CALEFFI SATK20 Series, SATK20403HE, SATK20103HE, SATK20203HE, SATK20305 Instructions For Installation, Commissioning And Maintenance

...
www.caleffi.com
SATK series compact wall-mounted heat interface unit
SATK20 series
INSTRUCTIONS FOR INSTALLATION, COMMISSIONING AND MAINTENANCE
Function
The SATK series heat interface unit allows independent control of heat regulation and domestic hot water production within centralised heating systems.
CONTENTS
78165.02 EN
Safety instructions
Dimensions Technical specifications
Commissioning
Electronic regulator
Safety and alarms
SATK20103HE SATK20203HE
SATK20303/SATK20403HE SATK20305
2
3
4
4
6
7
8
10
Product range
SATK20103HE Direct wall-mounted HIU for LOW temperature
heating, instantaneous domestic hot water production, power capacity 40 kW
SATK20203HE Direct wall-mounted HIU for MEDIUM temperature
heating, instantaneous domestic hot water production, power capacity 40 kW
SATK20303 Direct wall-mounted HIU for HIGH temperature
heating, instantaneous domestic hot water production, power capacity 40 kW
SATK20403HE Direct wall-mounted HIU for HIGH temperature
heating, instantaneous domestic hot water production, power capacity 40 kW. With pump on the primary side.
SATK20305 Direct wall-mounted HIU for HIGH temperature
heating, instantaneous domestic hot water production, power capacity 65 kW
Maintenance
Electric connections
Troubleshooting
Commissioning checklist
1
12
13
14
16
SAFETY INSTRUCTIONS
Primary circuit flow
Primary circuit return
Domestic hot water outlet
Domestic cold water inlet
Low temperature circuit flow
Low temperature circuit return
Medium temperature circuit flow
Medium temperature circuit return
High temperature circuit flow
High temperature circuit return
WARNINGS
1 The device must be installed, commissioned and maintained by qualified technical personnel in accordance with national regulations and/or relevant local
requirements.
2 If the device is not installed, pre-run checked and maintained correctly in accordance with the instructions provided in this manual, it may not work properly and
may endanger the user. 3 Clean the pipes of any particles, rust, incrustations, limescale, welding slag and any other contaminants. The hydraulic circuit must be clean. 4 Make sure that all connection fittings are watertight. 5 When connecting water pipes, make sure that threaded connections are not mechanically overstressed. Over time this may result in breakage, causing water
damage and/or personal injury. 6 Water temperatures higher than 50°C may cause severe burns. When installing, commissioning and maintaining the device, take the necessary precautions so
that these temperatures will not be hazardous for people. 7 In the case of particularly hard or impure water, there must be suitable provision for filtering and
current legislation. Otherwise the device may be damaged and will not work properly. 8 Any use of the device other than its intended use is prohibited. 9 Any coupling of the device with other system components must be made while taking the operational characteristics of both units into consideration. 10 An incorrect coupling could compromise the operation of the device and/or system.
IMPORTANT: Risk of electric shock. Live parts. Shut off the electric supply before opening the device box. 1 During installation and maintenance operations, always avoid direct contact with live or potentially hazardous parts. 2 The device must not be exposed to water drops or humidity, direct sunlight, the elements, heat sources or high intensity electromagnetic fields. This device cannot
be used in areas at risk of explosion or fire. 3 The device must be connected to an independent bipolar switch. If work has
automatic or time reset, or which may be reset accidentally. 4 Use suitable automatic protection devices in accordance with the electrical characteristics of the region where the device is installed and in compliance with current
legislation. 5 The device must always be earthed before it is connected to the electric supply. If the device has to be removed, always disconnect the earth connection after
disconnecting the electric supply conductors. Check that the earth connection has been made to the highest of standards under applicable legislation. 6 Electrical installation must only be carried out by a qualified technician, in accordance with legal requirements. 7 The device does not contain asbestos nor mercury.
These instructions must be read and understood before installing and maintaining the device. IMPORTANT! FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN A SAFETY HAZARD!
treating the water before it enters the device,
to be done on the device, cut off
the electric supply first. Do not use devices with
in accordance with
Key to symbols
NOTES: 1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit; 2 In the presence of hot water recirculation or if a non-return valve is fitted into the domestic cold water inlet, provision must be made to accomodate the expansion
of the water contained within the system and the heat interface unit.
3 All hydraulic connections must be checked before pressurising the system. Vibration during transport may cause the connections to become loose. DO NOT APPLY
EXCESSIVE TIGHTENING TORQUE otherwise the components may be damaged.
