CALECTRO UNIGUARD UG-2-A2 User Manual

Phone: +46 31-69 53 00 Fax: +46 31-29 32 91 info@calectro.com www.calectro.com
UNIGUARD UG-2-A2 STAND-ALONE-UNIT
Smoke detector for duct installation.
- One-tube air sampling system
- Service alarm
- Test hole on cover
- Simple installation
- Filter for dusty environments
- Simple service and maintainance
- Installer-friendly connection of cables
- Foolproof mountage of sampling tube
- Reset button on front cover
- Built-in alarm relay
FUNCTION
Uniguard has been developed to detect smoke in ventilation ducts and combines a smoke detector and an adaptor system where both tube and housing are specially designed for optimum airflow through the smoke detector. The system fulfils all the requirements for safe fire detection with airflow speeds from 0,2 m/s to 20 m/s. Uniguard has a built-in alarm relay to control fire-safety dampers, to stop ventilation fans, or to activate accoustic and optical alarms etc. The service alarm let you know when maintenance is needed, before a false alarm occur. The detector has a bayonet fitting to simplify mounting and removal. A contaminated detector will result in increased sensitivity and false alarms. To avoid nuisance alarms the detector has a service alarm (green LED). This indicates that the detector should be cleaned.
BASIC PRINCIPLES FOR POSITIONING
For the airflow through the adaptor to be representative of the airflow in the ventilation duct, install the detector at a place where normally flow meters etc. should be mounted, please see our installation instructions. You can also use your national or local rules for mountage according to "Methods for measuring airflow in ventilation systems".
ACCESSORIES Filter: F1- UG /10 pack Mounting bracket: UG-Beslag
(For insulated/circular ducts) Waterproof housing: UG-SH for outdoors, in cold attics etc.
TECHNICAL DATA Detector type: Ionisation - UG-2-A2I
Optical - UG-2-A2O
Voltage Supply: 24VAC 100 mA ±20% Operating temperature: -10°C to +50°C Maximum humidity: 99% rH Tested and approved according to EN-54: by LPC (England), VdS (Germany) Service alarm: Indicated with green LED Fire alarm: Indicated with red LED Adaptor housing: ABS Air sampling tube: Aluminium. Standard length
0,6 m. Hole diameter 35mm. The length of the venturi pipe shall be choosen based upon how wide the ventilation duct is. The venturi pipes are available in 3 lengths; 0,6, 1,5 and 2,8 m. When the ven­ tilation duct is wider than 0,6 m (dia), the venturi pipe should pen­ etrate the whole duct. Please see enclosed sketch.
Shorten the pipe to correct length.
Insert the end plug.
Put on the end plastic gasket.
Put on the rubber gasket, TET 26-35.
Drill a hole Ø 50 mm.
NOTE!
Drill a hole Ø 35 mm.
Diameter of the duct bigger than 0,6 m. The venturi pipe should penetrate the whole duct.
Drill a hole Ø 35 mm.
Max diameter of the duct 0,6 m.
Use the venturi pipe 0,6 m. Shorten the pipe, if necessary.
For ducts with a ø of less than 0,6 m use the 0,6 m tube. For ducts with a ø of between 0,6 m and 1,3 m use the 1,5 m tube. For ducts which are larger than 1,4 m use the 2,8 m tube.
The ventur i pipe shall not protrude more than 30 mm through the duct wall.
Phone: +46 31-69 53 00 Fax: +46 31-29 32 91 info@calectro.com www.calectro.com
UNIGUARD UG-2-A2 STAND-ALONE-UNIT
Smoke detector for duct installation.
DIMENSIONS
(mm)
INSTALLATION
The venturi tube is made of aluminium and can easily be shortened to suit the diameter of the duct. Hole diameter is 35 mm. With insulated or circular ducts - use the mounting bracket, hole diameter is then 50 mm.
MAINTAINANCE
When the detector becomes contaminated, sensitivity is increased, triggering the service alarm. This can be avoided for a considerable time by cleaning the detector once a year with a vacúum cleaner.
CHECKING AIR FLOW
The detector is equipped with a flow indicator which oscillates in the air stream when the detector is correctly installed. This gives simple confirmation that there is no leakage, and that air from the ventilation duct is flowing through the detector.
FUNCTION TEST
When installation is complete, the detector should be tested. This can be carried out with smoke or suitable testspray for example RDP-300 (from Calectro), use the test hole on cover. D o not forget to refit the plastic plug after test.
NB: When installing outdoors or in cold attics etc., where there is a risk for condensation, this requires that the detector is insulated from the surrounding air by means of for example our waterproof housing UG-SH, and marked with an extra indicator lamp, LED-01 and a sign marked "Hidden Detector".
FUNCTION
Normal operation: In normal operation the alarm relay is energized, and the relay contacts are closed between C and NC. Smoke alarm: The LED of the detector is showing red light and the relay contacts are changing to C and NO. Reset: After alarm the reset push-button has to be pressed in order to have the detector back into normal operation. Pre-alarm: When the detector is sensing smoke or
is dirty the LED of the detector will first show green colour before going into alarm with red light. If the detector is dirty, it will show green light. This is an optical indication (a pre-alarm or service-alarm) which means that the detector is contamined and if it is not cleaned, it will later on give a false
alarm. Failure: If there is something wrong with the detector, the alarm relay will change contacts: a) If the detector module is taken away b) If the supply voltage is interrupted
WIRING DIAGRAM
Alarm relay: ONE changing contact, max 250V, 2Amp
Note! Changing between AC and DC is made by a jumper.
The jumper is factory set to AC.
External reset button
Supply 24 VADC 100mA (±20%)
Alarm output
NC
NO
C
= 24 VDC
= 24 VAC