Figure 1-1 MODEL 4500L / 2750L / 6000L-P OUTPUT DRAWINGS--------------------------------------------------------2
Figure 2-1 6000L / 2750L and 4500L-3P REAR PANEL CONNECTIONS----------------------------------------------- 14
Figure 2-2 SYSTEM INTERCONNECT ------------------------------------------------------------------------------------------- 15
Figure 2-2 SYSTEM INTERCONNECT FOR MODE OPTION-------------------------------------------------------------- 16
Figure 2-2 SYSTEM INTERCONNECT ------------------------------------------------------------------------------------------- 17
Figure 2-2 SYSTEM INTERCONNECT ------------------------------------------------------------------------------------------- 18
Figure 2-3 FUNCTION TEST SETUP---------------------------------------------------------------------------------------------- 23
Figure 3-1 FRONT PANEL CONTROLS AND INDICATORS---------------------------------------------------------------- 25
Figure 3-2 REAR PANEL CONNECTIONS - 6000L/2750L/4500L --------------------------------------------------------- 27
Figure 3-3 FUNCTION STROBE CONNECTIONS----------------------------------------------------------------------------- 31
Figure 3-4 KEYPAD-------------------------------------------------------------------------------------------------------------------- 31
Figure 3-5 REMOTE COMMEND SEQUENCES ------------------------------------------------------------------------------- 52
Figure 3-6 CIIL PROGRAM SYNTAX---------------------------------------------------------------------------------------------- 69
Figure 3-7 CONFIDENCE TEST FLOW DIAGRAM---------------------------------------------------------------------------- 74
Figure 4-1 INTERNAL ADJUSTMENTS AND JUMPER LOCATIONS ---------------------------------------------------- 84
Figure 4-2 EQUIPMENT HOOKUP FOR PERIODIC CALIBRATION------------------------------------------------------ 90
Figure 4-3 FLOW DIAGRAM A REMOTE CALIBRATION-------------------------------------------------------------------- 94
Figure 4-3 FLOW CHART (continued)--------------------------------------------------------------------------------------------- 95
Figure 5-1 AC POWER SYSTEM BLOCK DIAGRAM------------------------------------------------------------------------106
Figure 5-2 OSCILLATOR MODULE BLOCK DIAGRAM---------------------------------------------------------------------108
Figure 6-1 MODULE LOCATION --------------------------------------------------------------------------------------------------115
-iv-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
SECTION 1 INTRODUCTION AND SPECIFICATIONS
1.1 INTRODUCTION
This instruction manual contains information on the installation, operation, calibration, and maintenance of all power
systems that use the 2750L-P,4500L-P and 6000L-P.
1.2 GENERAL DESCRIPTION
This power system is a high efficiency power source that provides a low distortion output. The output can be configured
in either a single or three-phase configuration.
A number of Power Sources can be configured to supply full output power up to 27000VA. Table 1-1 shows the output
VA per phase for each of the available power system models. The table also shows that increased power is available
at a reduced operating temperature of 35?C.
Figure 1-1 MODEL 4500L / 2750L / 6000L-P OUTPUT DRAWINGS
-2-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Full power is available at the maximum output voltage on either of two voltage ranges. The standard voltage
ranges are 135 and 270. Three optional voltage range pairs are available: 67.5/135, 156/312 and 200/400.
All "P" Power systems except for the 6000L will deliver full power from 45 to 2000 Hz. All 6000L-P power systems will
deliver full power from 45 to 440 Hz.
The 2750L-3P, 4500L-3P and 6000L-3P will deliver full power from 45 to 5000 Hz. The power sources are illustrated in
Figure 1-1. The 200/400 volt range (EHV Option) is specified for full power from 45 to 1000 Hz.
The output frequency of all "P" power systems can be programmed down to 17 Hz at a reduced output voltage.
1.3 ACCESSORY EQUIPMENT/RACK SLIDES
General Devices Model CTS-1-20-B307-2 rack slides may be attached to the sides of the power source using 10-32 X
1/2 flat head screws.
