Installation, commissioning and servicing instructions
Function
The DISCAL® air separator is used to continuously remove the air
contained in the hydronic circuits of heating and cooling systems.
The air discharge capacity of these devices is very high. They are
capable of removing automatically all the air present in the system
down to micro-bubble level.
The circulation of fully de-aerated water enables the equipment to
operate under optimum conditions, free from any noise, corrosion,
localized overheating or mechanical damage. Micro-bubbles, fusing
with each other, increase in volume (get larger) until they become
large enough to rise to the top where they are automatically
released.
This item is designed for use in closed hydronic systems. Do not use this item in plumbing applications. It does
not meet the low-lead plumbing standards of U.S. and Canada.
Product range
551 series DISCAL air separator for horizontal pipes, in brass compact with drain
Sizes ¾” integral sweat; ¾” NPT female (A without service check valve, AC with
service check)
551 series DISCAL air separator for horizontal pipes, in brass with drain
Sizes ¾” - 1” - 1 ¼” - 1 ½” - 2” NPT female; 1” - 1 ¼” - 1 ½” - 2” integral sweat
(A without service check valve, AC with service check)
551 series
Sizes
DISCAL air separator for horizontal pipes, in brass with drain
1” - 1 ¼” - 1 ½” - 2”
press (A without service check valve, AC with service check)
5517 series DISCAL air separator for horizontal or vertical pipes with rotating collar, in brass with
drain. Sizes
551 series DISCAL
¾” and 1” sweat union, press union and NPT male union
air separator for horizontal pipes, in steel with flanged connections with drain
Sizes 2” – 6” ANSI
NA551 series DISCAL air separator for horizontal pipes, in steel with flanged
connections with drain designed and built in accordance with Section
Scan to view
VIII, Division 1 of the ASME Boiler and Pressure Vessel Code and
tagged and registered with the National Board of Boiler and Pressure
Vessel Inspector, with ASME U-stamp. Sizes 2” – 12” ANSI.
Installation Tip
1
·
NA551 & 551 DISCAL
®
Technical specications
Brass air separator
Materials - body: brass
- internal element
(compact and rotating collar versions): 304 stainless steel
Suitable fluids: water, glycol solution
Max. percentage of glycol: 50%
Max. working pressure: sizes 2-6”: 150 psi (10 bar); sizes 8-12”: 200 psi (14 bar)
Temperature range: 32–270°F (0 –132°C)
Air separation efficiency: 100% to micro-bubble level
Connections - flanged: 2"– 12" ANSI B16.5 150 CLASS RF
- drain pipe: sizes 2 - 6 inch: 1" NPT male
sizes 8 - 12 inch: 2” NPT male
Agency Approval
NA551 series is designed and built in accordance with Section VIII, Division 1 of the ASME Boiler
and Pressure Vessel Code and tagged and registered with the National Board of Boiler and
Pressure Vessel Inspector, and CRN registered (12” pending, contact Caleffi).
2
Working Pressure & Temperature Limits
(Solder Type Limits Per ASTM Std. B16.18-1979)
FLOW-CONTROL
STYLE
SWEAT
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety related
instructions. When used, the safety alert symbol means.
ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO
FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
WARNING: This product can expose you to chemicals including lead, which is known
to the State of California to cause cancer and birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov.
CAUTION:
proper application, installation, and maintenance of systems in accordance
with all applicable codes and ordinances.
CAUTION: If the DISCAL valve is not installed, commissioned and
maintained properly, according to the instructions contained in this
manual, it may not operate correctly and may endanger the user.
TYPE OF
SOLDER
95-5
Tin-Antimony
50-50 tin-Lead125150
60-40 tin-Lead75250
All work must be performed by qualified personnel trained in the
MAXIMUM LIMITATIONS
PRESSURE PSI TEMPERATURE °F
150250
CAUTION: Make sure that all the connecting pipework is water tight.
CAUTION: When making the water connections, make sure that the
pipework connecting the DISCAL is not mechanically over-stressed. Over
time this could cause breakages, with consequent water losses which, in turn,
could cause harm to property and/or people.
CAUTION: Water temperatures higher than 100°F (38°C) can be dangerous.
During the installation, commissioning and maintenance of the DISCAL valve,
take the necessary precautions to ensure that such temperatures do not
endanger people.
Leave this manual for the user
3
CC
Dimensions
C
A
A
C
D
E
A
D
E
A
FF
B
CodeABCDEFWt (lb)
551003A*3⁄4" NPT31⁄16"23⁄16"53⁄8" 67⁄8"1⁄2"2.0
551022A*3⁄4" SWT 31⁄16"23⁄16"53⁄8" 67⁄8"1⁄2"2.0
* Add suffix C to sweat and NPT code number when ordering the brass
DISCAL to ship with expansion tank service check valve, code561402A.
E
B
F
B
C
1/2
”
D
CodeABCDEFWt (lb)
551705A3⁄4" NPT51⁄8"23⁄16"53⁄8" 91⁄4" 31⁄2"4.9
551765A3⁄4" press 63⁄8"23⁄16"53⁄8" 93⁄4” 31⁄2"4.9
551795A3⁄4" SWT6"23⁄16"53⁄8" 93⁄16” 31⁄2"4.9
551706A1" NPT63⁄4"23⁄16"53⁄8" 93⁄4” 31⁄2"4.9
551766A1" press63⁄4"23⁄16"53⁄8" 93⁄4” 31⁄2"4.9
551796A1" SWT7"23⁄16"53⁄8" 93⁄4” 31⁄2"4.9
551716*--33⁄4”23⁄16"53⁄8" 91⁄4" 31⁄2"4.4
* Body only, no end connection fittings. Source separately, see Caleffi
catalog for end connection code numbers.
CodeALay length
551765A3⁄4" press4 5⁄8"
551766A1" press4 3⁄4"
4