ). Connect the protection earth wire to the terminal (X5) before connecting the grid to the DCPS input.
All the electrical connections, including those for control (interface, remote controletc.), shall be done with the switches in OFF position and with the mains supply disconnected (thermal­magnetic circuit breaker in OFF position too
It must never be forgotten that the DCPS is a power supply, so users must take all
necessary precautions against direct or indirect contact.
Warning labels should be placed on all primary power switches installed in places far from the device to alert the electrical maintenance personnel of the presence of a voltage in the circuit up to 10 minutes after stopping the device.
In devices without isolation transformer, precautions must be taken as they are
not isolated from the alternating input line, and there might be dangerous voltage
between the output terminals and the ground.
3.2. Equipment views
Electrical connections:
X6
X7
X10 X8
X9
X4 X1
X5
X2
X3
Local front panel:
Page 14
14 / 55
Front view (with the door open):
Q2 Q3
Q1a
Detailed view of the signal connectors:
X12 X13
X11
X14
X15 X16
X17
Page 15
15 / 55
General view (with the front door closed):
Protection elements (Q*):
(Q1a) Input thermal-magnetic circuit breaker or disconnector according to power of
the equipment.
(Q2) Output disconnector. (Q3) Output fuses.
Connection elements (X*):
(X1) Phase input terminal R. (X2) Phase input terminal S. (X3) Phase input terminal T. (X4) Neutral input terminal N.
(X5) Earth connection terminal for main supply input ( ). (X6) DC phase output terminal W. (X7) DC phase output terminal V. (X8) DC phase output terminal U. (X9) DC negative terminal N.
(X10) Earth connection terminal for load or loads ( ). (X11) DB9 connector for RS485 communications.
Page 16
16 / 55
(X12) Terminals for external Emergency Power Off (EPO) button. (X13) DB9 connector for CAN communications (input). (X14) DB9 connector for CAN communications (output). (X15) RJ45 connector for MODBUS interface. (X16) DE15 connector for digital inputs and outputs. (X17) DE15 connector for analogic inputs and outputs.
3.3. Equipment reception
3.3.1. Unpacking and checking the content
On receiving the device, make sure that the power supply has not suffered any damage during the transportation. Otherwise, make all pertinent claims to the supplier or to CINERGIA.
The packing of the device consists of a wooden palette, a cardboard or wooden packaging (depending on the case), expanded polystyrene corner pieces, a polyethylene sleeve and bands; all recyclable materials. Therefore they should be disposed of according to current regulations. We recommend to keep the packaging in case its use is necessary in the future.
In order to unpack, cut the bands and remove the cardboard packaging with a vertical movement. In case of wooden packaging, remove it with the appropriate tools. Afterwards, remove the corner pieces and the plastic sleeve. At this point the equipment will be unpacked on the pallet. Please, use suitable tools to lower the power supply from the pallet.
After unpacking the equipment, check that the data in the nameplate (stuck on the inner part of the front door) correspond to those specified in the purchase order. Contact the supplier or CINERGIA in case of disconformity.
Keep the equipment in the original package if it will not be used in order to protect it from any possible mechanical damages, dust, dirt …etc.
3.3.2. Storage
The equipment shall be stored in a dry, ventilated place and protected against rain, water jets or chemical agents. It is advisable to keep the power supply into its original package, which has been designed to assure the maximum protection during the transport and storage.
Do not store the unit where the ambient temperature exceeds 40°C or falls below
-20°C, as this may degrade the electrical characteristics of the batteries.
3.3.3. Transport to location
The equipment includes castors to facilitate its transport to its final location.
It is important to check previously if the weight of the power supply is appropriate for the site where it will be located.
Page 17
17 / 55
It is also important to consider the most suitable means to place the power supply in its final location (floor, hoist, lift, stairs, etc).
3.3.4. Location
It is necessary to leave a minimum of 25 cm in the contour of the equipment for its ventilation. If possible, as shown in following figures, it is recommended to leave additional 75 cm to facilitate the operations of maintenance of the equipment or the interventions of the technical service in case of breakdown.
Recommendable minimum
distance, 1 m.
Recommendable minimum distance, 1 m.
Recommendable minimum distance, 1 m.
Page 18
18 / 55
Recommendable minimum
distance, 1 m.
Recommendable minimum distance, 1 m.
Recommendable minimum
distance, 1 m.
Recommendable minimum distance, 1 m.
The equipment may be installed in any place as long as the safety and ventilation requirements are fulfilled.
The power supply includes 2 levelling elements located near the front castors, which serve to immobilize the unit once it is in place.
To adjust the level, open the front door of the cabinet and proceed as follows:
By hand, loosen the levelling elements by turning them anticlockwise until they touch
the floor, and then, using a spanner, continue loosening until the castors are raised off the floor by a maximum 0.5 cm.
Close the door once more.
Page 19
19 / 55
3.4. Connection
3.4.1. Earth protection
As a device with class l protection against electric shocks, it is essential to install a protective
earth wire (connect earth ). Connect the protection earth wire to the terminal (X5) before connecting the grid to the DCPS input.
On the other hand, connect the protection earth wire to the terminal (X10) before connecting the load to the DCPS output.
3.4.2. Input connection, terminals (X1 to X5)
Connect the grid cables R, S, T and N to the terminals (X1), (X2), (X3) and (X4) respectively. This connection must always be done according to the label placed under the input screw terminals.
In case of discrepancies between labelling and this manual instructions, the label information will always prevail.
3.4.3. Output connection, terminals (X6 to X10)
The equipment has 3 output channels (U, V and W) and a common negative return (N). Therefore, the load must be connected between the channels and the common negative return (phase-N):
- DC phase output terminal U (X8)
- DC phase output terminal V (X7)
- DC phase output terminal W (X6)
- DC negative terminal N (X9)
In case of discrepancies between labelling and this manual instructions, the label information will always prevail.
3.4.4. Emergency Power Off terminals (X12)
The equipment owns two terminals dedicated to external Emergency Power Off (EPO).
The EPO must act as a normally closed contact, and thus, there are two possible options for connection:
a) Connecting an external Emergency pushbutton to X12 b) Installing a cable bridge to close the circuit in terminal X12 (in case EPO is not desired)
If option a) is chosen, the procedure is as follows:
1. Emergency shutdown activation: the Emergency pushbutton must be set in the
position in which it forces to open the circuit between the two terminals of X12.
2. Normal mode restoration: the Emergency pushbutton position must be inverted in
order to close the circuit again between the two terminals of X12.
Page 20
20 / 55
X12
3.4.5. Communications
There are several connectors dedicated to communications, which are listed below:
- Connector for RS485 communications (X11): DB9 connector to be used when Modbus
RS485 option is chosen.
- Connectors for CAN communications (X13, X14): DB9 connectors to be used when
parallelization of DCPSs is needed (X13 works as input and X14 works as output).