1.4 SPECIFICATIONS
Table 1-1 contains the operation specifications of the AC Power System. All specifications are tested in accordance
with standard California Instruments test procedures. The following specifications apply for operation at 100% of full
scale voltage, constant line voltages and under no-load and with External Sense Lines connected unless specified
otherwise.
NOTE: Increased current at 35?C is available up to 2000 Hz or 440Hz for 6000L.
(1) For UP option output VA and Current is limited to 50°C values.
For other Voltage Ranges: Current per phase = VA (per phase)/Voltage Range
Power factor: 0 to unity at full rated output VA
Peak Repetitive Current: 2.5 times the maximum TRMS current at 50?C
2750L & 6000L:4 times TRMS current at 50?C
Peak Non-repetitive Current: (10ms, 20ms for 6000L) 2.7 times the maximum TRMS current at 50?C
2750L & 6000L: 4 times TRMS current at 50?C
(1)
(1)
(1)
(1)
-4-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Voltage range: 135 and 270 (Standard)
67.5 and 135 (LV Option)
156 and 312 (HV Option)
200 and 400 (EHV Option)
Total Distortion: (Maximum for all harmonics and noise to 300 KHz at full power with linear load)
45 Hz to 2 KHz: 1% THD
to 5 KHz: 2% THD
Line regulation: ±0.02% of full scale for ±10% line change
Load regulation: ±0.05% of full scale from no load to full load
Voltage accuracy (no-load, 23?C, based on TRMS measurement, 45 to 5000 Hz values specified otherwise): ±0.135 volts from 5 to 135 volts
±0.54 volts from 135 to 312 volts
±1.5 volts from 5 to 200 volts (EHV Option), 45 to 1 KHz
±3.0 volts from 200 to 400 volts (EHV Option), 45 to 1 KHz
Add 2% of programmed value below 45 Hz.
Frequency Range: At Full Scale Voltage
2750L-3,4500L-3,
6000L-3 45 Hz to 5000 Hz at 50?C maximum currents All other models 45 Hz to 2000 Hz at 35?C maximum currents
All 6000L systems 45 Hz to 440Hz and 6000L-1P
At less than Full Scale Voltage: (Refer to graph below)
Frequency accuracy: ±0.001% of programmed value
Frequency resolution: 0.01 Hz to 99.99
0.1 Hz to 999.9
1 Hz to 5000 Hz
Phase angle accuracy (With the same load on each phase):
Phase B and C relative to phase A: ±2 degrees to 2 KHz
±3 degrees to 5 KHz
PROTECTION
-5-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Output overload: Automatic default with output relays open when programming from 5.0 volts.
Output short circuit: Immediate default with no automatic recovery.
Input Overvoltage: Overvoltage causes the circuit breaker to trip.
Loss of Input phase: No output for loss of Phase B or C.
Normal operation at reduced power with loss of Phase A.
Sense line fault: Immediate default of programmed output with relays open.
Temperature: Default of programmed output with relays open.
MEASUREMENTS (at 23?C)
Voltage accuracy: ±10 Digits of resolution
±2.0 volts from 0 to 200 volts (EHV option)
±3.5 volts from 200 to 400 volts (EHV option)
Voltage resolution: 0.1 volt for 1 digit
MODEL
2750L-3P, 6000L-3P
2750L-1P-EHV, 4500L-3P All Other Models
Current accuracy: ±10 Digits of resolution
Current resolution: 0.01 Amp 0.1 Amp For 1 digit
True power accuracy: ±10 Digits of resolution
True power resolution: 1 Watt 0.01 Kw For 1 digit
Apparent power resolution: 1 VA 0.01 KVA For 1 digit
Power factor resolution: .001 For 1 digit
Frequency ACCURACY (Hz) RESOLUTION (Hz)
45 to 99.99 Hz ±0.02 0.01
100 to 499.9 Hz ±0.2 0.1
500 to 999.9 Hz ±0.5 0.1
1000 to 5000 Hz ±10 1
NOTE: For frequencies below 45 Hz, add 2% of measured value to measurement accuracy specification.
