CAL Controls 9500P Operating Manual

Users Manual
CAL 9500P
Programmable
Process Controller
English Français Deutsch Italiano Español
CAL Controls

INDEX INSTRUMENT PANEL FEATURES

Initial Set-up 4
Tune or tune at setpoint program 5
Cycle-time recommendations 5
Error messages 6
Set-up procedure 6
Level 1 7 Level 2 7 Level 3 8 Output Options Table 8 Re-transmission 8 Level 4 9 Level A 10
PROGRAMMER 11
Function overview 11 Getting started (Programmer) 12 Program run mode 12 Display functions 12 Example program 13 Function map 14 Function list 16 Memory allocation table 17 Memory full indicator 17 Programming example 18 Program edit example 18
MECHANICAL INSTALLATION 19
DIN panel cut-out 19 Mounting 19 Cleaning 19
ELECTRICAL INSTALLATION 19
Typical application 20 Input options (diagrams) 21 Output options (diagrams) 21
INPUT SENSOR SELECTION 22
Temperature sensors 22 Linear input 22
SPECIFICATION 22 SAFETY AND WARRANTY 23
2
Right Red LED:
Program Holdback indicator
Orange Display:
Setpoint value or program selection
Green LED:
Setpoint 1 output indicator
Upper Red LED:
Setpoint 2 output indicator
Lower Red LED:
Setpoint 3 output indicator
Green Display:
Process variable or
Function/Option
ADJUSTMENTS
To enter or exit program mode: Press ▲ ▼ together for 3 seconds To scroll through functions: Press ▲ or ▼ To change levels or options: Press ✱ ▲ together or ✱ ▼ together To view setpoint units: Press To increase setpoint: Press ✱ ▲ together To decrease setpoint: Press ✱ ▼ together To reset latched alarm or tune fail: Press ▲ ▼ together briefly To run or Hold a program: Press ✱ ▼ together for 3 seconds
Notes: If in difficulty by becoming “lost” in program mode, press and together for 3
seconds to return to display mode, check the INSTRUMENT ADJUSTMENTS above and try again.
When in program mode, after 60 seconds of key inactivity the display will revert to either
inPt : nonE
or, if the initial configuration has been completed, the measured value. Any settings already completed will be retained. During Program Configuration it is recommended that this feature is inhibited. Select
ProG StAY
in Level 4.
This page can be photocopied and used as a visual aid and bookmark when working in other parts of the manual.
!
English
SINT PCYC SUB.P
Call sub-program number
nonE; 1 to number
of programs
Soak time interval
Cont; 0.1 to 1400
(10) min
Program re-cycle count
Cont; 1 to 999
DER.S DI.SS NO.AL PROG LOCK SET.L
Derivative sensitivity
0.1 to 1.0 x dEr.t (0.5)
Display averaging
dir; 1 to 32 (6)
Disable -AL- alarm
display
; on
Disable program auto-exit
Auto; StAY
Security lock
nonE; LEV 3; LEV 2; ALL
Change program entry point
Off; on
USER-PROTECTED SETTINGS
LEVL 4
SP2 output device
none; SSd; rly; (read only)
Sensor burn-out
uP.SC; dn.SC; 1u.2d; 1d.2u
Zero adjustment
0.0 to 25% sensor
full scale
Set Monitor
Off; on
Read Monitor
VAr; hi; lo deg
Read Tune Data
CtA; Ctb; Ct1; Ct2; Ct3; Ct4;
oS1; uS; oS2
Software version
