CALEFFI 5231 Series, 523168A, 523177A, 523170A, 523178A Installation And Commissioning Manual

...
Page 1
NA10341.03
ASSE 1017
www.caleffi.com
Low lead high-flow thermostatic mixing valves
© Copyright 2018 Caleffi
5231 Series
INSTALLATION AND COMMISSIONING MANUAL
Function
The thermostatic mixing valve is used in systems producing domestic hot water or in radiant heating systems. Its function is to maintain the temperature of the mixed water supplied to the user at a constant set value when there are variations in the supply pressure and temperature of the incoming hot and cold water or in the flow rate.
The 5231 series thermostatic mixing valves are ASSE 1017 approved for point of distribution and are designed specifically for systems requiring high flow rates and precise, stable temperature control. Optional stainless steel inlet port check valves are available separately, for field installation only.
Product range
5231 series thermostatic mixing valve. NPT male and sweat union connections, sizes 1", 1-1/4", 1-1/2", 2". Inlet port check valve s and outlet temperature gauge optional.
Technical characteristics Materials: - body: DZR low-lead brass (<0.25% lead content)
- shutter: PPSG40
- springs: stainless steel
- seals: peroxide-cured EPDM
- check valve extension (field installed): stainless steel
Suitable fluids: water, glycol solutions Max. percentage of glycol: 30% glycol solution Mixed temperature adjustment range: 95 – 150°F (32 – 66°C) Temperature stability: ± 3°F (± 2°C) Max. operating differential pressure (static): 200 psi (14 bar) Max. operating differential pressure (dynamic): 75 psi (5 bar) Hot water inlet temperature range: 120 – 195°F (49 – 91°C) Cold water inlet temperature range: 39 – 80°F (3.9 – 26.6°C) Max. inlet pressure ratio (H/C or C/H) for optimum performance: 2:1
Min. temp. difference between hot inlet and mixed outlet for optimum perf: 20°F (11°C) Max. water hardness: 10 grains Certified to:
1. ASSE 1017/CSA B125.3, certified by ICC-ES, file PMG-1357.
2. NSF/ANSI 372-2011, Drinking Water System Components-Lead Content Reduction of Lead in Drinking Water Act, California Health and Safety Code 116875 S.3874, Reduction of Lead in Drinking Water Act, certifed by ICC-ES, file PMG-1360.
1
Page 2
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to safety related instructions. When used, the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFET Y IS INVOLVED!
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
CAUTION: All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of systems in accordance with all applicable codes and ordinances.
CAUTION: If the thermostatic mixing valve is not installed, commissioned and maintained properly, according to the instructions contained in this manual, it may not operate correctly and may endanger the user.
CAUTION: Make sure that all the connecting pipework is water tight.
CAUTION: When making the water connections, make sure that the
pipework connecting the thermostatic mixing valve is not mechanically over-stressed. Over time this could cause breakages, with consequent water losses which, in turn, could cause harm to property and/or people.
CAUTION: Water temperatures higher than 100°F can be dangerous. During the installation, commissioning and maintenance of the thermostatic mixing valve, take the necessary precautions to ensure that such temperatures do not endanger people.
CAUTION: To prevent any damage which will cause the electronic mixing valve to not operate correctly, treat highly aggressive water before entering the thermostatic mixing valve.
Leave this manual for the user.
2
Page 3
CONSIGNE DE SÉCURITÉ
Ce symbole d'avertissement servira dans ce manuel à attirer l'attention sur la sécurité concernant instructions. Lorsqu'il est utilisé, ce symbole signifie.
ATTENTION! DEVENEZ ALERTE ! VOTRE SÉCURITÉ EST EN JEU ! NE PAS SUIVRE CES INSTRUCTIONS PEUT PROVOQUER UN RISQUE DE SECURITE.
ATTENTION: Tous les travaux doivent être effectués par du personnel
qualifié formé à la bonne application, installation et maintenance des systèmes conformément aux codes et règlements locaux.