Phase angle accuracy: ±2.0 degrees to 2 KHz, ±3 degrees to 5 KHz
Phase angle resolution: 0.1 degree
-6-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
SUPPLEMENTAL SPECIFICATIONS
LINE INPUT
Voltage: 187 to 252V
three-phase
L-L
2750L: Same as above except can also operate with 1-phase input with 187 to 252 volts.
6000L: 208 to 252V
UP Option: 342 to 456V
L-L
three-phase
L-L
Current (PF=.6, EFF=75%, V line=minimum, 3P, full load): 31 Amps
2750L-3P: 19 Amps
2750L-1P(input): 29 Amps
6000L-3P(output): 35 Amps
6000L-1P(output): 40 Amps
Frequency: 47 to 440 Hz
Efficiency: 75% (typical)
Surge Current:
(turn-on, V
= 252): 178 Amps
L-L
100 Amps for 6000L
SUPPLEMENTAL OUTPUT SPECIFICATIONS
Full current range:
Output noise voltage (20 KHz to 1 MHz at full-load):
200 millivolts (typical)
80 millivolts (typical for 6000L)
Voltage temperature coefficient: ±0.02 volts per ?C
Voltage stability (24 hours, at constant line, load and temp.):
±0.015% of full scale
Voltage Settling Time: (from start of voltage change from 5.0 VRMS or higher voltage to a higher voltage to within
2% of final value.)
No-load: 16 milliseconds
Full-load: 0.3 seconds (16 milliseconds to within 15% of final value)
Steady-State Output Impedance (ohms) = (voltage range) x (0.0005)/Full-load current
-7-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Frequency Temperature Coefficient: ±5 ppm of value per ?C
Frequency Stability: ±15 ppm of value per year
Isolation: Line input to output: >500 VRMS
Front panel controls:
Power On/Off circuit breaker
Keypad: 20-key keyboard
Analog Meter Phase Selection Switch
Bus: IEEE-488 (GPIB)
Subsets; SH1, AH1, T6, L3, SR1, RL2, DC1, DT1
Codes and Formats:
Numeric Representation: NR1, NR2 or NR3
Header: HR1 or HR2 (upper or lower case)
Message Separators: SR1
Data transfer rate: 200K bytes per second
Language: A California Instruments language which is upward compatible from other C.I. products
