Caleffi ZVR104 Install Instructions

Page 1
NA10333
www.caleffi.com
Z-one™ Relay Multi-Zone Valve Control
© Copyright 2014 Caleffi
• Compatible with low voltage 2, 3, or 4 wire thermostats
• R, W, C and TT Comm dual labeling at thermostat terminals
• Z-oneLink unlimited zone expansion
• Selectable priority with 1 hour time-out feature
• System pump status selectable during priority
• Circulator will start only after the zone valve end switch is closed
• Dry contacts for DHW (ZR/ZC), capable of switching line voltage
• Large terminal connections
• High Capacity 40 VA Transformer standard for 3 and 4 zone models-expandable to 80 VA, and 80 VA for the 6 zone model
• Automatic resettable fuse
• Controls system pump, secondary pump, and priority pump
• Front LED Lights
• 100% Factory tested with 3 year warranty
• ETL Approved
Product Range
Code ZVR103 Z-one™ Relay switching relays...............................................................three zone
Code ZVR104 Z-one™ Relay switching relays.................................................................four zone
Code ZVR106 Z-one™ Relay switching relays...................................................................six zone
Technical specifications
ZVR10X series
Function
The ZVR series is a multi-zone zone valve and boiler operating control for multiple zone hydronic heating or cooling systems. The ZVR series interfaces with low voltage thermostats, or any other low voltage controllers having a switching action. The ZVR series controls up to 3, 4, 5 or 6 zones, depending on model selected. In addition, a system circulator pump and secondary pump is turned on whenever any zone calls for heat. LED indicators provide functional status and easy system troubleshooting. The ZVR series is a perfect match with Caleffi’s Z-one™ motorized zone valves.
Materials
Housing plastic: ABS Front display lights: LCD Electrical Knockouts: (12) 1/2" size
Performance
Power supply: 120 VAC, 50/60 Hz Transformer voltage: 24 VAC
Maximum transformer load: 40 VA (ZVR103/4), 80 VA (ZVR106)
Electrical switch rating: 20A Max Combined
Electrical switch rating, ZR/ZC, DHW, XX: 120 VAC, 2A each Electrical switch rating pumps: 120 VAC, 5A each
Resettable Fuse: automatic Maximum temperature: 110°F (43°C) Maximum humidity: 90% non-condensing
Approvals: Certified to CSA C22-2 No.24
Conforms to UL Standard 873
Page 2
Dimensions
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZVR106
Six zone switching - Input: 120VAC 50/60Hz 20A MAX
Conforms to UL 873
4009064
CAUTION:
RISK OF ELECTRIC SHOCK - DISCONNECT ALL
INPUT POWER PRIOR TO SERVICING
Milwaukee, WI 53208 USA
POWER
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
T-STAT CALL
VALVE OPEN
A
B C
C
Code Zones A B C Wgt. (lbs)
ZVR103 3
ZVR104 4
ZVR106 6
9
9
1/4" 11" 3"
9
1/4" 11" 3"
3.2
3.2
3.2
1/4" 11" 3"
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION!
BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION: All work must be performed by qualified personnel trained in the
proper application, installation, and maintenance of systems in accordance with all applicable codes and ordinances.
CAUTION: Electrical shock hazard. Disconnect power before installation to prevent electrical shock or equipment damage. Make sure all connections are in accordance with the electrical wiring diagram and in accordance with national and local electrical codes.
WARNING: Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment. Avoid locations where excessive moisture, corrosive fumes, vibration, or explosive vapors are present.
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
Page 3
Installation
Inspection
Inspect packages for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products.
• Use only copper conductor supply wire suitable for at least 105° C
• All circuits must have a common disconnect and be connected to the same pole of the disconnect
Maintenance and Repair
The Caleffi Z-one™ multi-zone valve control comes with a resettable fuse and requires no maintenance. If control fails or is damaged, replace control with functional one.
Mounting
Mount the Caleffi Z-one™ switching relay box to a suitable surface. Slotted holes are provided for mounting purposes. Do not mount to a surface that exceeds 115°F (45°C). The unit must be only located in dry interior locations. It is not suitable for installation in hazardous locations and should not be placed close to any electromagnetic fields.
Cover removal
Hold either the left or the right end of the box up and at an angle. Use body for stabilizing relay box.
Roll cover off base.
Insert screwdriver and push tab inward, cover should release from base.
Page 4
Transformer
Installation
Mount box on stable surface using level.
Slide bottom end of transformer into bottom latch.
Feed wiring through hole near the top of the transformer and insert transformer plug into the socket.
Remove transformer(s) from packaging.
Snap top of transformer into latch arms.
Repeat process for 2nd transformer if six valve relay box.
Page 5
T-STAT 4
C
OM
T-STAT 5
C
R
W
T T COM
T-STAT 6
R
W
T T COM
6 Zone
ZVR106
MASTER SLAVE
C
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
6 Zone
ZVR106
PRIORITY
MASTER SLAVE
T-STAT 2
C
R
W
T T COM
T-STAT 3
C
R
W
T T COM
C
W
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
TSAT1 ZONE1
COMMS
D
P
C
W
6 Zone
ZVR106
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
MASTER SLAVE
C
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
Jumper set up
The jumpers on the ZVR series can be positioned for the following operations. Priority ON / Priority OFF: When priority jumper is ON, upon demand, zone 1 will operate as priority and all other zones are temporarily switched off (with 1 hour time-out). When priority mode is OFF, any zones that were active when zone 1 was switched on will remain on. Status During Priority ON / Status During Priority OFF: When status jumper is ON, the system pump will continue to operate during priority. Master / Slave: allows for unlimited expansion to additional ZVR relays.
Wiring terminals
X X
DHW
ZR/ZC
R
W
T T COM
T-STAT 1
When a zone has a demand from a thermostat (T T or R W) the control will send 24 VAC to the corresponding zone valve. When the zone valve end switch closes, the primary pump will switch on and the (X X) dry contacts will close to signal the boiler of a heating demand. Zone 1 can be used for priority (either a priority pump or valve). When the priority jumper is ON, a demand from T-Stat1 will activate 24VAC to valve 1 and the priority pump will switch on after the end switch closes (requires a jumper in the end switch terminals if a valve is not used). The DHW (ZR/ZC) dry contact will also close. Depending upon "Status During Priority" jumper, the system pump will either be ON or OFF.
R
C
W
T T COM
T-STAT 2
C
PRIORITY
ON OFF
STATUS DURING
PRIORITY
ON OFF
MASTER SLAVE
R
W
T T COM
T-STAT 3
R
C
T T C
W
Large screw terminals connections makes wiring easy with three pump screw terminal connections. Pump terminals connection have 120 VAC outputs for simplified pump connections. Zone valve connections can be 2, 3 or 4 wire.
Z-oneLink unlimited expansion allows adding addition ZVR series relay controls to a Master ZVR. Communication is accomplished by connecting three wires (bell or thermostat wire) to the communication terminals located in the upper right hand corner. The jumper is positioned to Master / Slave position. A demand for heat from any zone will fire the boiler and start the pump.
D
COMMS
P
Page 6
Example Wiring Diagram
Please reference Z-one™ Relay wiring guide for complete listing of wiring diagrams.