For the updated version of the technical documentation refer to www.caleffi.com
LEAVE THIS MANUAL AS A REFERENCE GUIDE FOR THE USER. DISPOSE OF IN ACCORDANCE WITH LOCAL REGULATIONS. THE MANUFACTURER RESERVES THE RIGHT TO CEASE PRODUCTION AT ANY TIME AND TO MAKE ANY CHANGES DEEMED USEFUL OR NECESSARY WITHOUT THE OBLIGATION OF PRIOR NOTICE.
2
Dimensions
SATK20305
SATK20103/203/303/403
10
450
65182,5
15490
550,5
49
65 101
65
265
430
10
450
65182,5
15490
550,5
49
65 207
65
430
A B C
3/4” M 1/2” M 3/4” F
SATK20103HE - SATK20203HE SATK20303 SATK20403HE technical specifications
Medium: water Maximum percentage of glycol: 30% Maximum medium temperature: 85°C
Maximum working pressure: - primary circuit: 1 MPa (10 bar)
Nominal DHW exchanger capacity: 40 kW Maximum recommended primary circuit flow rate: 1,2 m Maximum DHW circuit flow rate: 18 l/min (0,3 l/s) Minimum flow to activate domestic water flow meter: 2,7 l/min ±0,3 Maximum Dp on domestic water modulating valve: 90 kPa (0,9 bar) Maximum Dp on mixing valve: 90 kPa (0,9 bar)
Electric supply: 230 V (ac) ±10% 50 Hz Maximum power consumption: 80 W
Protection class: IP 40 Pump (not present on SATK20303): UPM3 15-70 Pump by-pass pressure setting: 45 kPa (0.45 bar) Actuators: stepper 24 V
Probes: NTC 10 kΩ
Safety thermostat (only on SATK20103HE): 55°C ±3
Materials
Components: brass EN 12165 CW617N Fitting pipes: steel Frame: RAL 9010 painted steel Protective shell cover: EPP Heat exchanger: brazed stainless steel
- domestic circuit: 1 MPa (10 bar)
3
20 W on SATK20303
SATK20305 technical specifications
Medium: water Maximum percentage of glycol: 30% Maximum medium temperature: 85°C
Maximum working pressure: - primary circuit: 1 MPa (10 bar)
- domestic circuit: 1 MPa (10 bar)
Nominal DHW exchanger capacity: 65 kW
/h
Maximum recommended primary circuit flow rate: 1,2 m
3
/h Maximum DHW circuit flow rate: 27 l/min (0,45 l/s) Minimum flow to activate domestic water flow meter: 2,7 l/min ±0,3 Maximum Dp on domestic water modulating valve: 90 kPa (0,9 bar) Maximum Dp on mixing valve: 90 kPa (0,9 bar)
Electric supply: 230 V (ac) ±10% 50 Hz Maximum power consumption: 20 W Protection class: IP 40 Actuators: stepper 24 V
Probes: NTC 10 kΩ
Materials
Components: brass EN 12165 CW617N Fitting pipes: steel Frame: RAL 9010 painted steel Protective shell cover: EPP Heat exchanger: brazed stainless steel
3
Installation
Raumthermostat
(Potenzialfreier Kontakt)
Sonde d’ambiance
(Contact sec)
Termostato de ambiente (Contacto sin potencial)
Ruimtesensor
(Schoon contact)
WARN IN G!
DO NOT CONNECT EXTERNAL
VOLTAGE SUPPLY TO THESE
TERMINALS
ATT EN ZI ON E!
NON ALIMENTARE IN TENSIONE
Termostato ambiente
(Contatto pulito)
Room thermostat
(Volt free connection)
Connection to the chrono-thermostat
The SATK series HIU is designed for installation in a sheltered domestic environment (or similar), therefore cannot be installed or used outdoors, i.e. in areas directly exposed to atmospheric agents. Outdoor installation may cause malfunctioning and hazards. If the device is enclosed inside or between cabinets, sufficient space must be provided for routine maintenance procedures. It is advisable to avoid positioning electrical devices under the HIU to avoid the risk of damage in the event of leaks from hydraulic fittings. If this advice is not heeded, the manufacturer cannot be held responsible for any resulting damage. In the event of a malfunction, fault or incorrect operation, the device should be deactivated; contact a qualified technician for assistance.
