Cal Controls 59615-1 Quick Reference

59615 MaxVU Rail Std Controller Concise manual (EN)
59615-1 MaxVU Rail Standard Controller
Concise Manual
1. INSTALLATION
Installation should only be performed by technically competent personnel. Standards compliance shall not be impaired when fitting into the final installation. It is the responsibility of the installing engineer to ensure that the configuration is safe. Local regulations regarding the electrical installation & safety must be observed. Impairment of protection will occur if the product is used in a manner not specified by the
manufacturer.
Due to the low weight of this instrument there are no special lifting or carrying considerations. Designed to offer a minimum of Basic Insulation only. Ensure that supplementary insulation suitable for Installation Category II is achieved when fully
installed.
To avoid possible hazards, accessible conductive parts of the final installation should be
protectively earthed in accordance with EN61010 for Class 1 equipment.
Output wiring should be within a Protectively Earthed cabinet. Sensor sheaths should be bonded to protective earth or not be accessible. Live parts should not be accessible without the use of a tool. When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should be used
to disconnect both LINE and NEUTRAL conductors simultaneously.
Do not position the equipment so that it is difficult to operate the disconnecting device. Ventilation slots must not be covered and adequate air circulation must be allowed. Use conductor sizes 30-12 AWG, minimum temp rating of cables to be 80c.
Terminal Wiring
CAUTION: Check information label on housing for correct operating
voltage before connecting supply to Power Inputs. Diagrams show all possible option combinations, check your exact product specification before connecting.
2. FRONT PANEL
Navigation & Editing
Press or keys to navigate between parameters or menu items. Press to highlight and edit a parameter value. Press or to change the parameter value, then press within 60 seconds to confirm change.
For example, changing the setpoint (SP).
Navigating to Setup Mode or Advance Configuration from Operator Mode:
Setup Mode - press & . Advanced Configuration - press & .
Returning to Operator Mode:
Press & to move back one level. After 120 seconds without key presses the unit returns automatically to the first Operator Mode screen.
3. SETUP (& FIRST POWER UP)
Important Note: When powered up for the first time, or after a factory reset (default) the
instrument enters Setup. The device remains in Setup, or will keep powering up back into Setup, until all parameters have been reviewed and the user exits Setup.
Some parameters may be hidden depending on configuration & hardware. Alternatively press & to enter Setup from Operator screen and & to exit.
Setup Lock
Enter code & press
Default 10
Parameter
Description
Default Value
>Input Type
J Thermocouple *
K Thermocouple
-200 – 1200ºC
-328 – 2192ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
K Thermocouple *
-240 – 1373ºC
-400 – 2503ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
PT100 *
-199 – 800ºC
-328 – 1472ºF
-128.8 – 537.7ºC
-199.9 – 999.9ºF
B Thermocouple
100 – 1824ºC 211 – 3315ºF
C Thermocouple
0 – 2320ºC
32 – 4208ºF
L Thermocouple *
0 – 762ºC
32 – 1403ºF
0.0 – 537.7ºC
32.0 – 999.9ºF
N Thermocouple
0 – 1399ºC
32 – 2551ºF
R Thermocouple
0 – 1795ºC
32 – 3198ºF
S Thermocouple
0 – 1762ºC
32 – 3204ºF
T Thermocouple *
-240 – 400ºC
-400 – 752ºF
-128.8 – 400.0ºC
-199.9 – 752.0ºF
Linear dc
0 – 20mA 0 – 50mV
0 – 5V
0 – 10V
4 – 20mA
10 – 50mV
1 – 5V
2 – 10V
>Input Units
°C or °F (hidden when a linear input is used)
°C
* Maximum of 1 decimal place for temperature inputs marked.
>Input Decimal Place
0000 *
000.0 *
00.00
0.000
0000
Scale Range max & min only visible when input is a linear type.
>Input Scale Range Maximum
Maximum for application working range.
1000
>Input Scale Range Minimum
Minimum for application working range.