ModCon boiler with
Primary/Secondary
mod/con! boiler
PRIORITY!
pump
X X
POWER IN
L
ZV1
SECONDARY!
pump
DHW
ZR/ZC
N
PRIORITY
PUMP
L
N
T T COM
T-STAT 1
SEC PUMP
N
L
CRW
STATUS DURING
PRIORITY
SYSTEM
L
T T COM
T-STAT 2
ON OFF
PUMP
N
CRW
PRIORITY
MOTOR
T T COM
T-STAT 3
ZVR106
6 Zone
ON OFF
ZONE 1
END
SWITCH
CRW
MOTOR
T T COM
T-STAT 4
ZONE 2
SWITCH
ZV4ZV3ZV2 ZV5 ZV6
CRW
CRW
T T COM
T-STAT 5
ZONE 3
END
END
SWITCH
MOTOR
MOTOR
T T COM
T-STAT 6
ZONE 4
END
SWITCH
CRW
MASTER SLAVE
MOTOR
ZONE 5
END
SWITCH
D
COMMS
P
MOTOR
ZONE 6
VENT
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
END
SWITCH
PWR
L
N
PRIORITY!
pump
SECONDARY!
pump
ZV1
ZV4ZV3ZV2 ZV5 ZV6
Page 7
Noncondensing boiler with
outdoor reset and indirect DHW
VENT
low flow resistance boiler
SYSTEM!
pump
ZV1
DHW!
aquastat
ZV2
ZV3
indirect DHW tank
ZV4
ZV5
ZV6
space heating demand
domestic water heating demand
boiler! reset!
controller
L N G
outdoor!
temperature!
sensor
CRW
STATUS DURING
PRIORITY
SYSTEM
PUMP
N
SYSTEM!
pump
T T COM
space heating thermostats
CRW
T T COM
THM 2
THM 3
ZRV106
6 Zone
Z6V
set to ON
PRIORITY
ZONE 1
END
SWITCH
MOTOR
ZV1 ZV2 ZV4 ZV5 ZV6ZV3
CRW
T T COM
MOTOR
ZONE 2
THM 4
SWITCH
D
CRW
SWITCH
P
PWR
COMMS
Master/Slave
THM1 ZONE1
THM2 ZONE2
THM3 ZONE3
THM4 ZONE4
THM5 ZONE5
THM6 ZONE6
ZONE 5
ZONE 6
END
SWITCH
END
SWITCH
MOTOR
END
MOTOR
CRW
CRW
T T COM
T T COM
THM 6
THM 5
ZONE 3
END
ZONE 4
END
SWITCH
MOTOR
MOTOR
DHW!
aquastat
DHW
X X
ZR/ZC
T T COM
THM 1
T T
ZC
ZR
PRIORITY
L
POWER IN
SEC PUMP
PUMP
L
N
N
L
L N G
Page 8
CALEFFI
pump
Modern boiler with Primary/Secondary and
two secondary pumps
SYSTEM!
pump
T T COM
T-STAT 1
SECPUMP
L
"B"!
pump
A10A9A8 A11 A12A7
D
CRW
CRW
PRIORITY
SYSTEM
L
STATUS DURING
ON OFF
PUMP
T T COM
T-STAT 2
N
MOTOR
T T COM
T-STAT 3
PRIORITY
ZONE1
ZVR106
6 Zone
ON OFF
END
SWITCH
CRW
CRW
CRW
T T COM
T T COM
T-STAT 4
T-STAT 5
ZONE2
ZONE3
END
END
SWITCH
SWITCH
MOTOR
MOTOR
MOTOR
CRW
N
T T COM
T-STAT 6
ZONE4
SWITCH
P
PWR
COMMS
TSAT1 ZONE1
MASTER SLAVE
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE5
ZONE6
END
END
END
SWITCH
SWITCH
MOTOR
MOTOR
"A"!
pump
A4A3A2 A5 A6A1
DHW
X X
ZR/ZC
PRIORITY
POWERIN
PUMP
N
L
N
L
T T COM
T-STAT 1
SECPUMP
L
CRW
SYSTEM
PRIORITY
L
T T COM
T-STAT 2
STATUS DURING
ON OFF
PUMP
CRW
CRW
T T COM
T T COM
T T COM
T-STAT 3
T-STAT 4
T-STAT 5
ZVR106
6 Zone
PRIORITY
ON OFF
ZONE1
ZONE2
N
MOTOR
ZONE3
END
END
SWITCH
END
SWITCH
SWITCH
MOTOR
MOTOR
CRW
N
D
CRW
T T COM
T-STAT 6
ZONE4
P
PWR
COMMS
TSAT1 ZONE1
MASTER SLAVE
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE5
ZONE6
END
END
SWITCH
END
SWITCH
SWITCH
MOTOR
MOTOR
CRW
MOTOR
DHW
X X
ZR/ZC
PRIORITY
POWERIN
PUMP
N
L
N
L
L N
SYSTEM!
pump
"A"!
A1
A4A3A2 A5 A6
"B"!
pump
A10A9A8 A11 A12A7
Caleffi North America, Inc. 3883 West Milwaukee Road Milwaukee, WI 53208 T: 414.238.2360 F: 414.238.2366
Page 9
WIRING GUIDE
The ZSR101 is a versatile single relay control with two outputs for operating a 120 VAC pump with boiler enable, or two 120 VAC devices without boiler enable. Features include rear knock outs for 4x4 junction box mounting, convenient pre-installed jumper for pump operation, and 10 amp total load rating.
The ZSR Series of controls is for zoning using pumps. Up to 6 zone pumps (model dependent) along with a primary pump can be operated. Zone priority is selectable with 1-hour time-out feature. Other features include pump exercising, selectable
post purge, and 3 pump ground terminals for simplied wiring.
Certified to CSA C22-2 No.24 Conforms to UL Standard 873
4009064
Form 031914 rev.1
The ZVR Series of controls is for zoning using zone valves. Up to 6 valves (model dependent), along with a system pump, secondary pump(s), and primary pump can be operated. Zone priority is selectable with 1-hour time-out feature. System pump status (on\off) during priority is also selectable. Replaceable snap-t 40 VA transformer standard for 3 & 4 zone mod­els – expandable to 80 VA with 2nd transformer. 6 zone model has two 40 VA (80 VA) transformers.
Page 10
2
Page 11
INDEX
Z-one Relay thermostat connections
Thermostat wiring ........................................................................................................................................................................... 3
ZSR101 - single zone relay
Product overview Operation and cover removal
A1 - Single thermostat ...................................................................................................................................................................................6
A2 - Multiple thermostats ....................................................................................................................................................................8
A3 - Single master thermostat, with TRVs, variable speed pump .................................................................................................... 10
ZSR103, ZSR104 & ZSR106 - multi-zone pump relay
Product overview ........................................................................................................................................................................... 12
Circuit board ..................................................................................................................................................................................13
Cover removal ................................................................................................................................................................................ 14
Product details B1 - Mod/Con boiler, hydro separator or buffer tank, zone pumps
B2 - Traditional boiler, indirect DHW w/ priority, zone pumps .......................................................................................................... 18
B3 - Mod/Con boiler, primary loop, closely spaced tees, zone pumps ............................................................................................ 20
ZVR103, ZVR104 & ZVR106 - multi-zone valve control
Product overview ........................................................................................................................................................................... 22
Circuit board ..................................................................................................................................................................................23
Cover removal, Transformer Installation .................................................................................................................................................24
Product details ............................................................................................................................................................................... 25
C1 - Mod/Con boiler, hydro separator, zone valves C2 - Mod/Con boiler, indirect DHW on primary side of hydro sep, zone valves
C3 - Mod/Con boiler, indirect DHW on load side of hydro sep, zone valves .................................................................................... 30
C4 - Mod/Con boiler, indirect DHW on primary side of hydro sep, master and slave control ........................................................... 32
C5 - Traditional boiler, indirect DHW (no priority) with valve ............................................................................................................. 34
C6 - Traditional boiler with reset control, priority indirect DHW with valve C7 - Mod/Con boiler, hydro separator, zone valve (more than 6), multiple secondary pumps
............................................................................................................................................................................ 4
........................................................................................................................................................................5
............................................................................................................................................................................... 15
................................................................................................. 16
........................................................................................................................ 26
............................................................................... 28
........................................................................................ 36
.......................................................... 38
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
3
Page 12
Z-one Thermostat Connections
COMMS
D
P
T-STAT 4
C
COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
PWR
PWR
PWR
ZONE1
WR
2-Wire Thermostats
4-Wire Thermostats
4
All Caleffi Z-one controls use the same interface to connect to thermostats. This interface is very flexible and allows many different types of thermostats to be connected to the control including 2, 3 and 4 wire versions. In addition, any type of switching device can be used to signal a heat demand by connecting the R & W (T & T) terminals together. The terminals are dual labeled
to help simplify wiring.