Preparation
After having established the point where the device has to be installed, perform the following operations:
· Mark the holes required for securing the HIU to the wall
· Mark the position of the hydraulic connections Check the measurements again and begin laying the following lines:
Hydraulic (see page 5):
1. connection to the central system line
2. heating circuit connection
3. domestic water circuit connection
Electric (see page 13):
1. 230 V (ac) – 50 Hz electric supply line
2. chrono-thermostat/thermostat line (potential-free)
3. centralised bus line for heat meter data transmission (if required)
4. centralised electric supply line for heat meter (if required)
Before installation, it is recommended to carry out accurate flushing of all the pipes of the system in order to remove any residue or impurities that could endanger correct operation of the HIU. Fix the HIU to the wall.
N.B.: the wall anchors (not supplied) can only guarantee effective support if inserted correctly (in accordance with good technical practice) into walls built using solid or semi-solid bricks. If working with walls built using perforated bricks or blocks, mobile dividing panels or any masonry walls other than those indicated, a preliminary static test must be carried out on the support system.
Electric connections
Make sure that the electrical system can withstand the maximum power consumption of the appliance, with particular emphasis on the cross-section of the cables. If you have any doubts, contact a qualified technician to request a thorough check of the electrical system. Electrical safety of the appliance is only achieved when it is correctly connected to an effective earthing system, made as specified in current safety regulations. This is a compulsory safety requirement.
The SATK series HIU is fitted for connection to a thermostat or chrono-thermostat, both standard and OpenTherm, for ambient temperature adjustment. The connection to this device (potential-free contact) must be made with the two-wire cable marked with the label shown below. Should it be necessary to extend this cable, use one with the same cross-section (max 1 mm
2
) and maximum length 30 m.
Commissioning
Filling the central heating system
Open the shut-off valves on the connections to the centralised line and, in the central heating system, proceed with charging the system to the design pressure. Once these procedures are complete, vent the system and check its pressure again (repeat the filling process if necessary)
System start-up
Before starting the HIU, visually check the hydraulic connection water-tightness and the electric wiring. After finishing the check, activate the electric supply to the HIU and check for the presence of any error signals. If there are any, eliminate the fault indicated and proceed as described below, setting the set point of the domestic water and heating cycles, programming the thermostat/chrono-thermostat according to the desired temperatures and times, and checking the operating cycles.
Fitting the cover
Place the casing over the frame, inserting the upper tabs (1) into the corresponding slots (2). Place the lower part of the casing over the frame. Tighten the screws (3).
2
1
Connection to the main supply
The device is supplied with an electric supply cable which is not fitted with a plug. The device should be electrically connected to a 230 V (ac) single­phase + earth mains supply using the three-wire cable marked with the label shown alongside, observing the LIVE (L) - NEUTRAL (N) polarities and the earth connection. This line must be connected to a circuit breaker device.
3
4
Heat meter installation
The HIU is designed to fit a compact heat meter (with incorporated return probe) with 1” threaded connections and 130 mm gauge. Before carrying out any maintenance, repair or part replacement work, proceed as follows:
- cut off the electric supply
- remove the cover
- close the shut-off valves
- empty the HIU using the drain cocks provided Proceed as described below to install the heat meter:
- remove the template (A)
- remove the cap (B)
- install the flow meter on the return pipe
- install the flow probe in the M10 pocket (B)
Please refer to the heat meter technical data sheets for further information.
Hydraulic connections
Hydraulic connections to the centralised line must be implemented using the manual shut-off valves supplied with the HIU, which allow any necessary maintenance work to take place without having to empty the centralised system. It is advisable to install manual shut-off valves (not supplied) also on the bottom connections to the apartment circuits. Before installation, it is recommended to carry out accurate flushing of all the pipes of the system in order to remove any residue or impurities that could endanger correct operation of the HIU. In order to facilitate these operations a manual bypass flushing valve is available (code 789100).
B
A
N.B. Install the valves as shown in the figure
N.B.:
1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit; 2 In the presence of hot water recirculation or if a non-return valve is fitted into the domestic cold water inlet, provision must be made to accomodate the expansion
of the water contained within the system and the heat interface unit;
3 All hydraulic connections must be checked before pressurising the system. Vibration during transport may cause the connections to become loose. DO NOT APPLY
EXCESSIVE TIGHTENING TORQUE otherwise the components may be damaged.
5
60
60
48
48
Electronic regulator
123456
Operating principle
All heating and domestic hot water functions offered by SATK20 series HIUs are controlled by a digital controller. The controller is factory set with different parameters and settings depending on the model (Table 1). There are a number of specific DIP SWITCHES on the controller circuit board; the way these are configured will determine the settings of the various models and the optional functions enabled.
• Trimmers for set point settings
These allow setting of the temperature set point for the heating and domestic water cycle (on low and medium temperature models) and view the associated set value on the display.