- Connector for MODBUS interface (X15): RJ45 connector. A standard Ethernet cable
must be connected between X15 and a Hub or a Router to communicate a remote PC with the DCPS.
3.4.6. Digital inputs and outputs
Digital inputs and outputs are gathered in X16. All of them are isolated and configurable.
Specifically, there are 5 digital inputs which operate at 24 V and 3 relay digital outputs.
Page 21
21 / 55
3.4.7. Analog inputs and outputs
Analog inputs and outputs are gathered in X17.
The analog inputs of DCPS are isolated and accept a voltage range from -10 to 10V. There are 3 analog inputs and, depending on the connection mode, there are two possible configurations for them:
- Parallel channels: the analog input Analog_In_1 is the reactive power command and
the Analog_In_2 depends on the power supply operation mode.
- Independent channels: there is no reactive power command and each analog input
corresponds to one phase. Their functionality depends on the power supply operation mode.
As it has been previously mentioned, an analog input can be configured as one magnitude (current, voltage…etc.) setpoint of a specific output channel. In this case, the magnitude in question of the output channel is proportional to the voltage of the respective analog input. For example, in independent current mode, for a 10 V analog input, the current of the respective output channel will be the maximum that the DCPS withstands (see catalogue).
Regarding analog outputs, they are also isolated and accept a voltage range from 0 to 10 V. Analogously to inputs, there are 3 analog outputs and each one corresponds to one different output channel scaled magnitude.
Page 22
22 / 55
4. OPERATION
4.1. Safety
Before operating the equipment, check that the Protective Earth is properly
connected.
Check out the electrical installation in both sides (input and output) of the
cabinet. All wires shall be connected and secured before proceeding to the
power supply start-up.
4.2. State Machine
The operation of the power supply is based on 6 different states (square) and 5 transitions (rhombs). Each state defines the behaviour and possible operations of the power supply.
Initialization
EMCY
sequence?
Standby
Yes
No
Enable?
Precharge
Yes
Ready
Run? Enable?
No
Run
Yes
Yes
Run? Enable?
Yes
No
Yes
Error
From any
Reset?
Yes No
Page 23
23 / 55
4.2.1. Initialization
During the initialization, the power supply control system checks the presence of all internal components, the embedded PC loads the operating system and the isolation detector runs a self-test.
No voltage is present at the DC bus and the IGBTs PWMs are completely stopped.
The transition from Initialization state brings the power supply to the Standby state as long as the emergency stop is deactivated (equipment armed) and the isolation detector performs a complete self-test successfully.
4.2.2. Standby
The Standby state keeps the power supply in low power mode until an Enable signal is received. While the power supply is in standby only the internal power supplies are energized. In particular, this means that there is no voltage in the DC link and no voltage/current is applied to the output of the power supply.
The transition from the Standby state is the Enable signal or, in case of errors, a Fault signal. The Enable signal will bring the State Machine to Precharge and eventually to the Ready state. If an error is detected the power supply will go into Alarm state.
4.2.3. Precharge
The Precharge is an internal transition state between Standby and Ready. During this state the DC link is gradually charged through resistors until the rated DC link voltage is reached. The transition will finish successfully as long as, in less than 10 seconds of precharge, the DC link has reached the specified voltage. Otherwise, the next state will be Alarm.
The Precharge state is only applicable to the grid side converter.
4.2.4. Ready
In the Ready state the power supply is ready to operate but no PWM signal is sent to IGBTs. The DC bus is charged to the rectified voltage and there is no voltage/current applied to the outputs.
The transition from Ready state can be the Run signal, the Not enable signal or, in case of errors, a Fault signal. When a Run signal is received the State Machine will evolve to the Run state. When a Not enable signal is received the State Machine puts the power supply on standby, thus discharging the DC link capacitors. If a fault is detected the power supply goes to Alarm state.
4.2.5. Run
In this state, the power supply is completely operational. Due to the power supply architecture, the grid side converter (Active Rectifier) will make the transition first while
Page 24
24 / 55
stabilizes the DC link voltage. After that, the output side will measure the actual output state (voltage levels) and will start the control algorithms and PWM.
This state can evolve to Standby state when a Not enable signal is received, to Ready state when a Not run signal is received or to Alarm state if an error condition is detected.
Please, note that, while the power supply is in Run state, it is not possible to change the connection mode from independent channels to parallelized channels.
4.2.6. Alarm
In this state, the power supply is stopped and kept in a safe condition: the DC link is discharged and the PWM signals are stopped.
The Alarm state can be reached by any fault detected during the normal operation of the power supply, for instance, an emergency stop activation (see Alarms chapter for further detail).
The only possible transition from Alarm state is to Initialization state. Once in Alarm state a Reset signal is required from the customer after clearing the fault condition. If the fault condition has not been cleared the power supply state will be kept in Alarm (for example, when heatsink overheating has occurred and the temperature is still high).
4.3. Operation modes
The DC Programmable power supply has 3 operation modes:
- Constant Current mode (CC): the power supply regulates the output current to the
setpoint defined by the user.
- Constant Voltage mode (CV): the power supply regulates the output voltage to the
setpoint defined by the user.
- Constant Power mode (CP): the power supply regulates the output power to the
setpoint defined by the user.
4.3.1. Current mode
The current mode is based on a PID controller with dynamic saturation limits which depend on the current limit configured. Find below the current regulation block diagram:
PID PWM Converter
Current feedback
Current
setpoint
Page 25
25 / 55
The user can configure:
- Amplitude: desired output current value.
- Sign: a positive sign represents a current sourced from the power supply. A negative
sign represents a current sunk by the power supply.
- Setpoint limitation: this limitation can be lower than the maximum power supply
output current. It can be useful when the power supply is connected to batteries since they may have different current limits for charging and discharging and those limits may be lower than the maximum power supply current.
Depending on the loads connected, the voltage limitation may be useful too and is available in any mode.
4.3.2. Voltage mode
The voltage mode is based on a PID controller with dynamic saturation limits which depend on the current limit configured. The power supply will limit the output current in case of reaching the configured limit.
PID
PID
PID
PWM Converter
Current feedback
Voltage feedback
Voltage/
power consig
Max.
Charging
current
Max.
Discharging
current
Page 26
26 / 55
The user can configure:
- Amplitude: desired output voltage value.
- Sign: the output voltage between channels U,V,W is always positive with respect to N.
No negative voltages can be set.
- Setpoint limitation: the maximum current may be controlled in this operation mode.
The maximum available voltage will affect to the limit of the voltage setpoint given, but it will not be controlled. Therefore, in those applications where the load imposes a higher voltage than the maximum available, the power supply will trigger an overvoltage alarm.
