Calpeda EASYMAT 5MM, EASYMAT 9, 2MM, EASYMAT 5MT, 2MT Original Operating Instructions

...
Variatore di frequenza Frequency converter Variateur de fréquence Variador de frecuencia Frequenzumwandler Регулятор частоты
EASYMAT
INSTRUCTIONS ORIGINALES POUR L’UTILISATION
P 444.06 F Page 30 Français
INSTRUCCIONES ORIGINALES DE USO P 444.06 E Página 44 Español ORIGINAL BETRIEBSANLEITUNG P 444.06 D Seite 58 Deutsch
ОРИГИНАЛЬНЫЕ ИНСТРУКЦИИ ПО ЭКСПЛУАТАЦИИ
P 444.06 RU ëÚ‡Ìˈ‡ 72 кЫТТНЛИ
1. Introduction
2. Special warnings regarding the frequency converter
3. Types
4. Operating conditions
5. Construction
5.1. Technical features
5.2. Pushbutton functions
5.3. Interface
5.3.1. System icons
5.3.2. Display area
5.3.3. Operating icons
5.4. Submersible pump applications or high long cables
6. Installation
7. Electrical connection
7.1. Power supply line
7.2. Motor connection
7.3. Pressure transducer
7.4. Cascade mode
7.4.1. Cascade mode installation
7.4.2. Cascade mode electrical connection
7.4.3. Cascade connection with 2 variable speed pumps
7.4.4. Cascade connection with 1 variable speed pump and 1 fixed speed pump
7.4.5. Cascade mode programming
7.4.6. Cascade mode plant starting
7.5. Float switch connection
7.6. Remote alarm connection
8. Dry-running protection
9. Parameters
9.1. Parameters of pump status
9.2. Programming parameters
10. Programming
10.1. PASSWORD Insertion
11. Parameters to check when starting up the unit.
11.1. Vessel pressure
12. Plant starting
12.1. Changing direction of rotation
13. Operation
13.1. Quick set point modification
14. Use of megaohmeter
15. Maintenance
16. Accessories
16.1. RA 100
16.2. Pipe housings Kit
16.3. Union kit
17. Disposal
18. High length cables EASYMAT applications
18.1. Reduction of the electromagnetic noise emissions
18.2. Reduction of the electromagnetic irradiated noises to the motor
19. Line filter EMC/RFI for EASYMAT applications
20. Electrical connection scheme
21. Plant conversion scheme
22. Pump installation scheme
22.1. One pump installation scheme
22.2. Two pump installation scheme
23. Declaration of conformity
Frequency converter
EASYMAT 5MM EASYMAT 9,2MM EASYMAT 5MT EASYMAT 7,5MT EASYMAT 9,2MT
OPERATING INSTRUCTIONS
16
1. Introduction
We strongly suggest that the operator carefully reads and follows the information contained in this instruction manual for the frequency converter.
Symbol used:
This symbol indicates high voltage
hazard. It draws attention to components
or procedures that could represent a potential danger to the health and welfare of the operator.
This symbol is used to draw the operator's
attention to situations of potential danger
for people or for operations that could cause damage to the product.
2. Special warnings regarding the frequency converter
We strongly suggest that the operator
carefully reads and follows the information contained in this instruction manual for the
frequency converter.
The FREQUENCY CONVERTER should
NEVER be opened or tampered with and guards that come with it should
never be removed.
The frequency converter must be
installed, adjusted and maintained by qualified personnel who understand the
risks involved.
The frequency converter must be fitted
with voltage surge and overload protection devices, in accordance with the
prevailing safety standards.
The connection of the alarms can
distribute power even when the frequency
converter is turned off. Ensure that there is no residual voltage on the terminals of the alarms.
All the power terminals and other
terminals must be inaccessible after
installation is completed.
The maximum output frequency must not
exceed the design frequency of the pump
being controlled. Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device.
If it is necessary to remove the frequency
converter, remove only the covers
required in order to disconnect the electrical cables. Take care not to damage the electronic cards.
Failure to comply with the safety
regulations not only causes risk to
personal safety and damage to the equipment, but also invalidates every right to assistance under warranty.
Electro-magnetic compatibility.
The frequency converter is constructed in compliance with European standard 2004/108CE.