ATTENTION: Si le réducteur de pression, termostatico regolabile, n'est pas installé, mis en service et entretenu correctement, selon les instructions contenues dans ce manuel, il peut ne pas fonctionner correctement et peut mettre en danger l'utilisateur.
ATTENTION: S'assurer que tous les raccordements sont étanches.
ATTENTION: Lorsque vous effectuez les raccordements d'eau, assurez-vous
que la tuyauterie reliant le termostatico regolabile n'est pas mécaniquement des overstressed. Au fil du temps, ceci pourrait causer des ruptures, avec pour consequence des pertes en eau qui, à leur tour, peuvent causer des dommages à la propriété et/ou les gens.
ATTENTION: Les températures de l'eau supérieure à 100°F (38°C) peut être dangereux. Au cours de l'installation, mise en service et l'entretien de le réducteur de pression, le termostatico regolabile, prendre les precautions nécessaires afin de s'assurer que de tells températures ne compromettent pas les gens.
ATTENTION: Pour prévenir tout dommage qui provoque le mitigeur électronique à ne pas fonctionner correctement, le traitement de l’eau très agressive avant d’entrer dans la vanne de le termostatico regolabile.
LAISSEZ CE MANUEL AVEC L’UTILISATEUR
3
Page 4
Operating principle
A thermostatic mixing valve mixes hot and cold water in such a way as to maintain a constant set temperature of the mixed water at the outlet. A thermostatic element is fully immersed into the mixed water. It then contracts or expands causing movement of the piston, closing either the hot or cold inlets, regulating the flow rates entering the valve. If there are variations of temperature or pressure at the inlets, the internal element automatically reacts attempting to restore the original temperature setting.
The Caleffi 5231 series mixing valves require a minimum temperature dif ferential from hot inlet to mixed water outlet of 20°F (11°C) to ensure the correct operation, and maximum pressure difference between the hot and cold inlet parts no greater than 2:1 ratio. Softened water use is highly recommended as the warranty is voided if used on water with hardness greater than 10 grains.
Control
The Caleffi 5231 series mixing valves require a minimum temperature differential from hot inlet to mixed water outlet of 20°F (11°C) to ensure the correct operation, and maximum pressure difference
COLD
HOT
between the hot and cold inlet par ts no greater than 2:1 ratio. Softened water
without inlet check valves
use is highly recommended as the warranty is voided if used on water with hardness greater than 10 grains.
COLD
with inlet check valves (field installed)
MIXED
HOT
Check valves field installed only: code NA10366 for 1” & 1¼” sizes; code NA10367 for 1½” & 2” sizes.
4
Page 5
Flow curves
6
100
p
(psi) (bar)
75
50
20
10
5 4
3
2
1
0.5
0.3
0.2
0.1
160
G
10
(l/s) (gpm)
5.0
2.0
1.0
0.5
0.4
0.3
0.2
0.1
0.05
0.04
0.03
0.02
0.01
p (ft of head)
172
115
46
23
11.5
9.2
6.9
4.6
2.3
1.15
0.92 0.4
0.69
0.46
0.23
2
.1
1” 1 1/2” 2”
5
.3
1 1/4”
10
20
1
50
1.5
3.25
Flow should never exceed standards for pipe size and material.
Size
Connection
Model
Min. Flow* (GPM)
Max.
Flow*
(GPM)
1" NPT 523160A 4.4 40 7
1" Sweat 523168A 4.4 40 7
1 ¼" NPT 523170A 4.4 40 7.6
1 ¼" Sweat w/
523177A 4.4 40 7.6
temp gauge
1¼" Sweat 523178A 4.4 40 7.6
1 ½" NPT 523180A 8.8 70 13
1 ½" Sweat 523188A 8.8 70 13
2" NPT 523190A 8.8 70 14.2
2" Sweat 523198A 8.8 70 14.2
*Recommended flow rates for temperature stabilty: ± 3°F (± 2°C).