4.3.3. Power mode
The power mode is implemented with a current PID. In this case, taking into account that the power equals to V·I, a linear controller may not be the optimum option to close this control loop. Consequently, in order to take advantage of the PID controller benefits, a linearization is made by dividing the power command by the output voltage of the power supply.
PID PWM Converter
Voltage feedback
Power consig
÷
Current feedback
As in current mode case, the user can configure:
- Amplitude: desired output power value.
- Sign: a positive sign represents a current sourced from the power supply. A negative
sign represents a current sunk by the power supply.
Page 27
27 / 55
- Setpoint limitation: this limitation can be lower than the maximum power supply
output current. It can be useful when the power supply is connected to batteries since they may have different current limits for charging and discharging and those limits may be lower than the maximum power supply current.
Depending on the loads connected, the voltage limitation may be useful too. However, there is no voltage control; only an alarm is triggered if the power supply voltage is beyond the limits set by the user.
4.3.4. Programmable limits
In constant current, constant voltage and constant power modes the maximum current and maximum voltage of the power supply can be limited too. The user can configure these values through the HMI:
Current
When the power supply reaches the configured value, the output current will be regulated to the limit defined. This limitation can be useful to protect a load with a maximum allowable current below the maximum current of CINERGIA power supply. For instance, to protect a battery against excessive discharge in constant current mode.
Voltage
The voltage protection differs from the current protection in that the output voltage will not be regulated. When the voltage reaches the maximum or minimum voltage defined by the user, an alarm will be triggered and the power supply will be stopped in alarm state (DC Overvoltage or DC Undervoltage).
4.4. Connection modes
As it has been previously mentioned, there are two different ways of connecting the power supply output:
Page 28
28 / 55
Independent mode: each output channel is connected to an independent load. In this
way, the power supply could, for instance, feed three independent loads at the same time and with different capacities, voltages, currents, etc.
Please be sure that no electrical connection between the channels exists, i.e.
that the loads are completely independent. Keep in mind that, if two channels are interconnected, a shortcircuit may appear in voltage based modes.
Parallel mode: all three channels are connected in parallel to increase the maximum
power supply output current. It is mandatory to shortcircuit by hardware the three output channels. All operation modes are available in this connection mode.
Four quadrant mode: the four quadrant mode is a particular case of the independent
mode in which the power supply may only be operated as a voltage source. In this case the load is connected only between phases without any reference to the N phase. As far as the load has no reference to the negative phase, the connected phases may be charged at any potential (keep it in mind).
In order to operate the output phases, Cinergia recommends a start-up voltage of 200V for each connected phase. From this initial voltage, sum the desired setpoint divided by 2 to one phase and subtract the same value to the other phase.
Changing the polarity of the load implies switching the setpoint values in the phases.
Due to the blanking time of the IGBTs, it is not possible to operate in this mode with voltages near 0V.
Please remember to disconnect the equipment before modifying the connection
mode.
4.5. Working with the equipment
Before powering the cabinet check step by step the following items (if the cabinet is powered for the first time, place the fuses in the fuseholder
before proceeding):
The power supply output must be disconnected:
Page 29
29 / 55
The grid side of the power supply is protected by a thermal-magnetic circuit breaker.
Be sure that this breaker is switched off:
Check that all wires are connected and secured before proceeding to the power supply
start-up.
If these steps are validated the power supply is ready to be started.
4.5.1. Start-up
Switch on the thermal-magnetic circuit breaker of the grid side of the power supply. After switching it on, the power supply will initiate the start-up sequence. This sequence will activate the cabinet fans for one second and, if an internal isolation transformer is used, an internal relay for the transformer precharge will also be activated.
At this point the power supply will start the initialization process, as described before. During this time the embedded PC will load the operating system and the communications program. The isolation detector will also perform a self-test before being operative. The power supply will ignore any command during this process.
The Initialization state can last up to 15 seconds. If every step is completed successfully the power supply will move automatically to Standby state.
Summarizing, to put the equipment in Run state the user should follow step by step the next checklist:
1. Connect the mains.
2. Turn on the input thermal-magnetic circuit breaker.
3. Activate the cabinet output by switching the disconnector.
4. Deactivate the emergency stop (pull out the button). (Initialization
Standby)
5. Send the Enable signal. (Standby
Precharge  Ready)
6. Select the connection mode between independent or parallel. This option cannot be
undone while the power supply is running.
7. Select the operation mode. Please keep in mind that not all loads are compatible with
all operation modes. For example, if the power supply is acting like a voltage source, do not connect any other voltage sources at the output.
8. Send the Run signal. (Ready
Run)
Please keep in mind that not all loads are compatible with all operation modes.
If the power supply is operated as a voltage source, please do not connect any
Page 30
30 / 55
other voltage sources at the output. If the power supply is operated as a current source, please do not connect any other current sources at the output.
4.5.2. Stop
Once the equipment is running (Run state) it may be stopped in three ways:
4.5.2.1. Full stop
This type of stop is recommended if the electrical connections are to be modified or the power supply will be stopped for a long time.
When the power supply is running, special care must be taken. It is strongly recommended to follow the next steps:
1. Send the Not enable signal to the power supply (Run
Ready Standby)
2. Press the emergency stop button (Standby
Alarm)
3. Disconnect the output disconnector
4. Wait at least 60 seconds (time to get discharged the internal DC link capacitors)
5. Disconnect the input thermal-magnetic circuit breaker
Before manipulating the cables in the cabinet terminals, please check the
voltages with a voltmeter to assure no voltage is present. The grid cable and the load must be completely unpowered before connecting or disconnecting
the cables. The user must be sure that the input and output switches are both
in OFF position.
4.5.2.2. Standby stop
This type of stop is recommended if the power supply will be stopped during some hours. The DC link is discharged and therefore aging of the DC bus capacitors is prevented.
Send the Not enable signal to the power supply. If the user wants to lock the power supply in order to avoid an accidental start-up, press the emergency stop button, and keep it pressed.
For restarting operation, release the emergency stop button and send the Reset signal. After doing this, proceed as a standard start-up sending the Enable signal.
NEVER connect or disconnect the cables while the power supply in Standby
state.
4.5.2.3. Ready
This type of stop is recommended if the power supply will be stopped for a short time. The DC link is kept charged and the power supply is ready to run.
Page 31
31 / 55
When the power supply is running, the user may send the Not run signal at any time. This will stop the IGBT’s PWM signals but all internal parts will be kept powered. To restart operation, send the Run signal.
NEVER connect or disconnect the cables while the power supply is in Ready state.
4.5.3. Emergency stop
The emergency stop button may be pressed at any time bringing the power supply to the Alarm state. The emergency stop shall be only used when an emergency is detected. Please, avoid to stop the equipment with the emergency button as a “normal practice” since it will contribute to premature component aging. To lock the power supply and bring it to the Alarm state, follow the Full stop procedure.