Functions Range Resolution Initialization
Voltage range 135/270 0.1 135
1
Voltage 0 to range 0.1 5.0
1
Phase angle 0 to 999.9 0.1 B = 240
C = 120
Output relay (GPIB only) Open or Close Open
External Sync Internal or External Internal
Storage Registers Registers 0 through 16
Frequency
Range: 45 to 5000 Hz for 4500L-3P & 2750L-3P
2000 Hz for all others. 440 Hz for 6000L.
Resolution: 0.01 Hz from 45.00 to 99.99 Hz
0.1 Hz from 100.0 to 999.9 Hz
1 Hz from 1000 to 5000 Hz
Default: 60 Hz (any other available)
1
Current Limit
-8-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
CURRENT LIMIT RANGE VOLTAGE RANGE(1) RESOLUTION DEFAULT
MODEL 135 270 (on 135 Range)
2750L-3P 0 to 7.40, 3.70 0.01 7.40
2750L-1P 0 to 22.22, 11.11 0.01 22.22
4500L-3P 0 to 12.34, 6.17 0.01 12.34
4500L-1P 0 to 37.04, 18.52 0.01 37.04
6000L-3P 0 to 14.82, 7.41 0.01 14.82
6000L-1P 0 to 44.44, 22.22 0.01 44.44
9000L/2-3P 0 to 24.68, 12.34 0.01 24.68
9000L/2-1P 0 to 74.08, 37.04 0.01 74.08
12000L/2-3P 0 to 24.68, 12.34 0.01 24.68
12000L/2-1P 0 to 74.08, 37.04 0.01 74.08
13500L/3-3P 0 to 37.04, 18.52 0.01 37.04
13500L/3-1P 0 to 111.2, 55.6 0.1 111.2
18000L/3-3P 0 to 44.44, 22.22 0.01 44.44
18000L/3-1P 0 to 133.4, 66.7 0.1 133.4
27000L/6-3P 0 to 74.08, 37.04 0.01 74.08
27000L/6-1P 0 to 222.2, 111.1 0.1 222.2
For other Voltage Ranges: Current Limit Range = (VA per phase)/Voltage Range
NOTE (1): For UP option refer to 50°C current values. Accuracy: -0 to +15% of programmed value
NOTE:
1
Independent control for each output phase
NOTE (*) Customer access to Initial/Default values for:
Frequency, Voltage, Voltage Range and Current Limit
OTHER PROGRAMMABLE FUNCTIONS
Register linking
Calibration of Phase, Output Voltage and measurement functions.
Ramp/Sweeps of Voltage, Frequency, Phase and Current Limit up to 2 functions simultaneously.
Service request (GPIB): Service Request for output faults, syntax errors and end of measurement.
Group execute trigger (GPIB): Trigger setups and terminate programs.
Status reporting: Serial Poll Status Byte and error messages.
Remote Shutdown A logic low input will program the voltage to 0 and open the Output Relays.
Output Relay: Controlled by GPIB. Normally open at power-up. Closed when the first function is
programmed from the front panel keypad.
External sense: Compensates for up to a 10% drop in the load lines.
Function Strobe Output: A 400 uS logic low output when any output is programmed.
External Sync: A 5 volt, 45 to 5 KHz, 5 milliamp TTL input. The output will track the frequency and
-9-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
phase of this input. Loss of this input will cause the output to default.
Indicators: 32 character LCD display, Output Overload, Over temperature Power On, High
Voltage Range.
Dimensions: 10.5 inches (26.7 cm) high, 23 inches (58.4 cm) deep and 19 inches (48.3 cm) wide.
Weight lbs (Kg): 175 (79.2)
Material: Aluminum for Front panel, rear panel and top cover.
Steel for chassis.
Finish: Front panel - painted gray 26440 per Federal Standard 595
Chassis - zinc plate type 2 class 2.
Rear panel and top cover - iridite.
Air intake/exhaust: Intake from both sides of chassis.
Exhaust to the rear.
Modularity: Oscillator, All amplifiers, DC power supplies, Current
Limit Board Assembly, Range-Relay Board, All displays
(mating connector): 3M Connector 3366-1001 plug
System Interface: 3M connector, 3367-1000 (J7)
IEEE-488 connector: J5
Chassis slides: Zero Manufacturing Company Model CTN-1-20-E94
Operating temperature: 0?C to 50?C
Storage temperature: -40?C to +85?C
Operating altitude: 0 to 6000 Ft.
-10-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
OPTIONS SPECIFICATIONS
Universal Input Power (UP option): 342 to 456 V
three phase
L-L
Output Voltage Ranges: 156/312 (HV option)
67.5/135 (LV option)
200.0/400.0 (EHV option)
Master: Must be used with LK option
Slave: Must be used with LK option
Square Wave (4500L-3P and 2750L-3P only) Performance from 50 Hz to 5 KHz:
Rise and Fall Time (10% to 90%): Less than 40 microseconds
Droop: Less than 10%
Overshoot (resistive load): Less than 20%
Mode: Allows power system to be programmed to a 1 or 3 phase output.
Auxiliary outputs (Option AX): Master and Slave options not available with this option
(All specifications at 23?C and verified with TRMS voltmeter. The Phase D sense lines must be connected to
the Phase D output.)