Consult unit
RESET
nonE; ALL
SP1.D SP2.D BURN REU.D REU.L SPAN ZERO CHEK READ TECH UER RSET
SP1 output device
none; rly; SSd; AnLG
Reverse outputs
1r.2d; 1d.2d; 1r.2r; 1d.2r
Reverse O/P LEDs
1n.2n; 1i.2n; 1n.2i; 1i.2i
Span adjustment
0.0 to 25% sensor
full scale
LEVL 3
CONFIGURE OUTPUT SAFETY SETTINGS CALIBRATION PERFORMANCE DATA
Read SP1 output %
0 to 100% read only
SP1 manual output %
0 to100% proportional
mode only
Limit SP1 output %
100 to 0%
Limit SP2 output %
100 to 0%
Main SP2 mode
nonE; dV.hi; dV.Lo; bAnd;
FS.hi; FS.Lo; Cool; EoP
Second SP2 mode
nonE; LtCH; hold; Lt.ho;
nLin
Display resolution
1 or 0.1 degree
Set scale maximum
0.0 Sensor max to sensor
full scale
Set scale minimum
0.0 Sensor min to sensor
full scale
Select input sensor
nonE
Select display units
nonE;°C; °F; bAr;
PSi; Ph; rH; SEt
\\
SP1.P HAND PL.1 PL.2 SP2.A SP2.B DISP HI.SC LO.SC INPT UNITLEVL 2
MANUAL ADJUSTMENTS SP2 MODES CONFIGURE INPUT
RANGING
TUNE BAND INT.T DER.T DAC CYC.T OFST SP.LK SET.2 BND.2 CYC.2LEVL 1
SP1 SETTINGS SP2 SETTINGS
Autotune or Park
Off; on; ParK; At.SP
SP1 Prop band (gain)/
hyst 0.1 deg to 100%
sensor f/s (10°C/18°F)
Integral time (reset)
Off; 0.1 to 60 min
(5 min)
Derivative time (rate)
Off; 1 to 200 sec
(25 sec)
Derivative approach
0.5 to 5.0 x bAnd
(1.5)
Cycle time or on/off
On.off; 0.1 to 81 sec
(20 sec)
Offset (manual reset)
0 to 50% x bAnd
(In.t = off)
Setpoint lock (SP1)
Off; on
Adjust SP2 setpoint
+/– sensor full scale or
full scale
SP2 prop band/Gain/
Hyst 0.1 deg to 100%
sensor f/s (2°C/3.6°F)
SP2 Cycle on/off
On.off; 0.1 to 81 sec
Program number
1 to 31
Run program
oFF; on; hoLd; dEL
inS; CoPY; PStE
Power failure
recovery mode
rSEt; Cont; hoLd
Program start value
PV; SP
Setpoint ramp time units
hour; 60s
Holdback value
oFF; 0.1 to 150
Event output (SP2A or SP3A)
nonE; 2d; 2E; 3d; 3E; 2d.3d;
2E.3d; 2d.3E; 2E.3E
PROG RUN FAIL ST.U SPRU SEG TYPE SPRR T.SP HB.V EO.PLEVL P
PROGRAMMER SETTINGS
S
egment number
1 to 126 max.
Define segment type
SPr; SoAK; StEP; LooP;
Call; EoP; dEL; inS
Setpoint ramp rate
1 to 9990 (100)
units/time
Adjust target setpoint
+/– sensor full scale or
full scale
Instrument address
0 to 255
Baud rate
1200; 2400; 4800
9600; 19k2
Data format
18n1; 18E1; 1801
TxRx activity
Off; on
ADDR BAUD DATA DBUCLEVL C
COMMS SETTINGS
High scale 1000
-1999 to 9999
Low scale 0
-1999 to 9999
Input high 50.0
0.1 to 50.0
Input low 10.0
0.0 to 49.9
Decimel 0000
000.0 or 00.00
Burnout SP3 - uPSC
dhSC
R
everse O/P3 3D
3r
AN.HI ANLO HI.IN LO.IN DECP SP3.A SP3.B SET.3 HYS.3 BRN.3 REV.3LEVL A
SP3 SAFETY SETTINGS
Main mode nonE
dv.hi; dVLo; bAnd; Fshi;
FSLo; EoP
Second mode nonE
LtCh; hoLd; Lt.ho
Set SP3 0
0 to 2500
Hysteresis SP3 20
1–100% sensor
full scale
SP3 ADJUSTMENTSSP3 MODESLINEAR SCALING AND INPUT SETTINGS
INITIAL SET-UP ENTRY
PROGRAM ENTRY (DEFAULT)
Level C only visible when COMMS Option fitted
KEY ✱ ▼ OR ✱ ▲ TOGETHER TO CHANGE LEVELS OR OPTIONS
KEY OR TO VIEW FUNCTIONS
3

