CAL Controls MAXVU16, MAXVU08 Specifications

CAL MAXVU Datasheet
Temperature and Process Controller
At a Glance
• 1/8 DIN (96 x 48mm) and 1/16 DIN (48 x 48mm)
• Universal input
• Up to 3 outputs
Overview
MAXVU has been designed to offer essential temperature control in a device that’s easy to install, fast to program and with improved display visibility.
MAXVU provides an affordable solution for applications where primary temperature control functions such as heat only or heat/cool are needed, it offers a universal input and up to 3 outputs with a choice of either relay or SSR.
Typical applications include packaging processes such as sealers and many more.
Specication
Input
Thermocouple J, K, C, R, S, T, B, L, N.
RTD 3 Wire PT100
DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to
5V, 1 to 5V, 0 to 10V, 2 to 10V. Scalable -1999 to 9999, with adjustable decimal point
Accuracy Thermocouple ±0.25% of full range ±1 LSD (±1°C
for thermocouple CJC). PT100 ±0.25% of full range, ±1LSD, DC Linear±0.2% of full range, ±1LSD.
Sampling 4 per second
Impedance >10MΩ resistive, except DC mA (5Ω) and V (47KΩ)
Sensor Break Detection
Outputs & Options
Relay SPST Form A relay; current capacity 2A at 250VA.
SSR Drive capability >10V DC @ 20mA
Serial Communications
<2 seconds (except zero based DC ranges), high
alarms activate for T/C, RTD and mV ranges, low alarms activate for mA or V ranges
>150,000 operations at rated voltage/current, resistive load
2 Wire RS485, 1,200 to 38,400 bps, Modbus RTU
• Selectable indicator mode
Fast conguration
Large clear display
• Depth 67mm
Key Features
High visibility 18mm display
digits (10.2mm lower display 1/16
DIN)
Quick setup menu with top 10
conguration parameters
Thermocouple, PT100 or linear DC sensor input
• Up to 3 outputs, relay or SSR
2 process alarms, high/low,
deviation or band.
• 3 button operation
2 x 4 digit display and 3 output status LEDs
Front panel conguration or via
PC conguration software
• RS485 Modbus RTU communications
Specication
Operating and Environmental
Temperature & RH 0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
Power Supply 100 to 240V 50/60Hz (mains powered version)
24V DC/AC +10%/-15%, AC 50/60Hz (low voltage version)
Front Panel Protection Standards CE, UL & cUL
EMI Complies with EN61326 (Susceptibility & Emissions)
Safety Considerations Complies with EN61010-1 & UL61010-1
Weight 1/8 DIN, 0.12kg excluding packaging
Communications
IP65 (Behind panel IP20)
Pollution Degree 2, Installation Category II
1/16 DIN x 0.08kg excluding packaging
RS485 Modbus RTU communication option
Dimensions
Front Fascia 1/16 DIN = 48 x 48mm
1/8 DIN = 96 x 48mm
Ordering Code
MV - xx 0 x - x x x x - 2 x U 0 xxxx
Format
1/16 DIN, 48 x 48mm 1/8 DIN, 96 x 48mm 08
67mm
Terminal Cover
blank Not Fitted S415 Fitted
Manual Language
1 English 2 French
Supply Voltage
110 to 240V AC M 24V AC / DC L
Output
Out 1 Out 2 Out 3
SSR SSR None A A 0 SSR Relay None A R 0 Relay Relay None R R 0 SSR SSR Relay A A R SSR Relay Relay A R R
Relay Relay Relay R R R
3 German
4 Italian
5 Spanish
6 Chinese
Option Slot 2
0 Not Fitted
C RS485 Communications
Loading...
+ 1 hidden pages