The SATK22 HIU allows independent control of heat regulation
and domestic hot water production within centralised heating
systems or systems served by district heating networks.
The heat interface unit features exceptional flexibility of
installation and remote controllable smart electronic functions
designed to enhance efficiency of the system.
NOTE: Due to the specification ordered, or the country of
destination, the actual unit may differ from those shown.
Content
Function1
Safety instructions1
Dimensions and connections 3
Technical specification3
Components & schematic SATK2210 & SATK22204
Components & schematic SATK2230 & SATK22405
Installation6
Heat meter installation8
Electrical connections8
Remote user interface11
Commissioning10
Remote user interface - quick guide12
Heating functions13
DHW functions15
Primary flow rate limitations17
Circulator - curves and settings18
Auxiliary microswitch19
Modbus20
Safety and alarms21
Electric circuit board and connections22
Maintenance23
Fault finding26
Check List27
Safety Instructions
WARNING
These instructions must be read and understood
before installing and maintaining the HIU.
CAUTION! FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN A SAFETY
HAZARD!
Product Range
SATK22103 Direct wall-mounted HIU for LOW temperature
heating. Domestic hot water capacity 50 kW
SATK22105 Direct wall-mounted HIU for LOW temperature
heating. Domestic hot water capacity 60 kW
SATK22203 Direct wall-mounted HIU for MEDIUM
temperature heating. Domestic hot water capacity 50 kW
SATK22205 Direct wall-mounted HIU for MEDIUM
temperature heating. Domestic hot water capacity 60 kW
SATK22305 Direct wall-mounted HIU for HIGH temperature
heating. Domestic hot water capacity 60 kW
SATK22403 Direct wall-mounted HIU for HIGH temperature
heating. Domestic hot water capacity 50 kW
1
1
1
1
with primary
1
1
pump
SATK22405 Direct wall-mounted HIU for HIGH temperature
heating. Domestic hot water capacity 60 kW
1
with primary
pump
1
Primary side head > 50 kPa, primary flow temperature 70˚C,
DHW 10 to 50˚C.
1 The device must be installed, commissioned and
maintained by qualified technical personnel in accordance
with national regulations and/or relevant local
requirements.
2 If the device is not installed, commissioned and maintained
correctly in accordance with the instructions provided in
this manual, it may not work correctly and may endanger
the user.
3 Flush the pipework thoroughly before installing the HIU to
remove any particles, rust, incrustations, limescale, welding
slag and any other contaminants.
The water circuits must be clean and free from debris.
4 Make sure that all connection fittings are watertight.
5 When connecting water pipes, make sure that threaded
connections are not mechanically overstressed. Over time
this may result in breakage, causing water damage and/or
personal injury.
6 Water temperatures higher than 50˚C may cause severe
burns. When installing, commissioning and maintaining the
device, take the necessary precautions so that these
temperatures will not be hazardous for people.
1
SATK22
Hightemperaturecircuit flow
Hightemperaturecircuitreturn
Mediumtemperaturecircuit flow
Mediumtemperaturecircuitreturn
Lowtemperaturecircuit flow
Lowtemperaturecircuitreturn
Domestic hotwateroutlet
Domestic cold water inlet
Primary circuit flow
Primary circuit return
7 In the case of particularly hard or impure water, there must
be suitable provision for filtering and treating the water
before it enters the device, in accordance with current
legislation. Failure to do so may result in the HIU becoming
damaged or working incorrectly.
8 Any use of the HIU other than it’s intended use is
prohibited.
9 Any coupling of the device with other system components
must be made while taking the operational characteristics
of both units into consideration.
10 An incorrect coupling could compromise the operation of
the device and/or system.
NOTE: Risk of electric shock. Live parts. Shut off the electric
supply before opening the HIU cover.
1 During installation and maintenance operations, always
avoid direct contact with live or potentially hazardous parts.
2 The device must not be exposed to dripping water or
humidity, direct sunlight, the elements, heat sources or high
intensity electromagnetic fields.
This device cannot be used in areas at risk of explosion or
fire.
3 The device must be connected to an independent bipolar
switch. If work has to be done on the device, switch off the
electric supply first. Do not use devices with automatic or
time reset, or which may be reset accidentally.
4 Use suitable automatic protection devices in compliance
with current legislation.