FUNCTIONS MENU

Range of Adjustment shown under description.
If applicable, factory settings shown in bold.
For a full description of menu functions refer to pages 7 to 10, and 16/17 in Programmer section.
Note: The letter K appears in the instrument display as the character K
This page can be photocopied and used as a visual aid and bookmark when working in other parts of the manual.
!
English
Press and hold and use the or buttons to select from the choices
Rly,SSd
or
AnLG
depending on the model supplied. SP2 and SP3 outputs will be automatically
allocated. (See output options table on page 8).
4 To enter initial configuration into controller memory
Press and hold both and buttons for 3 seconds. The display will now read
PArK
and measured variable (e.g. ambient temperature 23°).
PArK
is displayed because a
setpoint has not yet been entered.
To display setpoint units
Press and hold The displays will now read
unit
(eg. °C) and
0
To enter setpoint Press and hold and use button to increase or button to decrease the reading and
scroll to required setpoint value. (The digit roll-over rate increases with time).
THE CONTROLLER IS NOW OPERATIONAL
WITH THE FOLLOWING FACTORY SETTINGS
Proportional band/Gain 10ºC/18ºF/100 units Integral time/Reset 5 mins Derivative time/Rate 25 secs
Proportional cycle-time 20 secs (Typical setting for relay output) DAC Derivative approach control 1.5 (Average setting for minimum overshoot)
Note: For more precise control or for non temperature applications where a Linear input
transducer is being used, the controller may need to be tuned to the process. Please refer to the following section on AUTOTUNE.

AUTOTUNE

This is a single shot procedure to match the controller to the process. Select either Tune or Tune at Setpoint from the criteria given below.
The Tune program should be used for applications other than those listed under Tune at Setpoint below. The procedure will apply disturbances when the temperature or process
reaches 75% of the setpoint value, causing overshoot which is monitored in order to adjust the DAC overshoot inhibit feature. Care should be taken to ensure that any overshoot is safe for the process.
The Tune at Setpoint program is recommended when:
The process is already at setpoint and control is poor
The setpoint is less than 100°C in a temperature application
Re-tuning after a large setpoint change
Tuning multi-zone and/or heat-cool applications.
Notes: DAC is not re-adjusted by Tune at setpoint. Proportional Cycle Time can be pre-
selected before running the Autotune program. (see page 5).