Heating cycle
Domestic cycle
• LCD display
Allows viewing of heating and domestic hot water set point temperatures and the error codes.
Stand-by:
The following alternate every 5 seconds on the display:
Heating temperature set point (the return temperature is displayed if temperature regulation with compensated set point regulation is active, see page 9)
Domestic hot water temperature set point
User interface
The user interface, built into the PCB, consists of the following devices:
• LED indicator
The various functions and faults are signalled by either flashing or steady illumination of the LEDs.
ON - Electric supply 230 V (ac) DHW - Domestic cycle CH - Heating cycle FAULT - Fault detected
• RESET key
This allows restoration of normal function after the safety thermostat has been triggered and activation/deactivation of the floor slab heating function.
Table 1 – factory default settings
CODE
SATK20103HE
LOW temperature
6 5 4 3 2 1
see page
13
SWITCH SETTING SET POINT
Heating cycle ON:
The set point temperature is shown while the symbol flashes: (the return temperature is displayed if temperature regulation with compensated set point regulation is active, see page 9)
Domestic cycle ON:
The set point temperature is shown while the
symbol flashes:
HEATING DHW
25 – 45°C 42 – 60°C
SATK20203HE
MEDIUM temperature
SATK20303 / 20403HE / 20305
HIGH temperature
OFF
ON
OFF
ON
Factory set (do not change)
May be changed to activate optional functions Switch 1: modulating temperature regulation with compensated set point Switch 5: domestic hot water pre-heating function
45 – 75°C 42 – 60°C
- 42 – 60°C
6
Safety and alarms
69
76
5
6
79
80
Error codes associated with faults signalled by illumination of the FAULT LED are also shown on the display.
Probe fault
If a temperature probe fails, the associated cycle will be stopped immediately and disabled. Any requests to run cycles not associated to the previous one will continue to run normally.
Heating probe fault Error code: 5
Domestic hot water probe fault Error code: 6
Thermal safety valve fault SATK20103HE - LOW temperature Error code 76
Removing a fault
Normal operating conditions are restored automatically once the faulty safety valve is working properly again.
Incorrect switch setting Error code 79
Removing a fault
Restore correct switch setting according to table 1 (page 6).
Compensation probe fault SATK20103HE - SATK20203HE Error code: 15
Removing a fault
Normal operating conditions are restored automatically once the faulty probe is working properly again (see page 12).
Safety thermostat cut-out SATK20103HE - LOW temperature Error code 69
The HIUs configured to support low temperature heating continuously monitor the safety thermostat controlling the flow temperature. If the safety thermostat is activated during a general cycle, the heating circulation pump immediately comes to a stop and the modulating/mixing valve is completely closed. The thermal safety lock valve (SATK20103HE) is closed. In the event of a power failure, the thermal safety valve prevents hot water from entering the heating system. After the user has reset the block imposed by the safety thermostat, the shut-off valve can only be re-enabled when the mixing/modulating valves are completely closed again. This means that if a domestic water cycle is in progress, the activation of the shut-off valve will be postponed until the end of that domestic water cycle.
Removing a fault
To restore the operating mode press the manual RESET button.
Incorrect dip-switch configuration (heat interface unit disabled) Error code 80
Removing a fault
The heat interface unit is disabled due to incorrect setting of the dip-switches. Restore correct setting according to table 1 (page 6).
Automatic controller functions
Reset mixing/modulating valve to zero
Immediately after the power supply has been switched on, the position of the installed mixing/modulating valves is reset to zero.
Pump anti-clog
When the pump is not in use, it is powered on for a period of 5 seconds every 24 hours.
Mixing valve/modulating valve anti-clog
The anti-clogging cycle for the mixing/modulating valve is run every 24 hours.
