59615 MaxVU Rail Std Controller Concise manual (EN)
59615-1 MaxVU Rail Standard Controller
Concise Manual
Installation should only be performed by technically competent personnel.
Standards compliance shall not be impaired when fitting into the final installation.
It is the responsibility of the installing engineer to ensure that the configuration is safe.
Local regulations regarding the electrical installation & safety must be observed.
Impairment of protection will occur if the product is used in a manner not specified by the
manufacturer.
Due to the low weight of this instrument there are no special lifting or carrying considerations.
Designed to offer a minimum of Basic Insulation only.
Ensure that supplementary insulation suitable for Installation Category II is achieved when fully
installed.
To avoid possible hazards, accessible conductive parts of the final installation should be
protectively earthed in accordance with EN61010 for Class 1 equipment.
Output wiring should be within a Protectively Earthed cabinet.
Sensor sheaths should be bonded to protective earth or not be accessible.
Live parts should not be accessible without the use of a tool.
When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should be used
to disconnect both LINE and NEUTRAL conductors simultaneously.
Do not position the equipment so that it is difficult to operate the disconnecting device.
Ventilation slots must not be covered and adequate air circulation must be allowed.
Use conductor sizes 30-12 AWG, minimum temp rating of cables to be 80c.
CAUTION: Check information label on housing for correct operating
voltage before connecting supply to Power Inputs.
Diagrams show all possible option combinations, check your exact
product specification before connecting.
Press or keys to navigate between parameters or menu items.
Press to highlight and edit a parameter value.
Press or to change the parameter value, then press within 60 seconds to
confirm change.
For example, changing the setpoint (SP).
Navigating to Setup Mode or Advance Configuration from Operator Mode:
Setup Mode - press & .
Advanced Configuration - press & .
Returning to Operator Mode:
Press & to move back one level. After 120 seconds without key presses the
unit returns automatically to the first Operator Mode screen.
3. SETUP (& FIRST POWER UP)
Important Note: When powered up for the first time, or after a factory reset (default) the
instrument enters Setup.
The device remains in Setup, or will keep powering up back into Setup, until all
parameters have been reviewed and the user exits Setup.
Some parameters may be hidden depending on configuration & hardware.
Alternatively press & to enter Setup from Operator screen and & to exit.
-200 – 1200ºC
-328 – 2192ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
-240 – 1373ºC
-400 – 2503ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
-199 – 800ºC
-328 – 1472ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
100 – 1824ºC
211 – 3315ºF
0.0 – 537.7ºC
32.0 – 999.9ºF
-240 – 400ºC
-400 – 752ºF
-128.8 – 400.0ºC
-199.9 – 752.0ºF
0 – 20mA
0 – 50mV
0 – 5V
0 – 10V
4 – 20mA
10 – 50mV
1 – 5V
2 – 10V
°C or °F (hidden when a linear input is used)
* Maximum of 1 decimal place for temperature inputs marked.
0000 *
000.0 *
00.00
0.000
Scale Range max & min only visible when input is a linear type.
>Input
Scale Range Maximum
Maximum for application working range.
>Input
Scale Range Minimum
Minimum for application working range.
>Input
Digital I/P Action
None
Alarm Reset (clears latched alarms)
Ctrl Enable/Disable (disables control)
Ctrl Auto/Manual
Pre-Tune Start/Stop
Tune at SP Start/Stop
Heat Power
Cool Power
Alarm 1
Alarm 2
Alm. 1or2
Loop Alarm
Control Loop Alarm time is 2x Integral (PID) or Loop Alarm Time (if mode is On.Off)
Same options as Output 1 Usage
>Output 3
Usage
or
>Linear Outp
Usage
Same options as Output 1 Usage.
Heat
Cool
Retx PV
Retx SP
0-10V
2-10V
0-20mA
4-20mA
0-5V
1-5V
>Linear Outp
Scale Range Maximum
Maximum PV value corresponding to
maximum linear output.
>Linear Outp
Scale Range Minimum
Minimum PV value corresponding to
minimum linear output.
Range minimum to range maximum, or OFF
(maximum +1). OFF disables alarm.
Default PV High alarm type.
Same options as Alarm 1.
Default PV Low alarm type.
Modbus address from 1 to 255
1200, 2400, 4800, 9600, 19200 & 38400
>Control
Automatic Tuning
Off, Start Pre-Tune or Start Tune at SP *
*Start Tune at SP not available for Heat & Cool processes.
When you exit if necessary, press and to clear Control is Enabled Pop Up Alert.