GETTING STARTED

After power-up the controller requires programming with the following information:
Type of Sensor (See list of sensors p.22) Operating unit
°C °F bAr PSi Ph rh SEt
Allocation of Output Device to SP1/SP2 (Relay / SSd) or analogue. SP3 is always relay. Setpoint
When the above information has been programmed into the controller it will be operational with factory PID settings.
INITIAL SET-UP
On power-up the controller will display the self test sequence followed by the initial display
inPt : nonE
1 Select input sensor.
Press and hold and use the or buttons to scroll through the sensor selection
list until the correct sensor is displayed. Release the buttons. The display will now read selected sensor type e.g.
inPt : tCS
(type S thermocouple).
Press once The display will now read
unit : nonE
LINEAR INPUT
When Linear Input is selected, the display resolution of the setpoint and many other functions will be changed from the setting previously made at
di.SP
in Level 2, to that set
at
dECP
in Level A.
It is therefore recommended that on completion of the Initial Set-up the Linear Input settings in Level A be completed before moving on to configure Levels 1, 2 and 3. (see Set-up Procedure page 6).
2 Select operating unit.
Press and hold and use the or buttons to scroll through the unit selection list
until the correct unit is displayed. Release the buttons. The display will read selected unit e.g.
unit : °C
Press ▲ once The display will now read
SP1.d : nonE
3 Select SP1 (Main setpoint output device)
Analogue output
The allocation of the analogue output to SP1 automatically overrides the default proportional cycle time setting of 20 seconds. Where the analogue output is allocated to SP2, the default
CyC.2
setting on/off must be manually changed in Level 1 to a time proportioning setting to enable the analogue output to operate in proportional control mode.
4
English
AUTOTUNE (continued)
TUNE OR TUNE AT SETPOINT PROGRAM
Enter program (▲▼) and from the display
tunE : oFF
press and hold and press to
display
tunE : on
or
tunE : At.SP
Exit program mode (▲▼).
The TUNE program will now start. The display will show
tunE
as the process variable
climbs to setpoint. Note: Avoid tuning while running a program as SP1 may be different from the target
setpoint..
When the TUNE or TUNE AT SETPOINT program is complete the PID values are entered automatically. The process will rise to setpoint and control should be stable. If not, this may be because optimum cycle time is not automatically implemented. To set the cycle time see PROPORTIONAL CYCLE-TIME.

PROPORTIONAL CYCLE-TIME

The choice of cycle-time is influenced by the external switching device or load. eg. contactor, SSR, valve. A setting that is too long for the process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching device.
Factory set
To use the 20 sec factory set cycle-time no action is needed whether autotune is used or not.
To Manually Select AUTOTUNE Calculated CYCLE-TIME
When AUTOTUNE is completed, enter program (▲▼) and select
CYC.t
in Level 1. The
display will read
CYC.t : 20
(the factory setting).
To view the new calculated optimum value, press and hold both and buttons until indexing stops. The calculated value will be displayed eg.
A16
. If acceptable, exit program
(▲▼) to implement this setting.
To Pre-select Automatic Acceptance of AUTOTUNE Calculated CYCLE-TIME
Before AUTOTUNE is initiated select
CYC.t
in Level1, press and hold both ✱ and ▼ buttons
until indexing stops at
A
– – . Exit program (▲▼) to accept calculated value automatically.
To Manually Pre-select Preferred CYCLE-TIME
Before AUTOTUNE is initiated select
CYC.t
in Level 1, press and hold both and or
buttons until indexing stops at preferred value then exit program (▲▼) to accept.
CYCLE-TIME RECOMMENDATIONS

SECOND AND THIRD SETPOINTS (SP2 and SP3)