The emergency stop unpowers all the electromechanical devices in the cabinet so the power supply is stopped by hardware assuring a full stop. The internal contactors will be open so no power will be present at the DC link or at the ouput of the power supply. Only the control boards, the embedded PC and the local touchscreen remain powered.
4.5.4. Accidental shut down
When the power supply is suddenly disconnected from the mains special care must be taken for restarting it. When the power supply is shut down with a charged DC link, some thermal protections of the internal power supplies will prevent its start-up.
When an accidental shutdown happens, disconnect the mains and wait for at least 2 minutes for powering the cabinet again.
4.5.5. Alarms
There are different sources of alarm in the power supply. The following table describes them and offers possible causes and solutions to the user.
Code
Name
Cause
Solution
1
Watchdog
Internal microcontroller error.
If this alarm persists, contact Cinergia’s technical support.
2
Emergency sequence
The emergency stop button is activated or the EPO wire in no longer connected.
Unpress the emergency stop button or reconnect the EPO wire.
3
Drivers
IGBTs saturation protection has been activated. This alarm is triggered when
Contact Cinergia for technical support if this alarm persists. Check the equipment under test
Page 32
32 / 55
there is a sudden overcurrent in the power supply output.
before restarting the power supply.
4
Precharge timeout
Internal error caused by a low voltage in mains.
Check the grid voltage.
5
Overload in precharge
Internal alarm caused by a shortcircuit.
Contact Cinergia for technical support.
6
Overvoltage in the DC link
The DC link voltage has exceeded its maximum value.
Reduce the DC output step transition time.
Contact Cinergia for technical support if this alarm persists.
7
Undervoltage in the DC link
Undervoltage in the DC link caused by fast output transient.
Reduce the DC output step transition time.
Contact Cinergia for technical support if this alarm persists.
8
Phase overvoltage
The voltage in the grid is too high.
Check the grid voltage.
9
Phase undervoltage
The voltage in the grid is too low.
Check the grid voltage.
10
DC Overcurrent
The output current has exceeded the configured limitation.
Check the output load.
11
Heatsink overtemperature
Overtemperature in the heatsink.
Check enough space exists between the power supply and the wall.
There is insufficient air flow inside the power supply. Check that the fans are working correctly.
11
Sensor offset
Error caused by transducers malfunction.
Turn off the equipment, wait one minute, and turn it on again. This alarm can occur when the power supply is switched off accidentally under load.
Otherwise, contact Cinergia for technical support.
Page 33
33 / 55
12
No Heart Beat
Communication cable broken or control board without response.
Contact Cinergia in order to isolate the problem.
13
PLL error
The frequency of the grid is too high or low.
Check the grid frequency.
14
Mains lost
There is no voltage on the grid (short interruption or voltage dip).
Check the grid voltage.
15
Open loop
The power supply has reached the maximum voltage in current or power operation mode.
The load is not connected or its impedance is too high for the current setpoint.
16
Isolation
The isolation detector has detected a fault in the galvanic isolation.
Check if isolation fault disappears when the power supply has no load connected to the output. If it does, the isolation problem is in the load. If it does not, contact Cinergia.
17
Overload
The power supply is working beyond its rated values.
Check the parameters configured.
18
Shortcircuit
The power supply has detected a shortcircuit in the equipment under test
Check the equipment under test impedance.
4.5.6. Alarms reset
The user shall follow the next steps for resetting the alarms:
Press the emergency stop button. Send a Reset signal to the power supply. Send a Not enable and Not run signals (note: this step is done automatically when the
user is interfacing the power supply by the LCD or by the software provided by Cinergia).
Proceed as a standard start-up process by deactivating the emergency stop (pull out
the button).
A Reset will be performed only in the case that the alarm source has been cleared. If the problem persists after resetting the power supply, a new alarm will be triggered.
Page 34
34 / 55
5. LOCAL TOUCHSCREEN CONTROL PANEL
5.1. Basic functions
The LCD touchscreen main purpose is to provide the user with the necessary information about the power converters. Besides, the touchscreen allows the user to interact with the mother board and control multiple variables in regard to the DC power output of the power converters.
By means of the black bar in the upper side of the touchscreen, the user is constantly aware of the following variables:
Control Mode State of the power converters
The rest of information can be found throughout the menus and submenus.
5.2. Menus and submenus
5.2.1. General
There are four main menus:
Operational Configuration Alarms
A description of each one can be found in the following points.
Page 35
35 / 55
5.2.2. Operational
The main purpose of the Operational menu is, in case the LCD Control is activated, to allow the user to manage the power converters State Machine and to introduce current, voltage and both active and reactive power setpoints.
The user gets to read the following information as well:
Connection mode Output voltage Output current Output active power Reactive power
State Machine
By means of the ENABLE and RUN buttons the user can manage the power converters State Machine as long as the Control variable is set to LCD.
ENABLE: the function of this button depends on the power converters state:
o Standby State: the ENABLE button is released. By pressing the ENABLE button
the user orders the system to move to the Ready state.
o Ready & Run States: the ENABLE button is pressed. By pressing the ENABLE
button the user orders the system to disable the power converters.
The ENABLE button has no effect in every other state.
RUN: the function of this button depends on the power converters state:
o Ready State: the RUN button is released. By pressing the RUN button the user
orders the system to move to Run State.
o Run State: the RUN button is pressed. By pressing the RUN button the user
orders the system to return to Ready State.
The RUN button has no effect in every other state.
Page 36
36 / 55
Commands
The button COMMANDS allows the user to introduce different setpoints:
Voltage setpoints Current setpoints Active power setpoints
Once again, this function is only permitted when the Control variable is set to LCD. Information about the different kinds of setpoints that the user can introduce through the touchscreen can be found below. When the COMMANDS button is pressed, the following keyboard will appear.
The kind of setpoint to introduce will depend on the operation mode (Constant Voltage, Constant Current or Constant Power) and the connection mode (Independent or Parallel).The procedure to send a setpoint consists of the following steps:
1. Press COMMANDS button.
2. Introduce the first setpoint and press Enter.
3. Introduce the second setpoint and press Enter.
4. Introduce the third setpoint and press Enter.
5. Press SEND button.
If the user needs to erase the current setpoint being edited, the Cancel button (grey one) sets it to zero.
Page 37
37 / 55
In case the user wants to set a negative setpoint, this can be made by pressing the button +/-.
The Cancel button (green one) can be pressed anytime to return to the Operational menu without sending any setpoint.
Page 38
38 / 55
Voltage setpoint
The user can introduce an independent voltage setpoint per every channel.
Current setpoint
The user can introduce an independent current setpoint per every channel.
Active power setpoint
The user can introduce an independent power setpoint per every channel.
SET REACTIVE
The SET REACTIVE button allows the user to introduce a global reactive power setpoint. The procedure to follow is the same as with the COMMANDS button. Regardless of the current mode, the user is allowed to enter the desired reactive setpoint.
