Calpeda EASYMAT 5MM, EASYMAT 9, 2MM, EASYMAT 5MT, 2MT Original Operating Instructions

...
Variatore di frequenza Frequency converter Variateur de fréquence Variador de frecuencia Frequenzumwandler Регулятор частоты
EASYMAT
INSTRUCTIONS ORIGINALES POUR L’UTILISATION
P 444.06 F Page 30 Français
INSTRUCCIONES ORIGINALES DE USO P 444.06 E Página 44 Español ORIGINAL BETRIEBSANLEITUNG P 444.06 D Seite 58 Deutsch
ОРИГИНАЛЬНЫЕ ИНСТРУКЦИИ ПО ЭКСПЛУАТАЦИИ
P 444.06 RU ëÚ‡Ìˈ‡ 72 кЫТТНЛИ
1. Introduction
2. Special warnings regarding the frequency converter
3. Types
4. Operating conditions
5. Construction
5.1. Technical features
5.2. Pushbutton functions
5.3. Interface
5.3.1. System icons
5.3.2. Display area
5.3.3. Operating icons
5.4. Submersible pump applications or high long cables
6. Installation
7. Electrical connection
7.1. Power supply line
7.2. Motor connection
7.3. Pressure transducer
7.4. Cascade mode
7.4.1. Cascade mode installation
7.4.2. Cascade mode electrical connection
7.4.3. Cascade connection with 2 variable speed pumps
7.4.4. Cascade connection with 1 variable speed pump and 1 fixed speed pump
7.4.5. Cascade mode programming
7.4.6. Cascade mode plant starting
7.5. Float switch connection
7.6. Remote alarm connection
8. Dry-running protection
9. Parameters
9.1. Parameters of pump status
9.2. Programming parameters
10. Programming
10.1. PASSWORD Insertion
11. Parameters to check when starting up the unit.
11.1. Vessel pressure
12. Plant starting
12.1. Changing direction of rotation
13. Operation
13.1. Quick set point modification
14. Use of megaohmeter
15. Maintenance
16. Accessories
16.1. RA 100
16.2. Pipe housings Kit
16.3. Union kit
17. Disposal
18. High length cables EASYMAT applications
18.1. Reduction of the electromagnetic noise emissions
18.2. Reduction of the electromagnetic irradiated noises to the motor
19. Line filter EMC/RFI for EASYMAT applications
20. Electrical connection scheme
21. Plant conversion scheme
22. Pump installation scheme
22.1. One pump installation scheme
22.2. Two pump installation scheme
23. Declaration of conformity
Frequency converter
EASYMAT 5MM EASYMAT 9,2MM EASYMAT 5MT EASYMAT 7,5MT EASYMAT 9,2MT
OPERATING INSTRUCTIONS
16
1. Introduction
We strongly suggest that the operator carefully reads and follows the information contained in this instruction manual for the frequency converter.
Symbol used:
This symbol indicates high voltage
hazard. It draws attention to components
or procedures that could represent a potential danger to the health and welfare of the operator.
This symbol is used to draw the operator's
attention to situations of potential danger
for people or for operations that could cause damage to the product.
2. Special warnings regarding the frequency converter
We strongly suggest that the operator
carefully reads and follows the information contained in this instruction manual for the
frequency converter.
The FREQUENCY CONVERTER should
NEVER be opened or tampered with and guards that come with it should
never be removed.
The frequency converter must be
installed, adjusted and maintained by qualified personnel who understand the
risks involved.
The frequency converter must be fitted
with voltage surge and overload protection devices, in accordance with the
prevailing safety standards.
The connection of the alarms can
distribute power even when the frequency
converter is turned off. Ensure that there is no residual voltage on the terminals of the alarms.
All the power terminals and other
terminals must be inaccessible after
installation is completed.
The maximum output frequency must not
exceed the design frequency of the pump
being controlled. Operating at a frequency higher than the allowable frequency can cause higher current absorption and damage to the device.
If it is necessary to remove the frequency
converter, remove only the covers
required in order to disconnect the electrical cables. Take care not to damage the electronic cards.
Failure to comply with the safety
regulations not only causes risk to
personal safety and damage to the equipment, but also invalidates every right to assistance under warranty.
