Calorique EMBEDDED MELTING SYSTEM User Manual

Embedded Snow & Ice
Melting System
Installation Manual
CM1010 - 04-08-13
Before Installing
• Installation of this system must be made in accordance with National Electrical Code Article 426 - Fixed Outdoor Electric Deicing and Snow-Melting Equipment.
• For installation under concrete only.
• Do not install this system under tarmac or other hot-pour sur­facing materials.
• Do not incorporate any other outdoor electrical equipment in any branch circuit which feeds this heating system.
• This system must be connected to an electrical branch circuit incorporating a ground fault circuit interruper (GFCI) rated for equipment protection.
• Heating mats must never be run through or accross expansion joints.
• Do not run power leads, other electrical wiring or any other material between the heating mats and the surfacing material.
• Special care must be taken to ensure that expansion joints do not extend into the heating elements. Elements which are damaged are shock and fire hazards. If possible, order ele­ments sized so that the expansion joints can be cut between the elements and leave one inch (2.5 cm) between the ele­ments.
WARNING: Ensure that adequate drainage is provided for water runoff.
Components
• Calorique heating mats. Supplied by Calorique or authorized
distributor. See the following section for specifications of heat­ing mats.
• Electrical control device. Supplied by Calorique, automati­cally turns the system on and off based on the temperature, humidity, and presence of precipitation. This unit is a double­pole line voltage unit that meets National Electrical code requirements.
• Overcurrent Protection. User / installer supplied. The circuit breaker used with this sistem must have an overcurrent rating of 30 amps and an integral GFCI rated for 30mA equipment protection.
• Wiring and conduit. User / installer supplied. As required by national and local code for outdoor installation.
Junction boxes certified for use in outdoor, buried applica­tions.
Insulation (rigid foam or radiant barrier) User / installer supplied. When using rigid foam, the insulation must have the following properties:
• Walkways: one inch (2.5 cm) or thicker with a minimum
strength of 25 psi.
• Driveways and other vehicular traffic areas: two inches (5.0
cm) or thicker with a minimum strength of 60 psi.s
• Warning labels. Supplied by Calorique or authorized distribu­tor.
• Element Labels. Mounted on the non-heating leads. Both
labels must remain in place as they supply necessary infor­mation about the elements. If the leads are cut to length, the trimmed-off label must be reattached within two inches (5.0 cm) of the end of the cable.
• Junction Box Label. Must be attached to the junction box.
• Stakes. Supplied by Calorique or authorized distributor.
• Warrantee Card. This card must be filled out and returned to
Calorique to ensure proper registration of the warrantee.
• Specification Sheet. Provides specifications for all heating elements included with the system.