5.2.3. Configuration
The Configuration window provides the user with some helpful information about the following variables:
Connection mode Mode Control
By means of the upper buttons shown, the user may manage these variables in case the current Control variable is set to LCD.
Connection mode
The following screen appears when the user presses the Connection mode button:
Page 39
39 / 55
In case the Control variable is set to LCD, the user may change the current connection mode. Two types are available for the user to choose:
Independent Parallel
Pressing the BACK button the user can return to the main Configuration window.
Mode
The following screen appears when the user presses the Mode button:
In case the Control variable is set to LCD, the user may change the current mode. Three types of mode are available for the user to choose:
Constant V Constant C Constant P
Pressing the BACK button the user can return to the main Configuration window.
Page 40
40 / 55
Control
The following screen appears when the user presses the Control button:
In case the Control variable is set to LCD, the user may change the current control mode. Three types of control mode are available for the user to choose:
LCD Modbus Analog input
Pressing the BACK button the user can return to the main Configuration window.
5.2.4. Alarms
The Alarms window displays information about the power converters alarms. Any existing alarm will appear in this window.
In case the user is willing to reset the system, the RESET button permits him to do so.
Page 41
41 / 55
6. REMOTE COMMUNICATIONS
CINERGIA’s power supplies can be operated and supervised remotely through an Ethernet communications bus. An internal embedded PC, with CINERGIA’s proprietary software, allows
the exchange of information between the internal CAN bus and the external Modbus TCP/IP (Ethernet). In this way, the customer can build specific HMI client software application while CINERGIA’s power supply acts as a Modbus TCP/IP server.
Drivers x6 Drivers x6
Current
sensor x3
Voltage
sensor x2
Voltage
sensor x3
Current
sensor x3
Voltage
sensor x3
PE
-U
-U
PE
PE
EMC filter
EMC filter
DC output
1/3 channels
PE
DCPS
U
DSP
board
DSP
board
CAN/
Ethernet
board
CAN
MODBUS/TCP
ETHERNET
V W N
PE
R S T
N
PE
This Modbus TCP/IP slave has the following properties:
The memory map is as follows:
Property
Implementation
Function Codes:
0x04: READ_INPUT_REGISTER 0x03: READ_HOLDING_REGISTER 0x10: WRITE_MULTIPLE_REGISTER (Note: only 2 registers Write is allowed)
CRC
Not used. Included in the TCP stack.
Multiple connections
Only one master at one time allowed. Additional connection requests might be delayed or even rejected.
Idle connections
Idle connections might be closed by the slave. However, the listen socket will force the master to keep the connection active, even when there is no active connection at all.
Other
All variables are 32 bits long (2 registers). Their MODBUS addresses are 1 register long each one. All Read operations must start at the beginning of one variable, and must read an even number of registers. As for Write operations, ONLY 1 WRITE OPERATION OF 1 VARIABLE IS ALLOWED AT ONE TIME.
Page 42
42 / 55
Variable
MODBUS Address
(dec)
Size
ACCESS
TYPE
MIN
MAX
DESCRIPTION
AR_VRS
154
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhR-PhS
AR_VST
156
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhS-PhT AR_VTR
158
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhT-PhR
AR_VRN
162
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhR-N
AR_VSN
164
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhS-N
AR_VTN
166
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhT-N
AR_IR
170
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhR
AR_IS
172
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhS
AR_IT
174
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhT
AR_FR
178
2
RO
IQ21
_IQ(-440)
_IQ(440)
// Frequency PhR
AR_FS
180
2
RO
IQ21
_IQ(-440)
_IQ(440)
// Frequency PhS
AR_FT
182
2
RO
IQ21
_IQ(-440)
_IQ(440)
// Frequency PhT
AR_VDC
184
2
RO
IQ21 0 _IQ(850.0)
// DC link voltage
AR_TEMPIN
188
2
RO
IQ21
_IQ(-10.0)
_IQ(175.0)
// Input temperature
AR_TEMPOUT
190
2
RO
IQ21
_IQ(-10.0)
_IQ(175.0)
// Output temperature
AR_ERRORS
198
2
RO
UINT32
0
0X7FFFFFFF
// Active Rectifier Errors Vector
AR_HOBBESCW
220
2
RW
UINT32
0
0X7FFFFFFF
// Active Rectifier Control Word
AR_HOBBESSW
222
2
RO
UINT32
0
0X7FFFFFFF
// Active Rectifier Status Word
AR_READP0
226
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power Global
AR_READPR
228
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power R
AR_READPS
230
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power S
AR_READPT
232
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power T
AR_READQ0
236
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Reactive Power global
AR_READQR
238
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Reactive Power R
AR_READQS
240
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Reactive Power S
Page 43
43 / 55
AR_READQT
242
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Reactive Power T
AR_SETQ0
256
2
RW
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Reactive Power (Set-Point)
DCDC_VAB
296
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhA-PhB
DCDC_VBC