Z-one T-stat interface
R
T T COM
C
W
T-STAT 1
R
T T COM
C
W
T-STAT 2
R
W
T T COM
T-STAT 3
R
C
W
T T
Description
R = 24 VAC Supply
W = Heat Call
C = 24 VAC Common
Function
R&W: When connected, signals a heat demand.
R&C: Provides 24 VAC to powered thermostats.
There are a few different types of 2 wire thermostats including bi-metallic, power stealing and battery powered. All of these thermostats connect in the same manner to the Caleffi Z-one series of controls. Connect R to R and W to W. See below.
W
T COM
HM 2
C
T T COM
THM 3
CRW
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
CRW
D
COMMS
P
3-Wire Thermostats
Three wire thermostats get their power from the control they are connected to. R & C from the Z-one Control supply 24 VAC to the thermostat at all times while the W lead signals a heat demand.
To connect a 4-wire thermostat to the Z-one series controls, connect R to R, W to W and C to C. A jumper in the thermostat is also required between R & Rh as shown below. Similar to a 3-wire thermostat, R & C from the Z-one Control
supply constant 24 VAC to the thermostat.
COM
3
C
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
C R Rh W1
CRW
D
COMMS
P
P
Dry Contacts
A heat demand can also be initiated by any type of device that has dry contacts (dry contacts are a set of contacts that open and close but do not have any voltage present until supplied from an outside source). The end switch on a Z-one series zone valve is an example of a dry contact. Using a dry contact to connect R to W will initiate a heat demand.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
W
T COM
M 2
C
Always refer to the thermostat manufacturer’s instructions.
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION!
BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION: All work must be performed by qualified personnel trained in the
proper application, installation, and maintenance of systems in accordance with all applicable codes and ordinances.
Caleffi shall not be liable for damages resulting from misapplication or misuse of it products.
CRW
T T COM
THM 3
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
C
CRW
D
COMMS
P
W
T COM
M 2
T T COM
THM 3
CRW
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
CRW
D
COMMS
P
CAUTION: Electrical shock hazard. Disconnect power before installation to prevent electrical shock or equipment damage. Make sure all connections are in accordance with the electrical wiring diagram and in accordance with national and local electrical codes.
CAUTION: Avoid electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment. Avoid locations where excessive moisture, corrosive fumes, vibration, or explosive vapors are present.
Page 13
6 Zone
ZVR106
T-STAT 2
C
R
W
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
C
R
W
T T COM
T-STAT 1
CRW
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
CRW
T T COM
T-STAT 6
C
R
W
T T COM
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
MASTER SLAVE
Wiring of 2 wire or 3 zone valve to Cale Z-one Relay
Wiring a 2 wire zone valve to Cale Z-one Relay
Since a two wire actuator does not have an end switch for feedback to the relay box, the end switch terminals must have a jumper to simulate the end swith. If the end switch jumper is not installed, no
demand will be sent to the boiler and the pumps will not turn on
STATUS DURING
POWER IN
L
PRIORITY
ON OFF
PRIORITY
N
PUMP
L
SEC PUMP
N
L
SYSTEM
PUMP
N
L
N
MOTOR
PRIORITY
ON OFF
ZONE 1
SWITCH
END
ZONE 2
MOTOR
SWITCH
END
.
MOTOR
Wiring a 3 wire zone valve to Cale Z-one Relay
The Taco 570 zone valve presents a unique wiring challenge. When connecting the Taco 570 zone valve to the Caleffi Z-one Relay, the wiring of this valve can only be done in one way. The left motor terminal on the ZVR series control must be connected to terminal 2 on the zone valve. The right motor terminal must be connected to terminal 1 on the zone valve. Lastly, the left end switch terminal must be connected to terminal 3 on the zone valve. Failure to follow schematic will lead to damage of product.
TSAT5 ZONE5
TSAT6 ZONE6
ZONE 3
SWITCH
END
MOTOR
ZONE 4
SWITCH
END
ZONE 5
END
SWITCH
MOTOR
MOTOR
ZONE 6
SWITCH
END
M
1 2
3
5
Page 14
4009064
Certified to CSA C22-2 No.24 Conforms to UL Standard 873
6
ZSR101 - Single Zone Switching Relay
Overview
• Compatible with 2, 3 and 4-wire thermostats or other low voltage controllers with switching action
• 120 VAC input
• Heavy duty, sealed, DPDT, fuse protected relay (with spare fuse)
• Two dry contact outputs (Relay 1 and Relay 2) for operating 120 VAC pump with boiler enable or two devices without boiler enable
• 5 A capacity each relay - 10 A total
• Rear knock-outs for mounting onto 4”x4” junction box
• High capacity 6VA transformer
• Simplified wiring with pre-installed jumper
• 100% factory tested with 3 year warranty
• ETL certified
See technical brochure 01284-14 NA for more product information.
Page 15
1 Zone
ZSR101
C
R
W
T T COM
L
POWER IN
N
C
RELAY #1
NO
NC
C
RELAY #2
NO
NC
TRANSFORMER
PWR
ZONE
Operating Principles
When a zone has a demand from a thermostat (TT or R W) the relay will close sending 120 VAC to Relay #1 NO terminal and switching the pump on, and the C to NO dry contact on relay #2 closes, signaling the boiler of a heating demand.
R, W, C and T T Comm dual labeling at thermostat terminals. Compatible with low voltage 2, 3, or 4 wire thermostats other low voltage devices having a switching action.
Supply 120 VAC hot to terminal L and 120 VAC neutral to N. A factory installed jumper from L terminal to the C terminal of Relay 1 is supplied for simplified pump connection.
If dry contacts are desired from relay #1, remove the factory installed jumper between L and C.
Cover removal
R
W
T T COM
C
or any
6 VA Transformer.
120VAC input
power connection
Keyhole mounting
which fits a 4X4
junction box.
Dual labeled T-stat terminals.
Compatible with 2, 3 and 4
wire T-stats.
Pre-installed jumper.
Replaceable fuses.
Rear knockout for
4X4 junction box.
Mounting: Do not mount to a surface that exceeds 115°F (45°C). The unit must be only located in dry interior locations. Use only copper conductor supply wire suitable for at least 105° C. All circuits must have a common disconnect and be connected to the same pole of the disconnect. It is not suitable for installation in hazardous locations.
Hold either the left or the right end of the box up and at an angle. Use body for stabilizing relay box. Insert screwdriver and push tab inward.
Turn box and repeat inserting screwdriver and pushin tab inward on opposite side, cover should release from base.
Slide cover off base.
7
Page 16
A1 - Single thermostat
transformer
C
W
R
com
T
T
single zone relay
8
power
zone
Caleffi!
N LL
C N/O N/C C N/O N/C
N L
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
RELAY 1
RELAY 2
T T
Page 17
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120 VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
• A demand occurs and closes RW (TT)
• Relay #1 and relay #2 both fire connecting the common terminal to the NO terminal.
• If the factory installed jumper has not been removed, the NO terminal of relay #1 will deliver the hot leg of 120 VAC. Relay #2 has dry contacts.
• The zone LED illuminates.
• The demand is satisfied and opens RW (TT).
• The relay contacts return to their normal position (common to normally closed).
• The zone LED turns off.
9
Page 18
A2 - Multiple thermostats
transformer
C
W
R
com
T
T
single zone relay
Caleffi!
power
zone
End switch wires
R W
R
W
4-wire zone valve
R
W
4-wire zone valve
10
4-wire zone valve
RELAY 1
C N/O N/C C N/O N/C
N LL
RELAY 2
N L
Hydronic diagram is for illustration purposes only and could be missing system components.
24 VAC
T T
Page 19
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120 VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
• There is a demand by one of the t-stats which sends power to the corresponding zone valve.
• When the zone valve opens, its end switch contacts close and signal a demand to the RW (TT) contacts on the single zone relay control.
• Relay #1 and relay #2 fire
• If the factory installed jumper has not been removed, the NO terminal of relay #1 will deliver the hot leg of 120 VAC thus firing the pump.