0
>Input Digital I/P Action
None
Alarm Reset (clears latched alarms)
Ctrl Enable/Disable (disables control)
Ctrl Auto/Manual
Pre-Tune Start/Stop
Tune at SP Start/Stop
Ctrl
Enable/Disable
>Output 1 Usage
Heat Power Cool Power
Alarm 1 Alarm 2
Alm. 1or2
Loop Alarm
Heat Power
Control Loop Alarm time is 2x Integral (PID) or Loop Alarm Time (if mode is On.Off)
>Output 2 Usage
Same options as Output 1 Usage
Alarm 1
>Output 3 Usage or >Linear Outp Usage
Same options as Output 1 Usage.
Heat Cool
Retx PV Retx SP
Alarm 2
Retx SP
>Linear Outp Type
0-10V
2-10V 0-20mA 4-20mA
0-5V 1-5V
0-10V
>Linear Outp Scale Range Maximum
Maximum PV value corresponding to
maximum linear output.
Input type Max
>Linear Outp Scale Range Minimum
Minimum PV value corresponding to
minimum linear output.
Input type Min
>Alarm 1 Value
Range minimum to range maximum, or OFF
(maximum +1). OFF disables alarm.
Default PV High alarm type.
1373
>Alarm 2 Value
Same options as Alarm 1.
Default PV Low alarm type.
-240
Setpoint
Target setpoint.
0
>Coms Unit Address
Modbus address from 1 to 255
1
>Coms Baud Rate
1200, 2400, 4800, 9600, 19200 & 38400
9600
>Coms Parity
Odd, Even or None
None
>Control Automatic Tuning
Off, Start Pre-Tune or Start Tune at SP *
Off
*Start Tune at SP not available for Heat & Cool processes.
When you exit if necessary, press and to clear Control is Enabled Pop Up Alert.
4. OPERATOR MODE
Name
Details
User Screen
PV - top
SP - bottom
Temperature Unit - right.
Manual control
Manual Power is shown as P%.
Transmitter view enabled
Transmitter parameter = Enable, SP is hidden.
Important: The device still functions as a controller, using the local Setpoint.
Important: Visibility for parameters below must be set to Show in Operator sub-menu.
Alarm State
To clear latches press then to select Yes.
Press to accept.
Alarm active
Alarm set, but not
active
Alarm not set
Latch State
Output Latched
Latch set, but
output not Latched
Latch not set
Maximum PV
To clear press then to select Yes. Press to accept.
Screens show the Maximum & Minimum PV reached.
Minimum PV
Control Enable
OFF - Control output(s) disabled. (Ignored when in manual mode). ON - Control output(s) enabled.
Manual Control Enable
OFF - Automatic control, PID or On-Off control available. ON - Manual control, Manual Power shown as P% xxx.
Time On Remaining
On Timer
Visible when On Timer is active. See Ramp & Timers diagram.
Delay Time Remaining
Delay Timer
Visible when Delay Timer is active. See Ramp & Timers diagram.
Warnings & Error Messages
Caution: Do not continue your process until any issues are resolved.
Name
Details
Pop up Alerts: Warnings and
Confirmations
For example, Pop Up Alert for Alarm 1.
Pop Up Alerts need to be acknowledged. Press and to clear Pop Up Alert.
Pop up Alerts: Alarm 1, Alarm 2, Alarm 1 & 2, Starting Calibration, Calibration Ongoing,
Calibration Fail, Control is Enabled, Tune Error messages, Tuning in progress, Setup
not Completed & Offset in use (SP offset).
ALARM
Alternates with PV to show Alarm is active.
LATCH
Alternates with PV.
One or more outputs are latched on and no alarm is active.
HIGH
Process variable input > 5% over-range.
LOW
Process variable input > 5% under-range.
OPEN
Break detected in process variable input sensor, wiring or wrong
input type selected. Shows OPEN until resolved, control is off.
ERROR
Selected input range is not calibrated.
Shows ERROR until resolved, control is off.
TUNE
Alternates with SP. Auto-tuning is in progress.
P%
Manual power value replaces setpoint, shows P% xxx of power.
Ramp
Alternates with actual setpoint. Setpoint ramp is active.
OFF
Control is disabled. Control output(s) are off.
Control Delayed
Visible when Delay Timer is active. Control output(s) are off.
Tuning in progress
Alternates with setpoint. Tuning is active.
Tune Errors
Display alternates between Tune Error & Setpoint.