PV - top
SP - bottom
Temperature Unit - right.
Manual Power is shown as P%.
Transmitter parameter = Enable, SP is
hidden.
Important: The device still functions as a
controller, using the local Setpoint.
Important: Visibility for parameters below must be set to Show in Operator sub-menu.
To clear
latches press
then to select
Yes.
Press to
accept.
Alarm active
Alarm set, but not
active
Alarm not set
Output Latched
Latch set, but
output not Latched
Latch not set
To clear press then to select
Yes. Press to accept.
Screens show the
Maximum & Minimum PV
reached.
OFF - Control output(s) disabled. (Ignored when in manual mode).
ON - Control output(s) enabled.
OFF - Automatic control, PID or On-Off control available.
ON - Manual control, Manual Power shown as P% xxx.
Visible when On Timer is active.
See Ramp & Timers diagram.
Visible when Delay Timer is active.
See Ramp & Timers diagram.
Warnings & Error Messages
Caution: Do not continue your process until any issues are resolved.
Pop up Alerts:
Warnings and
Confirmations
For example, Pop Up Alert for Alarm 1.
Pop Up Alerts need to be acknowledged.
Press and to clear Pop Up Alert.
Pop up Alerts: Alarm 1, Alarm 2, Alarm 1 & 2, Starting Calibration, Calibration Ongoing,
Calibration Fail, Control is Enabled, Tune Error messages, Tuning in progress, Setup
not Completed & Offset in use (SP offset).
Alternates with PV to show Alarm is active.
Alternates with PV.
One or more outputs are latched on and no alarm is active.
Process variable input > 5% over-range.
Process variable input > 5% under-range.
Break detected in process variable input sensor, wiring or wrong
input type selected. Shows OPEN until resolved, control is off.
Selected input range is not calibrated.
Shows ERROR until resolved, control is off.
Alternates with SP. Auto-tuning is in progress.
Manual power value replaces setpoint, shows P% xxx of power.
Alternates with actual setpoint. Setpoint ramp is active.
Control is disabled. Control output(s) are off.
Visible when Delay Timer is active. Control output(s) are off.
Alternates with setpoint. Tuning is active.
Display alternates between Tune Error & Setpoint.
Remains visible until Automatic Tuning is turned Off.
PV within 5% of SP (for pre-tune)
Control is ON/OFF (not PID)
Tune at Setpoint not able to run
Important: Check your product code for exact hardware fitted.
Thermocouple
Calibration:
0.25% of full range, 1LSD & 1°C for Thermocouple CJC.
BS4937, NBS125 & IEC584.
0.25% of full range, 1LSD.
BS1904 & DIN43760 (0.00385//°C).
0.25% of full range, 1LSD.
>1M resistive, except dc mA (5) and V (47k)
Thermocouple, RTD, 4 to 20mA, 10 to 50mV, 2 to 10V and 1 to
5V ranges only. Control outputs turn off at sensor break.
DIGITAL INPUT (Isolated or Non-Isolated version)
Reset Alarm, Control Enable/Disable, Auto/Manual, Pre-Tune
Start/Stop or Tune at SP Start/Stop.
Non-isolated - Open or Close only.
Isolated - Open (2 to 24Vdc) or Closed (<0.8Vdc).
Closed to Open transition = Reset, Enabled, Auto or Start.
Form C SPDT (Op 1) / Form A SPST relay (other), 2A @ 250Vac.
>150,000 operations at rated voltage/current, resistive load.
SSR drive voltage >10V at 20mA
Output 3 option only: DC (Linear)
0 to 20mA, 4 to 20mA, 0 to 5V, 0 to 10V or 2 to 10V
Current Output 500 max, Voltage Output 500 min.
8 bits in 250ms (10 bits in 1s typical, >10 bits in >1s typical).
RS485 SERIAL COMMUNICATIONS (Modbus RTU)
1200, 2400, 4800, 9600, 19200 or 38400 bps.
For indoor use only, DIN-rail mounted in suitable enclosure.
<95% humidity 0°C to 55°C (Operating), –10°C to 80°C (Storage).
20% to 95% non-condensing.
Mains power version - 100 to 240Vac 10%, 50/60Hz, 9VA
Low voltage version - 24Vac +10/-15% 50/60Hz 9VA or 24Vdc
+10/-15% 5W.
EN61326-1:2013, Table 2 & Class A.
Warning: This is a Class A product. In a domestic environment, this product may cause
radio interference in which case the user may be required to take adequate measures.