• Relay #2 closes the TT contacts on the boiler signally a demand.
• The Zone LED illuminates.
• When the last of the T-stats is satisfied, the corresponding zone valves closes which opens the end switch contacts.
• The relay contacts return to their normal position turning off power to the system pump and opening the RW (TT) contacts.
• The Zone LED turns off.
11
Page 20
A3 - Single master thermostat, panel radiators with TRVs, variable speed pump
12
buffer tank
TRV
thermostatic!
radiator valves!
(TRV) on each!
radiator
TRV
TRV
TRV
TRV
TRV
C
W
R
com
T
T
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
N
power
zone
transformer
Caleffi!
single zone relay
RELAY 1
C N/ON/C C N/ON/C
N LL
RELAY 2
T
L
T
Page 21
Description of terminals
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120 VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
Sequence of Operation / Settings
• A single “master” thermostat is wired to the ZSR101 control. The master thermostat is set to a slightly higher set point than the desired room temperatures on the thermostatic radiator valves.
• When the temperature drops below the thermostat’s set point, a heat demand is initiated by closing the R & W terminals.
• Relay #1 and relay #2 both fire.
• If the factory installed jumper has not been removed, the NO terminal of relay #1 will deliver 120 VAC line to the variable speed circulator.
• Relay #2 closes the TT contacts on the boiler signaling a demand.
• The Zone LED illuminates.
• Using an outside air sensor and system temperature sensor located in the buffer tank, the boiler determines if the water in the boiler meets the target temperature based off the outside air reset curve.
• The relay contacts return to their normal position turning off power to the variable speed circulator and opening the RW (TT) contacts. Both the boiler and pump are no longer enabled.
• The Zone LED turns off.
• As long as the master thermostat is calling, the boiler will maintain the buffer tank to the target temperature.
• The thermostatic radiator valves modulate the flow through the panel radiators because the variable speed circulator is enabled.
• When the master thermostat reaches set point, the master thermostat will open the contact between R & W.
13
Page 22
4009064
Certified to CSA C22-2 No.24 Conforms to UL Standard 873
14
ZSR10X - Multi-Zone Pump Control
Overview
• Compatible with low voltage 2, 3, or 4 wire thermostats
• R, W, C and TT Comm dual labeling at thermostat terminals
• Z-oneLink unlimited zone expansion
• 120 VAC pump outputs
• Selectable priority with 1 hour time-out feature
• Selectable post purge and exercise
• Dry contacts for DHW (ZR/ZC), capable of switching line voltage
• High capacity transformer
• Large terminal connections
• Simplified wiring with extra ground terminals
• Heavy duty sealed relays
• Fuse protected (with spare fuse)
• Front LED lights
• 100% Factory tested with 3 year warranty
• ETL approved
See technical brochure 01286-14 NA for more product information.
Page 23
XX Closes for heat demand
and DHW
demand. Rated
for 120 VAC,
2 amps.
DHW (ZR/ZC)
closes only
during priority
call. Rated
for 120 VAC,
2 amps.
Dual labeled T-stat terminals. Compatible with
2, 3 and 4 wire
T-stats.
Selectable DIP
switches.
3 wire
communications to
expansion board.
Power ON LED.
LED for each
zone.
120 VAC input
power connection
Multiple ground connections for
easy wiring.
Replaceable
fuses (2 extra
included under
cover).
120 VAC zone
pump outputs.
120 VAC primary
pump output.
15
Page 24
Cover removal
16
Hold either the left or the right end of the box up and at an angle. Use body for stabilizing relay box.
Mounting: Do not mount to a surface that exceeds 115°F (45°C). The unit must be only located in dry interior locations. Use only copper conductor supply wire suitable for at least 105° C. All circuits must have a common disconnect and be connected to the same pole of the disconnect. It is not suitable for installation in hazardous locations.
Insert screwdriver and push tab inward, cover should release from base.
Roll cover off base.
Page 25
T-STAT 2
C
R
W
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
Maintenance and Repair: The Caleffi Z-one™ multi-zone pump control
COMMS
D
P
PWR
6 Zone
T-STAT 2
C
R
W
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
R
W
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
POWER IN
N
GROUNDS
L
PUMP 3
N
TRANSFORMER
L
N
T-STAT 4
C
R
W
T T COM
L
PUMP 4
N
L
PUMP 5
N
L
PUMP 6
N
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF
Priority ON
Primary OFF
Primary ON
Exercise OFF
Exercise ON
Post Purge OFF
Post Purge ON
ZSR106
6 Zone
T-STAT 2
C
R
W
T T COM
COMMS
D
P
T-STAT 3
C
R
W
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
PUMP 3
N
L
N
T-STAT 4
C
R
W
T T COM
L
PUMP 4
N
L
PUMP 5
N
L
PUMP 6
N
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF
Priority ON
Primary OFF
Primary ON
Exercise OFF
Exercise ON
Post Purge OFF
Post Purge ON
ZSR106
COMMS
D
P
PRIMARY
PUMP
L
N
C
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
COMMS
D
P
C
W
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
comes with two spare fuses. If control fails or is damaged, replace control with functional one.
Boiler connections: XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Communication connections: Connect terminals to matching terminal of slave boards D to D, P to P, Ground to Ground
Input Power: L = Line (hot leg) of 120 VAC supply N = Neutral of 120 VAC = Ground Note: when connecting 2 or more Z-one controls, all controls must be powered by the same 120 VAC circuit.
Zone pump outputs: Zone pumps run when corresponding thermostat initiates a demand. GROUND = Connect the ground from the pump to the ground terminal. PRIORITY PUMP = Runs when zone #1 calls. Can be programmed to be the priority zone. L = Line (hot leg) of 120 VAC to power the pump N = Neutral leg of 120 VAC to power the pump
The DIP Switches on the ZSR series can be positioned for the following operations. Master / Slave: allows for unlimited expansion to additional ZSR relays.
DipSwitches
Master Slave
Priority OFF
Primary OFF
Exercise OFF
Post Purge OFF
Priority ON Primary ON Exercise ON Post Purge ON
Priority OFF / Priority ON: When priority mode is ON, upon demand, zone 1 will operate as priority and all other zones are temporarily switched off (with 1 hour time-out). When priority mode is OFF, all zones remain active. Primary OFF / Primary ON: When primary mode is ON, the primary pump will continue to operate during priority. Exercise OFF / Exercise ON: When exercise mode is ON, each circulator is switched on for 30 seconds following 72 hours of inactivity. Post Purge OFF / Post Purge ON: When post purge is ON, the priority pump continues operating for 2 minutes after the priority zone is switched off.
Primary pump output: Primary pump runs when any zone pump runs. Its status during priority (on\off) can be programmed using the DIP switches. L = Line (hot leg) of 120 VAC to power the pump N = Neutral leg of 120 VAC to power the pump
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply.
WARNING: When connecting 2 or more Z-one controls, all controls must be powered by the same 120 VAC circuit.
WARNING: When replacing fuses, make sure power is disconnected to control box.
17
Page 26
6 Zone
T-STAT 2
CRW
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
CRW
T T COM
T-STAT 1
CRW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
POWER IN
N
GROUNDS
L
PUMP 3
N
TRANSFORMER
L
N
T-STAT 4
CRW
T T COM
L
PUMP 4
N
L
PUMP 5
N
L
PUMP 6
N
T-STAT 5
CRW
T T COM
T-STAT 6
CRW
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
PriorityOFF
PriorityON
PrimaryOFF
PrimaryON
ExerciseOFF
ExerciseON
PostPurge OFF
PostPurge ON
ZSR106
B1 - Mod/con boiler, hydro separator or buffer tank, zone pumps
Pump 2
Pump 1
Buffer tank- Optional hydraulic separator
Pump 3
18
Pump 4
N
L
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
Page 27
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (Hot leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Dip switch description
Master / Slave: Used when joining 2 or more controls together. Only one Master per group
Priority OFF / Priority ON: Used to set Zone #1 as the priority zone. All other zones will hold off during priority. Priority has a one hour time out feature to prevent freeze up.