298
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhB-PhC
DCDC_VCA
300
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhC-PhA
DCDC_VAN
304
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhA-NEG
DCDC_VBN
306
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhB-NEG
DCDC_VCN
308
2
RO
IQ21 0 _IQ(440.0)
// Voltage PhC-NEG
DCDC_IA
312
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhA
DCDC_IB
314
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhB
DCDC_IC
316
2
RO
IQ21
_IQ(-100.0)
_IQ(100.0)
// Current PhC
DCDC_VDC
326
2
RO
IQ21 0 _IQ(850.0)
// DC link Voltage
DCDC_TEMPOUT
332
2
RO
IQ21
_IQ(-10.0)
_IQ(175.0)
// Output temperature
DCDC_ERRORS
340
2
RO
UINT32
0
0X7FFFFFFF
// DCDC Errors Vector
DCDC_ERRORIRMS
342
2
RO
IQ21 0 _IQ(80.0)
// Error limit RMS Current
DCDC_ERRORIPIC
344
2
RO
IQ21
_IQ(0)
_IQ(100)
// Error limit Peak Current
DCDC_ERRORVAC
346
2
RW
IQ21
_IQ(0)
_IQ(620)
// Error limit Voltage Output
DCDC_ERRORVDC
348
2
RW
IQ21
_IQ(0)
_IQ(800)
// Error limit DC link voltage
DCDC_ALARMIRMS
352
2
RO
IQ21 0 _IQ(70.0)
// Alarm limit RMS current
DCDC_ALARMIPIC
354
2
RO
IQ21
_IQ(0)
_IQ(80)
// Alarm limit Peak current
DCDC_ALARMVAC
356
2
RW
IQ21
_IQ(0)
_IQ(580)
// Alarm limit Voltage Output
DCDC_ALARMVDC
358
2
RW
IQ21
_IQ(0)
_IQ(750)
// Alarm limit DC link voltage
DCDC_HOBBESCW
362
2
RW
UINT32
0
0X7FFFFFFF
// DCDC Control Word
DCDC_HOBBESSW
364
2
RO
UINT32
0
0X7FFFFFFF
// DCDC Status Word
DCDC_READP0
368
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power global
DCDC_READPA
370
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power A
DCDC_READPB
372
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power B
Page 44
44 / 55
DCDC_READPC
374
2
RO
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power C
DCDC_SETP0
388
2
RW
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power global (Set-Point)
DCDC_SETPA
390
2
RW
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power A (Set-Point)
DCDC_SETPB
392
2
RW
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power B (Set-Point)
DCDC_SETPC
394
2
RW
IQ10
_IQ10(-2000000)
_IQ10(2000000)
// Active Power C (Set-Point)
DCDC_BATSTATUSWORDGL
410
2
RO
UINT32
0
0X7FFFFFFF
// Battery Status Word (parallelized)
DCDC_BATERRORWORDGL
412
2
RO
UINT32
0
0X7FFFFFFF
// Battery Error Word (parallelized)
DCDC_ALARMBATHGL
414
2
RW
IQ21 0 0X7FFFFFFF
// Battery High Voltage Alarm (parallelized)
DCDC_ALARMBATLGL
416
2
RW
IQ21 0 0X7FFFFFFF
// Battery Low Voltage Alarm (parallelized)
DCDC_ALARMBATMAXCHGL
418
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Charging Current Alarm (parallelized)
DCDC_ALARMBATMINCHGL
420
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Discharging Current Alarm (parallelized)
DCDC_SETCHIGL
422
2
RW
IQ21 0 0X7FFFFFFF
// Recommended charging current (parallelized)
DCDC_SETCHVGL
424
2
RW
IQ21 0 0X7FFFFFFF
// Equalization battery voltage (parallelized)
DCDC_FLOATINGVGL
426
2
RW
IQ21 0 0X7FFFFFFF
// Floating voltage (parallelized)
DCDC_SETCHPGL
428
2
RW
IQ10 0 0X7FFFFFFF
// Battery capacity (parallelized)
DCDC_BATSOCGL
430
2
RO
UINT32
0
0X7FFFFFFF
// Battery State of Charge (parallelized)
DCDC_BATVDCGL
432
2
RO
UINT32
0
0X7FFFFFFF
// Battery DC voltage measured (parallelized)
DCDC_BATIDCGL
434
2
RO
UINT32
0
0X7FFFFFFF
// Battery Drain Current measured (parallelized)
DCDC_AHMEASUREDGL
436
2
RO
IQ10 0 0X7FFFFFFF
// Ah measured (parallelized)
DCDC_TIMEMEASUREDGL
438
2
RO
UINT32
0
0X7FFFFFFF
// Time measured (parallelized)
DCDC_BATSTATUSWORDA
442
2
RO
UINT32
0
0X7FFFFFFF
// Battery Status Word A
DCDC_BATERRORWORDA
444
2
RO
UINT32
0
0X7FFFFFFF
// Battery Error Word A
DCDC_ALARMBATHA
446
2
RW
IQ21 0 0X7FFFFFFF
// Battery High Voltage Alarm A
DCDC_ALARMBATLA
448
2
RW
IQ21 0 0X7FFFFFFF
// Battery Low Voltage Alarm A
DCDC_ALARMBATMAXCHA
450
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Charging Current Alarm A
DCDC_ALARMBATMINCHA
452
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Discharging Current Alarm A
Page 45
45 / 55
DCDC_SETCHIA
454
2
RW
IQ21 0 0X7FFFFFFF
// Recommended charging current A
DCDC_SETCHVA
456
2
RW
IQ21 0 0X7FFFFFFF
// Equalization battery voltage A
DCDC_FLOATINGVA
458
2
RW
IQ21 0 0X7FFFFFFF
// Floating voltage A
DCDC_SETCHPA
460
2
RW
IQ10 0 0X7FFFFFFF
// Battery capacity A
DCDC_BATSOCA
462
2
RO
UINT32
0
0X7FFFFFFF
// Battery State of Charge A
DCDC_BATVDCA
464
2
RO
UINT32
0
0X7FFFFFFF
// Battery DC voltage measured A
DCDC_BATIDCA
466
2
RO
UINT32
0
0X7FFFFFFF
// Battery Drain Current measured A
DCDC_AHMEASUREDA
468
2
RO
IQ10 0 0X7FFFFFFF
// Ah measured A
DCDC_TIMEMEASUREDA
470
2
RO
UINT32
0
0X7FFFFFFF
// Time measured A
DCDC_BATSTATUSWORDB
474
2
RO
UINT32
0
0X7FFFFFFF
// Battery Status Word B
DCDC_BATERRORWORDB
476
2
RO
UINT32
0
0X7FFFFFFF
// Battery Error Word B
DCDC_ALARMBATHB
478
2
RW
IQ21 0 0X7FFFFFFF
// Battery High Voltage Alarm B
DCDC_ALARMBATLB
480
2
RW
IQ21 0 0X7FFFFFFF
// Battery Low Voltage Alarm B
DCDC_ALARMBATMAXCHB
482
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Charging Current Alarm B
DCDC_ALARMBATMINCHB
484
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Discharging Current Alarm B
DCDC_SETCHIB
486
2
RW
IQ21 0 0X7FFFFFFF
// Recommended charging current B
DCDC_SETCHVB
488
2
RW
IQ21 0 0X7FFFFFFF
// Equalization battery voltage B
DCDC_FLOATINGVB
490