Remains visible until Automatic Tuning is turned Off.
tErr1
PV within 5% of SP (for pre-tune)
tErr2
Setpoint is ramping
tErr3
Control is ON/OFF (not PID)
tErr4
Control is manual
tErr5
Tune at Setpoint not able to run
tErr6
Sensor Break
tErr7
Timer Running
tErr8
Control is Disabled
5. SPECIFICATIONS
Important: Check your product code for exact hardware fitted.
PROCESS INPUT
Thermocouple Calibration:
0.25% of full range, 1LSD & 1°C for Thermocouple CJC. BS4937, NBS125 & IEC584.
PT100 Calibration:
0.25% of full range, 1LSD. BS1904 & DIN43760 (0.00385//°C).
DC Calibration:
0.25% of full range, 1LSD.
Sampling Rate:
4 per second.
Impedance:
>1M resistive, except dc mA (5) and V (47k)
Sensor Break Detection:
Thermocouple, RTD, 4 to 20mA, 10 to 50mV, 2 to 10V and 1 to 5V ranges only. Control outputs turn off at sensor break.
DIGITAL INPUT (Isolated or Non-Isolated version)
Functions:
Reset Alarm, Control Enable/Disable, Auto/Manual, Pre-Tune Start/Stop or Tune at SP Start/Stop.
Signal:
Non-isolated - Open or Close only. Isolated - Open (2 to 24Vdc) or Closed (<0.8Vdc). Closed to Open transition = Reset, Enabled, Auto or Start.
OUTPUTS
Relay Contacts:
Form C SPDT (Op 1) / Form A SPST relay (other), 2A @ 250Vac.
Relay Lifetime:
>150,000 operations at rated voltage/current, resistive load.
SSR Driver Capability:
SSR drive voltage >10V at 20mA
Output 3 option only: DC (Linear)
Types:
0 to 20mA, 4 to 20mA, 0 to 5V, 0 to 10V or 2 to 10V
Load Resistance:
Current Output 500 max, Voltage Output 500 min.
Resolution:
8 bits in 250ms (10 bits in 1s typical, >10 bits in >1s typical).
RS485 SERIAL COMMUNICATIONS (Modbus RTU)
Data Rate:
1200, 2400, 4800, 9600, 19200 or 38400 bps.
OPERATING CONDITIONS
Usage:
For indoor use only, DIN-rail mounted in suitable enclosure.
Ambient Temp:
<95% humidity 0°C to 55°C (Operating), –10°C to 80°C (Storage).
Relative Humidity:
20% to 95% non-condensing.
Altitude:
< 2000m
Power Supply:
Mains power version - 100 to 240Vac 10%, 50/60Hz, 9VA Low voltage version - 24Vac +10/-15% 50/60Hz 9VA or 24Vdc +10/-15% 5W.
ENVIRONMENTAL
Standards:
CE, UL & cUL.
EMI:
EN61326-1:2013, Table 2 & Class A.
Warning: This is a Class A product. In a domestic environment, this product may cause
radio interference in which case the user may be required to take adequate measures.
Safety:
UL61010-1 Edition 3, EN61010-1 Version 2010, Pollution Degree 2 & Installation Class 2.
Protection Rating:
IP20.
PHYSICAL
Unit Size:
Height - 99mm; Width – 22.5mm; Depth - 121mm
Ventilation:
A space of 80mm must be allowed above & below each unit.
Weight:
0.20kg maximum
ISOLATION
Ok /
Select
Up
Down
LEDs show respective output state: 1 2 3
Display turns off after 5, 15 or 30
minutes without key presses.
Bus Connector
pin-outs:
* Dedicated
configuration port
* NEVER DIRECTLY CONNECT DEDICATED CONFIGURATION SOCKET TO A USB PORT.
A
Data A
Data B
RS485 Data A (Rx/Tx+)
Communications
Output 3
Output 2
Power
Digital Input
RS485 Data B (Rx/Tx-)
Relay COM / Linear +
Relay NO / Linear -
Relay COM / SSR -
Relay NO / SSR +
Relay COM / SSR -
Relay NO / SSR +
Relay NC
Output 1 TC / RTD / Linear +
Volt-free or TTL
Compatible
L + N -
TC / RTD / Linear -
RTD
B
Display shows PV (process variable), units, SP (setpoint), alarm/latch statuses, error & warning messages.