7
2
1
3
4
7
5
6
9
14
10
12
11
13
15
17
8
10
16
18
1
23
4564
ON
SATK20103HE LOW temperature heat interface unit with high efficiency pump
2
1
3
4
5
7
12
8
9
11
13
15
6
14
16
10
1
23
4564
ON
Characteristic components
1. Frame
2. Electronic regulator
3. Thermal safety relief valve
4. Heating mixing valve
5. DHW production modulating valve
6. Heating flow temperature probe
7. Thermal safety thermostat
8. DHW temperature probe
9. DHW heat exchanger
10. Drain cock
11. Flow temp. compensation return probe
12. Pump UPM3 15-70
13. DHW priority flow meter
14. Protective pump by-pass
15. Heat meter spacer template
16. Air vent cock
17. System strainer/heat meter flow probe pocket
18. Primary circuit shut-off valves
Functional characteristics
Heating range 25–45°C Set point regulation
DHW production range 42–60°C
Optional functions
Domestic cycle: - DHW pre-heating function
Heating cycle: - modulating temperature regulation
with compensated set point
- floor slab heating function
Factory settings
*
* see page 13
SATK20203HE MEDIUM temperature heat interface unit with high efficiency pump
Characteristic components
1. Frame
2. Electronic regulator
3. Heating mixing valve
4. DHW production modulating valve
5. Heating flow temperature probe
6. DHW temperature probe
7. DHW heat exchanger
8. Drain cock
9. Flow temp. compensation return probe
10. Pump UPM3 15-70
11. Protective pump by-pass
12. DHW priority flow meter
13. Heat meter spacer template
14. Air vent cock
15. System strainer/heat meter flow probe pocket
16. Primary circuit shut-off valves
Functional characteristics
Heating range 45–75°C Set point regulation
DHW production range 42–60°C
Optional functions
Domestic cycle: - DHW pre-heating function Heating cycle: - modulating temperature regulation
with compensated set point
Factory settings
8
5
ON
1
OFF
Operating cycles
48
60
25
48
60
Domestic water cycle This cycle always takes priority over the heating cycle
When DHW cycle activation is requested due to DHW tapping by the user detected by the domestic water flow meter, the regulator controls the opening of the modulating valve in order to adjust the temperature detected by the domestic water probe to the selected set point value. When tapping ends, the modulating valve is fully closed. The active domestic hot water cycle is signalled by yellow DHW LED steady on. The domestic hot water cycle temperature set point can be set using trimmer P1 and shown on the display.
Heating cycle Set point regulation
When heating cycle activation is requested by the room thermostat, the circulation pump is powered while the mixing valve is activated gradually until the set point temperature is reached. At the end of the heating cycle, the circulation pump comes to a stop and the valve is closed. The active heating cycle is signalled by yellow CH LED steady on. The heating cycle temperature set point can be set using trimmer P2 and shown on the display.
Floor slab heating function - SATK20103HE
Facilitates the installation of underfloor heating systems at low temperatures. This function can only be activated and executed if there are no faults. It can be activated by pressing and holding the RESET button for 8 seconds. The yellow CH LED blinks while the floor slab heating function is in operation. The function lasts 240 hours and is carried out by simulating a request to run in heating mode starting from a set point of 25°C and rising in regular intervals to a temperature of 45°C. Once the maximum set point has been reached, the function is executed, following the same procedures, in reverse (from the maximum set point to the minimum set point). This function has priority over heating and hot water cycles, and can be suspended at any time by pressing and holding the RESET button for 8 seconds.
8 seconds
Optional functions (to activate/deactivate the optional functions
the electric power supply must always be turned off!)
Domestic cycle DHW pre-heating function
The function is enabled by setting dip switch 5 to the ON position. During periods when the domestic water cycle is not used, if the DHW probe detects a temperature 10°C below the SET value, the controller partially opens the domestic hot water modulating valve for the time required (max. 5 min.) to bring the exchanger to the condition wherein it can assure rapid DHW production. The domestic hot water pre-heating function is signalled by the flashing yellow DHW LED. This function is less of a priority than any domestic water or heating cycles.
Heating cycle Modulating temperature regulation with compensated set point SATK20103HE - SATK20203HE
The function is enabled by setting dip switch 1 to the OFF position. When the function is enabled, the flow temperature is modified according to the temperature detected by the compensation probe (located on the user return pipe). This allows constant monitoring of the effective thermal output of the floor slab with the consequent minimisation of system response times. If the function is enabled the display shows the return temperature, and the flow temperature is adjusted in accordance with the following formula:
D
Flow temperature = Return temperature +
In MEDIUM/HIGH temperature configuration: DT 8–22°C In LOW temperature configuration: DT 2–8°C
T
9
1
2
3
4
5
13
12
11
10
9
7
6
8
1
23
4564
ON
1
2
3
4
5
12
11
10
9
8
7
6
1
23
4564
ON
SATK20303 HIGH temperature heat interface unit
SATK20403HE HIGH temperature heat interface unit with high efficiency pump on the primary side
Characteristic components
1. Frame
2. Electronic regulator
3. Heating ON/OFF valve
4. DHW production modulating valve
5. Drain cock
6. DHW temperature probe
7. DHW heat exchanger
8. DHW priority flow meter
9. Pump (SATK20403HE only) UPM3 15-70 with protective by-pass
10. Heat meter spacer template
11. System strainer/heat meter flow probe pocket
12. Air vent cock
13. Primary circuit shut-off valves
Functional characteristics
Maximum heating temp. 85°C ON/OFF regulation
DHW production range 42–60°C
Optional functions
Domestic cycle: - DHW pre-heating function
Factory settings
SATK20305 High capacity HIGH temperature heat interface unit
Characteristic components
1. Frame
2. Electronic regulator
3. Heating ON/OFF valve
4. DHW production modulating valve
5. Drain cock
6. DHW temperature probe
7. DHW heat exchanger
8. DHW priority flow meter
9. Heat meter spacer template
10. Air vent cock
11. System strainer/heat meter flow probe pocket
12. Primary circuit shut-off valves
Functional characteristics
Maximum heating temp. 85°C ON/OFF regulation
DHW production range 42–60°C
Optional functions
Domestic cycle: - DHW pre-heating function
Factory settings
10
Operating cycles
48
––
48
5
ON
Domestic water cycle This cycle always takes priority over the heating cycle.