PRIMARY ALARM MODES
Configure SP2 output to operate as an alarm from
SP2.A
in Level 2 and set the alarm
setting in
SEt.2
Level 1.
Configure SP3 alarm mode
SP3.A
and setting
SEt.3
in Level A. The alarms will be individually triggered when the process value changes according to the options listed below.
dV.hi
Rises above the main setpoint by the value inserted at
SEt.2/3.
dV.Lo
Falls below the main setpoint by the value inserted at
SEt.2/3.
BAnd
Rises above or falls below the main setpoint by the value inserted at
SEt.2/3.
FS.hi
Rises above the full scale setting of
SEt.2
or
SEt.3.
FS.Lo
Falls below the full scale setting of
SEt.2
or
SEt.3.
EoP
Event Output (See Programmer section pages 11 to 18)
SUBSIDIARY SP2 / SP3 MODES
The following additional Subsidiary alarm functions can be added to any Primary alarm configurations using the settings found at
SP2.b
in Level 2 and
SP3.b
in Level A.
LtCh
Once activated, the alarms will latch and can be manually reset when the alarm condition has been removed.
Hold
This feature inhibits alarm operations on power-up and is automatically disabled once the process reaches the alarm setting.
Lt.ho
Combines the effects of both
LtCh
and
hoLd
and can be applied to any Primary
alarm configuration.
SECOND SETPOINT (SP2) Proportional control output Configure in Level 1 using
CyC.2
to select proportional cycle time and
bnd.2
to adjust
proportioning band. For Heat/Cool operation see Operating Manual. Additional in depth information on controller operation is available in the CAL 9400.PDF
available for down load from www
.cal-controls.com
In on–off mode,
bnd.2
adjusts SP2 hysterisis.
5
Output Device
Factory Setting
Recommended Minimum
Internal relays
20 seconds 20 seconds
10 seconds
Solid state drives
0.1 seconds
Hereafter in the Manual the symbol (▲▼) signifies both buttons are held pressed
for 3 seconds to ENTER or EXIT Program mode.
Alarm type On-Off operating mode SP2 and SP3 Proportional operating mode SP2 only
FS.HI
COOL
FS.LO
BAND
DV.LO
DV.HI
Deviation
Full scale
Strategy
Output state LED state Output state LED state
BAND
: on-off mode only
Output ON
(Relay or SSd
energised)
Output OFF (Relay or SSd de-energised)
LED ON
Temperature above setpoint
Legend
English
SP2 / SP3 OUTPUT AND LED STATUS IN ALARM CONDITION
SP2 / SP3 ALARM ANNUNCIATOR
If a Primary Alarm mode has been configured, when an alarm condition occurs the alarm annunciator
-AL-
will be displayed alternating with the process variable. The alarm together with the display, will be automatically reset as soon as the alarm condition has been cleared.
The annunciator may be disabled by selecting
no.AL: on
, in Level 4.
ERROR MESSAGES
SENSOR FAULT
Display flashes:
inPt: FAiL
Indicates: sensor open or short circuit or linear input over-range. Action: Check sensor/wiring/connectors
NON-VOLATILE MEMORY ERROR
Display flashes:
dAtA:FAiL
Action: De-power briefly. Replace unit if problem persists
MANUAL POWER ERROR
Display flashes:
hAnd :FAiL
SP1 set to on–off in
CYC.t
Action: Select proportional mode
IMMEDIATE FAIL ON AUTOTUNE START
Display flashes:
tunE :FAiL
Setpoint display 0
1. No setpoint entered.
Action: Enter setpoint
2. SP1 set to ON/OFF in
CyC.t
Action: Select proportional mode Note: To reset and clear error press ▲▼ together briefly to cancel message.
FAIL LATER DURING AUTOTUNE CYCLE
The thermal characteristics of the load exceed the Autotune algorithm limits. The failure point indicated by any display 0.0 in
tech
e.g.
Ctb
= 0.0
Action: 1. Change the conditions. eg. raise setpoint
2. Try
tunE : At.SP
3. If the error message persists, call local CAL representative for advice.
6

LINEAR INPUT

Set-up Procedure
The 4–20mA input model converts current into voltage using an internal resistor which spreads the signal across the input range 10 to 50 mV. using multiplier of 2.5. When using a transducer with an output less than 4–20mA, the input maximum and minimum mV values can be calculated using the same multiplier.
Models with 0 to 5V input use an internal resistor to spread the signal across the input range 0 to 50 mV using a divider of 100. Where a transducer provides a smaller output, the input maximum and minimum values can be similarly calculated.
Decide what scale minimum and maximum will be required, and whether the scale needs inverting. (See Level A; Linear Input Scaling for list of settings and limits, page 10).
The example below shows how a 4–20mA linear Input should be configured.
# e.g. 4–20mA = 60 to 260 units where 4mA = 60 units
Follow INITIAL SET-UP procedure (also see page 4).
1. Select input sensor Select
inPt:Lin
2. Select unit Select required unit, if not available Select
unit:SEt
3. Select SP1 output Select from:
Rly,SSd
or
AnLG
Enter initial configuration into controller memory DO NOT ENTER SETPOINT until Linear Input has been configured in Level A
See functions menu page 3 and functions list page 10.
Configure Linear Input Enter level A
(Then using example given # above)
4. Enter scale maximum Select
An.hi:260
5. Enter scale minimum Select
An.Lo:60
6. Enter input maximum Select
hi.in:50.0
7. Enter input minimum Select
Lo.in:10.0
8. Enter display resolution Select
dECP:0000
(WARNING – otherwise settings
marked may be altered)
Enter Linear Input configuration into controller memory and enter setpoint. Now configure Levels 1, 2 and 3 and if required proceed with AUTOTUNE. Note: Any apparent calibration errors can be removed using the
ZEro
and
SPAn
adjustments in Level 3.
Will be affected by dECP settings in Level A
English
7