Primary OFF / Primary ON: Sets the status of the primary pump when there is a priority call. This allows the DHW pump to be on either side of a hydro separator.
Exercise OFF / Exercise ON: When enabled the pumps will rub for 30 seconds after 72 hours without a demand.
Post Purge OFF / Post Purge ON: Allows the DHW pump to run for 2 minutes after the DHW demand has been satisfied.
Priority switch: OFF
Master / Slave switch: Master
Status During Priority switch: OFF
• A demand occurs from any T-stat (T-stat closes TT terminals). The “PUMP ON” LED illuminates for that zone.
• ZSR control sends 120 VAC to the corresponding zone pump and the primary pump outputs, XX contacts close to signal boiler of a demand.
• When the demand from the last T-stat calling is satisfied (T-stat opens TT terminals), the XX contacts are opened, the “PUMP ON” LED turns off and the 120 VAC to the zone pump and primary pump outputs are dropped.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
19
Page 28
B2 - Traditional boiler, indirect DHW w/ priority, zone pumps
Pump 3
Pump 4
Pump 5
boiler!
high limit!
control
Pump 1
DHW!
aquastat
Pump 2
DHW!
aquastat
20
Pump 6
DHW
X X
ZR/ZC
TRANSFORMER
outdoor!
temperature!
sensor
T T
ZC
ZR
POWER IN
L
12/20VA
N
L
N
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
GROUNDS
T T COM
THM 1
CRW
T T COM
THM 2
PRIORITY
PUMP 1
L
CRW
PUMP 2
L
N
CRW
T T COM
THM 3
6 Zone
Z6P
ZSR106
PUMP 3
L
N
T T COM
THM 4
N
PUMP 4
L
CRW
Priority OFF
Primary OFF
Exercise OFF
Post Purge OFF
N
T T COM
THM 5
DipSwitches
Master Slave
Priority ON Primary ON Exercise ON Post Purge ON
PUMP 5
N
L
CRW
T T COM
THM 6
PUMP 6
N
L
CRW
PRIMARY
PUMP
L
D
P
COMMS
N
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
Page 29
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (Hot leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Dip switch description
Master / Slave: Used when joining 2 or more controls together. Only one Master per group
Priority OFF / Priority ON: Used to set Zone #1 as the priority zone. All other zones will hold off during priority. Priority has a one hour time out feature to prevent freeze up.
Primary OFF / Primary ON: Sets the status of the primary pump when there is a priority call. This allows the DHW pump to be on either side of a hydro separator.
Exercise OFF / Exercise ON: When enabled the pumps will rub for 30 seconds after 72 hours without a demand.
Post Purge OFF / Post Purge ON: Allows the DHW pump to run for 2 minutes after the DHW demand has been satisfied.
Priority switch: ON (Zone #1 becomes priority)
Master/Slave switch: Master
Primary Status During Priority switch: OFF
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 6.
• The “PUMP ON” LED illuminates for that zone.
• ZSR control sends 120 VAC to the corresponding zone pump terminals to fire the zone pump and closes the XX contacts to signal a heat demand to the boiler. The PRIMARY PUMP output will also deliver 120 VAC even if no pump is connected.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), the “PUMP ON” LED turns off.
• 120 VAC is dropped from the corresponding zone pump terminals.
• If no other zones are calling, power is dropped to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
• If a demand occurs from the DHW aquastat (zone #1), The “PUMP ON” LED illuminates for Zone #1.
• If any other zone was calling (Zones 2 thru
6) when Zone #1 called, power (120 VAC) is dropped to those zone pumps.
• The XX and DHW contacts close.
• The PRIORITY PUMP contacts deliver 120 VAC
• Once the Zone #1 DHW demand is satisfied, power to the PRIORITY PUMP is dropped, the DHW contacts open.
• If a demand from zones 2 thru 6 is present, 120 VAC is delivered to the corresponding zone pump(s) and the “PUMP ON” LED for those zones will illuminate.
• The XX contacts close to signal a heat demand to the boiler.
• When all zones are satisfied, the XX contacts open and power (120 VAC) is turned off to all of the zone pumps.
DHW Time Out \ Freeze Prevention Feature
• After one hour of a priority demand, the control will open the DHW contacts and turn off power to the DHW pump.
• If a heating demand is present from Zones #2- 6, the control will satisfy those demands before going back to the DHW call.
• After the heating demands are met, the control will go back to DHW and re-set the one hour timer.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
21
Page 30
6 Zone
T-STAT 2
CRW
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
CRW
T T COM
T-STAT 1
CRW
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
POWER IN
N
GROUNDS
L
PUMP 3
N
TRANSFORMER
L
N
T-STAT 4
CRW
T T COM
L
PUMP 4
N
L
PUMP 5
N
L
PUMP 6
N
T-STAT 5
CRW
T T COM
T-STAT 6
CRW
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF
Priority ON
Primary OFF
Primary ON
Exercise OFF
Exercise ON
Post Purge OFF
Post Purge ON
ZSR106
B3 - Mod/Con boiler, primary loop, closely spaced tees, zone pumps
22
boiler pump
Pump 1
Primary pump
3
3
Pump 2
Pump 3
L
N
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
boiler pump
Primary pump
Page 31
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (Hot leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Dip switch description
Master / Slave: Used when joining 2 or more controls together. Only one Master per group
Priority OFF / Priority ON: Used to set Zone #1 as the priority zone. All other zones will hold off during priority. Priority has a one hour time out feature to prevent freeze up.
Primary OFF / Primary ON: Sets the status of the primary pump when there is a priority call. This allows the DHW pump to be on either side of a hydro separator.
Exercise OFF / Exercise ON: When enabled the pumps will rub for 30 seconds after 72 hours without a demand.
Post Purge OFF / Post Purge ON: Allows the DHW pump to run for 2 minutes after the DHW demand has been satisfied.
Priority switch OFF
Master / Slave switch: Master
Status During Priority switch: OFF
• A demand occurs from any T-stat (T-stat closes TT terminals). The “PUMP ON” LED illuminates for that zone.
• ZSR control sends 120 VAC to the corresponding zone pump and the primary pump outputs, XX contacts close to signal boiler of a demand.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), the XX contacts are opened, the “PUMP ON” LED turns off and the 120 VAC to the zone pump and primary pump outputs are turned off.
• ALTERNATE WIRING: The boiler pump can be controlled by the Mod/Con boiler if equiped to do so.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
23
Page 32
4009064
Certified to CSA C22-2 No.24 Conforms to UL Standard 873
24
ZVR10X - Multi-Zone Valve Control
Overview
• Compatible with low voltage 2, 3, or 4 wire thermostats
• R, W, C and TT Comm dual labeling at thermostat terminals
• Z-oneLink unlimited zone expansion
• Selectable priority with 1 hour time-out feature
• System pump status selectable during priority
• Pump will start only after the zone valve end switch is closed
• Dry contacts for DHW (ZR/ZC), capable of switching line voltage
• Large terminal connections
• High capacity 40 VA transformer standard for 3 and 4 zone models-expandable to 80 VA, and 80 VA for the 6 zone model
• Automatic resettable fuse
• Controls system pump, secondary pump, and priority pump
• Front LED Lights
• 100% Factory tested with 3 year warranty
• ETL approved
See technical brochure 01285-14 NA for more product information.
Page 33
Transformer
connections.
XX Closes for
heat demand
and DHW
demand. Rated
for 120 VAC
2 amps.
DHW (ZR/ZC)
closes only
during priority
call. Rated
for 120 VAC,
2 amps.
Dual labeled T-stat terminals. Compatible with
2, 3 and 4 wire
T-stats.
Master/Slave
jumper.
3 wire
communications
to expansion
board.
Power ON LED.
120 VAC input
power connection.
120 VAC output
to pumps.
System pump
(boiler pump) status during
priority can be
changed with
jumper.
ZONE #1
priority.
Zone valve motor
connections.
LED illuminates
when end switch
closes.
LED illuminates
with call for
heat.
Zone valve end switch
connection.