CV
5
Page 6
Use
Caleffi 5231 series thermostatic mixing valves are designed to be installed at the hot water heater and cannot be used for tempering water temperature at fixtures as a point-of-use valve. They are not designed to provide scald protection or chill protection service and should not be used where ASSE 1070 devices are required. Wherever a scald protection feature is required, ASSE 1070 certified mixing valves need to be installed. For safety reasons, it is advisable to limit the maximum mixed water temperature to 120°F.
Instantaneous production of hot water
Caleffi 5231 series thermostatic mixing valves are designed for use on domestic water heaters that have storage. The valve may deliver fluctuating mixed temperatures when used on instantaneous domestic water heaters.
Installation
Before installing a Caleffi 5231 series thermostatic mixing valve, the system must be inspected to ensure that its operating conditions are within the range of the mixing valve, checking, for example, the supply temperature, supply pressure, etc.
Systems where the Caleffi 5231 series thermostatic mixing valve is to be installed must be drained and cleaned out to remove any dirt or debris which may have accumulated during installation.
Failure to remove dirt or debris may affect performance and the manufacturer’s product guarantee. Softened water use is highly recommended as the warranty is voided if used on water with hardness greater than 10 grains.
The installation of filters of appropriate capacity at the inlet of the water from the mains supply is always advisable.
In areas which are subject to highly aggressive water, arrangements must be made to treat the water before it enters the valve.
Caleffi 5231 series thermostatic mixing valves must be installed in accordance with the diagrams in this manual, taking into account all current applicable standards.
Caleffi 5231 series thermostatic mixing valves can be installed in any position, either vertical or horizontal.
The following are shown on the mixing valve body:
- Hot water inlet, “H”.
- Cold water inlet, “C”.
- Mixed water outlet, unmarked.
In systems with thermostatic mixing valves, check valves must be installed to prevent undesirable fluid back flow. The 5231 series valves, codes listed in this instruction sheet, do not contain integral check valves, so those must be sourced separately. Caleffi offers inlet por t check valve assemblies separately, for field installation only to 5231 series valve.
It is essential that access to the valve is totally unobstructed for any maintenance which may be required to the valve or connections. The piping from/to the valve must not be used to support the weight of the valve itself.
Scan to view
·
5231 MixCal
TM
Installation Tip
6
Page 7
Locking the setting
Position the knob at the required value, unscrew the top screw, slide off the knob and put it back in such a way that the handle fits
3
1
M
I
2
N
M
A
X
into the internal slot of the knob. Tighten the head screw
Setting the temperature
The temperature is set to the required value
.
Index Point
by means of the adjusting knob with the graduated scale on the top of the valve.
Pos. Min 1 2 3 4 5 6 7 Max
T (°F) 95 104 109 117 122 129 136 142 150 T (°C) 35 40 43 47 50 54 58 61 66
with: T
= 155°F (68°C) · T
HOT
= 55°F (13°C) · P
COLD
INLETS
= 43 psi (3 bar)
Dimensions
C
B B
A
F
A
D
HC
A
E
Sweat version
110
130
90
D
F
70
E
50
30
150
170
190
210
A
A
7
Code A B C D E F Wt (lb)
523160A 1" NPT 4" 8" 7 5/8" 4 3/16" 3 3/8" 7.0
523168A 1" SWT 3 5/16" 6 5/8" 7" 3 1/2" 3 3/8" 7.0
523170A 1 1/4" NPT 4 1/8" 8 1/4" 7 3/4" 4 5/16" 3 3/8" 7.0
523177A 1 1/4" SWT 3 3/8" 6 3/4" 7 5/8" 4 1/8" 3 3/8" 9.0
523178A 1 1/4" SWT 3 3/8" 6 3/4" 7" 3 1/2" 3 3/8" 7.0
523180A 1 1/2" NPT 5 1/8" 10 1/4" 9 3/16" 5 7/16" 3 3/4" 17
523188A 1 1/2" SWT 4 1/16" 8 1/8" 8 1/8" 4 3/8" 3 3/4" 17
523190A 2" NPT 5 1/8" 10 1/4" 9 1/2" 5 3/4" 3 3/4" 18
523198A 2" SWT 4 5/16" 8 5/8" 8 5/8" 4 7/8" 3 3/4" 18
7
Page 8
Dimensions with check valves
C
B B
F
A
D
A
HC
Sweat version
A
E
A
110
130
150
90
D
F
170
70
E
190
50
30
210
A
Code A B C D E F Wt (lb)
1" NPT 5 1/2" 10 7/8" 7 5/8" 4 3/16" 3 3/8" 9.0
1" SWT 4 3/4" 9 1/2" 7" 3 1/2" 3 3/8" 9.0
NA10366
NA10367
Dimensions for 5231 models with field installed inlet check valve assembles, code numbers listed in first column.