5 The device must always be earthed before it is connected to
the electric supply. If the device has to be removed, always
disconnect the earth connection after disconnecting the
electric supply. Check that the earth connection has been
made to the highest of standards under current legislation.
6 Electrical installation must only be carried out by a qualified
technician, in accordance with current requirements.
7 The HIU does not contain asbestos or mercury.
8 The HIU should only be used by an authorised adult.
NOTES:
1 Install water hammer arresters to compensate for any
overpressure in the domestic water circuit.
2 In the presence of hot water re-circulation or if a check valve
is fitted into the domestic cold water inlet, suitable devices
must be used to accommodate the expansion of the
medium contained within the system and the heat interface
unit.
3 All hydraulic connections must be visually checked while
pressurising the system. Vibration during transport may
cause the connections to become loose. If a fitting needs to
be tightened apply an appropriate tightening torque,
otherwise the components may become damaged.
Key to SymbolsSafety Instructions
General Information
• Please leave the manual as a reference guide for the user.
• Dispose of any packaging in an appropriate manner, most
of which can be recycled.
• In this Installation, Operation and Maintenance guide we
have endeavoured to make the information as accurate as
possible.
We cannot accept any responsibility should it be found
that in any respect the information is inaccurate or
incomplete or becomes so as a result of further
developments or changes to the products.
Protective shell cover:EPP
Density:45 kg/m
Working temperature range:3 to 90˚C
Thermal conductivity:0.04 W/mK
3
2
SATK22
85707060 60
490
75
130
245
42 28
444
514
All connections G¾B
Dimensions
Connections
Technical Specification
Medium:Water
Max. percentage of glycol30%
Max. temperature:90˚C
Max. static working pressure:Primary:10 bar
Secondary:10 bar
Domestic hot water:10 bar
Primary circuit Nominal flow rate:1.2 m
Nominal pressure loss on primary circuit:0.5 bar
Max. differential pressure:6 bar
Domestic water circuit max. flow rate:24 l/min (0.4 l/s)
Min.flow rate to activate domestic flow sensor:2.0 l/min ±0.3
3
/h
Power supply:230 V (ac)±10% 50 Hz
Max. power consumption:80 W
1Frame
2Electronic regulator
32-way modulating valve - heating
42-way modulating valve - DHW
5130 mm space for heat meter
6¼”F pressure port
7Return temperature probe
8Connection for M10 x 1 heat meter return probe
9Primary drain cock
10Differential pressure control valve
11Mesh strainer + ¼” F pressure port
12Heating flow temperature probe
13*Safety thermostat
14Secondary drain cock + mesh strainer
15Pump
16Flow meter (turbine + sensor)
17Mesh strainer
18 Heating exchanger primary drain
19DHW temperature probe
20DHW heat exchanger
21Connection for M10 x 1 heat meter flow probe
24Water hammer arrester
25Heat exchanger primary circuit air vent
*only included in SATK2210
Schematic Diagram SATK2210 and SATK2220
4
SATK22
1
2
3
4
5
6
7
8
9
10
11
131416
21
23
22
20
19
18
17
1
2
3
4
5
6
7
8
9
10
11
1213 1516
21
23
22
20
19
18
17
TA
2
V
V
V
V
V
V
3
4
7
5
6
8
9
10
11
21
13
14#
19
22
20
23
16
17
18
12*
15*
* SATK2230. only
# SATK2240. only
Components - SATK2230 (HIGH temperature)
Components - SATK2240 (HIGH temperature with pump)
Components - SATK2230 & SATK2240
Item Component
1Frame
2Electronic regulator
32-way modulating valve - heating
42-way modulating valve - DHW
5130 mm space for heat meter
6¼”F pressure port
7Return temperature probe
8Connection for M10 x 1 heat meter return probe
9Primary drain cock
10Differential pressure control valve
11Mesh strainer + ¼” F pressure port
12*¹/” connection for DPCV code 789122
13Secondary drain cock + mesh strainer
14# Pump
15*Spool piece
16Flow meter (turbine + sensor)
17Mesh strainer
18 Heating exchanger primary drain
19DHW temperature probe
20DHW heat exchanger
21Connection for M10 x 1 heat meter flow probe
22Water hammer arrester
23Heat exchanger primary circuit air vent
Schematic Diagram SATK2230 and SATK2240
*only included in SATK2230
#only included in SATK2240
5
SATK22
Installation
The SATK22 HIU is designed for installation in a sheltered domestic environment (or similar), therefore it cannot be installed or
used outdoors, i.e. in areas directly exposed to the weather. Outdoor installation may cause malfunctioning and hazards.