Electro-magnetic compatibility.
The frequency converter is constructed in compliance with European standard 2004/108CE.
Responsibility:
The manufacturer is not liable for malfunctioning if the product has not correctly been installed, damaged, modified, and/or run outside the recommended work range or not in accordance with other indications given in this manual. The Manufacturer declines all responsibility for possible errors in this instructions manual, if due to misprint or error in copying. The Manufacturer reserves the right to make any modifications to products that it may consider necessary or useful, without affecting the essential characteristics. The responsibility of the manufacturer is limited to the product and excludes costs or greater damage caused by incorrect installation.
3. Types
Type
Freqeuency converter
Standard power
(single-phase) max current output
V230 motor
A kW
Easymat 5MM 5 0,37 - 0,55 Easymat 9,2MM 9,2 0,75 - 1,1
Type
Freqeuency converter
Standard power
(three-phase) max current output
V230 motor
A kW
Easymat 5MT 5 0,75 - 1,1 Easymat 7,5MT 7,5 1,5 - 1,8 Easymat 9,2MT 9,2 2,2
17
4. Operating conditions
(Standard execution)
The electrical panel functions correctly under the following power and installation characteristics:
- Power fluctuation: +/-10% max
- Frequency fluctuations: +/- 4 % max
- Ambient temperature: -10 °C a + 40 °C
- Relative humidity: from 20% to 90% without condensation
- Vibration: max 5,9 m/s
2
(0,6 g) to 10-55 Hz
- Altitude: no higher than 1000 m, inside a closed
environment.
- Max liquid temperature:
• 50 °C EASYMAT 5MM, 9,2MM, 5MT, 9,2MT
• 40 °C EASYMAT 7,5MT
- Minimum delivery: 3 l/min
The current distributed by the frequency converter must be equal to or lower than the maximum current absorbed by the motor to control.
5. Construction
(Standard execution)
The system is composed of:
- Frequency converter.
- Pressure transducer.
- Pipe housings.
- Fixing screws.
- Terminal board.
- Cable glands.
- Multi-hole gaskets.
5.1. Technical features
Power supply interface: 230V ± 10% Protection: IP55 Display: LCD Display Keyboard: 6 buttons Digital inputs: - float switch for dry-running
protection
- tank fill float switch
- safety pressure switch Analogue inputs: pressure transducer 4-20 mA Digital outputs: general alarm, the display shows
the type of alarm (see paragraphs
7.6. and 9.3.) Connectivity: RS485 Protections: - dry-running protection
- over-current
- over-heating
- under-voltage and over-voltage
- short-circuit protection on the motor phase
5.2. Pushbuttons functions
Through this button you can start the pump
.
Through this button you can stop the pump
.
Through this button you have access to frequency converter programming parameters. If you already are on the programming function, by pushing this button you go up on the menù
.
Through this button you have access to frequency converter programming parameters. If you have changed a parameters, by pushing this button you can confirm the indicated value.
Through this button you can increase parameters or to change the visualized parameter.
Through this button you can decrease parameters or to change the visualized parameter.
5.3. Interface
The graphic interface of the display is divided in three visualization areas: - system icons
- display area
- operating icons
P460
4.93.410
4.93.409.1
18
5.3.1. System icons
AUTO MODE
The system is operating in auto mode.
MANUAL MODE
The system is operating in manual mode.
SET-UP MODE ACTIVATED
It shows that the set-up menu is activated. When a icon is blinking you are modifying
a parameter. You can confirm with enter.
ALARM
It indicates that there is a fault on the system, the error number appears on the display area. When you are on the set-up mode the alarm icon will not appear
SENSOR STATE
It indicates that the system is connected with the pressure transducer; if it is blinking there is a fault on the pressure transducer.
PUMP STATE
It indicates if the pump is running or in stand-by state.
CASCADE MODE
It indicates that the cascade control mode is working. The 2 upper symbols show if the pump is running or if the pump is in stand-by. The lower symbol informs if the pump is the master (lighted icon) or slave (blinking icon).
5.3.2. Display area
It is composed from an incremental bar proportional with the displayed value and its measure unit The display is backlit, the light will be turn off after 20s of system inactivity.