When DHW cycle activation is requested due to DHW tapping by the user detected by the domestic water flow meter, the regulator controls the opening of the modulating valve in order to adjust the temperature detected by the domestic water probe to the selected set point value. When tapping ends, the modulating valve is fully closed. The active domestic hot water cycle is signalled by yellow DHW LED steady on. The general domestic water cycle temperature set point can be set using trimmer P1 and shown on the display.
Heating cycle ON-OFF regulation
When the room thermostat requests the start of a heating cycle, the valve is opened completely, allowing water to circulate at the temperature supplied by the central heating system (ON/OFF regulation). The valve is closed on completion of the heating cycle. The active heating cycle is signalled by lighting of the yellow CH LED. No value is shown on the display.
Optional functions (to activate/deactivate the optional functions the electric power supply must always be turned off!)
Domestic cycle DHW pre-heating function
The function is enabled by setting dip switch 5 to the ON position. During periods when the domestic water cycle is not used, if the DHW probe detects a temperature 10°C below the SET value, the controller partially opens the domestic hot water modulating valve for the time required (max. 5 minutes) to bring the exchanger to the condition wherein it can assure rapid DHW production. The domestic hot water pre-heating function is signalled by the flashing yellow DHW LED. This function is less of a priority than any domestic water or heating cycles.
11
Maintenance
All maintenance procedures should be carried out by an authorised technician. Regular maintenance guarantees better efficiency and helps to save energy. Before carrying out any maintenance, repair or part replacement work, proceed as follows:
- Cut off the electric supply
- Remove the cover
- Close the shut-off valves
- Empty the heat interface unit using the drain cocks provided.
Replacing the valve actuator
- Disconnect the actuator cable, lightly pressing the tab on the connector and extracting it (see page 13, ref. 4-8)
- Extract the fixing clip (D) and then the actuator
- Position the new actuator (E)
- Insert the fixing clip, respecting the correct direction
- Reconnect the connector.
D
Heat exchanger replacement
- Remove the heat exchanger, loosening the 2 hex socket head screws fixing it in place (A)
- Replace the heat exchanger and the O-Rings.
- Tighten the two fixing screws (A).
N.B. The pins fixing the heat exchanger are positioned in such a way as to allow it to be placed only in the correct direction.
A
Strainer cleaning
All heat interface units have a strainer on the inlet for water from the centralised system. To clean these strainers, carry out the following maintenance procedure:
- Unscrew the cap (B)
- Remove the strainer mesh and discard any impurities
- Put the strainer mesh back in
- Screw the cap back on.
A
E
Replacing the valve obturator
- Disconnect the valve actuator (see previous paragraph)
- Extract the obturator, unscrewing the locking nut (F)
- Replace the obturator, screw on the locking nut (F) and then insert the actuator
- Insert the fixing clip, respecting the correct direction
- Reconnect the connector.
F
Replacing the DHW priority flow meter
- Disconnect the flow meter cable acting on the connector (see page 13, ref. 2)
- Extract the flow sensor (G)
- Position the new sensor
- Reconnect the connector respecting the only possible way it can be inserted.
B
Temperature probe replacement
- Disconnect the probe cable, lightly folding the tab (C) and extracting the connector (see page 13, ref. 1-3-7)
- Unscrew the probe
- Fit the new probe
- Reconnect the connector respecting the only possible way it can be inserted.
C
G
Replacing or cleaning the priority flow meter turbine and strainer
- Extract the flow sensor (G)
- Unscrew and remove the cartridge (H)
- Eliminate any impurities on the strainer mesh and, if necessary, change the cartridge
- Screw the cartridge back into place
- Refit the flow sensor.