UL61010-1 Edition 3, EN61010-1 Version 2010,
Pollution Degree 2 & Installation Class 2.
Height - 99mm; Width – 22.5mm; Depth - 121mm
A space of 80mm must be allowed above & below each unit.
LEDs show respective output state: 1 2 3
Display turns off after 5, 15 or 30
minutes without key presses.
* Dedicated
configuration port
* NEVER DIRECTLY CONNECT DEDICATED CONFIGURATION SOCKET TO A USB PORT.
Output 1
TC / RTD / Linear +
Volt-free or TTL
Compatible
Display shows PV (process variable),
units, SP (setpoint), alarm/latch
statuses, error & warning messages.
Non-Isolated
Digital Input
NonIsolated
Digital
Input
59615 MaxVU Rail Std Controller Concise manual (EN)
6. SAFETY & WARNING SYMBOLS
Caution, refer to the manual.
Alternating or direct current
could be present.
Equipment protected through-out
by double insulation.
7. ADVANCED CONFIGURATION
Advanced Configuration gives access to all possible parameters; however, the device
hides parameters that are irrelevant to your exact product specification & configuration.
Advanced Configuration Navigation
Enter by pressing & . Press or to navigate to the required menu, then press
to enter.
Press & to exit up 1 level. Depending upon which menu you enter it may be
necessary to exit 2 or 3 levels for Operator Mode.
Advanced Configuration main menu
Includes Status, Control & Manual Mode enable/disable.
Configure the process input.
Single or two-point calibration adjustments for the process input.
Configuration parameters for the outputs.
PID control tuning & configuration parameters.
Setpoint & timer settings.
Modbus communications settings.
Lock codes and Factory Default.
Control what appears in Operator Mode.
View serial number & manufacturing details.
Alarm active
Alarm set, but not
active
Alarm not set
Output
Latched
Latch set but output
not Latched
Latch not set
To clear press then
to select Yes.
Press to accept.
Maximum and Minimum PV recorded whilst
powered up or since last reset.
To clear press then to select Yes.
Press to accept.
OFF - Control output(s) disabled. (Ignored
when in manual mode) SP replaced by OFF.
ON - Control output(s) enabled. Setpoint visible
in User screen.
OFF - Instrument in automatic control mode
(PID or On-Off control).
ON - Manual control ON. Power shown as
Pxxx % in Operator mode, in place of SP.
See Input Type table in SETUP (& FIRST
POWER UP).
Displayed as °C or °F
(Units are hidden when a linear input is used)
Maximum for application working range
Max allowed for
Input Type.
Minimum for application working range
Min allowed for
Input Type.
OFF or 0.5 to 100.0 seconds in 0.5
increments
Enable Enables the internal thermocouple
CJC (Cold Junction Compensation).
Disable Disables the internal CJC.
External compensation must be provided for
thermocouples.
None
Alarm Reset (clears latched alarms)
Ctrl Enable/Disable
Ctrl Auto/Manual
Pre-Tune Start/Stop
Tune at SP Start/Stop (not available for
heat/cool)
Single-point offset or two-point calibration adjustment for process input. Can be used
together, if required.
Shifts the input value up or down by a single offset amount across
the entire range.
Enter value at which the low point error was measured.
Enter equal, but opposite offset value to the observed low point
error.
Enter value at which the high point error was measured.
Enter an equal, but opposite offset value to the observed high
point error.
Heat
Cool
Alarm 1
Alarm 2
Alm. 1or2
Loop Alarm
Control Loop Alarm is set as 2x Integral (PID) or Loop Alarm Time (On.Off control)
Direct - Output active when alarm triggers
Reverse - Output active when alarm is not
triggered
Off - Alarm doesn’t latch
On – Alarm latches & needs to be cleared
Direct - LED Indicator lit when output is active
Reverse - LED Indicator lit when output is
inactive
Same options as Output 1 - Usage
Same options as Output 1 - Alarm Action
Same options as Output 1 - Alarm Latching
Same options as Output 1 - LED Indicator
>Output 3
or >Linear Outp
3rd output - either Relay/SSR driver (Output 3) or Linear.
>Output 3
Usage
>Linear Outp
Usage
Output 3 - same options as Output 1 - Usage
Heat
Cool
PV Retransmit
SP Retransmit
Output 3:
Alarm 2
Linear:
SP
Retransmit
Same options as Output 1 - Alarm Action
Same options as Output 1 - Alarm Latching
Same options as Output 1 - LED Indicator
0-10V
2-10V
0-20mA
4-20mA
0-5V
1-5V
>Linear Outp
Scale Range Maximum
Display value for maximum output, -1999 to 9999
>Linear Outp
Scale Range Minimum
Display value for minimum output, -1999 to 9999
PID control tuning & configuration & Loop Alarm. Hidden if no control outputs are set.