5.3.3. Operating icons
Constant pressure mode
The system keeps the pressure constant when the quantity of water requested by the user changes.
Fixed speed mode
The system works at a fixed speed that user can choose according to need.
5.4. Submersible pumps applications or long cables
To operate a submerged pump (or surface pump),where the distance from the inverter is more than 10 m, see paragraph 18.
Submersible motor must operate with a
frequency between 30 Hz (minimum
operating frequency) and 50 Hz (maximum frequency) for 50 Hz motors, and between 30 and 60 Hz for 60 Hz motors.
The running up time from 0 to 30 Hz and
the running down time from 30 Hz and 0,
must be as short as possible, according to the motor power to operate.
6. Installation
For easy assembling and disassembling of the frequency converter we recommend to respect the minimum distances as show in figure herebelow.
In case of reduced distances connect the frequency converter with the proper unions (see paragraph 16.3.). Do not install the control panel in places exposed to direct sunlight or near sources of heat.
Fasten the heatsink (a) to the pipe by means of the pipe housings (b1-b2) and the screws (c) in equipment.
4.93.412.5
250
100
4.93.412
b2c b1 a
19
The pressure transducer (d) must be installed on the system. We always advise the installation of a small accumulator (e) (8 ltrs minimum) on the pump delivery side.
7. Electrical connection
Electrical connection must be carried out by a qualified electrician in accordance with local regulations.
Follow all safety standards. The unit must be properly earthed (grounded).
Follow the instructions in the wiring diagram attached.
Once the electrical connection has been completed, remove any pieces of wire, sheath, washers or any other foreign bodies that may be found inside the frequency converter.
For the electrical connections on both the terminal board and the motor use cable with a maximum section of 2,5mm
2
. We also
advise the use of insulated pin terminals. Bad connections may damage the electronic
circuit.
7.1. Power supply line
Power supply line must comply with the provisions under paragraph 4.
If a differential protection is necessary, install a type A differential switch, protected against untimely activation and with threshold of intervention of 30 mA.
Electrical connection
7.2. Motor connection
The power supply line of the electrical motor must be connected directly to the output terminal of the inverter.
To comply with the standards of electromagnetic compatibility, use a shielded three-pole cable (for MM models) or a shielded four-pole cable (for MT models) with external protection sheath.
The power supply line of the motor must never run parallel to the power line of the electrical panel.
Electrical connection
d
e
4.93.412.1
4.93.413.6
20
7.3. Pressure transducer
The pressure transducer is an analogical instrument with an output signal of 4-20 mA that continuously reads the pressure in a system.
Features:
Standards: EN 50081-1, EN 50082-2. Voltage: 8-28 V Pressure range: 0-6; 0-10; 0-16 bar Output: 4-20 mA Working temperature: da 0 a +50 °C Protection: IP 65 Hydraulic connection : G 1/4 male Weigth: ~ 60 g
Electrical connection
Pressure transducer terminal box supplied by us
7.4. Cascade mode
The EASYMAT frequency converters are prearranged for use in pressure boosting sets with up to 3 pumps in the following versions:
- Pressure boosting sets with 2 variable speed pumps
- Pressure boosting sets with 3 variable speed pumps
- Pressure boosting sets with 1 variable speed pump and 1 fixed speed pump (single-phase)
7.4.1.
Cascade mode
installation
Connect the frequency converters on the delivery pipes of the pumps, the installation must comply with the provisions under paragraph 6. Connect the pressure transducer to the delivery manifold of the pressure boosting sets.
It is advised to install the pressure
transducers on the same point of the delivery manifold and complete the
installation with a pressure gauge.
7.4.2.
Cascade mode
electrical
connection
Connect the supply cables to the motors and to the power supply following the instructions under paragraph 7. The power supply must comply the provisions of the paragraph 4-5.
The connection with the power supply
must be made with interpositions of magnetothermal bipolar switches (one for
each frequency converter).
For these frequency converters an earth leakage circuit breaker or ground fault circuit interrupter, type B. This circuit breaker or interrupter must be marked with the following symbols:
7.4.3. Cascade connection with variable speed pumps
Electrical connection with 2 pumps
By means a proper cable make the connection of the clamps number 4-5-6 of both frequency converters.