H
When carrying out maintenance on the electrical part, for the connections follow the diagram on page 13. After concluding maintenance, proceed with the filling and checking operations described in the chapter “Commissioning” and fit the cover. If you require any information regarding spare parts, please contact Caleffi spa.
12
Electric connections
FUSE 5x20
1
2 3
4
6
5
9
10
13
11
12
6 35
4 21
14
s5SARESOLOPERCOLLEGAMENTOACOD
s5SETHISWIREFORCONNECTIONTOCODEONLY
s°NgUTILISERQUEPOURLALIAISONAVECCODE
s6ERWENDEN3IEDIESES'ERËTNURZUM!NSCHLUSS
ANDIE!RT.R
s'EBRUIKDEZEENKELVOORAANSLUITINGOPCODE
s5TILICESOLAMENTEPARALACONEXIØNCONCØD
s5SARESOLOPERCOLLEGAMENTOACOD
s5SETHISWIREFORCONNECTIONTOCODEONLY
s°NgUTILISERQUEPOURLALIAISONAVECCODE
s6ERWENDEN3IEDIESES'ERËTNURZUM!NSCHLUSS
ANDIE!RT.R
s'EBRUIKDEZEENKELVOORAANSLUITINGOPCODE
s5TILICESOLAMENTEPARALACONEXIØNCONCØD
7
8
Raumthermostat
(Potenzialfreier Kontakt)
Sonde d’ambiance
(Contact sec)
Termostato de ambiente (Contacto sin potencial)
Ruimtesensor
(Schoon contact)
Termostato ambiente
(Contatto pulito)
Room thermostat
(Volt free connection)
6
ON
6
ON
1
2
3
4
5
6
7
8
9
10
11
12
13
14
DHW temperature probe
DHW priority flow meter
Flow temp. compensation return probe
DHW production valve actuator
Thermal safety thermostat
Thermal safety valve
Heating flow temperature probe
Heating valve actuator
Earth
Pump
Electric supply 230V (ac)**
Room thermostat**
Fuse
HIU enabling
SATK20303
SATK20305
SATK20203HE
SATK20103HE
SATK20403HE
xxxx xxxx xx xxxx x x xx xxxx xxxx xx x xxxx xxxx xxxx
*xxx
N.B.:
The pump cable connector is polarised. Insert the connector correctly and do not attempt to force it in the wrong position.
* This connection may not be available ** To be wired during installation (Room thermostat not supplied)
Dip-switch 6 configuration
If the regulator is equipped with the “HIU enabling” cable (refer to line 14 in the above table), dip-switch 6 must be set to OFF
Vice versa, if this connection is absent, the dip-switch must be set to ON.
MAX 30 m
(potential-free line)
13
Troubleshooting
FAULT DESCRIPTION INDICATIONS POSSIBLE CAUSE OF FAULT OPERATIONS TO BE PERFORMED
primary circuit shut-off valves closed open the valves
modulating valve actuator connector disconnected reconnect actuator connector
modulating valve actuator disconnected from valve body reconnect actuator
call qualified personnel to have it
replaced
restore correct connection
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
serviced
call qualified personnel to have it
serviced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
restore correct connection
call qualified personnel to have it
replaced
restore correct connection
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
call qualified personnel to have it
serviced
open the valves
call qualified personnel to have it
serviced
call qualified personnel to have it
serviced
call qualified personnel to have it
serviced
call qualified personnel to have it
serviced
Water is not
heated
The water is hot
but does not
reach the
desired
temperature
Hot water
temperature is
too high
Hot water flow
rate is
insufficient
Hot water flow
rate is zero
DHW LED on
FAULT LED on + error
code 6 active
FAULT LED on + error
code 79 active
F
AULT LED on + error
code 80 active
DHW led off
all LEDs are off
DHW LED on
DHW LED on
DHW LED on
DHW LED off
modulating valve actuator faulty
DHW temperature probe cable inverted with heating
probe
presence of air in the system vent the system
electronic controller not working
valve obturator blocked in closed position
centralised system not working/cold contact person in charge of system
DHW temperature probe disconnected reconnect probe
DHW temperature probe faulty
incorrect switch setting restore correct switch setting
incorrect switch setting restore correct switch setting
DHW priority flow meter disconnected reconnect flow meter
DHW priority flow meter faulty
No electric power supply restore HIU electric supply
protection fuse burnt out
domestic water cycle temperature set point too low increase set point
Primary circuit strainer of the HIU clogged
heat exchanger partly clogged
modulating valve actuator faulty
valve obturator blocked in intermediate position
DHW temperature probe cable inverted with heating
probe
excessive demand for DHW decrease demand
electronic controller not working
centralised system temperature insufficient contact person in charge of system
primary circuit flow rate insufficient contact person in charge of system
domestic water cycle temperature set point too high decrease set point
DHW temperature probe cable inverted with heating
probe
modulating valve actuator faulty
valve obturator blocked in intermediate or open position
electronic controller not working
primary circuit excessive pressure contact person in charge of system