Responsibility:
The manufacturer is not liable for malfunctioning if the product has not correctly been installed, damaged, modified, and/or run outside the recommended work range or not in accordance with other indications given in this manual. The Manufacturer declines all responsibility for possible errors in this instructions manual, if due to misprint or error in copying. The Manufacturer reserves the right to make any modifications to products that it may consider necessary or useful, without affecting the essential characteristics. The responsibility of the manufacturer is limited to the product and excludes costs or greater damage caused by incorrect installation.
3. Types
Type
Freqeuency converter
Standard power
(single-phase) max current output
V230 motor
A kW
Easymat 5MM 5 0,37 - 0,55 Easymat 9,2MM 9,2 0,75 - 1,1
Type
Freqeuency converter
Standard power
(three-phase) max current output
V230 motor
A kW
Easymat 5MT 5 0,75 - 1,1 Easymat 7,5MT 7,5 1,5 - 1,8 Easymat 9,2MT 9,2 2,2
17
4. Operating conditions
(Standard execution)
The electrical panel functions correctly under the following power and installation characteristics:
- Power fluctuation: +/-10% max
- Frequency fluctuations: +/- 4 % max
- Ambient temperature: -10 °C a + 40 °C
- Relative humidity: from 20% to 90% without condensation
- Vibration: max 5,9 m/s
2
(0,6 g) to 10-55 Hz
- Altitude: no higher than 1000 m, inside a closed
environment.
- Max liquid temperature:
• 50 °C EASYMAT 5MM, 9,2MM, 5MT, 9,2MT
• 40 °C EASYMAT 7,5MT
- Minimum delivery: 3 l/min
The current distributed by the frequency converter must be equal to or lower than the maximum current absorbed by the motor to control.
5. Construction
(Standard execution)
The system is composed of:
- Frequency converter.
- Pressure transducer.
- Pipe housings.
- Fixing screws.
- Terminal board.
- Cable glands.
- Multi-hole gaskets.
5.1. Technical features
Power supply interface: 230V ± 10% Protection: IP55 Display: LCD Display Keyboard: 6 buttons Digital inputs: - float switch for dry-running
protection
- tank fill float switch
- safety pressure switch Analogue inputs: pressure transducer 4-20 mA Digital outputs: general alarm, the display shows
the type of alarm (see paragraphs
7.6. and 9.3.) Connectivity: RS485 Protections: - dry-running protection
- over-current
- over-heating
- under-voltage and over-voltage
- short-circuit protection on the motor phase
5.2. Pushbuttons functions
Through this button you can start the pump
.
Through this button you can stop the pump
.
Through this button you have access to frequency converter programming parameters. If you already are on the programming function, by pushing this button you go up on the menù
.
Through this button you have access to frequency converter programming parameters. If you have changed a parameters, by pushing this button you can confirm the indicated value.
Through this button you can increase parameters or to change the visualized parameter.
Through this button you can decrease parameters or to change the visualized parameter.
5.3. Interface
The graphic interface of the display is divided in three visualization areas: - system icons
- display area
- operating icons
P460
4.93.410
4.93.409.1
18
5.3.1. System icons
AUTO MODE
The system is operating in auto mode.
MANUAL MODE
The system is operating in manual mode.
SET-UP MODE ACTIVATED
It shows that the set-up menu is activated. When a icon is blinking you are modifying
a parameter. You can confirm with enter.
ALARM
It indicates that there is a fault on the system, the error number appears on the display area. When you are on the set-up mode the alarm icon will not appear
SENSOR STATE
It indicates that the system is connected with the pressure transducer; if it is blinking there is a fault on the pressure transducer.
PUMP STATE
It indicates if the pump is running or in stand-by state.
CASCADE MODE
It indicates that the cascade control mode is working. The 2 upper symbols show if the pump is running or if the pump is in stand-by. The lower symbol informs if the pump is the master (lighted icon) or slave (blinking icon).
5.3.2. Display area
It is composed from an incremental bar proportional with the displayed value and its measure unit The display is backlit, the light will be turn off after 20s of system inactivity.
5.3.3. Operating icons
Constant pressure mode
The system keeps the pressure constant when the quantity of water requested by the user changes.
Fixed speed mode
The system works at a fixed speed that user can choose according to need.
5.4. Submersible pumps applications or long cables
To operate a submerged pump (or surface pump),where the distance from the inverter is more than 10 m, see paragraph 18.
Submersible motor must operate with a
frequency between 30 Hz (minimum
operating frequency) and 50 Hz (maximum frequency) for 50 Hz motors, and between 30 and 60 Hz for 60 Hz motors.
The running up time from 0 to 30 Hz and
the running down time from 30 Hz and 0,
must be as short as possible, according to the motor power to operate.