Phase D:
Voltage: 26.0 Vrms fixed
Accuracy: ±2%
Current: 3.0 Amps (Max)
Frequency: 360 to 440 (Tracks the main outputs)
Phase: Tracks the Phase A output
Accuracy: ±1 degree. (All outputs at half load, 400 Hz)
Distortion: 1% THD maximum with linear load
Line Regulation: ±0.05% using external sense
Load Regulation: ±0.05% using external sense
Phase E
Voltage: 5.0 Vrms fixed
Accuracy: ±5%
Current: 5.0 Amps (Max)
-11-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Frequency: 360 to 440 Hz (Tracks the main outputs)
Phase: Tracks the phase A output with Phase D
Distortion: 1% THD maximum with linear load
Line Regulation: ±0.1% for 10% line change
Load Regulation: ±10% from no-load to full-load
MATE (MT option)
CIIL language
DFI connector
Confidence Test (Tests 3 phases for output, oscillator drive, phase relationship, frequency and current
limit.)
MIL-704D (704D option)
Performs all sections of MIL-STD -704D
2-PHASE (2P): 2-phase operation
RTCA/DO-160C (DO160C option)
Performs all sections of RTCA/DO-160C
SYSTEMS
MODEL POWER PER PHASE MAX CURRENT PER PHASE (135V RANGE)
Inspect the unit for any possible shipping damage immediately upon receipt. If damage is evident, notify the carrier.
DO NOT return an instrument to the factory without prior approval. Do not destroy the packing container until the unit
has been inspected for damage in shipment.
2.2 POWER REQUIREMENTS
The AC Power System has been designed to operate from a three-phase AC line voltage. The input line voltage may
be between 187 volts and 252 volts line-to-line for the standard product or 342 to 456 volts line-to-line for the UP option.
The frequency may be between 47 Hz and 440 Hz. Select an AC input line and hookup wire to the AC Power System
that will deliver 40 amps per phase and still supply a minimum of 187 volts line-to-line. Refer to Figure 2-2 for circuit
breaker requirements of all multichassis power system. The 6000L power system must have a minimum of 208V
a full rated load on the output.
2.3 MECHANICAL INSTALLATION
The power system has been designed for rack mounting in a standard 19 inch rack. The unit should be supported from
the sides with optional rack slides. See Accessory Equipment/Rack Slides in paragraph 1.3. The cooling fan at the
rear of the unit must be free of any obstructions which would interfere with the flow of air. A 2.5 inch clearance should
be maintained between the rear of the unit and the rear panel of the mounting cabinet. Also, the air intake holes on the
sides of the power source must not be obstructed. See Figure 1-1.
2.4 INPUT WIRING
The AC Power System must be operated from a three-wire three-phase service with a fourth wire for common. The
common wire is connected to the chassis of the AC Power System. The mains source must have a current rating
greater than or equal to the AC Power System circuit breaker, 40 amps. Refer to Figure 2-1 for the input power
connections. Refer to Figure 2-2 for all multichassis power systems.
The 2750L may also be operated from a 1-phase input. The 1-phase line input must be connected between the øB and
øC terminals of TB3 on the rear panel. These terminals are identified as terminals 2 and 3 of TB3 in Figure 2-1.
L-L
for
-13-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Figure 2-1 6000L / 2750L and 4500L-3P REAR PANEL CONNECTIONS
Voltages up to 480 VAC are available in certain sections
of this power source. This equipment generates
potentially lethal voltages.
DEATH
on contact may result if personnel fail to observe safety
precautions. DO NOT touch electronic circuits when
power is applied.
-19-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
2.5 OUTPUT CONNECTIONS
The output terminal block, TB1, is located at the rear of the power system. For a single power source power system, all
load connections must be made at TB1. The external sense inputs allow the power system output voltages to be
monitored directly at the load and must be connected. The external sense wires are connected at J6 on the rear panel.
Refer to Figure 2-2 for all connections .
The output power cables must be large enough to prevent a voltage difference greater than 2 VRMS between the
voltage at TB1 and the voltage between External Sense HI and LO input. Table 2-1 shows the maximum length of the
output wires. The table assumes the External Sense input is connected at the load.