Input
Alarm State
Alarm 1
Alarm 2
Loop
Latch State
Out 1
Out 2
Out 3
Bus Connector (optional)
Mounting & Unmounting
Non-Isolated Digital Input
Isolated Digital Input
Configuration Port
Configuration Port
Non­Isolated Digital Input
Isolated Digital Input
RS485 Comms
Not Applicable
No Isolation
Reinforced
Isolation
RS485 Comms
Linear
Linear
SSR
SSR
Relay
Relay
Universal Input
Universal Input
PSU
PSU
or
59615 MaxVU Rail Std Controller Concise manual (EN)
6. SAFETY & WARNING SYMBOLS
Risk of electric shock.
Caution, refer to the manual.
Alternating or direct current
could be present.
Equipment protected through-out
by double insulation.
7. ADVANCED CONFIGURATION
Advanced Configuration gives access to all possible parameters; however, the device hides parameters that are irrelevant to your exact product specification & configuration.
Advanced Configuration Navigation
Enter by pressing & . Press or to navigate to the required menu, then press
to enter.
Press & to exit up 1 level. Depending upon which menu you enter it may be necessary to exit 2 or 3 levels for Operator Mode.
Advanced Configuration main menu
Advanced Lock
Enter code & press
Default 20
Menus
Description
User
Includes Status, Control & Manual Mode enable/disable.
Input
Configure the process input.
User Calibration
Single or two-point calibration adjustments for the process input.
Outputs
Configuration parameters for the outputs.
Control
PID control tuning & configuration parameters.
Setpoint & Timer
Setpoint & timer settings.
Alarms
Alarm configuration.
Communication
Modbus communications settings.
Display
Lock codes and Factory Default.
Operator Screens
Control what appears in Operator Mode.
Information
View serial number & manufacturing details.
User
Parameter
Description
Default Value
Alarm State
Alarm active
Alarm set, but not
active
Alarm not set
n/a
Latch State
Output
Latched
Latch set but output
not Latched
Latch not set
To clear press then
to select Yes.
Press to accept.
n/a
Maximum PV
Maximum and Minimum PV recorded whilst
powered up or since last reset.
To clear press then to select Yes.
Press to accept.
n/a
Minimum PV
Control Enable
OFF - Control output(s) disabled. (Ignored
when in manual mode) SP replaced by OFF.
ON
ON - Control output(s) enabled. Setpoint visible
in User screen.
Manual Control Enable
OFF - Instrument in automatic control mode
(PID or On-Off control).
OFF
ON - Manual control ON. Power shown as Pxxx % in Operator mode, in place of SP.
Input
Parameter
Description
Default Value
Input Type
See Input Type table in SETUP (& FIRST
POWER UP).
K Thermocouple
Units
Displayed as °C or °F
(Units are hidden when a linear input is used)
°C
Decimal Place
0000
0000
000.0
00.00
Not for temperature.
0.000
Scale Range Maximum
Maximum for application working range
Max allowed for
Input Type.
Scale Range Minimum
Minimum for application working range
Min allowed for
Input Type.
Filter Time
OFF or 0.5 to 100.0 seconds in 0.5
increments
2.0
CJC Enable
Enable Enables the internal thermocouple
CJC (Cold Junction Compensation).
Enable
Disable Disables the internal CJC.
External compensation must be provided for
thermocouples.
Parameter
Description
Default Value
Digital I/P Action
None
Alarm Reset (clears latched alarms)
Ctrl Enable/Disable
Ctrl Auto/Manual
Pre-Tune Start/Stop
Tune at SP Start/Stop (not available for
heat/cool)
Ctrl Enable/Disable
User Calibration
Single-point offset or two-point calibration adjustment for process input. Can be used together, if required.
Parameter
Description
Default Value
Offset
Shifts the input value up or down by a single offset amount across the entire range.
0
Low Point
Enter value at which the low point error was measured.
Lower
Limit
Low Offset
Enter equal, but opposite offset value to the observed low point error.