Electrical connection with 3 pumps
By means a proper cable make the connection of the clamps number 4-5-6 of each frequency converters.
User must provide a jumper connection
into 1 frequency converter as shown in the picture.
Check the correct connection sequence and
check that terminals of each cable are connected on the clamp with same number.
To comply with the standards of
electromagnetic compatibility, for cable
length greater than 1 meter, it is recommend the use of a shielded cable with protection sheath connected on the ground of both frequency converters.
7.4.4. Cascade connection with 1 variable speed pump and 1 fixed speed pump
Connect the clamps 10-11 with a contactor with max.250 Vac and 450 mA maximum resistive current, connect to the contactor the power supply
-
+
4.93.413.1
2211 33
1
3
2
4
+
RS 485
0-
4.93.413.2
+
RS 485
0-
+
RS 485
0- +
RS 485
0-
21
cable and the motor cable of the fixed speed pump.
The connection with the power supply must be made with interpositions of magnetothermal bipolar switches with proper size and with a type A differential switch protected against untimely activation and with threshold of intervention of 30 mA.
The use of the cascade mode with 1 fixed speed pump not allow connection of a remote alarm or a control panel remote alarm RA100.
7.4.5. Cascade mode programming
Pressure boosting sets with 2 variable speed pumps.
After the connection, change the AP09 parameter from OFF to UU for both frequency converters, define which frequency converter will work on master mode and for this frequency converter change the AP10 parameter from SLA (slave) to MAS (master).
Pressure boosting sets with 3 variable speed pumps.
After the connection, change the AP09 parameter from OFF to UU for both frequency converters, define which frequency converter will work on master mode and for this frequency converter change the AP10 parameter from SLA(slave) to MAS (master). Then parameter AP15 must be changed for each “slave” frequency converter. The first slave frequency converter must be set as “SLA1”, and the second slave frequency converter must be set as “SLA2”. For the right behavior of the booster set it is recommended to switch off and switch on all the frequency converter.
This configuration define an address for each frequency converter, if not correctly configured, cascade mode will not work properly.
Pressure boosting sets with 1 variable speed pump and 1 fixed speed pump (single-phase).
After the connection, change the AP09 parameter from OFF to UF for the frequency converter.
7.4.6. Cascade mode plant starting
Check that all the cascade mode parameters are with the desired values, the parameters that can change the cascade mode operation are:
AP16 Cascade mode start fall pressure set-up AP17 Cascade mode restart delay AP18 Cascade mode fall pressure limit set-up
To do the plant starting follow the instructions under paragraph 12.
7.5.
Float switch connection
To connect a float-switch connect to the connections 8-9 the cables of the float switch. The float switch can be used for:
- dry-running protection if, in cascade mode, the frequency converter which is connected the float switch is failure, the float switch cannot shut off the pumps.
Electrical connection
7.6. Remote alarm connection
To connect a remote alarm connect to the connections 10-11 the possible remote alarm or the control panel for remote alarm RA100. The remote alarm can be used to signal:
- error on the frequency converter (see
paragraph 9.3.) (nO).
- the frequency converter is running (nC).
Operating limits: 250 Vac, 450 mA maximum resistive current.
Electrical connection
4.93.413.3
+
-
4.93.413.7
+
RA 100
-
4.93.413.4
22
23
8. Dry-running protection
The frequency converter is equipped with a dry­running protection for the pumps. When the pressure on the system remain for a time higher than the dry-run time (AP05) lower than value of the dry-run pressure (AP07) the protection system stop the pump. It is possible the use of an external float switch for the dry-running protection (see paragraph 7.5.). In this case the pumps start with a delay time (in seconds) defined by AP19 (Digital input restart time), the time will be counted after the change of the float switch state. For entering the programming mode see paragraph 10.
9. Parameters
On the frequency converter the following informations are displayed:
- Parameters of pump status.
- Programming parameters.
- Alarms.
9.1. Parameters of pump status
They allow to visualize:
- the modulation frequency of the pump (basic display).
- the pressure of the system.
- the line absorbed current.