Table 2-1 MAXIMUM LENGTH OF OUTPUT WIRES
WIRE
GAGE (AWG)
14
12
10
8
For a single power source, 1-phase power system the output power is available on TB1, pins 3 and 4.
The External Sense inputs must be connected or an AMP FAULT error message will be shown on the display and
reported through the external interface.
Refer to Figure 2-2 for all multiple power source power system hook-ups.
NOTE: A special hook-up is required for all multiple power source power systems with the MODE Option.
MAXIMUM LENGTH (ft) OF WIRE BETWEEN OUTPUT (HI) AND LOAD
MAX LENGTH (ft) = 2/(MAX CURRENT PER PHASE X 0.0027)
MAX LENGTH (ft) = 2/(MAX CURRENT PER PHASE X 0.0017)
MAX LENGTH (ft) = 2/(MAX CURRENT PER PHASE X 0.00111)
MAX LENGTH (ft) = 2/(MAX CURRENT PER PHASE X 0.00061)
Refer to Figure 2-2 for the connections. The 1-phase output for a single power source with the MODE
Option is available from TB1, pins 3 and 4.
2.6 OUTPUT VOLTAGE RANGES
The standard voltage ranges for this AC power system are 135 and 270. Selection of the 270 volt range causes the
front panel "HIGH RANGE" lamp to illuminate. The range may be changed from either the front panel keypad or
through the GPIB input. All voltages are programmed line-to -neutral for 3-phase operation.
2.7 FUNCTION TEST
Refer to Figure 2-3 for the test setup.
Perform the following test sequence.
1) Apply the AC line power and turn on the front panel circuit breaker. No loads should be connected to
the output terminal block.
2) Verify that the POWER ON lamp is lit.
-20-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
3) With the front panel keypad program the HI output voltage range with the following key sequences:
4 ENT To select the Range screen (RNG)
To program the HI range (ex., 270 volt range):
270 PRG ENT
4) Verify the HIGH RANGE lamp is lit.
5) Program the output to maximum voltage with the following key sequences:
Depress the MON key 1 time to select the Amplitude screen (AMP).
To program the voltage to maximum.
(Maximum Range value) PRG ENT
6) Verify that the front panel voltmeter indicates approx imately the programmed value for all three phases
or for phase A for a 1-phase system.
7) Program the AC Power System to the low range with the following keystrokes:
4 ENT (low voltage range value) PRG ENT
8) Program the output to the maximum low voltage range voltage:
5 ENT (maximum low voltage range value) PRG ENT
9) Observe each of the outputs with the oscilloscope or distortion analyzer. The outputs should be clean
sine waves having less than 1.0% distortion.
10) Apply full loads to each phase (Refer to Table 4-1). Verify that the voltage of each phase remains
within (0.0005 x voltage range) volts of the no-load voltage. The waveforms shall still appear clean on
the oscilloscope and have less than 1% distortion.
11) Program the Current Limit to 5.0 amps:
8 ENT
5 PRG ENT
12) The display should show the error message 'AMP ABC FAULT' for a 3-phase system. The error
message may not, however, include all of the phases. The output will default to a programmed value
of 5.0 volts with the output relays open.
2.8 REAR PANEL DIP SWITCH (SW1)
The rear panel Dip Switch is used only for the output phase configuration in high power multi-chassis systems.
The following product/system configurations must have the DIP switches set to the logic "1", or OFF position.
a.) All single chassis systems
b.) All chassis with the Oscillator/Controller installed.
c.) All chassis in systems with the MODE option installed.
-21-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
d.) All chassis in systems with Single Phase output.
e.) Both chassis in a 9000L/2-3 or 12000L/2-3 system.