0
High Point
Enter value at which the high point error was measured.
Upper
Limit
High Offset
Enter an equal, but opposite offset value to the observed high point error.
0
Outputs
Parameter
Description
Default Value >Output 1
Usage
Heat
Cool Alarm 1 Alarm 2
Alm. 1or2
Loop Alarm
Heat
Control Loop Alarm is set as 2x Integral (PID) or Loop Alarm Time (On.Off control)
Alarm Action
Direct - Output active when alarm triggers
Reverse - Output active when alarm is not
triggered
Direct
Latching
Off - Alarm doesn’t latch
On – Alarm latches & needs to be cleared
Off
LED Indicator
Direct - LED Indicator lit when output is active
Reverse - LED Indicator lit when output is
inactive
Direct
>Output 2
Usage
Same options as Output 1 - Usage
Alarm 1
Alarm Action
Same options as Output 1 - Alarm Action
Direct
Latching
Same options as Output 1 - Alarm Latching
Off
LED Indicator
Same options as Output 1 - LED Indicator
Direct
>Output 3 or >Linear Outp
3rd output - either Relay/SSR driver (Output 3) or Linear.
>Output 3 Usage
>Linear Outp Usage
Output 3 - same options as Output 1 - Usage
Heat
Cool
PV Retransmit SP Retransmit
Output 3:
Alarm 2
Linear:
SP
Retransmit
>Output 3 Alarm Action
Same options as Output 1 - Alarm Action
Direct
>Output 3 Alarm Latching
Same options as Output 1 - Alarm Latching
Off
>Output 3 LED Indicator
Same options as Output 1 - LED Indicator
Direct
>Linear Outp Type
0-10V
2-10V 0-20mA 4-20mA
0-5V 1-5V
0-10V
>Linear Outp Scale Range Maximum
Display value for maximum output, -1999 to 9999
Input type
Max
>Linear Outp Scale Range Minimum
Display value for minimum output, -1999 to 9999
Input type
Min
Control
PID control tuning & configuration & Loop Alarm. Hidden if no control outputs are set.
Parameter
Description
Default Value
Proportion Heat Band
ON/OFF (0.0) or PID control in display units.
1 to 9999 - 0 decimal places
0.1 to 999.9 - 1 decimal place
0.01 to 99.99 - 2 decimal places
0.001 to 9.999 - 3 decimal places
161
Proportion Cool Band
161
Auto Reset (Integral)
0.01 to 99.59.
and OFF (0.00) (minutes & seconds).
5.00
Parameter
Description
Default Value
Rate (Derivative)
0.01 to 99.59 or OFF (0.00) (minutes & seconds).
1.15
Overlap/ Deadband
In display units, range -20 to +20% of Heat & Cool
Proportional Band
0
Differential (On/Off)
Visible when using On/Off control.
In display units centred about the setpoint.
Range: 0.1% to 10.0% of input span
8
Loop Alarm Time
Visible when On/Off control & Loop Alarm assigned to
an output.
Sets time before the loop alarm triggers.
(minutes & seconds)
99.59
Manual Rst (Bias)
Manual Reset 0 to 100%
(-100% to 100% if heat/cool control)
25%
Heat Cycle Time
0.1 to 512.0 seconds
32.0
Cool Cycle Time
32.0
Output Interlock
Prevents simultaneous activation of both heat & cool
outputs. On / Off
Only set to On if Overlap/Deadband = 0.
Off
Heat Power Limit
% power upper limit 0 to 100%
100%
Cool Power Limit
% power upper limit 0 to 100%
100%
Power Up Action
Last - Powers up with control enable in the same state
as on power off or power failure.
On - Always powers up with control enabled.
Last
Automatic Tuning
Off
Start Pre-Tune
Start Tune at SP *
Off
*Start Tune at SP not available for Heat & Cool process.
Setpoint
Parameter
Description
Default Value
Enable Timer
Enabled
Enables the Delay and On Timers. Applies at next power­up / control enable.
Disabled
Disabled
Delay and On Timers ignored. (Setpoint ramping still functions.)
Delayed Start Time
Time from power-up or control enable before control begins from 00.01 to 99.59. or OFF (0.00. (hours & minutes) If OFF control starts immediately.