Starting form the basic display by pushing of the directional arrow (plus) or (minus) the
other parameters are displayed. Example:
9.2. Programming parameters
To display the programming parameters, select
(menu).
Will be displayed progressively:
UP - User settings: these are the basis settings
that user can change.
AP - Advanced settings: these settings are
available only to qualified personnel. To enter password is required (see paragraph 10.1.).
SA - Technical assistance settings: these are
the advanced parameters, only technical assistance personnel are allowed to access this menu. Password is required (see paragraph 10.1.).
MAn - Fixed speed mode activation: this allows
activation of the fixed speed mode and the working frequency. Only qualified personnel are allowed to access this menu. Password is required (see paragraph
10.1.).
AE - Advanced parameters: this allows for the
display of secondary parameters which can be useful for system diagnostics.
AE01 Software release AE02 Supply voltage (V) AE03 Last 5 faults
Supply voltage visualization example.
By pushing the button (menu) the UP parameter appears. Select the AE parameter by
pushing the (plus) up to arrive at the correct
parameter , confirm with (enter).
Select the parameter by pushing the
button (plus) and confirm with (enter). Supply voltage is displayed.
9.2.1. UP – User settings
Description Standard Modifications Note
UP01 restart mode power failure rA
[rA = automatic; rM = manual] UP02 Nominal pump current (A) 0,1 UP03 Nominal pump frequency (Hz) 50 UP04 Direction of rotation ---
[ --- = std rotation; --- = inverted rotation] UP05 Set point pressure (bar) 1,5
9.2.2. AP – Advanced settings
To enter password is required (see paragraph 10.1.)
Description Standard Modifications Note
AP01 Pressure transducer set-up (bar) 10
[sensor full-scale] AP02 Ramp down (s) 3 AP03 Ramp-up (s) 2 MT
(fixed value for MM) 0 MM AP04 Time before stop (s) 30 AP05 Dry-run time (s) 10 AP06 First dry-run time (s) 60 AP07 Dry-run pressure (bar) 1,5 AP08 System dynamic 3
[1 = fast dynamic; 5 = slow dynamic] AP09 Cascade mode oFF
[oFF; UU = cascade mode with double inverter;
UF = cascade mode with an inverter] AP10 Master/Slave setting SLA
MAS = master; SLA = slave AP11 Reset to factory set-up AP12 Digital input activation 1
[0 = oFF; 1 = no; 2 = nC] AP13 Digital output activation 0
[0 = oFF; 1 = on; 2 = no; 3 = nC] AP14 Restart fall pressure set-up (bar) AP15 Pump address SLA1 AP16 Cascade mode start fall pressure set-up (bar) 0,3 AP17 Cascade mode restart delay (s) 10 AP18 Cascade mode fall pressure limit set-up (bar) 0,6 AP19 Digital input delay time (s) 30
[float switch delay time]
24
4.93.410
P460
9.2.3. SA – Technical assistance settings
To enter password is required (see paragraph 10.1.)
Description Standard Modifications Note
SA01 SA02 SA03 Pressure PID (Proportional gain) 2,8 SA04 Pressure PID (Integral time constant) 5,5 SA05 Pressure PID (Derivative time constant) 5,0 SA06 Min. run frequency (Hz) 30 SA07 Max frequency (Hz) 60 SA08 Set point pressure step up (bar) 0,3 SA09 Pressure step up time (s) 3 SA10 Pressure step up ramp (bar/s) 0,3 SA11 Set point control ramp (bar/s) 0,4 SA12 Carrier frequency 7010 SA13 Singlephase starting frequency (Hz) 80 SA14 Singlephase starting voltage (V) 195 SA15 Nominal voltage (V) 220
9.2.4. MAn – Fixed speed mode activation
To enter password is required (see paragraph 10.1.)
Description Standard Modifications Note
MAn1 Fixed speed mode activation oFF MAn2 Working frequency [MAn2 ≤ UP03] (Hz) 45
a
9.3. Alarms
Displayed alarm Causes
Er01 Blockage due to no water The device is in failure due to no water.
The system try to restart automatically.
- One attempt every 10 minutes for 6 times.
- One attempt every hour for 24 times.
- One attempt every 24hours for 30 times.
Er02 Pressure transducer fault Not connected cable, broken connection, pressure
transducer spoiled.