If the appliance is enclosed inside or between cabinets, sufficient space must be provided for routine maintenance procedures.
It is NOT recommended to place electrical devices underneath the HIU, as they may become damaged in the event of leaks
occurring at the hydraulic fittings. If this advice is not heeded, the manufacturer cannot be held responsible for any resulting
damage.
In the event of a malfunction, fault or incorrect operation, the appliance should be de-activated; contact a qualified technician for
assistance.
Before installation, it is recommended to carry out a thorough flushing of all the pipe work in order to remove any debris or
impurities that could prevent the correct operation of the HIU.
In order to facilitate these operations a manual bypass flushing valve is available (Code 789110).
NOTE:
When the first fix bracket is not used we recommend installing manual shut-off valves, especially on the connections to the primary
line, thus allowing any necessary maintenance work to be carried out without having to empty the centralised system.
Hydraulic connections - reversibility
Installation of the SATK22 heat interface unit is reversible (top down) with the exception of the LOW temperature Unit SATK2210.
Installation in the two positions is possible with or without the first fix bracket Code 789023.
Installation with Mounting Bracket
Ensure the wall is structurally suitable for mounting the HIU, follow the instruction below.
• Using the mounting bracket as a template mark the position of the holes required to secure the HIU to the wall. Ensure the
mounting bracket is horizontal.
• Hang the HIU onto the wall bracket and secure to the wall using the fixing holes provided.
• Mark the position of the hydraulic connections
Check the measurements again and based on the above connection diagram and the dimensions shown on page 3, proceed with the
installation of the following lines:
1 connection to the central system line
2 heating circuit connection
3 domestic water circuit connection
NOTE:
We recommend installing manual shut-off valves, especially on the connections to the primary lines, thus allowing any necessary
maintenance work to be carried out without having to empty the centralised system.
Before installation, it is recommended to carry out thorough flushing of all the pipes of the system in order to remove any residue or
debris that could endanger correct operation of the HIU.
In order to facilitate these operations a manual bypass flushing valve is available (code 789110).
6
SATK22
Installation with mounting bracket
Connections at the bottom
Connections at the top
Installation with mounting bracket and first fix bracket
Ensure the wall is structurally suitable for mounting the HIU, follow this instruction below.
• Using the mounting bracket as a template mark the position of the holes required to secure the HIU to the wall. Ensure the
mounting bracket is horizontal.
In order to facilitate these operations a manual bypass flushing valve is available (code 789110).
Connections at the bottom
7
SATK22
A
B
Electric supply
Connections at the top
Hydraulic connections
Based on the dimensions and connection diagram on page 3.
• Connection to the central primary heating system.
• Connect to the apartment heating system.
• Connect to the domestic hot water system (DHW).
NOTE:
When installing with the connections at
the bottom secure with safety screws as
shown.
Install the SATK22 as shown and using
sealing washers connect the HIU to the
valves on the first fix bracket.
Heat meter installation
The HIU is designed to house a compact heat meter (with
incorporated return probe) with 1” threaded connections and
length of 130 mm.
Before carrying out any maintenance, repair or part
replacement work, proceed as follows:
• Switch off the electric supply
• Remove the cover
• Close the shut-off valves
• Drain the HIU using the drain cocks provided
• Remove the spool piece (A)
• Remove the cap (B)
• Install the flow meter on the return pipe. To tighten the nuts
apply maximum tightening torque of 25 Nm, taking account
of the recommendations of the heat meter manufacturer.
• Install the flow probe in the M10 pocket (B).
Please refer to the heat meter technical data sheets for further
information.
Electrical Installation
Connecting to the electricity supply
The HIU is supplied with an electric supply cable which is not
fitted with a plug.
The appliance should be electrically connected to a 230 V (ac)
single-phase + earth mains supply using the three-wire cable
marked with the label as specified below, observing the LIVE (L)
- NEUTRAL (N) polarities and the earth connection. This line
must be connected to an On/OFF switch.
8