2
RW
IQ21 0 0X7FFFFFFF
// Floating voltage B
DCDC_SETCHPB
492
2
RW
IQ10 0 0X7FFFFFFF
// Battery capacity B
DCDC_BATSOCB
494
2
RO
UINT32
0
0X7FFFFFFF
// Battery State of Charge B
DCDC_BATVDCB
496
2
RO
UINT32
0
0X7FFFFFFF
// Battery DC voltage measured
DCDC_BATIDCB
498
2
RO
UINT32
0
0X7FFFFFFF
// Battery Drain Current measured B
DCDC_AHMEASUREDB
500
2
RO
IQ10 0 0X7FFFFFFF
// Ah measured B
DCDC_TIMEMEASUREDB
502
2
RO
UINT32
0
0X7FFFFFFF
// Time measured B
DCDC_BATSTATUSWORDC
506
2
RO
UINT32
0
0X7FFFFFFF
// Battery Status Word C
DCDC_BATERRORWORDC
508
2
RO
UINT32
0
0X7FFFFFFF
// Battery Error Word C
DCDC_ALARMBATHC
510
2
RW
IQ21 0 0X7FFFFFFF
// Battery High Voltage Alarm C
Page 46
46 / 55
DCDC_ALARMBATLC
512
2
RW
IQ21 0 0X7FFFFFFF
// Battery Low Voltage Alarm C
DCDC_ALARMBATMAXCHC
514
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Charging Current Alarm C
DCDC_ALARMBATMINCHC
516
2
RW
IQ21 0 0X7FFFFFFF
// Battery Max Discharging Current Alarm C
DCDC_SETCHIC
518
2
RW
IQ21 0 0X7FFFFFFF
// Recommended charging current C
DCDC_SETCHVC
520
2
RW
IQ21 0 0X7FFFFFFF
// Equalization battery voltage C
DCDC_FLOATINGVC
522
2
RW
IQ21 0 0X7FFFFFFF
// Floating voltage C
DCDC_SETCHPC
524
2
RW
IQ10 0 0X7FFFFFFF
// Battery capacity C
DCDC_BATSOCC
526
2
RO
UINT32
0
0X7FFFFFFF
// Battery State of Charge C
DCDC_BATVDCC
528
2
RO
UINT32
0
0X7FFFFFFF
// Battery DC voltage measured C
DCDC_BATIDCC
530
2
RO
UINT32
0
0X7FFFFFFF
// Battery Drain Current measured C
DCDC_AHMEASUREDC
532
2
RO
IQ10 0 0X7FFFFFFF
// Ah measured C
DCDC_TIMEMEASUREDC
534
2
RO
UINT32
0
0X7FFFFFFF
// Time measured
DCDC_DCVOLTAGEGLOBAL
538
2
RW
IQ21 0 0X7FFFFFFF
// Global DC voltage command
DCDC_DCVOLTAGEPHA
540
2
RW
IQ21 0 0X7FFFFFFF
// Phase A voltage command
DCDC_DCVOLTAGEPHB
542
2
RW
IQ21 0 0X7FFFFFFF
// Phase B voltage command
DCDC_DCVOLTAGEPHC
544
2
RW
IQ21 0 0X7FFFFFFF
// Phase C voltage command
DCDC_ACVOLTAGEGLOBAL
548
2
RW
IQ21 0 0X7FFFFFFF
// Global DC current command
DCDC_ACVOLTAGEPHA
550
2
RW
IQ21 0 0X7FFFFFFF
// Phase A current command
DCDC_ADCVOLTAGEPHB
552
2
RW
IQ21 0 0X7FFFFFFF
// Phase B current command
DCDC_ADCVOLTAGEPHC
554
2
RW
IQ21 0 0X7FFFFFFF
// Phase C current command
DCDC_MAXAGLOBAL
558
2
RW
IQ21 0 0X7FFFFFFF
// Current limit (Global)
DCDC_MAXAPHA
560
2
RW
IQ21 0 0X7FFFFFFF
// Current limit (Phase A)
DCDC_MAXAPHB
562
2
RW
IQ21 0 0X7FFFFFFF
// Current limit (Phase B)
DCDC_MAXAPHC
564
2
RW
IQ21 0 0X7FFFFFFF
// Current limit (Phase C)
DCDC_MAXVGLOBAL
568
2
RW
IQ21 0 0X7FFFFFFF
// Global DC maximum allowable voltage
DCDC_MAXVPHA
570
2
RW
IQ21 0 0X7FFFFFFF
// Phase A maximum allowable voltage
DCDC_MAXVPHB
572
2
RW
IQ21 0 0X7FFFFFFF
// Phase B maximum allowable voltage
Page 47
47 / 55
DCDC_MAXVPHC
574
2
RW
IQ21 0 0X7FFFFFFF
// Phase C maximum allowable voltage
DCDC_MINVGLOBAL
578
2
RW
IQ21 0 0X7FFFFFFF
// Global DC minimum allowable voltage
DCDC_MINVPHA
580
2
RW
IQ21 0 0X7FFFFFFF
// Phase A minimum allowable voltage
DCDC_MINVPHB
582
2
RW
IQ21 0 0X7FFFFFFF
// Phase B minimum allowable voltage
DCDC_MINVPHC
584
2
RW
IQ21 0 0X7FFFFFFF
// Phase C minimum allowable voltage
The Bit Coded Variables descriptions are:
CONTROL WORD
bits
31..12
11
10 9 8..5
4..3 2 1
0
Definition
reserved
reserved
reserved
Connection mode
Function
LocalRemote
RunReady
Enable
Reset
0: Independent
1: Parallel
0: Voltage 1: Icnt 2: Pcnt 3: Bat. Charge 4:Rsvd
0: Local 1: Modbus 2: External ADC
0:Ready
0: Disabled
1:Reset
STATUS WORD
bits
31..17
16
15
11
10..8
7..6 5 4
3..0
Definition
reserved
reserved
reserved
Connection mode
Function
LocalRemote
RunReady
Enable
State Machine
0: Independent
1: Parallel
0: Voltage 1: Icnt 2: Pcnt 3: Bat. Charge 4:Rsvd
0: Local 1: Modbus 2: External ADC
0:Ready
0: Disabled
s_Init: 1 s_StandBy: 2 s_PreCharge: 3 s_Ready: 4 s_Run: 5 s_Alarm: 6 s_Calibration: 7
Page 48
48 / 55
ERRORS
bits
7 6 5 4 3 2 1
0
Definition
Phase overvoltage
Undervoltage in the DC link
Overvoltage in the DC link
Precharge overload
Precharge time
Drivers
EMCY sequence
Watchdog
Overvoltage in phase
The DC link is discharged
The DC link is overcharged
Overload in Precharge State
Internal error, the voltage in mains is too low
Internal error
Emergency stop or isolation device is activated
Digital processor is blocked
bits
21
18
15
12
11
10 9 8
Definition
Mains lost
PLL error
Node without heartbeat
Transducers offset
Room overtemperature
Heatsink overtemperature
Phase overcurrent
Phase undervoltage
There is no voltage in the grid
PLL out of range
Internal error, communication between converters is lost
Some transducers are not working properly
Not used
Heatsink overtemp
Overcurrent in one phase
Undervoltage in phase
bits
31..26
25
24
23
22
Definition
reserved
Shortcircuit
Overload
Isolation detector
Open loop
The power supply output is shortcircuited
The power supply is beyond its rated limits
There is an isolation fault in the power supply
When the power supply is in current or power mode, the circuit is opened
Page 49
49 / 55
6.1. IQ MANAGEMENT
Many of the parameters of this equipment are defined as IQ numbers (Texas Instruments nomenclature). An IQ number refers to a 32 bit signed fixed point number where the number of fractional bits is specified. For instance, IQ21 means that the number has 21 fractional bits, 10 integer bits and 1 bit is for the sign.