Er03 Blockage due to low supply voltage Supply voltage lower than 190V.
- The system automatically restart when the clamp voltage is higher than 190V.
Er04 Blockage due to high rectified voltage Supply voltage higher than 250V.
- The system automatically restart when the clamp voltage is lower than 250V.
Er05 Blockage for memory failure Er06 Blockage due to overcurrent in the electro
pump motor
Er07 Blockage due to overcurrent in the
frequency converter
Er08 Blockage due to direct short circuit between
the phases of output terminals Er09 Blockage due to overheating Er10
Blockage due to overheating of the power module Er11 Blockage due to low voltage 24 V Er12 Stop for float switch intervention The system will restart with a delay defined by AP19
from the state variation of the float switch. The control
panel for remote alarm not report this alarm. Er13 Internal hardware error Contact the technical assistance Er14 Cascade mode communication error Check the RS 485 connection or that both pumps
are enabled.
In case of multiple fault, scroll with the buttons (plus) or (minus) to visualize the fault sequence. In case of thermal block it is advised to check the causes that have created the problem before restart the pump operation.
25
10. Programming
To enter programming, select (menu). Use the buttons (plus) or (minus) to move to the
programming parameter to be modified and select
(enter) to confirm. Use the buttons (plus) or (minus) to move to the parameter to be
modified and select (enter) to confirm, with the buttons (plus) or (minus) increase or
decrease the value. From this moment the set-up
icon start blinking until the value is confirmed
with (enter).
To exit the program, push (menu) until when you arrive on the basic display. When you go in the set-up mode appear the icon
.
Example of parameter variation.
In order to modify the set point pressure from 3.0 bars to a 2.8 bars:
select (menu) and then with the buttons (plus) or (minus) until you move to
programming parameter UP. Confirm with (enter) and then with the buttons (plus) or
(minus) move to the parameter UP05. Confirm
with (enter) and then with the buttons (plus) or (minus) change the value up to the
desired value. From this moment the set-up icon
start blinking until the value is confirmed with
(enter).
To exit the program, push (menu) until you arrive on the basic video, when you are out from
the set-up mode the icon disappear .
10.1. PASSWORD insertion
To enter on a menu with password, four numbers appear on the display, the number to insert is
blinking. By pushing buttons (plus) or (minus) you can change the blinking value. If you
confirm with (enter) the next number start blinking. If the password is correct you can enter on the MENU, if the password is wrong the first number restart blinking.
To exit the program, push (menu) until you arrive on the basic display, when you are out from
the set-up mode the icon disappear .
password value
user 1959
Technical assistance contact the technical
assistance
11. Parameters to check when starting up the unit
There are 4 programming parameters that need to be checked when the unit is started up:
• Parameter UP02 NOMINAL PUMP CURRENT
The nominal current of the pump must be set.
If the value input is inappropriate there is the risk of pump damage or to have an unexpected overcurrent alarm.
• Parameter UP03 NOMINAL PUMP
FREQUENCY
The nominal frequency of the pump must be set.
If the value input is inappropriate there is the risk of higher current absorption or pump damage.
• Parameter UP05 SET POINT PRESSURE
The working pressure of the pump must be set. If the value input is inappropriate for the needs
of the system, the value can be increased or decreased using the (plus) or (minus)
keys.
If during the first start-up of the unit, filling the system takes longer than 1 minute and the unit signals a dry-running alarm, Increase the parameter AP06, until the pressure rises above the set value and the pump remain on. (Make sure the pump are primed).
11.1. Vessel pressure
Once the new working pressure is entered, the tank pre-loaded pressure must be changed to be 2/3 of the working pressure (i.e. 4 bar working pressure,tanks to be pre-loaded at 2.7 bar).
26
12. Plant starting
ATTENTION: never run the pump dry
not even for a short trial run. Start the
pump after filling completely with liquid.
After completing hydraulic and electrical connection and checked the preloaded pressure (for booster set with membrane tank), start the plant as indicated below:
Prime the pumps (see the pumps instructions).
Pump with suction lift:
- Fill the suction pipe and the pump body by means of the plug hole located close to the delivery port of the pump.
