½” Pressure Balance Valve Trim
Installation Instructions
TO-PBL-XX
PB-R
(ROUGH)
TO-PBL-XX_ii_110112.doc Pg 1
CALIFORNIA FAUCETS RECOMMENDS THAT ALL PLUMBING PRODUCTS BE INSTALLED BY
A LICENSED PROFESSIONAL
TEMPERATURE SETTING
• Remove MUDGUARD (1), SETSCREW (2), and
STEM-GUARD (3) from CARTRIDGE-STEM (4)
• Place STEM (5) onto CARTRIDGE-STEM (4) and
secure in place with SCREW (6) as shown
WARNING: This valve is factory set to deliver water at the highest
temperature possible. It is the installer’s responsibility
set the desired and/or required maximum temperature setting to
prevent risk on scalding or other severe injury prior to consumer use.
The valve MUST
installation. The installer is responsible to set this high temperature
limit based on user preferences and all local plumbing code
requirements. This valve does NOT monitor temperature. The valve
will avoid anti-scald situations, due to pressure and flow fluctuations in
supply lines, by regulating pressure during operation.
have the high temperature limit stop set during
• Remove temperature limit STOP (8) from
CARTRIDGE (7)
• Rotate STEM (5) counter-clockwise (CCW) to
start water flow. Temperature will become hotter
as stem is rotated. Use temperature measuring
device at outlet flow to determine maximum
temperature
IMPORTANT: To prevent severe injury, maximum temperature
setting should be no greater than 115ºF. The high temperature MUST
meet all local plumbing code requirements.
to properly
• Place temperature limit STOP (8) back onto
CARTRIDGE (7)
• Lower temperature is achieved by rotating the
temperature limit STOP (8) clockwise (CW). This
limits the rotation of the cartridge stem which in
turn limits maximum temperature
Lowest Setting
Possible
CC
Reduced Setting
“Warm”
Reduced Setting
“Very Warm”
Factory Setting
“Hot”
110-115°F
TO-PBL-XX_ii_110112.doc Pg 2