flow meter strainer clogged
possible domestic water system shut-off valves
partially closed
centralised domestic circuit cold water flow rate
insufficient
possible domestic water system shut-off valves closed open the valves
no cold water in centralised domestic circuit
flow meter strainer completely clogged
heat exchanger completely blocked
14
FAULT DESCRIPTION INDICATIONS POSSIBLE CAUSE OF FAULT OPERATIONS TO BE PERFORMED
heating cycle temperature set point too low increase set point
check programming of chrono-
thermostat
call qualified personnel to have it
serviced
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
restore correct connection
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
check programming of chrono-
thermostat
call qualified personnel to have it
replaced
call qualified personnel to have it
replaced
The room
is not reaching
the desired
temperature
CH LED on
CH LED off
all LEDs are off
FAULT LED on + error
code 5 active
chrono-thermostat temperature setting incorrect
HIU strainer clogged
heating valve actuator faulty
heating valve obturator blocked
modulating valve actuator connector disconnected reconnect actuator connector
DHW temperature probe cable inverted with heating
probe
presence of air in the system vent the system
pump (if present) not working
pump cable (if present) not connected restore connection
possible system shut-off valves/terminals closed open the valves
centralised system temperature insufficient contact person in charge of system
electronic controller not working
primary circuit flow rate insufficient contact person in charge of system
centralised system not working contact person in charge of system
chrono-thermostat time setting incorrect
chrono-thermostat not working check chrono-thermostat
Electric supply cut off restore HIU electric supply
Protection fuse burnt out
heating temperature probe faulty
Start-up of the
heat interface
unit heating
function triggers
the safety circuit
breaker
FAULT LED on + error
code 15 active
FAULT LED on + error
code 69 active
FAULT LED on + error
code 76 active
FAULT LED on + error
code 79 active
F
AULT LED on +
error code 80 active
All LEDs are off pump connector inserted the wrong way round
compensation temperature probe faulty
safety thermostat cut-out
safety relief valve faulty
incorrect switch setting restore correct switch setting
incorrect switch setting restore correct switch setting
call qualified personnel to have it
replaced
call qualified personnel to have it
serviced
call qualified personnel to have it
serviced
check that the pump cable connector is
inserted the right way round
15
Commissioning checklist
Model Checks to be performed
1 all Is the heat interface unit properly secured to the wall?
2 all Has the system flushing been carried out?
3 all Check strainers and clean them if necessary
4 all Is the heat meter (if present) connected?
5 all Is the heat meter (if present) connected to the building datalogger (if required)?
6 all Is the DCW line fitted with a pressure reducing valve?
7 all Is the system protected by water hammer arresters?
8 all
SATK20103HE
9
SATK20203HE
Has the domestic exchanger pre-heating function (normally off) been activated (if required)?
Has the modulating temperature regulation with compensated set point (normally off) been activated (if required)?
10 all Is the heat interface unit connected to the 230 V (ac) electric supply?
11 all Is the room thermostat (potential-free contact) connected?
Has the visual inspection of electrical connections inside the heat interface unit given
12 all
a positive result? Are the connections compliant with specifications and made in accordance with best practices?
13 all Are the shut-off valves open?
14 all Has the visual inspection of the hydraulic connections given a positive result?
15 all Has the system been filled and vented?
16 all Is the heat interface unit powered (green “ON” LED lit)?
17 all No alarm code (“fault” LED lit) on heat interface unit regulator?
18 all
SATK20103HE
19
SATK20203HE
Has the DHW temperature been set to the required value? (42–50°C recommended)
Has the heating flow temperature been set to a correct value?
20 all Is the primary circuit at working temperature?
21 all Check that “CH” LED lights approx. 10 seconds after the thermostat trips
SATK20103HE
22
SATK20203HE SATK20403HE
23 all
24 all
Check that the pump operates correctly on tripping of the thermostat (check that secondary flow pipes start to heat up)
Simulate minimal DHW tapping (approx 3 l/min) and check that “DHW” LED lights and that water is supplied at the required temperature
Simulate abundant DHW tapping and check, by means of the installed heat meter, that the primary circuit flow rate is sufficiently high
Loading...