FUNCTION LIST (LEVELS 1 to 4 and A)

Note: A Functions Menu is shown on page 3.
LEVEL 1
Function Options
[Factory settings] shown in brackets
SELECT AUTOTUNE (see pages 4/5)
tunE [oFF] on PArK At.SP
Used to switch the Autotune feature on and off, to select
PArK
or Autotune at setpoint.
PArK
temporarily turns the output(s) off. To use select
PArK
and exit program mode. To
disable re-enter program at
tunE
and select
oFF
.
SP1 OPERATING PARAMETERS
bAnd 0.1 to * C/°F [10ºC/18ºF/100 units]
SP1 proportional band/Gain or Hysteresis
* 100% (
Hi.Sc
) sensor maximum Proportional control eliminates the cycling of on-off control. Output power is reduced, by time proportioning action, across the proportional band.
int.t oFF 0.1 to 60 minutes [5.0]
SP1 integral time/reset
Auto-corrects proportional control offset error
dEr.t oFF 1 - 200 seconds [25]
SP1 derivate time/rate
Suppresses overshoot and speeds response to disturbances
dAC 0.5 - 5.0 x bAnd [1.5]
SP1 derivative approach control dAC
Tunes warm-up characteristics, independent of normal operating conditions, by adjusting when derivative action starts during start-up (smaller dAC value = nearer setpoint).
CyC.t A – – on.oF 0.1 - 81 sec [20]
SP1 proportional cycle-time (see pages 9/10) Determines the cycle rate of the output device for proportional control. Select
on.oF
for
ON/OFF mode.
oFSt 0 to * °C/°F/units [0]
SP1 offset/manual reset
* ±50%
bAnd
. Applicable in proportional and ON/OFF mode with integral disable:
Int.t : oFF
.
SP.LK [oFF] on
Lock main setpoint
Locks the setpoint preventing unauthorised adjustment.
SP2 OPERATING PARAMETERS (see page 6)
Function Options
[Factory settings] shown in brackets
SEt.2
[
0] to * °C/°F/units
Adjust SP2 setpoint
* Deviation Alarms
DV.hi, DV.Lo, bAnd
25% sensor maximum.
* Full scale alarms
FS.hi, FS.Lo
sensor range f/s
bnd.2 0.1 - * °C/°F/units [2.0 °C/3.6°F 2 units]
Adjust SP2 hysteresis or proportional band/gain
(see
CyC.2
setting)
* 100% sensor f/s (
Hi.Sc
)
CyC.2 [on.oFF] 0.1–81 seconds
Select SP2 ON/OFF or proportional cycle-time
Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for proportional mode.
LEVEL 2
MANUAL CONTROL MODES Function Options
[Factory settings] shown in brackets
SPI.P 0 to 100 % ‘read only’
Read SP1 output percentage power
hAnd [oFF] 1 to 100 % (not in ON/OFF)
SP1 manual percentage power control
For manual control should a sensor fail. Record typical
SP1.P
values beforehand.
PL.1 100 to 0 % duty cycle [100]
Set SP1 power limit percentage
Limits maximum SP1 heating power during start-up and in proportional band.
PL.2 100 to 0 % duty cycle [100]
Set SP2 percentage power limit (cooling)
SP2 OPERATING MODES (see page 5)
SP2.A [nonE] dV.hi dV.Lo bAnd FS.hi FS.Lo Cool EoP
Main SP2 operating mode
SP2.b [nonE] LtCh hoLd nLin
Subsidiary SP2 mode: latch/sequence Non-linear cool proportional band
LEVL 1