For the representation of the negative numbers:
 

   
And for the positive numbers:
 

 
As an example, 1.4142 in IQ10 representation:
   
Below there is a C# sample code for the representation:
IQ10 functions:
public double IQ10toFloat(double Var) { if (Var > 2147483648) //if the value is bigger than 2^31 (positive) { Var = Var - 4294967296; // Var - 2^32 Var = Var / (1024); // Var/(2^10) } else { Var = Var / (1024); } return Var; }
public UInt32 FloatToIQ10(double Var) { UInt32 Retorn=0;
if (Var <0 ) // if negative { Var = (1024*Var) + 4294967296; // x*2^10 + 2^32 } else { Var = Var * (1024); } Retorn = Convert.ToUInt32(Var); return Retorn; }
Page 50
50 / 55
IQ21 functions:
public double IQ21toFloat(double Var) { if (Var > 2147483648) //if the value is bigger than 2^31 (positive) { Var = Var - 4294967296; // Var - 2^32 Var = Var / (2097152); // Var / (2^21) } else { Var = Var / (2097152); //Var/(2^21) } return Var; }
public UInt32 FloatToIQ21(double Var) { UInt32 Retorn = 0;
if (Var < 0) // if negative { Var = (2097152 * Var) + 4294967296; // Var*2^21 + 2^32 } else { Var = Var * (2097152); // Var*2^21 } Retorn = Convert.ToUInt32(Var); return Retorn; }
Page 51
51 / 55
7. HUMAN MACHINE INTERFACE
CINERGIA delivers, within the scope of the supply, a Human Machine Interface software that communicates with the equipment using MODBUS protocol. This application is based on Windows 7/Windows XP. The software can be installed by executing Setup.exe file in Administrator Mode and following the instructions of the application.
The software is based in a Tab Dialog, so each tab has different uses:
- OPERATION
- SUPERVISION
- ALARM
- I, V,P CONFIGURATION
7.1. Operation tab
A- Information about the status of the equipment and buttons to control it:
- Enable / Disable: the corresponding led shows whether the equipment is
enabled or disabled.
- Run / Ready: the corresponding led shows whether the equipment is running or
is ready for operation.
- Reset: it allows the user to reset all the alarms that have occurred and that have
been previously announced.
B- Selection of the operating mode and information about the active one:
- Current Control / Voltage Control / Power Control
- Parallelized Outputs / Independent Outputs
Page 52
52 / 55
C- Connection parameters for the communications:
- IP of the equipment (192.168.55.204), port (502). This equipment has a fixed IP.
- Pooling time [ms] is the time to refresh all parameters. The minimum value
recommended is 500 ms.
- Connect / Disconnect / Pause buttons
D- Information about the State Machine of the two converters of the equipment (Active Rectifier and DC/DC Output).
7.2. Supervision tab
A- Information about electrical parameters of both converters:
- Voltage, current, frequency, temperatures, active and reactive power.
B- Trend plots of voltage, current and power:
- Only one variable per plot is allowed at the same time.
- The refreshing time is defined by the pooling time, therefore it is not possible to
detect fast transients of the variable.
Page 53
53 / 55
7.3. Alarm tab
In this tab, the alarm status of each converter is shown.
7.4. I, V, P configuration tab
A- Information and setpoints for the electrical parameters associated to the Current, Voltage and Power operating modes. By using the Send button the data is downloaded to the equipment.
B- Setpoint of the reactive power for the grid-tied Active Rectifier. The information is sent to the equipment after pressing the Send button.
Page 54
54 / 55
8. WARRANTY AND MAINTENANCE
Fans and capacitors must be replaced at the end of their useful lifetime.
Inside the equipment there are dangerous voltages and metallic parts at high
temperatures even when the equipment is stopped. The direct contact may
cause electrocutions and burns. All the operations must be done by authorized
technical staff.
8.1. Replacing the output fuses
This operation must be performed by personnel experienced with electrical
systems. The direct contact can cause electrocutions and burns.
In order to replace the output fuses follow procedure below:
1. Stop the power supply following the instructions of FULL STOP
2. Turn the output switch-disconnector (Q2) to the OFF position
3. Open the fuse holder and replace the fuses
The output fuses can only be replaced by ultrafast models type Gould aR 660V (14x51 or 22x58 mm, depending on the unit model) of the same dimensions and rating.
8.2. Fans
The useful lifetime of the fans used to cool the power circuits depends on the use and environment conditions. It is recommended their preventive replacement by authorized technical staff.
8.3. DC bus capacitors
The useful lifetime of the DC bus capacitors and those ones used in the input and output filtering depends on the use and the environment conditions. It is recommended their preventive replacement by authorized technical staff.
8.4. Warranty
CINERGIA warrants that the delivered equipment is free from any defect affecting the functioning thereof for a time period not exceeding one (1) year from the Ex Works delivery date. If a purchased CINERGIA product becomes defective because of a faulty component or manufacturing, at any time during its standard warranty period, CINERGIA shall provide one of the following solutions:
• On-site technical assistance;
• Product or component repair at CINERGIA’s premises.
Page 55
55 / 55
• Replacement of the defective product or component;
The decision whether to perform the assistance on-site, to repair or replace the faulty product and/or component shall be taken in any case exclusively by CINERGIA.
8.5. Claim procedure
The warranty rights can be exercised during the validity of the warranty period and immediately upon detecting any abnormalities, except in the case of visible defects, in which case the claim shall be submitted within a maximum time of 7 days from the date of receipt of the equipment and always prior to their installation.
If defect of malfunction is detected, please proceed as follows:
• Immediately notify in writing CINERGIA by submitting a brief report describing the type of fault detected and all the data contained in the product data plate, attaching a copy of the purchase invoice/receipt. Such documentation shall be sent to the email address of the Sales Team (comercial@cinergia.coop).
• Upon receiving the documentation, CINERGIA will analyse it to decide whether the intervention required is covered by the warranty terms described herein.
• If the claim is covered by the warranty terms, CINERGIA shall provide on-site technical assistance or, alternatively, can request the shipping of the defective product and/or component to have it repaired at CINERGIA premises. At last, CINERGIA shall decide to send a replacement product and/or component. The faulty product and/or component shall be returned to CINERGIA. Any shipping damages attributable to improper packaging shall not be covered by warranty.
• Failure to return the replaced equipment within 10 (ten) standard days shall authorize
CINERGIA to invoice the equipment supplied as replacement.
• In case the defect of the returned equipment is deemed not to be covered by the warranty,
CINERGIA shall issue an invoice to the purchaser for the repair activity.
• If on arrival at CINERGIA’s premises the returned equipment is deemed to be in perfect operating conditions, CINERGIA shall be authorized to issue an invoice for all the costs resulting from its replacement (analysis and testing of the equipment and shipping costs).
• CINERGIA reserves the right to provide a different model of product and/or component to process the claims covered by the warranty terms, in case the original model and/or component is out of production.
Loading...