Components
• Calorique heating mats. Supplied by Calorique or authorized
distributor. See the following section for specifications of heating mats.
• Electrical control device. Supplied by Calorique, automatically turns the system on and off based on the temperature,
humidity, and presence of precipitation. This unit is a doublepole line voltage unit that meets National Electrical code
requirements.
• Overcurrent Protection. User / installer supplied. The circuit
breaker used with this sistem must have an overcurrent rating
of 30 amps and an integral GFCI rated for 30mA equipment
protection.
• Wiring and conduit. User / installer supplied. As required by
national and local code for outdoor installation.
• Junction boxes certified for use in outdoor, buried applications.
• Insulation (rigid foam or radiant barrier) User / installer supplied.
When using rigid foam, the insulation must have the following
properties:
• Walkways: one inch (2.5 cm) or thicker with a minimum
strength of 25 psi.
• Driveways and other vehicular traffic areas: two inches (5.0
cm) or thicker with a minimum strength of 60 psi.s
• Warning labels. Supplied by Calorique or authorized distributor.
• Element Labels. Mounted on the non-heating leads. Both
labels must remain in place as they supply necessary information about the elements. If the leads are cut to length,
the trimmed-off label must be reattached within two inches
(5.0 cm) of the end of the cable.
• Junction Box Label. Must be attached to the junction box.
• Stakes. Supplied by Calorique or authorized distributor.
• Warrantee Card. This card must be filled out and returned to
Calorique to ensure proper registration of the warrantee.
• Specification Sheet. Provides specifications for all heating
elements included with the system.