25
Page 34
Cover removal
26
Hold either the left or the right end of the box up and at an angle. Use body for stabilizing relay box.
Transformer Installation
Mount box on stable surface using level.
Insert screwdriver and push tab inward, cover should release from base.
Remove transformer(s) from packaging.
Roll cover off base.
Slide bottom end of transformer into bottom latch.
Mounting: Do not mount to a surface that exceeds 115°F (45°C). The unit must be only located in dry interior locations. Use only copper conductor supply wire suitable for at least 105° C. All circuits must have a common disconnect and be connected to the same pole of the disconnect. It is not suitable for installation in hazardous locations.
Snap top of transformer into latch arms.
Feed wiring through hole near the top of the transformer and insert transformer plug into the socket.
Repeat process for 2nd transformer if using six valve relay box.
Page 35
COMMS
D
P
T-STAT 3
C
COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
6 Zone
ZVR106
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
MASTER SLAVE
C
W
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
6 Zone
ZVR106
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
PRIORITY
ON OFF
MASTER SLAVE
T-STAT 2
C
R
W
T T COM
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
W
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
TSAT1 ZONE1
COMMS
D
P
T-STAT 6
C
R
W
T T COM
Maintenance and Repair: The Caleffi Z-one™ multi-zone valve relay comes with
R
6 Zone
T-STAT 2
C
R
W
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
R
W
T T COM
L
PUMP 2
N
PRIMARY
PUMP
L
PRIORITY
PUMP 1
N
L
PUMP 3
N
TRANSFORMER
L
N
T-STAT 4
C
R
W
T T COM
L
PUMP 4
N
L
PUMP 5
N
L
PUMP 6
N
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
PWR
ZONE1
ZONE2
ZONE3
ZONE4
ZONE5
ZONE6
DipSwitches
Master Slave
Priority OFF
Priority ON
Primary OFF
Primary ON
Exercise OFF
Exercise ON
Post Purge OFF
Post Purge ON
ZSR106
6 Zone
ZVR106
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
L
PRIORITY
PUMP
N
L
SEC PUMP
N
STATUS DURING
PRIORITY
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
ON OFF
L
SYSTEM
PUMP
N
MASTER SLAVE
T-STAT 2
C
R
W
T T COM
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 1
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
6 Zone
ZVR106
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
MASTER SLAVE
C
COMMS
D
P
T-STAT 3
C
R
W
T T COM
T-STAT 4
C
R
W
T T COM
T-STAT 5
C
R
W
T T COM
T-STAT 6
C
R
W
T T COM
a resettable fuse and requires no maintenance. If control fails or is damaged, replace control with functional one.
The ZVR series of controls is programmed by positioning a series of jumpers. Example photo to right shows jumper in off position (left photo) and on position (right photo). Jumpers are used for the following operations. Priority ON / Priority OFF: When priority
PRIORITY
jumper is ON, upon demand, zone 1 will operate as priority and all other zones are
ON OFF
temporarily switched off (with 1 hour time­out). When priority mode is OFF, any zones that were active when zone 1 was switched on will remain on.
Status During Priority ON / Status During Priority OFF: When status jumper is ON,
STATUS DURING
PRIORITY
ON OFF
the system pump will continue to operate during priority. Master / Slave: allows for unlimited expansion to additional ZVR relays.
Boiler Connections
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls
MASTER SLAVE
including priority. Typically connected to TT on boiler control. DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Communication connections
Connect terminals to matching terminal of slave boards D to D, P to P, Ground to Ground Use 18 gauge thermostat wire. Wire should be shielded if located in close proximity to high voltage wiring.
D
COMMS
P
PW
Thermostat connections
R = 24 VAC. W = Heat call C = Common of 24 VAC
R
T T COM
C
W
T-STAT 1
R
W
T T COM
T-STAT 2
R
T T
W
Heat demand is initiated by closing R to W.
C
24 VAC is always present between R & C.
Zone valve connections
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone valve. Must be jumpered if using a 2 –wire zone valve.
Input power
POWER IN
L
GROUNDS
N
L = Line (hot leg) of 120 VAC supply N = Neutral of 120 VAC = Ground
Pump outputs
calls for heat except the priority zone when it is enabled. PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump for DHW.
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\ off) during a priority call is selected via a jumper SEC PUMP = Runs when any zone
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply.
WARNING: When connecting 2 or more Z-one controls, all controls must be powered by the same 120 VAC circuit.
27
Page 36
6 Zone
ZVR106
T-STAT 2
CRW
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
CRW
T T COM
T-STAT 1
CRW
T T COM
L
POWER IN
N
T-STAT 4
CRW
T T COM
T-STAT 5
CRW
T T COM
T-STAT 6
CRW
T T COM
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
L
PRIORITY
PUMP
N
L
SEC PUMP
N
STATUS DURING
PRIORITY
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
ON OFF
L
SYSTEM
PUMP
N
MASTER SLAVE
L
N
PRIORITY!
pump
SECONDARY!
pump
ZV1
ZV4ZV3ZV2 ZV5 ZV6
mod/con! boiler
C1 - Mod/Con boiler, hydro separator, zone valves
28
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
SYSTEM
Page 37
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
Priority Jumper: OFF
Master / Slave Jumper: Master
Status During Priority: OFF
• A demand occurs from any T-stat (T-stat closes TT terminals). The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is turned off to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
29
Page 38
C2 - Mod/Con boiler, priority indirect DHW on primary side of hydro sep, zone valves
mod/con! boiler
ZV4ZV3ZV2 ZV5 ZV6
DHW!
aquastat
30
Buffer tank- Optional hydraulic separator
PRIORITY!
pump
SYSTEM!
L
N
pump
X X
POWER IN
L
SECONDARY!
pump
DHW!
AQUASTAT
DHW
ZR/ZC
N
PRIORITY
PUMP
L
PRIORITY!
pump
T T COM
T-STAT 1
SEC PUMP
L
N
SECONDARY!
pump
N
CRW
STATUS DURING
PRIORITY
SYSTEM
L
T T COM
T-STAT 2
ON OFF
PUMP
N
CRW
PRIORITY
MOTOR
CRW
T T COM
T-STAT 3
ZVR106
6 Zone
ON OFF
ZONE 1
END
SWITCH
T T COM
T-STAT 4
ZONE 2
MOTOR
END
SWITCH
CRW
MOTOR
T T COM
T-STAT 5
ZONE 3
END
SWITCH
CRW
T T COM
T-STAT 6
ZONE 4
SWITCH
MOTOR
ZV4ZV3ZV2 ZV5 ZV6
END
CRW
MASTER SLAVE
MOTOR
ZONE 5
END
SWITCH
D
COMMS
P
MOTOR
ZONE 6
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
END
SWITCH
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
SYSTEM!
pump
Page 39
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
• Priority Jumper: ON (Zone #1 becomes priority)
• Master/Slave Jumper: Master
• Status During Priority: OFF
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 6. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is dropped to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
• If a demand occurs from the DHW aquastat (zone #1), The “T-STAT CALL” LED illuminates for Zone #1 and the “VALVE OPEN” LED will illuminate. (When using a DHW pump, a jumper must be installed on Zone #1 end switch terminals.)
• If any other zone was calling (Zones 2 thru
6) when Zone #1 called, power (24 VAC) is dropped to those zones.
• The XX and DHW contacts close.
• The PRIORITY PUMP contacts deliver 120 VAC
• The SEC PUMP and SYSTEM PUMP are off.
• Once the Zone #1 DHW demand is satisfied, power to the PRIORITY PUMP is dropped, the DHW contacts open.
• If a demand from zones 2 thru 6 is present, 24 VAC is delivered to the corresponding zone valve(s) and the “T-STAT CALL” LED’s illuminate.
• When the zone valve end switch closes, the “VALVE OPEN” LED illuminates, the XX contacts close, the SEC PUMP and SYSTEM PUMP terminals deliver 120 VAC.
DHW Time Out \ Freeze Prevention Feature
• After one hour of a priority demand, the control will open the DHW contacts and turn off power to the DHW pump and Zone Valve #1.