For multiple-chassis power systems, with a multi-phase output (9000L/2-2, 13500L/3-3, 27000L/6-3, and 40500L/9-3)
the DIP switches should be set to the following positions:
DIP SWITCH
D C B A
PHASE A MASTER AND SLAVE 1 1 1 1
PHASE B 1 1 1 0
PHASE C 1 1 0 1
-22-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Figure 2-3 FUNCTION TEST SETUP
-23-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
SECTION 3 OPERATION
3.1 GENERAL
The AC Power System may be programmed from the front panel or through the IEEE-488 external interface. The rear
panel of the AC Power System holds the power input and output terminals external sense connector, system interface
connector, IEEE-488 interface connector and the chassis ground stud.
3.2 FRONT PANEL CONTROLS
All front panel controls are shown in Figure 3-1. A voltmeter selector switch is located at the right side of the front panel
voltmeter. The three position switch changes the signal applied to the voltmeter from the three output phases.
A three-pole circuit breaker is on the left side of the front panel. The circuit breaker is used to switch power to the unit.
When the circuit breaker is switched ON, the amber indicator lamp above the circuit breaker illuminates.
The front panel has a subpanel with a keypad, remote lamp, LCD display and a viewing angle adjustment. The 20-key
keypad allows the power source to be manually programmed at the front panel. The knob labeled VIEW ANGLE may
be turned to adjust the contrast of the front panel display. The remote lamp illuminates when the AC Power System
has been addressed through the IEEE-488 interface (GPIB).
3.3 FRONT PANEL INDICATORS
A lamp is located just above the input circuit breaker. It illuminates when power is applied and the circuit breaker is on.
An analog voltmeter, that indicates from 0 to 300 volts, shows the actual voltage of the phase A, B and C outputs. The
phase is determined by a three position toggle switch at the right side of the meter.
An OVERTEMP lamp illuminates when the temperature of the power amplifier heatsinks has surpassed a maximum set
level. When the fault is detected, the outputs are disabled and must be reprogrammed after the overtemperature
condition has been eliminated.
An OVERLOAD lamp illuminates when the output current exceeds the programmed current limit value. The outputs will
default to 0.0 volts and the output relays will open shortly after the condition occurs.
-24-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
Figure 3-1 FRONT PANEL CONTROLS AND INDICATORS
-25-
INSTRUCTIONAL MANUAL 2750L-P/4500L-P/6000L-P
August, 2001 Rev. K
A HIGH RANGE lamp illuminates when the AC Power System is programmed to the high voltage range.
An LCD digital display shows the numeric value of all programmed output parameters. It also shows all error
messages and measured values.
A REMOTE lamp illuminates when the AC Power System has been addressed from the IEEE-488 interface.
3.4 REAR PANEL CONNECTIONS
(Refer to Figure 3-2 for all rear panel connections.)
3.4.1 POWER INPUT
TB3 is the terminal block for the 3-phase input voltage. Terminals 1, 2 and 3 connect to each leg of the 3-phase input.
Terminal 5 is the chassis connection which should be connected to the input mains ground.
3.4.2 POWER OUTPUT
TB1 is the power output terminal block. Refer to Table 3-1 for identification of the TB1 terminals. Terminal 3 and 4 are
used for a 1-phase system. Refer to Figure 2 -2 for the output of all multiple power source power systems.
1 Phase C Output HI
2 Phase B Output HI
3 Phase A Output HI
4 Output Neutral
Table 3-1 POWER OUTPUT TERMINAL BLOCK (TB1)
3.4.3 EXTERNAL SENSE
J6 is the external sense input connector. The external sense input of the master 4500L must be connected to the
respective AC Power System output. If the inputs are not connected, an AMP FAULT error message will be generated.
Table 3-2 identifies the pins of connector J6.
1 Phase A Sense HI Phase A Output HI
2 Phase B Sense HI Phase B Output HI
3 Phase C Sense HI Phase C Output HI
4 Neutral Sense Neutral Output
5 Phase D sense HI Phase D Output HI
6 Phase D sense LO Phase D Output LO
Table 3-2 EXTERNAL SENSE CONNECTOR (J6)
-26-
Loading...
+ 121 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.