OFF
Ramp Rate
Rate actual setpoint changes from current PV to target setpoint following power-up or control enable. From 0.001 to 9999. or OFF (1000) (Units / hr).
Any setpoint changes also follow this rate.
OFF
On Time
The time the target setpoint will be maintained once reached, from 00.01 to 99.59 or Off (00.00) (hours & minutes)
Infinite (100.00) - control remains on indefinitely.
Infinite
Upper Limit
Used to limit the Maximum setpoint value.
Scale Range
Maximum
Lower Limit
Used to limit Minimum setpoint value.
Scale Range
Minimum
Offset
Offsets the setpoint. For use in multi-zone setpoint slave applications. Offset in use pop-up appears when SP is changed.
0
Alarms
Parameter
Description
Default Value
>Alarm 1
Type
None PV High PV Low
Deviation
Band
PV High
Value
Range minimum to range maximum, or OFF (maximum +1). OFF disables alarm.
1373
Parameter
Description
Default Value
Hysteresis
0 to full span.
1
>Alarm 2
Type
Same options as Alarm 1
PV Low
Value
-240
Hysteresis
1
>Options
Alarm Inhibit temporarily deactivates alarms at power-up & on change in setpoint.
Alarm Inhibit
None Alarm 1 Alarm 2
Alarm 1 & 2
None
Alarm Notification
None Alarm 1
Alarm 2
Alarm 1 & 2
Alarm 1 & 2
Sensor Break Alarm
On - activates both alarms, if configured, when a sensor break is detected.
Off
Communications
Modbus communications settings, only shown when RS485 option is fitted.
Parameter Name
Description
Default Value
Unit Address
Modbus address from 1 to 255
1
Baud Rate
Coms data rate in kbps 1200, 2400, 4800, 9600, 19200 & 38400.
9600
Parity
Parity checking: Odd, Even or None
None
Display
Lock codes & Factory Defaults.
Parameter Name
Description
Default Value
Setup Unlock Code
View & adjust Setup lock code. From 1 to 9999 or Off for no lock code.
10
Advanced Unlock Code
View & adjust Advanced lock code. From 1 to 9999 or Off for no lock code.
20
Screen Timeout
Screensaver time 5, 15 or 30 mins.
5
Selected language
Display language, 2 available – English plus either German or French.
English
Transmitter
Transmitter view Enable hides the setpoint.
Important: The device still functions as a controller even though SP is hidden.
For transmitter function, Linear Outp – Usage must be PV Retransmit or SP Retransmit.
Disable
Reset to Defaults
Reset parameters back to factory defaults. To clear press then to select Yes.
Press to accept.
Operator Screens
Controls what appears in Operator Mode.
Parameter Name
Description
Default Value
Control Enabled
Hide or Show parameters in Operator
Mode.
Hide
Manual Ctrl Enabled
Hide
Alarm State
Hide
Latch State
Show
Maximum PV
Hide
Minimum PV
Hide
Remaining On Time
Hide
Remaining Delay Time
Hide
Information (Read-Only)
Parameter Name
Description
PRL
DOM
The hardware/software revision level.
Date of manufacture (mmyy).
FW Version
FW Type
The firmware version number & code type.
Serial
Instrument serial number.
Out1 Out2 Out3
SSR (SSR driver) or Relay
SSR (SSR driver) or Relay.
None, SSR (SSR driver), Relay or Linear.
Comm
DI
Comms option - Fitted or None.
Digital Input options – Iso (isolated) or NonIs (non-isolated).
① ② ③
Ramp & Timers diagram delay, ramp and timer
From power up or control enable the unit delays process control until the Delay Timer
expires (time set by Delayed Start Time). Setpoint ramps from the current PV to the target setpoint at Ramp Rate (SPr indicates ramping). If Ramp Rate is OFF the active setpoint steps directly to target setpoint. When the active setpoint reaches the target setpoint, the On Timer counts down (time set by On Time). When the On Timer finishes the control switches off. If On Time is set to INF then the
control stays on.
Please refer to the full manual for further information on any topic.
Alarm State
Alarm 1
Alarm 2
Loop
Latch State
Out 1
Out 2
Out 3
Loading...