• If a heating demand is present from Zones #2- 6, the control will satisfy those demands before going back to the DHW call.
• After the heating demands are met, the control will go back to DHW and re-set the one hour timer.
31
Page 40
C3 - Mod/Con boiler, priority indirect DHW on load side of hydro sep, zone valves
Buffer tank- Optional hydraulic separator
32
X X
POWER IN
L
ZV4ZV3ZV2 ZV5
SECONDARY!
P
MOTOR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE 6
END
SWITCH
pump
PWR
DHW!
AQUASTAT
SYSTEM!
pump
PRIORITY!
pump
DHW!
AQUASTAT
DHW
ZR/ZC
T T COM
T-STAT 1
PRIORITY
SEC PUMP
PUMP
N
L
N
L
CRW
CRW
T T COM
T-STAT 2
STATUS DURING
PRIORITY
ON OFF
SYSTEM
PUMP
N
L
N
T T COM
T-STAT 3
ZVR106
PRIORITY
ON OFF
ZONE 1
MOTOR
6 Zone
END
SWITCH
CRW
MOTOR
T T COM
T-STAT 4
ZONE 2
END
SWITCH
CRW
T T COM
T-STAT 5
ZONE 3
MOTOR
END
SWITCH
CRW
T T COM
T-STAT 6
ZONE 4
MOTOR
SWITCH
END
CRW
MASTER SLAVE
MOTOR
ZONE 5
SWITCH
D
END
COMMS
ZV6
L
N
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
Page 41
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
Priority Jumper: ON (Zone #1 becomes priority)
Master/Slave Jumper: Master
Status During Priority: ON
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 6. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is dropped to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
• If a demand occurs from the DHW aquastat (zone #1), The “T-STAT CALL” LED illuminates for Zone #1 and the “VALVE OPEN” LED will illuminate. (When using a DHW pump, a jumper must be installed on Zone #1 end switch terminals.)
• If any other zone was calling (Zones 2 thru
6) when Zone #1 called, power (24 VAC) is dropped to those zones.
• The XX and DHW contacts close.
• The PRIORITY PUMP and SYSTEM PUMP contacts deliver 120 VAC
• The SEC PUMP is off.
• Once the Zone #1 DHW demand is satisfied, power to the PRIORITY PUMP and SYSTEM PUMP is dropped, the DHW contacts open.
• If a demand from zones 2 thru 6 is present, 24 VAC is delivered to the corresponding zone valve(s) and the “T-STAT CALL” LED’s illuminate.
• When the zone valve end switch closes, the “VALVE OPEN” LED illuminates, the XX contacts close, the SEC PUMP and SYSTEM PUMP terminals deliver 120 VAC.
DHW Time Out \ Freeze Prevention Feature
• After one hour of a priority demand, the control will open the DHW contacts and turn off power to the DHW pump and Zone Valve #1.
• If a heating demand is present from Zones #2- 6, the control will satisfy those demands before going back to the DHW call.
• After the heating demands are met, the control will go back to DHW for and re-set the one hour timer.
33
Page 42
C4- Mod/Con boiler, priority indirect DHW on primary side of hydro sep, expansion control
pump
Buffer tank - Optional hydraulic separator
34
DHW!
AQUASTAT
X X
POWER IN
L
L
ZV4ZV3
X X
POWER IN
N
DHW
ZR/ZC
ZV5
PRIORITY
PUMP
L
N
ZV6
T T COM
T-STAT 1
SEC PUMP
L
ZV7
CRW
CRW
T T COM
T-STAT 2
STATUS DURING
PRIORITY
ON OFF
SYSTEM
PUMP
N
L
N
MOTOR
ZV2
SECONDARY!
pump
PRIORITY!
pump
SYSTEM!
pump
DHW!
AQUASTAT
DHW
ZR/ZC
T T COM
T-STAT 1
PRIORITY
SEC PUMP
PUMP
N
L
N
L
CRW
CRW
T T COM
T-STAT 2
STATUS DURING
PRIORITY
ON OFF
SYSTEM
PUMP
N
L
N
T T COM
T-STAT 3
PRIORITY
ZONE 1
MOTOR
ON OFF
CRW
T T COM
T-STAT 4
ZVR106
6 Zone
ZONE 2
END
SWITCH
MOTOR
END
SWITCH
CRW
T T COM
T-STAT 5
ZONE 3
MOTOR
SWITCH
CRW
T T COM
T-STAT 6
ZONE 4
END
MOTOR
END
SWITCH
CRW
MASTER SLAVE
MOTOR
ZONE 5
END
SWITCH
D
COMMS
P
MOTOR
ZONE 6
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
END
SWITCH
PWR
T T COM
T-STAT 3
ZVR106
6 Zone
PRIORITY
ON OFF
ZONE 1
END
SWITCH
CRW
MOTOR
ZV9ZV8
T T COM
T-STAT 4
ZONE 2
END
SWITCH
CRW
ZV10
T T COM
T-STAT 5
ZONE 3
MOTOR
END
SWITCH
ZV11
CRW
T T COM
T-STAT 6
ZONE 4
MOTOR
SWITCH
END
ZV12
CRW
MASTER SLAVE
MOTOR
ZONE 5
END
SWITCH
D
COMMS
P
MOTOR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
ZONE 6
END
SWITCH
PWR
L
N
PRIORITY!
pump
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
SECONDARY!
pump
SECONDARY
pump
SYSTEM!
pump
SYSTEM
ZV4ZV3ZV2 ZV5 ZV6
L N
ZV7
ZV10ZV9ZV8 ZV11 ZV12
Page 43
Description of terminals
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
Sequence of Operation / Settings
Control #1 (Master)
Priority Jumper: ON (Zone #1 becomes priority)
Master/Slave Jumper: Master
Status During Priority: OFF
Control #2 (Slave)
Priority Jumper: OFF
Master/Slave Jumper: Slave
Status During Priority: OFF
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 12. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
NOTE: The SEC PUMP output is only fired on the control that receives the t-stat call. For instance, if a zone from control #1 calls, the SEC PUMP on control #1 fires but SEC PUMP on control #2 does not. When using a single secondary pump with 2 controls, the secondary pump must be connected to the “SYSTEM PUMP” terminals. (An alternative wiring option for secondary pump is to wire the secondary pump to the “SEC PUMP” terminals of both controls).
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is dropped to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
• If a demand occurs from the DHW aquastat (zone #1), The “T-STAT CALL” LED illuminates for Zone #1 and the “VALVE OPEN” LED will illuminate. (When using a DHW pump, a jumper must be installed on Zone #1 end switch terminals.)
• If any other zone was calling (Zones 2 thru
12) when Zone #1 called, power (24 VAC) is dropped to those zones.
• The XX and DHW contacts close.
• The PRIORITY PUMP contacts deliver 120 VAC
• The SEC PUMP and SYSTEM PUMP are off.
• Once the Zone #1 DHW demand is satisfied, power to the PRIORITY PUMP is dropped, the DHW contacts open.
• If a demand from zones 2 thru 12 is present, 24 VAC is delivered to the corresponding zone valve(s) and the “T-STAT CALL” LED’s illuminate.
• When the zone valve end switch closes, the “VALVE OPEN” LED illuminates, the XX contacts close, the SEC PUMP and SYSTEM PUMP terminals deliver 120 VAC.
• DHW Time Out \ Freeze Prevention Feature
• After one hour of a priority demand, the control will open the DHW contacts and turn off power to the DHW pump and Zone Valve #1.
• If a heating demand is present from Zones #2- 12, the control will satisfy those demands before going back to the DHW call.
• After the heating demands are met, the control will go back to DHW for and re-set the one hour timer.