- Fill the suction tube by pouring water through the plug hole on the suction manifold of the pump.
Pump with positive suction head:
- Open the gate-valve in the suction pipeline.With sufficient head, the water will overcome the resistance of the non-return valve fitted in the suction side of the pump and will fill the pump body. Otherwise, prime the pump with the plug hole near the delivery port.
Never run the pump for more than five minutes with closed gate valve.
Starting pump
When the freqeuncy converter is switched on, the pump are not operating and on the screen appears OFF.
Press the button (play) to change the pump status from STOP to run. The pump starts up with
the acceleration ramp set to reach the wished pressure.
When the motor starts turning, check the direction of rotation.
If the pump has been primed correctly, after a few seconds the pressure will begin to increase on the display. If, after a few seconds‚ operation the pressure
remains at 0.0, stop the pump by selecting (stop) as priming has not been carried out correctly and the pump is idling. Re-prime the pump and repeat the starting up procedure.
12.1. Inversion of the direction of rotation
To change the direction of rotation of the motor,
push the button (menù) and then with the button (plus) move up to the programming
parameter UP. Confirm with (enter) and with the button (plus) move up to the parameter
UP04, confirm with enter (enter) and by pushing of the button (plus) change the value,
confirm with (enter). To exit the program,
push (menù) until you arrive on the basic display, when you are out from the set-up mode
the icon disappear .
13. Operations
The frequency converter is programmed to manage the automatic operation of 1 or 2 pumps, all at variable speed. Depending on user consumption, the pumps start to guarantee the amount of water necessary at the set pressure. When one pump has reached 50 Hz and water requirements increase, the second pump will begin operations.
The pumps are protected against:
- operation when dry, by means of a floating
switch and level sensor,
- over/under voltage (frequency converter),
- thermal overload (frequency converter).
13.1. Quick set point modification
If the frequency converter is operating in constant pressure mode it is possible to change the set point pressure without enter on the user
parameter (UP menu). Pushing the button (enter) for more than 5 seconds you will enter directly to the set point pressure (UP05 parameter).
By pushing of the buttons (plus) or (minus) change the pressure value and confirm
with (enter). By pushing of the button (menu) the system will return to the basic display (see paragraph 9.1.).
27
14. Use of megaohmeter
Megging of an installation incorporating the frequency converter is not allowed, because the electronics may be damaged. If megging is necessary, disconnect the frequency converter and use the megaohmeter directly on the terminal box of the pump.
15. Maintenance
Inspect the tank pre-loaded pressure of the delivery vessel periodically.
16. Accessories
16.1. RA 100 Control panel for remote alarm.
Dimensions: 110x150x70 Power supply: 220-230 V single-phase Signals all pump assembly malfunctions detected:
- No water intake.
- Assembly malfunction.
- Converter failure.
5-Watt flashing red light plus 75 dB - 3600 Hz acoustic alarm, for use in areas of loud noise, positioned in such a way as to be visible from a distance. The control panel is fitted to an energized panel led and an alarm reset pushbutton.
RA 100
16.2. Pipe housings kit
Pipe housings for G1, G1 1/4 and G1 1/2 pipes. For the G1 1/2 version of the EASYMAT it is required change the screws assembled on the heatsink with the screws provided with the G1 1/2
pipe housing kit.
16.3. Unions kit
Steel pipe with unions and pressure transducer arrangement.
17. Disposal
Observe the local regulations and dispose of any control gear accordingly. This product contains electrical and electronic components and should be disposed of accordingly.