Will be affected by dECP settings in Level A
LEVL 2
English
8
INPUT SELECTION AND RANGING
dI.SP [1] 0.1
Select display resolution: for display of process value, setpoint,
OFSt, Set.2, hi.SC, LoSC
.
hi.SC
[sensor maximum] sensor maximum
°C/°F/units
Set full scale
Lo.SC
[sensor minimum] sensor minimum
°C/ºF/units
Set scale minimum (default 0°C/32°F or 0 units)
inPt
Select input sensor
[nonE]
(See SENSOR SELECTION table, page 22) NB. If Linear Input selected, start configuration from Level A.
unit [nonE] °C °F bAr Psi Ph rh SEt
Select required operating unit from above options
LEVEL 3
OUTPUT CONFIGURATION
Note 1: ‘Read only’ after initial configuration.
rSET ALL
full reset to factory settings
required to change
SP1.d
subsequently.
Note 2: Depending on the Model, SP1 and SP2 may be fitted with any of three output
types, RLY, SSd or Analogue (Specification on page 11/12) where appropriate, these must be allocated during initial configuration. SP3 is always fitted with RLY.
Output Options Table
Model SP1 Output SP2 Output SP3 Output
95111P
RLY RLY RLY
95001P
SSd RLY RLY RLY SSd RLY
95221P
SSd SSd RL
Y
*95X11P
AnLG RLY RLY
RLY AnLG RLY
*95X21P
AnLG SSd RLY
SSd AnLG RLY
* Substitute for X in table above, Analogue options B = 4–20mA, C = 0–5V, D = 0–10V
Will be affected by dECP settings in Level A
Re-transmission
* These models above offer the option of using the analogue output for Re-transmission.
Select
bAndorbnd.2
value in
LEVL 1
to equal the full range setting in
LEVL A
and if
using SP1 output, set
int.t
and
dErt.t
in
LEVL 1
to off.
Example: Set-Up using a Model 95B11P to Re-transmit the 4-20 mA input, scaled 0 to 100 units. SP1 relay is used as the control output and SP2 analogue output is used for re­transmission.
Note: Read in conjunction with Linear Input Set-up Procedure on page 6.
Function Options
[Factory settings] shown in brackets
From initial power-up;
Set
inPt nonE
to
inPt Lin
unit nonE
to
unit SEt
(for example)
SP1.d nonE
to
SP1.d rLY
To scale the input, select
LEVL A
, then:
Set
dECP
to
000.0
(e.g. required resolution)
An.hi
to
100.0
An.Lo
to
0.0
hi.in
to
50
(ie 20mA)
Lo.in
to
10
(ie 4mA)
To align SP2 analogue re-transmission with SP1 control output, select LEVL 2 then:
Set
SP2.A
to
FS.hi
And in LEVL.1
Set
SEt.2
to
50
(ie 50% of display range)
bnd.2
to
100
(ie 100% of display range)
Finally, set SP1 setpoint value as required for process to start.
Using SP1 output for re-transmission
Set
int.t
to off
dErt
to off
rev.d
to
1d.2d
to invert SP1 output
SP1 Setpoint to midscale
burn
Sensor burn-out/break protection
Caution: Settings affect fail safe state.
SP1 SP2
[uP.SC]
Upscale Upscale
dn.SC
Downscale Downscale
1u.2d
Upscale Downscale
1d.2u
Downscale Upscale
Retransmission range is limited to the sensor full scale value (Example RTD = 400C/752F).
LEVL 3
LEVEL 2 CONTINUED
English
Loading...
+ 16 hidden pages