35
Page 44
C5 - Traditional boiler, indirect DHW (no priority) with valve, zone valves
36
X X
POWER IN
L
SYSTEM!
pump
ZV2
ZV3
ZV4
ZV5
ZV6
ZV1
DHW!
aquastat
DHW
ZR/ZC
T T COM
THM 1
CRW
T T COM
THM 2
CRW
T T COM
THM 3
CRW
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
ZRV106
6 Zone
Z6V
STATUS DURING
SEC PUMP
L
PRIORITY
SYSTEM
PUMP
N
PRIORITY
PUMP
N
N
L
PRIORITY
MOTOR
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
SWITCH
D
CRW
Master/Slave
P
COMMS
PWR
THM1 ZONE1
THM2 ZONE2
THM3 ZONE3
THM4 ZONE4
THM5 ZONE5
THM6 ZONE6
ZONE 5
ZONE 6
END
END
SWITCH
MOTOR
MOTOR
END
SWITCH
L
N
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
Page 45
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
Priority Jumper: OFF
Master/Slave Jumper: Master
Status During Priority: OFF
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 6 otr the aquastat on zone #1. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is turned off to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
37
Page 46
C6- Traditional boiler with reset control, priority indirect DHW with valve, zone valves
38
SYSTEM!
pump
ZV2
ZV3
ZV4
ZV5
ZV6
ZV1
DHW!
aquastat
DHW!
aquastat
DHW
X X
ZR/ZC
ZR
ZC
T T
T T COM
THM 1
CRW
T T COM
THM 2
CRW
T T COM
THM 3
ZRV106
CRW
T T COM
THM 4
CRW
T T COM
THM 5
CRW
T T COM
THM 6
6 Zone
Z6V
STATUS DURING
POWER IN
L
SEC PUMP
L
PRIORITY
SYSTEM
PUMP
N
PRIORITY
PUMP
N
N
L
PRIORITY
MOTOR
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
D
CRW
COMMS
Master/Slave
P
PWR
THM1 ZONE1
THM2 ZONE2
THM3 ZONE3
THM4 ZONE4
THM5 ZONE5
THM6 ZONE6
ZONE 5
ZONE 6
END
MOTOR
END
SWITCH
MOTOR
SWITCH
L
N
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
Page 47
Description of terminals
Sequence of Operation
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
Priority Jumper: ON (Zone #1 becomes priority)
Master/Slave Jumper: Master
Status During Priority: ON
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 2 thru 6. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SEC PUMP and SYSTEM PUMP. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
• If no other zones are calling, power is dropped to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
• If a demand occurs from the DHW aquastat (zone #1), The “T-STAT CALL” LED illuminates for Zone #1 and the “VALVE OPEN” LED will illuminate. (When using a DHW pump, a jumper must be installed on Zone #1 end switch terminals.)
• If any other zone was calling (Zones 2 thru
6) when Zone #1 called, power (24 VAC) is dropped to those zones.
• The XX and DHW contacts close.
• The PRIORITY PUMP and SYSTEM PUMP contacts deliver 120 VAC
• The SEC PUMP is off.
• Once the Zone #1 DHW demand is satisfied, power to the PRIORITY PUMP and SYSTEM PUMP is dropped, the DHW contacts open.
• If a demand from zones 2 thru 6 is present, 24 VAC is delivered to the corresponding zone valve(s) and the “T-STAT CALL” LED’s illuminate.
• When the zone valve end switch closes, the “VALVE OPEN” LED illuminates, the XX contacts close, the SEC PUMP and SYSTEM PUMP terminals deliver 120 VAC.
DHW Time Out \ Freeze Prevention Feature
• After one hour of a priority demand, the control will open the DHW contacts and turn off power to the DHW pump and Zone Valve #1.
• If a heating demand is present from Zones #2- 6, the control will satisfy those demands before going back to the DHW call.
• After the heating demands are met, the control will go back to DHW and re-set the one hour timer.
39
Page 48
6 Zone
ZVR106
T-STAT 2
CRW
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
CRW
T T COM
T-STAT 1
CRW
T T COM
L
POWER IN
N
T-STAT 4
CRW
T T COM
T-STAT 5
CRW
T T COM
T-STAT 6
CRW
T T COM
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
L
PRIORITY
PUMP
N
L
SEC PUMP
N
STATUS DURING
PRIORITY
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
ON OFF
L
SYSTEM
PUMP
N
MASTER SLAVE
6 Zone
ZVR106
T-STAT 2
CRW
T T COM
COMMS
D
P
DHW
ZR/ZC
X X
T-STAT 3
CRW
T T COM
T-STAT 1
CRW
T T COM
L
POWER IN
N
T-STAT 4
CRW
T T COM
T-STAT 5
CRW
T T COM
T-STAT 6
CRW
T T COM
PWR
TSAT1 ZONE1
TSAT2 ZONE2
TSAT3 ZONE3
TSAT4 ZONE4
TSAT5 ZONE5
TSAT6 ZONE6
L
PRIORITY
PUMP
N
L
SEC PUMP
N
STATUS DURING
PRIORITY
ZONE 1
END
SWITCH
MOTOR
PRIORITY
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
ON OFF
ON OFF
L
SYSTEM
PUMP
N
MASTER SLAVE
L
N
"A"!
pump
SYSTEM!
pump
A4A3A2 A5 A6
"B"!
pump
SYSTEM!
pump
"A"!
pump
"B"!
pump
A1
A10A9A8 A11 A12A7
A4A3A2 A5 A6A1
A10A9A8 A11A12A7
L
N
C7 - Mod/Con boiler, hydro separator, zone valves (more than 6), multiple secondary pumps
40
Hydronic diagram is for illustration purposes only, some components have been removed for simplicity.
Page 49
Description of terminals
Sequence of Operation / Settings
= Ground
N = Neutral (common leg of 120 VAC)
L = Line (live leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
Boiler terminals
XX = Dry contacts rated up to 120 VAC, 2 Amps. Closes when any zone calls including priority. Typically connected to TT on boiler control.
DHW (ZR/ZC) = Dry contacts rated up to 120 VAC, 2 Amps. Closes only when priority is enabled and calling. Typically used to close ZR\ZC (120 VAC) or DHW contacts (24 VAC) on boiler controls equipped with these features.
Pump terminals
SYSTEM PUMP = Runs when any zone calls for heat. When priority is enabled, the status of the pump (on\off) during a priority call is selected via a jumper
SEC PUMP = Runs when any zone calls for heat except the priority zone when it is enabled.
PRIORITY PUMP = Runs when the priority zone calls. A jumper is required between the END SWITCH terminals when using a pump.
Valve terminals
Motor = 24 VAC to power the zone valve motor End Switch = Connects to end switch on zone
valve. Must be jumpered if using a 2 –wire zone valve.
Control #1 (Master)
Priority Jumper: OFF
Master/Slave Jumper: Master
Status During Priority: OFF
Control #2 (Slave)
Priority Jumper: OFF
Master/Slave Jumper: Slave
Status During Priority: OFF
• A demand occurs from a T-stat (T-stat closes TT terminals) in zones 1 thru 12. The “T-STAT CALL” LED illuminates for that zone.
• ZVR control sends 24 VAC to the corresponding zone MOTOR terminals to open the zone valve.
• When the end switch on the zone valve closes, the control sends 120 VAC to SYSTEM PUMP and to the SEC PUMP located on the ZVR control that is seeing the demand. The “VALVE OPEN” LED illuminates for that zone and the XX contacts close to signal a heat demand to the boiler.
NOTE: The SEC PUMP output is only fired on the control that receives the t-stat call. For instance, if a zone from control #1 calls, the SEC PUMP on control #1 fires but SEC PUMP on control #2 does not.
• When the demand from the T-stat is satisfied (T-stat opens TT terminals), both the “T-STAT CALL” and “VALVE OPEN” LED’s turn off.
• If no other zones are calling, power is turned off to the SEC PUMP and SYSTEM PUMP and the XX contacts are opened.
WARNING: NEVER CONNECT R & C DIRECTLY, this will be a direct short on the 24 VAC supply
• 24 VAC is dropped from the corresponding zone MOTOR terminals.
41
Page 50
42
Calef North America, Inc. / 3883 W Milwaukee Rd / Milwaukee, WI 53208
Tel: 414.238.2360 / Fax: 44.238.2366
www.calef.com/usa / sales@calef.com
©Copyright 2014 Calef North America, Inc
Loading...