28
29
Modifica parametro - Change parameter - Changement de paramètre
Cambio de parámetros - Parameterwert ändern - изменение параметра
4.93.414.1
4.93.414.2
4.93.414.3
Max. ø 4,5 mm
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
90
20. Schemi collegamento elettrico Electrical connection scheme Schémas du branchement électrique Esquemas de conexión eléctrica Schemata der elektrischen Anschlüsse Электрические схемы
макс ø 4,5 мм
91
4.93.414.6
4.93.414.5
4.93.414.4
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
92
4.93.414.5
4.93.414.5
4.93.414.5
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
СЕТЬ
ДВИГАТЕЛЬ
4.93.412.2
4.93.412.3
4.93.412.6
22. Schema installazione pompa
Pump installation scheme Schéma de l’installation de la pompe Esquema de instalación de la bomba Installationsschema der Pumpe
Схемы установки насоса
22.1. Schemi installazione ad 1 pompa
One pump installation scheme Schémas de l’installation à 1 pompe Esquema de instalación a 1 bomba Installationsschema mit 1 Pumpe Схема установки с 1 насосом
21. Schema conversione impianto Plant conversion scheme Schéma de modification de l’installation Esquema de conversión de la instalación Konversionsschema der Anlage Схема переоснастки системы
93
22.2. Schemi installazione a 2 pompe
Two pump installation scheme Schémas de l’installation à 2 pompes Esquema de instalación a 2 bombas Installationsschema mit 2 Pumpen Схема установки с 2 насосами
4.93.412.4
94
DICHIARAZIONE DI CONFORMITÀ
Noi CALPEDA S.p.A. dichiariamo sotto la nostra esclusiva responsabilità che il variatore di frequenza, tipo e numero di serie riportati in targa, sono conformi a quanto prescritto dalle Direttive 2004/108/CE, 2006/95/CE, e dalle relative norme armonizzate CE EN 55014-1, CE EN 55022, CE EN 61000-3-3, CE EN 61000-4-2, CE EN 61000-4-3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11.
We CALPEDA S.p.A. declare that our frequency converter, with pump type and serial number as shown on the name plate, are constructed in accordance with Directives 2004/108/EC, 2006/95/EC, and assume full responsability for conformity with the standards CE EN 55014-1, CE EN 55022, CE EN 61000-3-3, CE EN 61000-4-2, CE EN 61000-4-3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11.
DECLARATION OF CONFORMITY
I
GB
Montorso Vicentino, 09.2014
DECLARATION DE CONFORMITE
Nous, CALPEDA S.p.A., déclare sous sa seule responsabilité que le convertisseur de fréquence, type et numéro de série indiqués sur la claque, sont conformes aux prescriptions des Directives 2004/108/CE, 2006/95/CE et des normes harmonisées correspondantes CE EN 55014-1, CE EN 55022, CE EN 61000-3-3, CE EN 61000-4-2, CE EN 61000-4­3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11.
En CALPEDA S.p.A. declaramos bajo nuestra exclusiva responsabilidad que el convertidor de frecuencia, tipo y número de serie de la placa de nombre, son conformes a las disposiciones de las Directivas 2004/108/CE, 2006/95/CE y de la normas CE EN 55014-1, CE EN 55022, CE EN 61000-3-3, CE EN 61000-4-2, CE EN 61000-4-3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11.
DECLARACION DE CONFORMIDAD
F
E
Компания "Calpeda S.p.A." заявляет под свою исключительную ответственность, что регулятор частоты, тип и паспортный номер которого указаны на заводской табличке, отвечает требованиям Директив 2004/108/СЕ, 2006/95/СЕ и соответствующих унифицированных стандартов CE EN 55014-1, CE EN 55022, CE EN 61000-3-3,
CE EN 61000-4-2, CE EN 61000-4-3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11.
ÑÂÍ·‡ˆËfl ÒÓÓÚ‚ÂÚÒÚ‚Ëfl
RU
KONFORMITÄTSERKLÄRUNG
Wir, das Unternehmen CALPEDA S.p.A., erklärt unter eigener Verantwortung, dass der Frequenzumwandler, Typ und Seriennummer auf dem Typenschild angegeben, mit den Vorschriften 2004/108/CE und 2006/95/CE sowie mit den harmonisierten Vorschriften CE EN 55014-1, CE EN 55022, CE EN 61000-3-3, CE EN 61000-4-2, CE EN 61000-4-3, CE EN 61000-4-4, CE EN 61000-4-5, CE EN 61000-4-6, CE EN 61000-4-11 übereinstimmen.
D
Il Presidente
Marco Mettifogo
95
Calpeda s.p.a. - Via Roggia di Mezzo, 39 - 36050 Montorso Vicentino - Vicenza / Italia
Tel. +39 0444 476476 - Fax +39 0444 476477 - E.mail: info@calpeda.it www.calpeda.it