1 1/4" NPT 5 5/8" 11 1/8" 7 3/4" 4 5/16" 3 3/8" 9.0
1 1/4" SWT 4 3/4" 9 5/8" 7 5/8" 4 1/8" 3 3/8" 11.0
1 1/4" SWT 4 3/4" 9 5/8" 7" 3 1/2" 3 3/8" 9.0
1 1/2" NPT 7 3/8" 14 3/4" 9 3/16" 5 7/16" 3 3/4" 19
1 1/2" SWT 6 1/4" 12 5/8" 8 1/8" 4 3/8" 3 3/4" 19
2" NPT 7 3/8" 14 3/4" 9 1/2" 5 3/4" 3 3/4" 20
2" SWT 6 1/2" 13 1/8" 8 5/8" 4 7/8" 3 3/4" 20
8
Page 9
Replacement ttings
Code
52316 0A
52316 8A 1" Sweat union 31554 FD
52 3170 A 1-1/4" MNPT union R416 60
52 3178 A 1-1/4" Sweat un ion 4178 7 C ST
52 317 7A
52318 0A 1-1/2” MNPT union 41371A
52318 8A 1-1/2” Sweat union 41788 CS T
52319 0A 2” MNPT union 41372 A
52319 8A 2” Sweat union F0000496
Description
1" MNPT union
1-1/4” Sweat union
with outlet temp. gauge*
Tailpiece
all por ts (3)
NA10009
4178 7 C ST
(2 only)
Inlet Check
Valve
Assemb ly (2)**
NA1 03 66
NA1 03 67 NA10 461 R518 38 R50060
* Replacement outlet mixed temperature gauge adapter complete with outlet tailpiece, union nut and gasket, and
temperature gauge (30-210°F), code NA10315.
**Field installed only
Outlet
adapter with
Temperature
Gauge**
NA1 0476 R31589 R 50057
Union
nuts ( 3)
R31589
(2 only
- 17 7A)
Gaskets
R500 57
(2 only -
177A )
(3)
Replacement parts
Point of distribution mixed temperature gauge adaptor fits high flow 5231 series mixing valves. Removable gauge fits into temperature well. Gauge dial is 2" diameter and scale from 30—210º F. Low-lead brass body.
Code Description Lbs
NA10315 1¼" sweat with gauge 0.5
NA10476 For 1” & 1 ¼” * 3.0
NA10476 For 1 ½” & 2” * 4.0
688003A Replacement gauge with pocket well 0.2
R39591 Replacement temperature gauge 0.2
* Requires separately ordered union nut, tailpiece and union washer. See replacement fittings table above.
Inlet check valve assembly for mounting on inlet union tail pieces of 5231 mixing valves. Stainless steel body, acetal plastic check valve insert with NBR o-ring.
Code Description Open Pressure Lbs
NA10366 Check valve assembly 1” & 1¼" 0.23 psi 1 .0 NA10367 Check valve assembly 1½" & 2" 0.20 psi 1.5
5231
Replacement body. Meets requirements of ANSI/NSF 372-2011.
ASSE 1017
Code Description Min. Flow (gpm) Cv Lbs
523179 A 1½" union thread 4.4 7.6 5. 0 523199A 2½" union thread 8.8 14.2 15.0
Includes no fittings or union nuts.
Certified to: ICC-ES listed to ASSE 1017/CSA B125.3, Low lead.