ON/OFF (0.0) or PID control in display units.
1 to 9999 - 0 decimal places
0.1 to 999.9 - 1 decimal place
0.01 to 99.99 - 2 decimal places
0.001 to 9.999 - 3 decimal places
0.01 to 99.59.
and OFF (0.00) (minutes & seconds).
0.01 to 99.59 or OFF (0.00) (minutes & seconds).
In display units, range -20 to +20% of Heat & Cool
Proportional Band
Visible when using On/Off control.
In display units centred about the setpoint.
Range: 0.1% to 10.0% of input span
Visible when On/Off control & Loop Alarm assigned to
an output.
Sets time before the loop alarm triggers.
(minutes & seconds)
Manual Reset 0 to 100%
(-100% to 100% if heat/cool control)
Prevents simultaneous activation of both heat & cool
outputs. On / Off
Only set to On if Overlap/Deadband = 0.
% power upper limit 0 to 100%
% power upper limit 0 to 100%
Last - Powers up with control enable in the same state
as on power off or power failure.
On - Always powers up with control enabled.
Off
Start Pre-Tune
Start Tune at SP *
*Start Tune at SP not available for Heat & Cool process.
Enables the Delay and On
Timers. Applies at next powerup / control enable.
Delay and On Timers ignored.
(Setpoint ramping still functions.)
Time from power-up or control enable before control
begins from 00.01 to 99.59.
or OFF (0.00. (hours & minutes)
If OFF control starts immediately.
Rate actual setpoint changes from current PV to
target setpoint following power-up or control enable.
From 0.001 to 9999.
or OFF (1000) (Units / hr).
Any setpoint changes also follow this rate.
The time the target setpoint will be maintained once
reached, from 00.01 to 99.59
or Off (00.00) (hours & minutes)
Infinite (100.00) - control remains on indefinitely.
Used to limit the Maximum setpoint value.
Used to limit Minimum setpoint value.
Offsets the setpoint. For use in multi-zone setpoint
slave applications.
Offset in use pop-up appears when SP is changed.
None
PV High
PV Low
Deviation
Band
Range minimum to range maximum, or
OFF (maximum +1). OFF disables
alarm.
Alarm Inhibit temporarily deactivates alarms at power-up & on change in setpoint.
None
Alarm 1
Alarm 2
Alarm 1 & 2
None
Alarm 1
Alarm 2
Alarm 1 & 2
On - activates both alarms, if
configured, when a sensor break is
detected.
Modbus communications settings, only shown when RS485 option is fitted.
Modbus address from 1 to 255
Coms data rate in kbps
1200, 2400, 4800, 9600, 19200 & 38400.
Parity checking: Odd, Even or None
Lock codes & Factory Defaults.
View & adjust Setup lock code.
From 1 to 9999 or Off for no lock code.
View & adjust Advanced lock code.
From 1 to 9999 or Off for no lock code.
Screensaver time 5, 15 or 30 mins.
Display language, 2 available – English plus either
German or French.
Transmitter view Enable hides the setpoint.
Important: The device still functions as a
controller even though SP is hidden.
For transmitter function, Linear Outp – Usage
must be PV Retransmit or SP Retransmit.
Reset parameters back to factory defaults.
To clear press then to select Yes.
Press to accept.
Controls what appears in Operator Mode.
Hide or Show parameters in Operator
Mode.
The hardware/software revision level.
Date of manufacture (mmyy).
The firmware version number & code type.
Instrument serial number.
SSR (SSR driver) or Relay
SSR (SSR driver) or Relay.
None, SSR (SSR driver), Relay or Linear.
Comms option - Fitted or None.
Digital Input options – Iso (isolated) or NonIs (non-isolated).
Ramp & Timers diagram – delay, ramp and timer
① From power up or control enable the unit delays process control until the Delay Timer
expires (time set by Delayed Start Time).
② Setpoint ramps from the current PV to the target setpoint at Ramp Rate (SPr indicates
ramping). If Ramp Rate is OFF the active setpoint steps directly to target setpoint.
③ When the active setpoint reaches the target setpoint, the On Timer counts down (time
set by On Time).
④ When the On Timer finishes the control switches off. If On Time is set to INF then the
control stays on.
Please refer to the full manual for further information on any topic.