6. Installation
For easy assembling and disassembling of the frequency converter we recommend to respect the minimum distances as show in figure herebelow.
In case of reduced distances connect the frequency converter with the proper unions (see paragraph 16.3.). Do not install the control panel in places exposed to direct sunlight or near sources of heat.
Fasten the heatsink (a) to the pipe by means of the pipe housings (b1-b2) and the screws (c) in equipment.
4.93.412.5
250
100
4.93.412
b2c b1 a
19
The pressure transducer (d) must be installed on the system. We always advise the installation of a small accumulator (e) (8 ltrs minimum) on the pump delivery side.
7. Electrical connection
Electrical connection must be carried out by a qualified electrician in accordance with local regulations.
Follow all safety standards. The unit must be properly earthed (grounded).
Follow the instructions in the wiring diagram attached.
Once the electrical connection has been completed, remove any pieces of wire, sheath, washers or any other foreign bodies that may be found inside the frequency converter.
For the electrical connections on both the terminal board and the motor use cable with a maximum section of 2,5mm
2
. We also
advise the use of insulated pin terminals. Bad connections may damage the electronic
circuit.
7.1. Power supply line
Power supply line must comply with the provisions under paragraph 4.
If a differential protection is necessary, install a type A differential switch, protected against untimely activation and with threshold of intervention of 30 mA.
Electrical connection
7.2. Motor connection
The power supply line of the electrical motor must be connected directly to the output terminal of the inverter.
To comply with the standards of electromagnetic compatibility, use a shielded three-pole cable (for MM models) or a shielded four-pole cable (for MT models) with external protection sheath.
The power supply line of the motor must never run parallel to the power line of the electrical panel.
Electrical connection
d
e
4.93.412.1
4.93.413.6
20
7.3. Pressure transducer
The pressure transducer is an analogical instrument with an output signal of 4-20 mA that continuously reads the pressure in a system.
Features:
Standards: EN 50081-1, EN 50082-2. Voltage: 8-28 V Pressure range: 0-6; 0-10; 0-16 bar Output: 4-20 mA Working temperature: da 0 a +50 °C Protection: IP 65 Hydraulic connection : G 1/4 male Weigth: ~ 60 g
Electrical connection
Pressure transducer terminal box supplied by us
7.4. Cascade mode
The EASYMAT frequency converters are prearranged for use in pressure boosting sets with up to 3 pumps in the following versions:
- Pressure boosting sets with 2 variable speed pumps
- Pressure boosting sets with 3 variable speed pumps
- Pressure boosting sets with 1 variable speed pump and 1 fixed speed pump (single-phase)
7.4.1.
Cascade mode
installation
Connect the frequency converters on the delivery pipes of the pumps, the installation must comply with the provisions under paragraph 6. Connect the pressure transducer to the delivery manifold of the pressure boosting sets.
It is advised to install the pressure
transducers on the same point of the delivery manifold and complete the
installation with a pressure gauge.
7.4.2.
Cascade mode
electrical
connection
Connect the supply cables to the motors and to the power supply following the instructions under paragraph 7. The power supply must comply the provisions of the paragraph 4-5.
The connection with the power supply
must be made with interpositions of magnetothermal bipolar switches (one for
each frequency converter).
For these frequency converters an earth leakage circuit breaker or ground fault circuit interrupter, type B. This circuit breaker or interrupter must be marked with the following symbols:
7.4.3. Cascade connection with variable speed pumps
Electrical connection with 2 pumps
By means a proper cable make the connection of the clamps number 4-5-6 of both frequency converters.
Electrical connection with 3 pumps
By means a proper cable make the connection of the clamps number 4-5-6 of each frequency converters.
User must provide a jumper connection
into 1 frequency converter as shown in the picture.
Check the correct connection sequence and
check that terminals of each cable are connected on the clamp with same number.
To comply with the standards of
electromagnetic compatibility, for cable
length greater than 1 meter, it is recommend the use of a shielded cable with protection sheath connected on the ground of both frequency converters.
7.4.4. Cascade connection with 1 variable speed pump and 1 fixed speed pump
Connect the clamps 10-11 with a contactor with max.250 Vac and 450 mA maximum resistive current, connect to the contactor the power supply
-
+
4.93.413.1
2211 33
1
3
2
4
+
RS 485
0-
4.93.413.2
+
RS 485
0-
+
RS 485
0- +
RS 485
0-
21