9
Page 10
Commissioning
After installation, the valve must be tested and commissioned in accordance with the instructions given below, taking into account current applicable standards.
1) Ensure that the system is clean and free from any dirt or debris before commissioning the thermostatic mixing valve. Be sure water hardness is less than 10 grains.
2) It is recommended that the temperature is set using a suitable calibrated digital thermometer. The valve must be commissioned by measuring the temperature of the mixed water at the outlet.
3) The maximum outlet temperature from the valve must be set taking account of the fluctuations due to simultaneous use. It is essential for these conditions to be stabilized before commissioning.
4) Adjust the temperature using the adjusting knob on the valve. For safety reasons, it is advisable to limit the maximum mixed water temperature to 120°F in domestic hot water systems.
Maintenance
Service tests should be carried out regularly to monitor the mixing valve performance, as deterioration of performance could indicate that the valve and/or the system require maintenance. If, during these tests, the temperature of the mixed water has changed significantly in comparison with the previous test, the details given in the installation and commissioning sections should be checked and maintenance carried out.
The following aspects should be checked regularly to ensure that the optimum performance levels of the valve are maintained. Every 12 months at least, or more often if necessary.
1) Check and clean the system filters.
2) Check that any non-return valves positioned upstream of the Caleffi valve are operating correctly, without problems caused by impurities.
3) Limescale can be removed from internal components by immersion in a suitable de-scaling fluid.
4) When the components which can be maintained have been checked, commissioning should be carried out again.
10
Page 11
Application diagrams
Radiant panels heating system application
HOTCOLD
MIX
MIN
M
A
X
7
1
2
COLD
BLUE
HOT RED
MIX
MIN
M
A
X
712
SUPPLY
C
A
LE
F
F
I
CA
L
E
FF
I
CALEFFI
CALEFFI
10
0
8 6 4 2
10
0
8 6 4 2
CALEFFI
CALEFFI
10
0
8 6 4 2
10
0
8 6 4 2
10
0
8 6 4 2
10
0
8 6 4 2
SUPPLY
HOTCOLD
7 X A M
MIN
1
2
10
10
10
10
10
10
8
8
8
8
8
8
6
6
6
6
6
6
4
4
4
4
4
4
2
2
2
2
2
2
0
0
0
0
0
0
CALEFFI
CALEFFI
I
I F F
FF E
LE
L
A
CA
C
CALEFFI
CALEFFI
MIX
Key to symbols
Safety relief valve
Check valve
Isolation valve
Expansion vessel
Filter
Pump
Globe Valve
RETURN
Domestic water system with recirculation connected to tank
7 X A M
N MI
1
2
T
STORAGE
HOT WATER
HEATER
Domestic water system without recirculation connected to tank
Radiant panel loop
7 X A M
N MI
1
2
T
STORAGE
HOT WATER
HEATER
11
Page 12
Troubleshooting
Under normal operating conditions the Caleffi 5231 series thermostatic mixing valve will provide a very high level of per formance. However, in some circumstances, where our maintenance plan is not followed, the following problems may arise.
Symptom Cause Corrective action
Hot water at the cold taps a) Operation of check valve
•  Replace faulty check valves
is hindered; check valve is not sealing correctly
b) Check valves not fitted
Fluctuating mixer water temperature
a) Erratic supply
temperatures at the inlets
•  Restore inlet conditions 
within the limits of the valve
of the valve
b) Starvation of the water
supplies at the inlets of thevalve
c) Incorrect commissioning
ofthe valve
Erratic flow of water from thevalve
a) Insufficient water supplies b) Fluctuations in supply
•  Stabilize inlet supply 
conditions
pressures/temperatures
c) Adverse effect created by
other draw off points on the system
No flow of water from thevalve
a) In-line filters blocked b) Insufficient supply
pressures
c) Debris obstructing
•  Clean filters
•  Restore inlet supplies
•  Clean debris or scale 
fromvalve
valveoperation
12
Caleffi North America, Inc. 3883 West Milwaukee Road Milwaukee, WI 53208 T: 414.238.2360 F: 414.238.2366
01-19-18